3.3kV-27kV
Air Insulated Switchgear
Leading the future of electrification
3.3kV - 27kV
Air Insulated Switchgear
Leading the future of electrification
GE
GE is a diversified organization covering a myriad of market segments, including infrastructure,
finance and media. From energy, water, transportation and health to access to money and
information, GE serves customers in more than 100 countries and employs more than 300,000
people worldwide.
The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light
Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston
Electric Company created the General Electric Company. GE is the only company listed in the Dow
Jones Industrial Index today that was also included in the original index in 1896.

Industrial Solutions
GE Industrial Solutions, a division of GE Energy Management, is a global leading provider in
power distribution, offering a wide range of services and products which include medium and low
voltage power distribution equipment and components, motor & control systems and service
products that are safe, reliable and offer high performance.

Honour
2010 World's Most Innovative Companies
2011 Worlds Most Admired Companies

2009 Worlds Most Respected Companies

2011 Best Global Brand

2008 Worlds Most Respected Companies 2007 Worlds Best R&D Companies
More Than 90 Years

90 of Interrupter
Experience
GE pioneered experimental vacuum
interrupters in the 1920s. Refined it and
introduced the world's first 15kV Vacuum
circuit breaker in the 1960s. To date, this
interrupter design has been the world
leader in vacuum technology and has
accumulated over 55 years of reliable field
service.

Universal

A Applications
SecoGear is designed, assembled and tested
to meet or exceed applicable IEC, GB and
DL standards. It is suitable for applications
in all major industries including T&D, Oil
& Gas, Automotive, Processing plants,
World Class Quality Iron and Steel mills, Mining, Commercial
buildings, etc.
Manufactured, assembled and tested It provides protection for all types of
all in the same sophisticated facility, applications: coble, overhead lines, motors,
SecoVac is the product of state of the art capacitors, transformers, busbar sections,
manufacturing processes assured by ISO etc.
9001:2008 and ISO 14001 certification.
Precision tooled parts, computer aided
design and advanced production
techniques, as well as the protection of
the 'E Coat' (cathodic electrocoating) paint
process have resulted in a standard of
excellence unmatched in the industry.

Environment
Consciousness
eco Selecting low environmental impact
technologies has become increasingly
important to engineers tasked with
choosing equipment for an application.
With commitment to environment
protection, the solid insulation of epoxy
resin is used for SecoVac series MV
embedded pole vacuum circuit breaker
instead of SF6 gas.
Contents
General Introduction
GE
GE Industrial Solutions

Product Description
SecoGear Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02
Solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 07
Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 08
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Product Introduction
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 15
Control and Operation . . . . . . . . . . . . . . . . . . . . . . . . 17
Technical Characteristics . . . . . . . . . . . . . . . . . . . . . 18
Operation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 19
Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
IEC Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Configurations
Typical Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Incoming/Feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Incoming with Measuring (VT) . . . . . . . . . . . . . . . . . 24
Busbar Earthing Switch . . . . . . . . . . . . . . . . . . . . . . . 25
Incoming/Feeder (VT, SA, ESW) . . . . . . . . . . . . . . . . 26
Busbar Tie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Riser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Riser with VT & CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
VT Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Incoming with VT/ES . . . . . . . . . . . . . . . . . . . . . . . . . 31
Riser with ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
CPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Measurement, Protection and Control


Multilin 3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Multilin 650 Family . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Switchgear Compartment
Vacuum Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . 45
Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Voltage Transformer Truck. . . . . . . . . . . . . . . . . . . . 51
Earthing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Operation Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Installation Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
SecoGear 3.3kV-27kV Air Insulated Switchgear

MV Switchgear with better reliability and safety.

For over 80 years, General Electric has provided medium voltage


equipment combining advanced technology with engineering
excellence. The SecoGear range provides the highest safety and
Product Description

reliability standards with a cost effective solution in the public


distribution, industry and building sectors.

02
SecoGear 3.3kV-27kV Air Insulated Switchgear

Product Description
SecoGear Series
3.3/7.2/12/13.8/15/17.5/24/27kV
Switchgear
Indoor, metal-enclosed switchgear designed for the MV

D
section of HV/MV and MV/MV substation
Air insulated switchgear with a compact design
B
Safe and Reliable switchgear for universal indoor applications

Designed with full metallic segregation of its internal

compartments
A
Equipped with the latest design embedded pole SecoVac

vacuum circuit breaker


Cable compartments with ample space for ease of power

cable connection
C
Fully arc-proof unit up to 40kA for 1 second AFLR

Tested in accordance with the IEC and GB international

standards
Unit compartment Tested to UBC zone 4 IBC 2012 and GB intensity 9 for Seismic

Front panel features easy operation and low maintenance


A Circuit breaker compartment Complete interlocking system to prevent incorrect operation
B Busbar compartment
and to improve safety
C Cable compartment
D Low voltage compartment
Innovative in its design, GE' s SecoGear is compact Air insulated
switchgear and leads the industry in safety, reliability,
performance and sustainability. Fully IEC certified at the KEMA
and IPH test labs to IEC 62771-100 and 62771-200.
SecoGear Switchgear is suited to provide control and protection
for cables, transformers, capacitors and motors used across
many industries. SecoGear excels anywhere that medium voltage
power has to be switched, controlled and protected.

03
SecoGear 3.3kV-27kV Air Insulated Switchgear

Built to highest quality standards Circuit breaker making and


breaking capacity
SecoGear is designed and fully third-
party type tested to the latest IEC 62271- The SecoVac vacuum circuit breaker is
Product Description

200 standards. It is fully isolated by subjected to the rated current and short-

earthed metal partitions for all the major circuit current breaking tests.

compartments. It is equipped with GE' s Furthermore, it is also subjected to the

very latest series of IEC vacuum circuit opening and closing of capacitive and

breakers type SecoVac, which are fully inductive loads, capacitor banks and/or

third party type tested in accordance cable lines.

with IEC 62771-100. Using GEs state of


Fully type tested to latest IEC
the art technology, and manufactured
standards
in accordance with the highest quality
standards; our engineers have integrated The switchgear is type tested to the
core technologies. These technologies latest IEC 62271-200 and has the third
such as circuit breaker and mechanism party certification to prove internal arc
design, vacuum arc control technology, containment classification of AFLR from
insulation technology and electrical field 31.5kA for 1 second and up to 40kA for
control and analysis combine to build 1 second. This means protection against
a highly reliable and compact system. harm to personnel in the unlikely event of
SecoGear benefits from GE' s best an internal arc in the cable compartment,
practices incorporated in our current vacuum circuit breaker compartment and Earthing switch making capacity
medium voltage. the bus bar compartment in any direction:
The typical rated voltage of SecoGear front, rear and sides of the switchgear. The earth switch of the SecoGear

is 3.3/7.2/12/13.8/15/17.5/24/27kV and switchgear can be closed under short-

rated current ranges for SecoGear up to circuit up to 40kA. The earth switch is

17.5 is from 630A to 4000A(4000A is force interlocked to avoid being operated

cooling), for SecoGear 24/27kV the rated on circuits which are still live. However,

current is up to 2500A. All SecoGear with a should the switch be accidentally closed

switching device is equipped with SecoVac then safety of the operating personnel is

vacuum circuit breaker with corresponding assured by arc fault containment.

specifications.

04
SecoGear 3.3kV-27kV Air Insulated Switchgear

Shock wave
Zone4 [SRS]
Minimum (1.0,3.63974E-001) Maximum (2.454353,2.5735E+000)
10.000

1.0000

g
Mechanical operations
0.1000
1.0000 10.000 100.00
Hz

The mechanical endurance tests on all


the operating parts ensure the reliability

Product Description
of the apparatus. General experience Marine application
in the electro-technical sector shows
IP degree Approvals
that mechanical faults are one of the
American Bureau of Shipping (ABS)
most common causes of a fault in an The IP protection degree is the resistance
Seismic Certification UBC Zone 4
installation. offered by SecoGear against penetration
Seismic Certification- IBC 2012
The circuit breaker is tested by carrying of solid objects and liquids. This degree
out a high number of operations - higher of resistance is indicated by the prefix IP
Inclination
than those which are normally carried out followed by two characters (IP 4X is for the
by installations in the field. The Inclination test proved that SecoGear
enclosure and IP 2X for the partitions.).
Furthermore, the switchgear components can continue operating as intended,
The first number identifies the degree
are part of a quality control program even when inclined at an angle up to
of protection against the entrance of
and samples are regularly taken from 25 degrees on all four sides and with an
solid objects, the second one is related
the production lines and subjected to ambient temperature of 50C, IP42.
to liquids. IP41 and IP42 available by
total mechanical life tests to verify that The exposure to these severe service
customer request.
the quality is identical to that of the conditions confirms the suitability of

components subjected to the type tests. SecoGear to marine unstable conditions.

Vibration
High ambient temperatures
The operating conditions on marine
platforms and shipping installation require
The service conditions for the electrical
the capability to work in environments
apparatus in marine installations are
affected by vibrations.
generally more severe than those in
SecoGear was exposed to a resonance
normal land applications. Temperatures
search and endurance random, which
are a main factor and for this reason the
consists of a random vibration test
shipping register regulations require the
according to IACS E10.
switchgear to be able to operate at higher
Vibration Sweep Test
ambient temperatures (40 C or higher).
From 2 to 13.2 Hz displacement 1.0

(peak value)
From 13.2 to 100 Hz acceleration

amplitude of 0.7 g
Vibration Endurance Tests 90 minutes

05
SecoGear 3.3kV-27kV Air Insulated Switchgear

Minimal costs during service due to:

Robust maintenance-free design with minimum number of parts

SecoVac vacuum circuit breaker has a long life of 10,000 operations without the need for active

maintenance
An advanced vacuum interrupter contact design prevents hot spots, creates less heat and minimizes

electrode erosion to yield longer life


Product Description

Low end of life disposal costs due to:

- Vacuum switching technology


- Air insulation
- Recycling or re-use of all materials possible
- No special decommissioning procedures necessary

User interface friendly

Cable connection and user interfaces for operation on the same side of the unit

Up to 6 cables per phase with standard compression lug for ease of cable connection

Secondary cable entry points on both sides of the low voltage compartment top plate

Secondary cable wiring runs over the length of the switchgear to help with inter-unit wiring

Secondary cable terminals positioned at a good reachable height within the low voltage compartment

Clear and simple, straightforward operation, panels combined with an active LED mimic diagram

Low lifetime cost

Low initial costs due to:


Compact footprint

Cable access from front or rear

Cable entry from either top or bottom

Easy-access cable compartment for ease of cable connection

Integrated arc chamber

Back to wall configuration with front cable access

06
SecoGear 3.3kV-27kV Air Insulated Switchgear

Solutions

Rack in/out draw out mechanism


SecoGear has a draw out mechanism that is designed to avoid misalignment during
racking, therefore overheating of the primary disconnect is totally prevented. The
draw out mechanism is bolted to the enclosure frame with a double bended support.

SecoGear offers you: GE's Multilin protection,


monitoring and control relays
Flexible and adapted solution

The experience of GE a global electrical SecoGear provides the most efficient

manufacturer means to control and protect a wide

Product Description
Dedicated engineering range of applications
With the use of GE Multilin devices,

Smart distribution SecoGear can be easily integrated


into a monitoring and control system
Intuitive industrial and utility protective
relays for feeders, motors and transformers

Remote control solution Key benefits of Multilin Protection


Relays
By special order request

For remote control from a central Easy to use and cost effective

control room for intelligent switchgear Effortless draw-out construction

systems Environmental monitoring system to

The following functions of SecoGear alarm on destructive operating conditions

are provided: Easy to use interface and set up in one step

- Motorized draw out mechanism for Accelerated Life Cycle tested to ensure

remote connect and test position reliability under abnormal conditions

- Remote opening and closing the Advanced diagnostics to increase

switchgear device reliability

- Motorized line side earth switch Flexible communications with multiple

ports & protocols to allow seamless


integration
Easy access to information via multiple

communication network options


Powerful Security Audit Trail

07
SecoGear 3.3kV-27kV Air Insulated Switchgear

Applications

Utilities and power plants


Power generation stations
Transformer stations
Switching stations
Main and auxiliary switchgear
Product Description

Industry
Oil and Gas
Mining
Marine
Pulp and Paper
Cement
Textiles
Chemicals
Automotive
Petrochemical
Data Center
Metallurgy

Transport
Airports
Ports
Railways
Underground transport

Services
Supermarkets
Shopping malls
Hospitals
Large infrastructure and civil works

08
SecoGear 3.3kV-27kV Air Insulated Switchgear

Applications Product Description

09
SecoGear 3.3kV-27kV Air Insulated Switchgear

P13
Safety

Internal Arc Containment


When developing modern medium IAC test. SecoGear up to 27kV passes the
voltage switchgear, personnel safety must 31.5kA/1s.
take priority. This is why the SecoGear All high voltage primary compartment

switchgear has been designed and tested are provided with pressure relief
to withstand an internal arc due to a flaps located on the topside of the
short-circuit current of the same current switchgear
level as the maximum shorttime withstand Any overpressure inside the

level. compartment caused by internal


Product Description

The tests show that the metal housing arcing will be released through the
of SecoGear switchgear provides an pressure relief flaps
enhanced degree of protection for
personnel near the switchgear in the case
of an internal arcing fault.
SecoGear up to 17.5kV passes the 40kA/1s SCALE 1,000

Arc release channel

Arc Release System Arc skirt (optional)

Arc Release System is a perfect solution tunnel and evacuate to the outside of the The switchgear units have been tested
for E-house, marine and other limited room. according to IEC 62271-200:2003 for the
places, which do not allow hot particles Switchgear with standard arc release following Internal Arc Classification. The
and gases into the room. And it also system can be used where the room SecoGear have pass type test IAC AFLR
guarantees personnel safety. height is greater than 3000mm. At the 40kA/1s for 17.5kV and for 27kV 31.5kA/1s
Each panel is fitted with two metal mesh location of the exhaust exits from the with skirt as below.
boards on the top of it. The pressure switchroom, personal access should be
generated by arc fault makes it open, limited.
allowing the gas and particles into the

SCALE 1,000

Interlock
1152 650 650 1000 1200

800 3100 800 800 2180


500

900
C View
1152
2720

546

2200

1500
Arc Release System Arc skirt (optional)

10
SecoGear 3.3kV-27kV Air Insulated Switchgear

Interlock
GE safety interlock systems guarantee The earthing switch can be opened

the highest level of personnel safety only when the cable compartment
preventing operator errors from occurring. door is closed
SecoGear is designed with a number The secondary plug can be inserted or

of interlocking systems to prevent mis- removed only when the circuit breaker
operation: is in the test position
The circuit breaker can only be moved The circuit breaker can only be closed

from test to connect position and vice when the circuit breaker is positively

Product Description
versa when circuit breaker is opened located in the test or connect position
The earthing switch cannot be closed When the circuit breaker is removed

when the circuit breaker is in the from connect position, the metal
connect position and in the traveling shutters will close automatically
position between test and connect preventing access to live connections
The cable compartment door can be

opened only when the earthing switch


is closed

Description of the interlock system Key Condition


Key-lock for VCB rack in
Key will be free when the truck in the disconnect position
A Functional truck racking-in lock
Key will be trapped when the truck in the rack-in position
B Key-lock for Earthing switch
Key will be free when the earthing switch is open
C Earthing switch closing lock
Key will be trapped when the earthing switch in closed position
Key will be free when the earthing switch closed
C Earthing switch opening lock
Key will be trapped when the earthing switch in open position
Safety
SCALE 1,000

Arc release channel

SCALE 1,000

Interlock

11
SecoGear 3.3kV-27kV Air Insulated Switchgear

Environment
Increasing global legislation concerning the use of green -
house gases such as SF6 gas and their related disposal costs,
makes vacuum technology with its reliability, low maintenance,
and low environmental impact the choice for now and the
future.
As the world strives to reduce the amount of SF6 gas used
in all applications there is a responsibility on the users of
electrical switchgear to find, where appropriate, alternatives to
SF6 gas as an insulation and switching medium. Air and solid
insulation switchgear systems incorporating vacuum switching
Product Description

technologies are a reliable, safe and economic alternative for


use in electrical systems below 36kV and therefore should be
used instead of SF6 gas insulated systems.
Modern medium voltage switchgear employing vacuum
technology together with air and epoxy resin insulation
provides:
Minimum number of parts and components

No special requirements for the end-of-life disposal of the

switchgear
Environmentally-friendly materials used in the design

No use of SF6-gas for switching and insulation

No risk of damaging leaks of SF6 gas or of toxic byproducts

Energy-efficient production and assembly, with

environmentally friendly energy sources


Minimal number of transition points in the primary design

enables low energy loss during operation


Only re-usable and/or recyclable materials used

Environmentally friendly design

GE's production plants act entirely in its materials to ensure that they have compact, environmentally friendly design
accordance with the rules and procedures the lowest possible impact on the for the circuit breaker and the switchgear.
of the ISO 14001 environmental certificate environment. It is essential that they are Because the switching medium - vacuum
during development and production equally safe for people not just during use, is used, SecoGear can be completely
processes. but at the end of service life too. Within recycled at the end of its life without
Material selection and the number of SecoGear and the SecoVac vacuum circuit any issues relating to safety procedures,
parts that are used to manufacture the breaker, a combination of solid (cast-resin) special handling or safe disposal.
SecoGear are critical to determining and air is used as insulation. The cast-
how environmentally friendly the resin technology, in combination with
manufacturing process is. GE selects electrical field calculations, provides a very

12
SecoGear 3.3kV-27kV Air Insulated Switchgear

Environmentally friendly Energy efficient assembly

From the very beginning GE made a SecoGear is produced in an energy


fundamental choice not to use SF6 as efficient environment. Standard
a switching and insulation medium for processes and materials are used in the
primary medium voltage equipment. SF6 design and require no special handling
is on the list of greenhouse gasses in the or manufacturing processes, thus
Kyoto protocol and is the most potent reducing the amount of energy required
of the six main greenhouse gasses, with to manufacture and assemble the
a Global Warming Potential (GWP) of switchgear.

Environment
23,000. Many other medium voltage
switchgear systems use SF6 gas as the

Product Description
insulating medium. Leakage of SF6 gas Efficient use of materials
from switchgear contributes significantly
to the threat of the greenhouse effect and Besides the energy sources, special

associated climate change. They also focus is placed on the efficient use of

require additional safety measures and material during assembly. For example

special handling requirements at the end by using advanced nesting tools the

of life. hot dipped galvanized steel plates are


cut with the least amount of waste, and
similar principles are followed in the
design and manufacture of other product
Minimum service checks on site
components
SecoGear is designed for a lifetime of at
least 20 years; therefore the energy usage
for maintenance activities during this Re-use or recycling of materials
long period is minimal. Due to the green
insulation and switching technology, All materials of SecoGear and SecoVac

there is also no leakage of the harmful can be reused, all materials are not any

SF6 gas during its lifetime and no need for impact on the environment, it fully reflects

performing extra maintenance activities the GE corporate social responsibility to

on SF6 gas pressure checks. design and produce products.

Minimal energy loss during


operation

The number of electrical contact or


changeover points within the SecoGear
system has been kept to an absolute
minimum. This reduces the potential
number of "hot spots" and prevents
additional energy loss associated with
contact surfaces.

13
SecoGear 3.3kV-27kV Air Insulated Switchgear

Product Introduction
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 15
Control and Operation . . . . . . . . . . . . . . . . . . . . . . . . 17
Technical Characteristics . . . . . . . . . . . . . . . . . . . . . 18
Operation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 19
Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Product Introduction

IEC Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

14
SecoGear 3.3kV-27kV Air Insulated Switchgear

Product Introduction
1 Low voltage compartment

The compartment is isolated with earthed metal partitions and


has ample space for control and protection devices.
A fully isolated metal wire way is mounted at the top of each
switchgear panel; this connects together to form a
continuous low voltage wire way that runs along
the entire length of the switchgear.

2
2 Busbar compartment

Busbars are totally enclosed in their own earthed


metal compartment which vents into the arc
3
chamber. Fully insulated along their entire length,

Product Introduction
the busbars for up to 17.5kV SecoGear are type
4
tested for ratings up to 4000A, 40kA for 3 seconds,
up to 27kV SecoGear are type tested for rating up to
2500A, 31.5kA for 3 seconds. For 24/27kV SecoGear,
the busbars are type tested for rating up to 2500A,
31.5kA for 3 seconds. Epoxy moldings separate
switchgear sections.
6

3 Vacuum circuit breaker


compartment

Fully isolated by earthed metal partitions, with

8
its own pressure relief channel into the arc
chamber. The compartment provides all the safety
7
9
interlocking mechanisms required for safe and
reliable operation of the vacuum circuit breaker.
Manual operation buttons allow for full operation of the
vacuum circuit breaker from the front of the switchgear with
the door fully closed. The circuit breaker is mechanically
interlocked with the compartment door so that the door
cannot be opened until the circuit breaker is switched off and
racked out into the Test position.

15
SecoGear 3.3kV-27kV Air Insulated Switchgear

4 Automatic shutters

When the circuit breaker is in Test or Disconnect position, the


shutters automatically close to isolate the fixed contact from
any live parts. Shutters can be individually and automatically
operated for bus side and feeder side connection in close
position.

5 Earth switch 8 Cable compartment

The earthing switch can be Cable supports are provided to


operated from the front of the secure cables. Cable clamps are
switchgear. It is mechanically applied for fix the cables. And the
interlocked with the circuit metal floor cover is removable.
breaker truck so that the earthing switch can only be operated Infrared sight glass window can
when the circuit breaker is open in Test/Disconnect position as be offered.
well. The switch is also mechanically interlocked with the cable
compartment for additional safety.
Product Introduction

9 Earth bar

Earth bar is made of copper and


6 Current transformers
installed in the bottom of cable
Current transformers are cast compartment. The earth bar
in resin, and totally enclosed. system has been fault tested and
This provides superior protection runs vertically and horizontally
against pollutants and moisture. with each panel section and is connected to the earth switch.
It can be equipped with one
or more independent magnetic cores with equal or different 10 Surge arrester
characteristics for measuring, metering and protection purposes.
Surge arrester is used to protect
electric equipment against
transient operating or lightning
7 Voltage transformers
over-voltage. It is connected
Voltage transformers are cast between primary conductor and
in resin, and totally enclosed. ground for protecting protective load from damage effect. When
This provides superior protection the operating or lightning over-voltage occurs, surge arrester
against pollutants and moisture. immediately limits over-voltage amplitude and protects the
It can be equipped with one insulation of device.
or more independent magnetic cores with equal or different
characteristics for measuring, metering and protection purposes.

16
SecoGear 3.3kV-27kV Air Insulated Switchgear

Control and Operation

1 Low voltage control and protection compartment


Panel with all controls and indicators clearly visible
3
and easy to operate

1
2 Protection relay
GE has a range of Multilin relay options that can 2
be fitted as standard. However, customer specific
protection relays from any manufacturer can be 4 5
fitted to the compartment door

6
3 Mimic diagram
Easy to understand mimic diagram of each circuit

4 Circuit breaker position indicator


Breaker position indication shows the breaker
in the connected/service or disconnected/test
position
7

5 Electrical operation with circuit breaker status


indicator

Product Introduction
Breaker open/closed status indicator.
Breaker open/closed command switch.
Optional LED indication of spring charge 8
mechanism charged status

6 Voltage detection system


Each circuit breaker panel can be equipped with an 9
optional standard three phase voltage detection
system for voltage detection to IEC 61243-5

7 Viewing windows
The circuit breaker compartment door viewing
window provides visual indication of the position of
the circuit breaker indicating:
- The status of the breaker
- The status of the spring charged mechanism

8 Circuit breaker racking operate hole


Circuit breaker racking in/out operate hole
Electrical operation for racking in/out available

9 Earthing switch operate hole


Earthing switch open/close
Electrical operation for Earthing switch available

17
SecoGear 3.3kV-27kV Air Insulated Switchgear

Technical Characteristics

Rated voltage kV 3.3 7.2 12 15 17.5 24 27


Rated power frequency (1min) kVp 10 20 28 36 38 50 65
Rated lightning impulse (1.2/50s) kV 20 60 75 95 95 125 125
Rated frequency Hz 50/60 50/60
Rated current A 630/1250/1600/2000/2500/3150/4000* 630/1250/1600/2000/2500
Rated short time withstand kA 25/31.5/40 31.5
Rated peak value withstand current kAp 65/82/104 82
Enclosure IP4X IP4X
IP level for weather protection
Between compartment IP2X IP2X

*Force cooling

Protection Construction
IP4X for the enclosure Internal arc withstand (classification IAC): AFLR

IP2X between each compartment 3 compartments (classification LSC2B according to IEC 62271-200)

IP42 optional All the metal surfaces in the panels are corrosion proof
Product Introduction

IP41 / IP42 optional Panels are produced using hot dipped galvanized steel sheet

Busbar fully insulated for 7.2kV, 12kV, 13.8kV, 15kV, 17.5kV, 24kV, 27kV

Connections
Front and/or rear access

Cable entry from bottom or top

18
SecoGear 3.3kV-27kV Air Insulated Switchgear

Operating Conditions

Normal operating conditions Note on any special climatic


operating conditions
The switchgear is fundamentally designed
for the normal service conditions for When the switchgear is operated in areas
indoor switchgear to IEC Publication with high humidity and/or major rapid
62271-1. The following limit values, among temperature fluctuations, there is a risk
others, apply. of condensation. Preventive action (e.g.
Ambient temperature fitting the electric heater) must be taken
- Maximum +40C in consultation with the manufacturer to
Special operating conditions
- 24h-Medium +35C avoid the condensation and any resulting
- Minimum -15C SecoGear is suitable for operation in the corrosion or other adverse effects. The
Humidity climate of indoor type according to IEC control of the heaters depends on the
- Highest average value measured over standard. Special operating conditions relevant project.
24 hours must be discussed with GE in advance.

- Relative humidity 95% For example: At site altitudes above 1000

- Highest average value measured over m, the effects of the reduction in density of

Product Introduction
1 month the air on the dielectric properties must be

- Relative humidity 90% taken into account.


The maximum site altitude is 1000 m Increased ambient temperatures must

above sea level be compensated for in the design of the


Seismic Rating up to Uniform Building busbar and the branch conductors as well

Code (UBC) 1997 Zone 4 as the withdrawable parts; otherwise the


Seismic Rating up to IBC 2012 for 27kV current carrying capacity will be reduced.

SecoGear Fitting additional ventilation facilities can


assist heat dissipation in the switchgear
panel.

High altitude application

The insulating capacity of the switchgear


with rated values of short-time power-
frequency withstand voltage and impulse
withstand voltage according to IEC 62271-1.

19
SecoGear 3.3kV-27kV Air Insulated Switchgear

Storage Conditions

In order to retain all of the functional units


qualities when stored for prolonged periods,
we recommend that the equipment is stored
in its original packaging, in dry conditions
sheltered from the sun and rain at a
temperature of between 15C and + 40C.
For storage: -30C.

IEC Standards
SecoGear complies with the standards
and specifications for factory assembled
metal enclosed switchgear and has been
type tested in accordance with the IEC
publications as given below.
Product Introduction

IEC 62271-100: 2008 High-voltage alternating current circuit breakers.


IEC 62271-200: 2003 AC Metal enclosed switchgear and control gear for rated voltages
above 1kV and up to 52kV.
IEC 62271-102: 2001 High-voltage alternating current disconnector and Earth Switches.
IEC 62271-1: 2007 The common specification for high voltage switchgear and
control gear Standards.
IEC 60529:1989 Degrees of protection as provided by enclosures (IP Code).

20
SecoGear 3.3kV-27kV Air Insulated Switchgear

Configurations
Configurations
Typical Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Incoming/Feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Incoming with Measuring (VT) . . . . . . . . . . . . . . . . . 24
Busbar Earthing Switch . . . . . . . . . . . . . . . . . . . . . . . 25
Incoming/Feeder (VT, SA, ESW) . . . . . . . . . . . . . . . . 26
Busbar Tie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Riser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Riser with VT & CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
VT Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Incoming with VT/ES . . . . . . . . . . . . . . . . . . . . . . . . . 31
Riser with ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
CPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

21
SecoGear 3.3kV-27kV Air Insulated Switchgear

Typical Panels

The SecoGear series comprises 11 basic configuration applications.


The table below can be used to link requirements to functional units and gives basic
information on the general composition of each unit.

3.3kV-27kV
Incoming with Incoming/Feeder
Incoming/Feeder Busbar Earthing Switch Busbar Tie Riser
measuring (VT) (VT, SA, ESW)
Configurations

Riser with VT & CT VT Panel Incoming with VT/ES Riser with ES CPT

24kV-27kV
Incoming with ES & VT Incoming with ES & VT
Riser with ES CPT
(24kV) (27kV)

22
SecoGear 3.3kV-27kV Air Insulated Switchgear

Incoming/Feeder

P26
Rated Voltage (kV)
7.2 12 15 17.5 24 27
Rated Insulation Level
Power frequency withstand voltage (kV) 20 28 36 38 50 65
Lightning impulse withstand voltage (kV) 60 75 95 95 125 125
630
1250
1600
Rated current (A) 2000
2500
3150
4000*
25

Configurations
Breaking capacity (kA) 31.5
40
25
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 650 800 1000 650 800 1000 650 800 1000 650 800 1000 800 1000 800 1000
Height (H) 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2400 2400 2400 2400
Top Access 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900 - - - -
Depth (D)
Bottom Access 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1800 1800 1800 1800

Estimated Weight (kg) 615 615 615 615 1100 1100

*4000A switchgear with force cooling


17

22
04

23
SecoGear 3.3kV-27kV Air Insulated Switchgear

Incoming with Measuring (VT)

P32
Rated Voltage (kV)




7.2

12

15

17.5

24 27
Rated Insulation Level
Power frequency withstand voltage (kV) 20 28 36 38 50 65
Lightning impulse withstand voltage (kV) 60 75 95 95 125 125
630
1250
1600
Rated current (A) 2000
2500
3150
4000*
25
Configurations

Breaking capacity (kA) 31.5


40
25
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 650 800 1000 650 800 1000 650 800 1000 650 800 1000 800 1000 800 1000
Height (H) 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2400 2400 2400 2400
Depth (D) 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1800 1800 1800 1800

Estimated Weight (kg) 615 615 615 615 1100 1100

*4000A switchgear with force cooling

10

SCALE 1,000

24
SecoGear 3.3kV-27kV Air Insulated Switchgear

Busbar Earthing Switch

Rated Voltage (kV)


7.2 12 15 17.5

+P23
Rated Insulation Level
Power frequency withstand voltage (kV)



20

28

36

38

Lightning impulse withstand voltage (kV) 60 75 95 95


630
1250
1600
Rated current (A) 2000
2500
3150
4000*
25

Configurations
Breaking capacity (kA) 31.5
40
25
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 650 800 1000 650 800 1000 650 800 1000 650 800 1000
Height (H) 2640 2640 2640 2640 2640 2640 2640 2640 2640 2640 2640 2640
Top Access 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900
Depth (D)
Bottom Access 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400

Estimated Weight (kg) 615 615 615 615

*4000A switchgear with force cooling


86
76

25
SecoGear 3.3kV-27kV Air Insulated Switchgear

Incoming/Feeder (VT, SA, ESW)

+P24
Rated Voltage (kV)
7.2 12 15 17.5 24 27
Rated Insulation Level
Power frequency withstand voltage (kV) 20 28 36 38 50 65
Lightning impulse withstand voltage (kV) 60 75 95 95 125 125
630
1250
1600
Rated current (A) 2000
2500
3150
4000*
25
Configurations

Breaking capacity (kA) 31.5


40
25
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 650 800 1000 650 800 1000 650 800 1000 650 800 1000 800 1000 800 1000
Height (H) 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2400 2400 2400 2400
Top Access 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900 1900 - - - -
Depth (D)
Bottom Access 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1800 1800 1800 1800

Estimated Weight (kg) 615 615 615 615 1100 1100

*4000A switchgear with force cooling

26
SecoGear 3.3kV-27kV Air Insulated Switchgear

Busbar Tie

P28
Rated Voltage (kV)




7.2

12

15

17.5

24 27
Rated Insulation Level
Power frequency withstand voltage (kV) 20 28 36 38 50 65
Lightning impulse withstand voltage (kV) 60 75 95 95 125 125
630
1250
1600
Rated current (A) 2000
2500
3150
4000*
25

Configurations
Breaking capacity (kA) 31.5
40
25
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 650 800 1000 650 800 1000 650 800 1000 650 800 1000 800 1000 800 1000
Height (H) 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2400 2400 2400 2400
Depth (D) 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1800 1800 1800 1800

Estimated Weight (kg) 615 615 615 615 1100 1100

*4000A switchgear with force cooling

01

B C

SCALE 1,000

27
SecoGear 3.3kV-27kV Air Insulated Switchgear

Riser

P29
Rated Voltage (kV)




7.2

12

15

17.5

24 27
Rated Insulation Level
Power frequency withstand voltage (kV) 20 28 36 38 50 65
Lightning impulse withstand voltage (kV) 60 75 95 95 125 125
630
1250
1600
Rated current (A) 2000
2500
3150
4000*
25
Configurations

Breaking capacity (kA) 31.5


40
25
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 650 800 1000 650 800 1000 650 800 1000 650 800 1000 800 1000 800 1000
Height (H) 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2400 2400 2400 2400
Depth (D) 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1800 1800 1800 1800

Estimated Weight (kg) 615 615 615 615 1100 1100

*4000A switchgear with force cooling

B C

SCALE 1,000

28
SecoGear 3.3kV-27kV Air Insulated Switchgear

P30
Riser with VT & CT

Rated Voltage (kV)


7.2 12 15 17.5 24 27
Rated Insulation Level
Power frequency withstand voltage (kV) 20 28 36 38 50 65
Lightning impulse withstand voltage (kV) 60 75 95 95 125 125
630
1250
1600
Rated current (A) 2000
2500
3150
4000
25

Configurations
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 800 1000 800 1000 800 1000 800 1000 800 800
Height (H) 2200 2200 2200 2200 2200 2200 2200 2200 2400 2400
Depth (D) 1400 1400 1400 1400 1400 1400 1400 1400 1800 1800
Estimated Weight (kg) 615 615 615 615 1100 1100

JSZV17-15R

15
95.5
76

01

29
SecoGear 3.3kV-27kV Air Insulated Switchgear

VT Panel

Rated Voltage (kV)


7.2 12 15 17.5 24 27
Rated Insulation Level
Power frequency withstand voltage (kV) 20 28 36 38 50 65
Lightning impulse withstand voltage (kV) 60 75 95 95 125 125
25
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 800 1000 800 1000 800 1000 800 1000 800 800
Height (H) 2200 2200 2200 2200 2200 2200 2200 2200 2400 2400
Depth (D) 1400 1400 1400 1400 1400 1400 1400 1400 1800 1800
Estimated Weight (kg) 615 615 615 615 1100 1100
Configurations

JSZV17-15R

15
95.5
76

30
SecoGear 3.3kV-27kV Air Insulated Switchgear

P29
Incoming with VT/ES

Rated Voltage (kV)


24/27
Rated Insulation Level
Power frequency withstand voltage (kV) 50
Lightning impulse withstand voltage (kV) 125
630
1250
Rated current (A) 1600
2000
2500
25
Breaking capacity (kA)
31.5
25

Configurations
Short time withstand current (kA/3s)
31.5
Dimensions (mm)
Width (W) 800 1000
Height (H) 2400 2400
Depth (D) 1800 1800
Estimated Weight (kg) 1100

*4000A switchgear with force cooling

31
SecoGear 3.3kV-27kV Air Insulated Switchgear

P31
Riser with ES

Rated Voltage (kV)


27
Rated Insulation Level
Power frequency withstand voltage (kV) 65
Lightning impulse withstand voltage (kV) 125
630
1250
Rated current (A) 1600
2000
2500
25
Breaking capacity (kA)
31.5
25
Configurations

Short time withstand current (kA/3s)


31.5
Dimensions (mm)
Width (W) 800 1000
Height (H) 2400 2400
Depth (D) 1800 1800
Estimated Weight (kg) 1100

*4000A switchgear with force cooling

32
SecoGear 3.3kV-27kV Air Insulated Switchgear

CPT

P32
Rated Voltage (kV)
27
Rated Insulation Level
Power frequency withstand voltage (kV) 65
Lightning impulse withstand voltage (kV) 125
630
1250
1600
Rated current (A) 2000
2500
3150
4000*
25

Configurations
Breaking capacity (kA) 31.5
40
25
Short time withstand current (kA/3s) 31.5
40
Dimensions (mm)
Width (W) 800 1000
Height (H) 2400 2400
Depth (D) 1800 1800
Estimated Weight (kg) 1100

*4000A switchgear with force cooling

33
SecoGear 3.3kV-27kV Air Insulated Switchgear

Configurations scheme

P33
3.3kV-27kV

Scheme Number 01 02 03 04 05 06

Primary Scheme

Rated Curent (A) 630~4000 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum Circuit Breaker 1 1 1 1 1 1
Current Transformer 3 3 3 3 3 3
Main Voltage Transformer
Apparatus High Voltage Fuse
Earthing Switch 1 1 1 1
Arrester 3 3
Configurations

Application I/F I/F I/F I/F I/F I/F


Switchgear Width (mm) 650/800/1000 650/800/1000 650/800/1000 650/800/1000 650/800/1000 650/800/1000

Scheme Number 07 08 09 10 11 12

Primary Scheme

Rated Curent (A) 630~4000 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum Circuit Breaker 1 1 1 1 1 1
Current Transformer 2 2 3 3 2 3
Main Voltage Transformer 2 3
Apparatus High Voltage Fuse 2 3
Earthing Switch
Arrester
Application B B B B I/F I/F
Switchgear Width (mm) 650/800/1000 650/800/1000 650/800/1000 650/800/1000 650/800/1000 650/800/1000

Scheme Number 13 14 15 16 17 18

Primary Scheme

Rated Curent (A) 630~4000 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum Circuit Breaker 1 1
Current Transformer 2 3
Main Voltage Transformer 3 3 2 2 3 3
Apparatus High Voltage Fuse 3 3 3 3 3 3
Earthing Switch 1
Arrester 3 3
Application I/F I/F VT VT VT VT
Switchgear Width (mm) 650/800/1000 650/800/1000 800/1000 800/1000 800/1000 800/1000

*for up to 17.5kV SecoGear, special requirement for 6 CT is available. Please contact GE for detail.

34
SecoGear 3.3kV-27kV Air Insulated Switchgear

Configurations scheme

P34
3.3kV-27kV

Scheme Number 19 20 21 22 23 24

Primary Scheme

Rated Curent (A) 630~4000 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum Circuit Breaker
Current Transformer 2 2 3 3
Main Voltage Transformer 2 2 3 3
Apparatus High Voltage Fuse 2 2 3 3
Earthing Switch
Arrester

Configurations
Application R R M M M M
Switchgear Width (mm) 650/800/1000 650/800/1000 650/800/1000 650/800/1000 650/800/1000 650/800/1000
Scheme Number 25 26 27

Primary Scheme

Rated Curent (A) 630~1250 630~4000 630~4000


Vacuum Circuit Breaker 1 1
Current Transformer 2 3 3
Main Voltage Transformer 3 3
Apparatus High Voltage Fuse 3 3
Earthing Switch 1 1
Arrester 1
Application M I/F I/F
Switchgear Width (mm) 650/800/1000 650/800/1000 650/800/1000

24kV-27kV
Scheme Number 28 29 30 31

Primary Scheme

Rated Curent (A) 1250~2500 1250~2500 1250~2500 1250~2500


Vacuum Circuit Breaker 1 1
Current Transformer 3 3
Main Voltage Transformer 3 3 2
Apparatus High Voltage Fuse 3 3 3
Earthing Switch 1 1 1
Arrester
Application I/F I/F R M
Switchgear Width (mm) 800/1000 800/1000 800 1000

*for up to 17.5kV SecoGear, special requirement for 6 CT is available. Please contact GE for detail.

35
SecoGear 3.3kV-27kV Air Insulated Switchgear
Monitoring and Protection

Measurement, Protection
and Control
Multilin 3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Multilin 650 Family . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

36
SecoGear 3.3kV-27kV Air Insulated Switchgear

Measurement, Protection and Control


For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/3Series.htm

Multilin 3 Series
Intuitive industrial and utility
protective relay systems
for feeders, motors and
transformers

Key benefits
Easy-to-use and cost effective protection and control for Application flexibility with the use of programmable logic

feeders, motors and transformers elements


Effortless draw-out construction eliminates requirements for Large backlit display with 40 characters for easy viewing of

Monitoring and Protection


test switches and reduces downtime relay information and settings
Environmental monitoring system to alarm on destructive Flexible communications with multiple ports & protocols to

operating conditions to enable preventative maintenance allow seamless integration into new and existing infrastructure
Easy-to-use interface and set up in one simple step Easy access to information via multiple communication

Accelerated Life Cycle Tested to ensure reliability of relay network options including USB, Serial, Fiber & Copper Ethernet
operation under abnormal conditions Reduced wiring with support for remote I/O

Advanced power system diagnostics to increase reliability Reduce setup and configuration time with the Simplified Motor

through fault and disturbance recording capabilities Setup screen


Arc Flash mitigation via zone inter-tripping, flex curves and Powerful Security Audit Trail tool to increase security and

multiple setting groups minimize system risks by tracking setting changes

Applications
Advanced protection, monitoring & control relays for feeders Distribution utility down stream breaker protection

(Multilin 350), motors (Multilin 339) and transformers (Multilin Medium voltage utility feeders with advanced control features

345) including, cold load pickup, auto reclose and multiple setting
Industrial feeders with enhanced breaker monitoring and groups
diagnostics

37
SecoGear 3.3kV-27kV Air Insulated Switchgear

Features Easy-to-use
Protection & control Drawout construction
(for Multilin 350 Feeder Protection System) The Multilin 3 Series offers a complete
Phase, neutral and ground TOC and IOC drawout feature eliminating the need for
Undervoltage, overvoltage, frequency rewiring after testing has been concluded.
Neutral/ground directional The withdrawable feature also eradicates
Negative sequence overcurrent the need to disconnect communication
ANSI, IAC, IEC, flex curves cables, e.g. fiber, copper, RJ45, etc and
Overview
Cable Thermal Model protection helps retain communication status even
Breaker failure The Multilin 3 Series of protection relays after a relay has been withdrawn from its
Cold load pick-up are a highly functional, economical case.
Four-shot auto reclose protection relays for feeders, motors and

8 digital inputs, 7 contact outputs transformers. By providing an economical

Two setting groups system for protection, control, monitoring


and metering, and both local and
Metering & monitoring
remote user interfaces in one assembly,
Event Recorder: 256 events with 1ms
the Multilin 3 Series relays effectively
time stamping
eliminate the need for expensive discrete
Oscillography with 32 samples per
components.
cycle and digital states
The Multilin 3 Series provides detailed
IRIG-B clock synchronization
diagnostic information allowing users to
Relay & Asset Health Diagnostics
troubleshoot and minimize downtime.
Security audit trail
Detailed diagnostics is provided via the
Advanced communications
User interface and programming 256 1ms time stamped event recorder
Monitoring and Protection

and the 192 cycle Oscillography report Easy integration into new or existing
4x20 character LCD display
sampled at 32 samples per cycle. infrastructure
Control panel with 12 LED indicators
The robust Multilin 3 Series streamlines With several Ethernet and serial port
Front USB and rear serial, Ethernet and
user work flow processes and simplifies options, and a variety of communication
Fiber ports
engineering tasks such as configuration, protocols, the Multilin 3 Series provides
Multiple protocols - IEC 61850 & 61850
wiring, testing, commissioning, and advanced and flexible communication
GOOSE, ModBus RTU, ModBus
maintenance. This cost-effective relay selections enabling seamless integration
TCP/IP, DNP 3.0, IEC 60870-5-104, IEC
also offers enhanced features such as into new or existing applications.
60870-5-103
diagnostics, preventative maintenance, The Multilin 3 Series supports various
EnerVista software industry standard protocols such as, IEC
device health reports and advance
An industry-leading suite of software 61850 & IEC 61850 GOOSE, Modbus RTU,
security features.
tools that simplifies every aspect of Modbus TCP/IP, DNP3.0, IEC 60870-5-104
working with Multilin devices and IEC 60870-5-103.
Document and software archiving

toolset to ensure reference material


and device utilities are up-to-date

38
SecoGear 3.3kV-27kV Air Insulated Switchgear

Enhanced diagnostics EnerVistaTM Launchpad Security


Preventative maintenance EnerVista Launchpad is a complete set of Security audit trail
The Multilin 3 Series allows users to track powerful device setup and configuration tools The Multilin 3 Series monitors security
relay exposure to extreme environmental that is included at no extra charge with the SR and reliability of asset protection. The
conditions by monitoring and alarming Relays. Multilin 3 Series protection devices
at high temperatures. This data allows Set up the Multilin 3 Series Relays - and any offer complete traceability of any
user to proactively schedule regular other Multilin device - in minutes. Retrieve relay setting and command changes,
maintenance work and upgrade activities. and view oscillography and event data at allowing the user to quickly identify
All relays utilize EnerVista setup TM
the click of a button changes made to the relay.
software for communication, monitoring Build an instant archive on any of the

and metering. Actual values, setpoints, latest Multilin manuals, service advisories,
status, trending, and waveform capture application notes, specifications or
information may all be viewed via firmware for your SR Relay
the software, and can be used for Automatic document and software version

troubleshooting. updates via the internet and detailed e-mail


notification of new releases

User Interface
SETPOINT GROUP 1, 2:
These indicators are continuously on if corresponding group provides settings for protection elements.
TRIP:
Indicator turns on when relay detects a trip condition.
Operates the trip relay to open the breaker.
ALARM:
While relay detects an alarm condition, indicator flashes.
PICKUP:
Indicator lights steady when any protection feature pickup threshold exceeded.

Monitoring and Protection


DISPLAY:
4 line text for easy viewing of key data.

LEDs:
10 LED indicators for quick diagnostics.

KEYPAD:
Ten button keypad for access to device interrogation and change of settings.

FRONT PORT:
Electrically isolated front USB communication port.

Protection Features ANSI Device Numbers & Functions


Device
BUS Number Function
27P Phase Undervoltage
27X Auxiliary Undervoltage
BUS VT
49 Thermal Model
52 50P Phase Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
50G Ground/Sensitive Ground
79 27P 59P 27X 59X 59_2 59N 81U 81O Instantaneous Overcurrent
TRIP CLOSE 1 1 1 1 1 1 1 2 2 50BF Breaker Failure
MONITORING 50_2 Negative Sequence Overcurrent
3 51P Phase Timed Overcurrent
51G Ground Timed Overcurrent
50P 50N 51P 51N 50_2 49 METERING
51N Neutral Timed Overcurrent
2 2 1 1 1 1 59P Phase Overvoltage
59X Auxiliary Overvoltage
CLP 50BF 79 59N Neutral Overvoltage
59_2 Negative Sequence Overvoltage
1 67G Ground Directional Overcurrent
50G 50G/
51G 67N Neutral Directional Overcurrent
51G TRANSIENT RECORDER
EVENT RECORDER 79 Autoreclose
2 1 81U Underfrequency
81O Overfrequency
350 RELAY CLP Cold Load Pickup

Latched Lockout available as a standard feature


LOAD

39
SecoGear 3.3kV-27kV Air Insulated Switchgear

Measurement, Protection and Control


For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/F650.htm

Multilin 650 Family


Advanced protection,
control and monitoring system

Key benefits
Unique built-in control features - Comprehensive protection Cost Effective Access information - Via multiple protocols,

plus programmable logic through standard RS232 & RS485 Ethernet Ports
Flexible and cost effective control for complex systems - Optimal integration flexibility via open standard protocols -
Monitoring and Protection

Use IEC compatible programmable logic to customize the Modbus RTU, DNP 3.0 Level 2, IEC 60870-5-104, IEC 61850, IEC
functionality of your protection & control system to address 870-5-103
unique, site specific applications Minimize communication down time - Reliable redundant

Human machine interface (HMI) - Standard backlit LCD display Ethernet Communication ports with 10/100BaseTX, 100BaseFX
with 4 x 20, optional 16 x 40 (240 x 128 pixels) graphical LCD, with ST connectors and optional double 100BaseFX, with ST
programmable buttons and directional keys for selecting connectors
setting menus and submenus Complete asset monitoring - Full metering including demand

Minimize replacement time - Modular with card draw-out & energy


construction Follow technology evolution - Flash memory for product field

Reduce troubleshooting time and maintenance costs - IRIG-B upgrade


time synchronization, event reports, waveform capture, data
logger

Applications
F650: Management and primary protection of distribution G650: Distributed generation management device

feeders and bus couplers G650: Reliable Distributed Generation interconnection

F650: Backup protection of busses, transformers and power protection system


lines W650: Wind turbine protection, control and monitoring

G650: Packaged generator mains failure detection W650: Distributed generation grid interconnection device

40
SecoGear 3.3kV-27kV Air Insulated Switchgear

Features
Protection and control User interface
Up to 32 Programmable digital inputs Large graphic (16 x 40) or regular (4 x 20) character display

Up to 16 digital outputs Easy-to-use control via Shuttle key

Trip Circuit Supervision Front USB port or standard RS232

Redundant power supply option Rear wire 10/100BaseTX Ethernet for LAN connection

Configurable PLC logic according to IEC 61131-3 Rear wire CAN bus port (OPEN CAN protocol - W650)

Fully configurable graphic display HMI interface Optional fibre optic 100BaseFX Ethernet, single or redundant

Alarms panel Optional rear RS485 port

1 ready LED and 15 programmable LED indicators


Monitoring and metering EnerVistaTM Integrator providing easy integration of data in the
Energy metering Data logger
650 relay into new or existing monitoring and control systems
Demand metering Sequence of event

Trip circuit monitoring Self diagnostic

Oscillography

Overview Metering
The Multilin 650 family has been designed screens. The Multilin 650 provides the following
as a comprehensive protection, control, The metering capability allows 0.5% metering values.
metering and monitoring package. The accuracy for current and 1% from 10V to Current: Ia, Ib, Ic, In, Ig, Isg

microprocessor based architecture 208V for voltage in metering range. Phase-to-phase and phase-to-ground

is a complete solution for different Monitoring functions include a 479 voltage values for bus and line: Van,
applications that complies with the most event recorder, and a programmable Vbn, Vcn, Vab, Vbc, Vca, Vx

Monitoring and Protection


relevant international standards. oscillography recorder. Active power (per phase and total) : Wa,

All the elements required for each The Multilin 650s communications Wb, Wc, W
application have been integrated into a capability and option make the product Reactive power (per phase and total) :

single package for a cost-effective, reliable very unique. These units include VARa, VARb, VARc, VAR
and simple utilization. The low number of a maximum of three independent Power factor (per phase and total)

components, thanks to the use of state- communication ports: COM1, COM2 Frequency

of-the-art but mature technology, deliver and COM3, with many physical choices These signals are available for local

a very high reliability. through the use of two removable plug- display and accessible remotely using
Hardware inputs and outputs have been and-play boards. communications
designed in a modular way that allow The brain of the Multilin 650 units includes
easy migration from simple to more a powerful built-in virtual PLC. This PLC Recording functions
complex applications. can be programmed according to the IEC The recording functions within the Multilin
The control functions include a full- 61131-3 language by functional block 650 include:
scheme virtual PLC with an optional diagrams. Event recorder capable of storing 479

graphical display. The combination of 650 units come with 8 to 32 digital inputs time-tagged events (1 true millisecond
both elements provide total control for and with 8 to 16 outputs depending on accurate tagging)
a bay. This means real-time monitoring options. All digital inputs may be filtered Up to 20 separate oscillography records

of breakers and selector switches, open with a separate debounce time to tailor can be stored in memory. The capacity
and close commands supervised by the customer requirements. of each record will depend on the type of
programmable interlockings and metering oscillo selected (1 Mbyte/Max. No. Osc)

41
SecoGear 3.3kV-27kV Air Insulated Switchgear

These records are stored in non volatile Communications


memory. Therefore, there is no need Multilin 650 units incorporate up to TCP/IP and IEC 60870-5-104.
for internal battery monitoring or three ports that operate independently.
maintenance. Redundant ports are available for high
reliability applications:
Trip circuit monitoring Available protocols for rear port 1 and 2
Multilin 650 units offer as an option two are ModBus RTU, IEC 103 and serial DNP
complete supervision circuits for breaker 3.0.
trip and closing coils and circuits. These The third port is located in a removable
supervision inputs monitor both the communications card. This plug-and-
battery voltage level and the continuity of play card can be easily changed in the
the trip and/or closing circuits, applying future as new standards arrive to the
current through those circuits and market, thus providing a migration path
checking that it flows properly. In order to the customer.
to apply this feature it is necessary to The protocol available for the third port
choose I/O board 1 option 2. is DNP 3.0 over TCP/IP, UDP/IP, ModBus

User Interface

Graphic 16 x 40 or text 4 x 20 LCD display

Fluorescent backlight to improve visibility

Multicolor programmable LEDs with label panel


Monitoring and Protection

Local/Remote/Off pushbutton with LEDs

Key control for easy navigation

Ergonomic programmable keys

Electrically isolated front USB communication port


ANSI Device Numbers & Functions
Device
Number Function
25 Synchrocheck
27/27X Bus/Line Undervoltage

Functional Block Diagram 32


32FP
Sensitive Directional Power
Forward Power
32N Wattmetric zero-sequence directional
46 Negative Sequence Time Overcurrent
47 Negative Sequence Voltage
48 Blocked Rotor
49 Thermal Image - overload protection
1
52 50 BF Breaker Failure
50PH/PL Phase Instantaneous Overcurrent (High/Low)
50N Neutral Instantaneous Overcurrent
79
1 CLOSE TRIP 27X 50G Ground Instantaneous Overcurrent
3
Monitoring 50SG Sensitive Ground Instantaneous Overcurrent
3 59X 50IG Isolated Ground Instantaneous Overcurrent
BROKEN 3
50BF 49 50PH 50PL 46 48 32FP 32 32N CONDUCTOR 51PH/V 51PL/V 67P
R R 50N 51N 67N 51N Neutral Time Overcurrent
1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
25 51G Ground Time Overcurrent
1
51SG Sensitive Ground Time Overcurrent
1 2 2 51PH/V Voltage Restraint Phase Time Overcurrent
50G 51G 67G 51PL/V
3 3 3
1 59/59X Bus/Line Overvoltage
50SG 51SG 50IG 67SG METERING 59NH/NL Neutral Overvoltage - High/Low
3 3 3 3
3V_0 67P Phase Directional Overcurrent
3 67N Neutral Directional Overcurrent
67G Ground Directional Overcurrent
67SG Sensitive Ground Directional Overcurrent
47 27 59 VTFF 81U 81O 81R 79 Autorecloser
3 3 3 1 3 3 3
59NH 81 U/O Under/Over Frequency Broken Conductor
3
Detection
59NL N/A Load Encroachment
F650 Digital Bay Controller 3
81R Frequency Rate of Change
EN F650 BLOCK F.CDR
VTFF VT Fuse Failure Detection

42
SecoGear 3.3kV-27kV Air Insulated Switchgear

Device setup & document Logic, IEC 61850 system


management toolset configuration and Real-Time
monitoring
The EnerVistaTM launchpad software is a
powerful toolset used for the complete Viewpoint Engineer is the most advanced
support and management of Multilin tool for protection & control engineers and
products. Support application including commissioning staff available. Use the
product software, manuals, and setting full-featured Graphical Logic Designer to
files management is used to ensure build and annotate complex Flexlogic
your important files are kept up-to-date and then observe it in real-time with the
and easily accessible. Site Management Graphical Logic Monitor. Use the System
will allow you to properly maintain your Designer option to design and annotate
asset and devices by providing real-time IEC 61850 communication schemes,
diagnostic data and reports. including ICD file import and SCD file
export for non-GE IEDs.

Monitoring and Protection


Security auditing, device and Easy-to-Use monitoring and data OPC connectivity to automation
asset health reporting and fault recording and historian applications
data retrieval
Viewpoint Monitoring provides simplified Seamless integration of GE Multilin and
Viewpoint Maintenance provides security visualization of real-time data from all generic Modbus devices into existing DCS,
auditing, device and asset health GE Multilin using ready-made Plug-and- SCADA systems and other data consumer
reporting as well as easily accessible fault Play screens. Built-in data logger, alarm applications (data historians, data
data. With a comprehensive security audit annunciator and time synchronization visualization tools) using standard open
report, changes to the device settings, round out this HMI package. Third-party OPC/DDE connectivity.
including the MAC address, are recorded devices can be incorporated using either
enabling compliance with NERC / Critical generic Modbus RTU or Modbus TCP/IP or
Infrastructure Protection Standards. IEC 61850 and optional OPC/DDE server
Device and Asset status reports detail connectivity can link to existing facility
current and historical health for both the DCS or SCADA systems.
intelligent protection device and the asset
being protected.

43
SecoGear 3.3kV-27kV Air Insulated Switchgear
Spare Parts

Switchgear Compartment
Vacuum Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . 45
Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Voltage Transformer Truck. . . . . . . . . . . . . . . . . . . . 51
Earthing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Operation Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

44
SecoGear 3.3kV-27kV Air Insulated Switchgear

Vacuum Circuit Breaker


SecoVac VB2 Plus embedded pole vacuum circuit breaker 7.2kV, 12kV, 17.5kV, 24kV and 27kV
Safety, more reliability and High performance in a compact package

SecoVac VB2 Plus of Modular design

Features and benefits Applications


Industry leading vacuum and solid insulation technology Serving global 50 Hz and 60 Hz

Fixed and withdrawable versions available Segments of the electrical industry: industrial, commercial,

Environmentally friendly design - no SF6 gas utility, mining, marine and off-shore
Conformance to the latest IEC standards - IEC 62271-100 Protecting transformers, capacitor banks, motors, busbar

and IEC 62271-1 sections and cables


Numerous safety features for maximum personnel Suitable for special environment conditions: shock, vibration

protection and high ambient temperature


User friendly operation with easy access and minimal

inspection
Compact and cost effective

Flexible with a full line of accessories and OEM Solution

Spare Parts

45
SecoGear 3.3kV-27kV Air Insulated Switchgear

Circuit Breaker Characteristics


Rated Voltage kV 7.2 12 15 17.5 24 27
Rated power frequency withstand (1min) kV 20 28 36 38 50 65
Rated lightning frequency impulse withstand voltage
kVp 60 75 95 95 125 125
(1.2/50s)
Rated Frequency Hz 50/60 50/60
Rated Current A 630/1250/1600/2000/2500/3150/4000* 1250, 2500
Rated short-circuit breaking current kA 25/31.5/40 31.5
Percentage of DC component Up to 50% 52%
Rated short-circuit closing current kAp 65/82/104 82
Rated short time withstand current kA 25/31.5/40 31.5
Rated peak value withstand current kAp 65/82/104 82
Rated duration time for short-circuit s 3 3
Opening Time ms 20~50 20~50
Closing Time ms 30~70 30~70
Rated auxiliary control voltage V 36/48/60/110/220 V DC 110/220 V AC
Operation sequence O-0.3s-CO-180s-CO/ O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO
Mechanical life operations Quantity 10,000 (M 2) 10,000 (M 2)
Electrical Endurance class E2 E2 (list 1)
Single capacitor bank Switching current A 400 400
Rating for Earthing Switch short time withstand current 40kA 1s 31.5kA 1s

* Force cooling

Main circuit resistance of SecoVac

Item Unit Value


Rated Current A 1250~1600 2000~4000
Resistance 45 25

Coil Characteristics

Rated voltage Rated voltage Rated voltage


(V) (V) (V)
DC 24 DC 48 DC 220~240
DC 30 DC 60~72 AC 110~130
DC 36 DC 110~130 AC 220~240

*Power consumption 350VA

Motor Characteristics
Spare Parts

Rated voltage Energy storing period under rated operation voltage Input Power
Normal operation voltage range
(V) (s) (W)
DC 24 85%-110% <15s 150
DC 30 85%-110% <15s 150
DC 48 85%-110% <15s 150
DC 60 85%-110% <15s 150
DC 110 85%-110% <15s 150
DC 125 85%-110% <15s 150
DC 220 85%-110% <15s 150
DC 230-240 85%-110% <15s 150
AC 110 85%-110% <15s 150
AC 125 85%-110% <15s 150
AC 220 85%-110% <15s 150
AC 230-240 85%-110% <15s 150

46
SecoGear 3.3kV-27kV Air Insulated Switchgear

Internal wiring diagram (AC) 17.5kV

Spring Charge Motor Closing Circuit Breaker Interlock Circuit Opening Circuit Truck Interlock Circuit

26 24 25 10 52 30 6 3 5 7 9 23 27 28 29 8 1

V2 V4 V3

CC
V1 K0
TC V5 A~
(13) C+ B-
(14) S2 Y4 1
D~
ZC
M S4
BC
2

(51) (53) (73) (11) 91 31 41 71 61 63 23 33 83 93


(52) S5
(54) S5
S5 (12) S5 92 32 42 72 62 64 24 34 84 94 S5
(74)
(5) (2)
K0
(3)

43 43
44 S8 44 S9
(21) (13) (21)

(22) S3 (14) S3 (22) S1

36 34 35 20 53 54 31 32 16 13 15 17 19 33 37 38 39 18 40

11 2 4 47 57 55

13 33 23 53

14 S9 S9 S9 54 S9
34 24

13 33 23 53
14 34 24 54
S8 S8 S8 S8

21 43 13 81
22 S5 44 S5 14 S5 S5
82

21 22 51 50 12 14 48 49 58 56

S9: Limit switch (working position) CC: Closing coil KO: Anti-pumping relay (optional)
S8: Limit switch (testing position) TC: Trip coil BC: Electromagnet for locking (optional)
S4: Electromagnet for locking's auxiliary switch M: Spring Charge Motor ZC: Electomagnet for locking truck (optional)
S5: Auxiliary switch V1~V4: Rectitier
S1~S3: Energy storing travel switch

Note:
1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state. Spare Parts
2. The polarity in dashed frame should be connected to common DC voltage terminal.
3. Rectifier will be removed if DC is applied.

47
SecoGear 3.3kV-27kV Air Insulated Switchgear

Internal wiring diagram (AC) 27kV

Spring Charge Motor Closing Circuit Breaker Interlock Circuit Opening Circuit Truck Interlock Circuit

26 24 25 10 52 30 6 3 5 7 9 23 27 28 29 8 1

V2 V4 V3

CC
V1 K0
TC V5 A~
(13) C+ B-
(14) S2 Y4 1
D~
ZC
M S4
BC
2

(51) (53) (73) (11) 91 31 41 71 61 63 23 33 83 93


(52) S5
(54) S5
S5 (12) S5 92 32 42 72 62 64 24 34 84 94 S5
(74)
(5) (2)
K0
(3)

43 43
44 S8 44 S9
(21) (13) (21)

(22) S3 (14) S3 (22) S1

36 34 35 20 53 54 31 32 16 13 15 17 19 33 37 38 39 18 40

11 2 4 47 57 55

13 33 23 53

14 S9 S9 S9 54 S9
34 24

13 33 23 53
14 34 24 54
S8 S8 S8 S8

21 43 13 81
22 S5 44 S5 14 S5 S5
82

21 22 51 50 12 14 48 49 58 56

S9: Limit switch (working position) CC: Closing coil KO: Anti-pumping relay (optional)
S8: Limit switch (testing position) TC: Trip coil BC: Electromagnet for locking (optional)
S4: Electromagnet for locking's auxiliary switch M: Spring Charge Motor ZC: Electomagnet for locking truck (optional)
S5: Auxiliary switch V1~V4: Rectitier
S1~S3: Energy storing travel switch

Note:
1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.
Spare Parts

2. The polarity in dashed frame should be connected to common DC voltage terminal.


3. Rectifier will be removed if DC is applied.

48
SecoGear 3.3kV-27kV Air Insulated Switchgear

Internal wiring diagram (AC) 17.5kV/27kV (with UVB)

motor circuit closing circuit locking circuit opening circuit latch circuit

24 25 10 52 30 6 3 5 7 9 23 27 28 29 8 1
26

V2 V4 V3

CC
V1 K0
TC V5 A~
(13) C+ B-
(14) S2 Y4 1
D~
ZC
M S4
BC
2

(51) (53) (73) (11) 91 31 41 71 61 63 23 33 83 93


(52) S5
(54) S5
S5 (12) S5 92 32 42 72 62 64 24 34 84 94 S5
(74)
(5) (2)
K0
(3)

43 43
44 S8 44 S9
(21) (13) (21)

(22) S3 (14) S3 (22) S1

36 34 35 20 53 54 31 32 16 13 15 17 19 33 37 38 39 18 40

UVR circuit

43 11 2 4 47 57 55

13 33 23 53

14 S9 S9 S9 54 S9
34 24

MM UM

13 33 23 53
14 34 24 54
S8 S8 S8 S8

21 43 13 81
22 S5 44 S5 14 S5 S5
82

44 21 22 51 50 12 14 48 49 58 56

S9: Limit switch (service position) CC: Closing coil UM: UVR
S8: Limit switch (test position) TC: Opening coil V1~V5: Rectifier
S4: Electromagnet for locking's A.S. M: Motor K0: Anti-pumping relay (optional)
S1~S3: Energy storing travel switch MM:UVR PCB(optional) ZC: Electromagnet for locking truck(optional)
S5: Auxiliary switch BC: Electromagnet for locking (optional) Spare Parts

Note:
1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.
2. The polarity in dashed frame should be connected to common DC voltage terminal.

49
SecoGear 3.3kV-27kV Air Insulated Switchgear

Component

Current Transformer Ground Fault Sensing CT Voltage Transformer


Current transformers are cast in resin, and It is of the type insulated in resin and Voltage transformers are cast in resin,
totally enclosed. This provides superior is used to supply measurement and and totally enclosed. This provides
protection against pollutants and moisture. protection devices. These CTs can be superior protection against pollutants
It can be equipped with one or more furnished in either a solid or split core and moisture. It can be equipped with
independent magnetic cores with equal design. They can be used either for one or more independent magnetic cores
or different characteristics for measuring, measuring phase currents or for detecting with equal or different characteristics
metering and protection purposes. the earth fault current. They conform to for measuring, metering and protection
Current 1250A the CT type is LZZB-17 the IEC 60044-1 Standards. purposes.
150A1 or A4 CT type: LMZC
Current > 1250A the CT type is LMZB1-17
17.5kV 27kV
VT type: VT type:
Recommended CT JDZ17-15A JDZ11-25
JDZX11-15C JDZX11-25E
Primary Current Type Ratio Accuracy Class Protection Class
Fuse type: Fuse type:
0.5 or 0.5s
500/5A 5P or 10P
0.2 or 0.2s XRNP 17.5/1A JDZX15-25R
0.5 or 0.5s
500/1A 5P or 10P
0.2 or0.2s
500A 25kA/3s LZZB-17 500
0.5 or 0.5s
500-250/5A 5P or 10P
0.2 or 0.2s
0.5 or 0.5s
500-250/1A 5P or 10P
0.2 or0.2s
0.5 or 0.5s
1000/5A 5P or 10P
0.2 or 0.2s
Spare Parts

0.5 or 0.5s
1000/1A 5P or 10P
0.2 or0.2s
1000A 25kA/3s LZZB-17 1000
0.5 or 0.5s
1000-500/5A 5P or 10P
0.2 or 0.2s
0.5 or 0.5s
1000-500/1A 5P or 10P
0.2 or0.2s
0.5 or 0.5s
3000/5A 5P or 10P
0.2 or 0.2s
0.5 or 0.5s
3000/1A 5P or 10P
0.2 or0.2s
3000A 25kA/3s LZZB-17 3000
0.5 or 0.5s
3000-1500/5A 5P or 10P
0.2 or 0.2s
0.5 or 0.5s
3000-1500/1A 5P or 10P
0.2 or0.2s

50
SecoGear 3.3kV-27kV Air Insulated Switchgear

Voltage Transformer
Truck
The withdrawable trucks also allow Earthing Switch
replacement of the fuses with the
switchboard in service. Truck racking- The earthing switch can be operated

out with the door closed automatically from the front of the switchgear. It is

operates closure of a metallic segregation mechanically interlocked with the circuit

shutter between the live parts of breaker truck so that the earthing switch

the switchgear and the instrument can only be operated when the circuit

compartment. breaker is open in the Test/Disconnect


position as well. The switch is also
mechanically interlocked with the cable
compartment for additional safety.

Earthing switch characteristics

Specification Unit Data


Rated voltage kV 7.2/12/15/17.5 24 27
Rated Work frequency withstand voltage (1min)
kV 20/28/36/38 50 65
in open condition of switch
Rated Lighting impulse withstand voltage (peak value)
kVp 60/75/95/95 125 125
in open condition of switch
Spare Parts
Rated short-time withstand current (3s) kA 31.5/40 31.5
Rated peak value withstand current kAp 82/104 82
Rated short circuit making current kAp 82/104 82
Centre distance between phases mm 170/210/275 220/275
Electric endurance class E1 E1
Mechanical endurance Times 2000 2000

51
SecoGear 3.3kV-27kV Air Insulated Switchgear

Cable Connection
The cable compartment contains current Max. cross
Max. number of Range of cable Range of
transformers, voltage transformers (fixed), Rated voltage Panel width section of
parallel cables clamp reducer ring
cables
withdrawable, and earthing switch, (kV) (mm) per Phase (mm2) (mm) (mm)
depending on the individual operating 650 3*
requirements. 7.2/12/15/17.5/27 800 4* 630 35-54 27-62

The cable compartment is constructed for 1000 4*

installation of three current transformers. * If more cable required need increase the depth of switchgear.
When all the three current transformers
are not required, dummies can be installed
in their place to maintain the same
installation and connection procedures.
The fixed voltage transformers (optional)
are connected on the primary side
with busbar and fitted with HRC fuses.
The earthing switch can be operated
by manual, with position indicated by
mechanical indicator on the driveshaft
and the auxiliary switch. Three surge
arrestor (optional) can be mounted in the
space available.

Operation Tool

Gear door locks key Rack handle for truck Earthing switch handle
Spare Parts

52
SecoGear 3.3kV-27kV Air Insulated Switchgear

Installation guide

Installation Guide
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

53
SecoGear 3.3kV-27kV Air Insulated Switchgear

Installation Guide
In order to obtain an optimum installation sequence and ensure
high quality standards, site installation of the switchgear should
only be carried out by specially trained personnel, or supervised
and monitored by qualified personnel, or by personnel supervised
and monitored by responsible persons.
On commencement of installation on site, the switch-room
must be fundamentally finished, provided with lighting and the
electricity supply, lockable, dry and with facilities for ventilation,
It is also required that the basic frame and indoor ground
of substation should be checked and accepted before the
construction, It must be ensure that the ceiling height is sufficient
for the opening travel of the pressure relief plates and clearance
for exhaust.
Tolerances for laying the floor frame are:
Evenness tolerance: 1mm within a measuring length of 1m,
Straightness tolerance: 1mm per 1m, but not more than 3mm
over entire length of frame.

Panel layout for switchgear arrangement


800

Power Cable Duct


1400 for 17.5kV
1800 for 27k

SecoGear P/V

Control Cable Duct


1200 n*650/800/1000 1200
2500

Control Cable Duct


1400 for 17.5kV
1800 for 27k

SecoGear P/V
Installation guide

Power Cable Duct


800

54
SecoGear 3.3kV-27kV Air Insulated Switchgear

Switch room cable duct arrangement

17.5kV 400 250

For 650mm panel

800
Power Cable Duct

70
150
40
760
1400

1400
Basic Frame
1360
280 210

30
250
Control Cable Duct

550 250

For 800mm panel

800
Power Cable Duct

70
150
40
760
1400

1400
Basic Frame
1360
280 210

30
250

Control Cable Duct

750 250
800

For 1000mm panel Power Cable Duct


70
150
40

Installation guide
760
1400

1400

Basic Frame
1360
280 210

30
250

Control Cable Duct

55
SecoGear 3.3kV-27kV Air Insulated Switchgear

Switch room cable duct arrangement

27kV 600

Power Cable Duct

800
70
150
Basic Frame
1800

1800
1700

30
800

800

Power Cable Duct

800
70
150
Basic Frame
1800

1800
1700

30

1000
Installation guide

56
SecoGear 3.3kV-27kV Air Insulated Switchgear

Cross section view of switchgear room layout

17.5kV

800 1500

2200
70 1400 30
Top Curface of basic frame
3~5mm above ground

Basic Frame
150 0.0m
280

-0.25m
380

Strap of control cable duct


Figured steel plate (t=5mm)

Control Cable Duct 250*250

800 300 760


Power Cable Duct 800*1000

27kV

800 1900
2400

70 1800 30
Top Curface of basic frame
3~5mm above ground

Basic Frame
140 250 +5.0m
130
300

Strap of control cable duct


Installation guide

Figured steel plate (t=5mm)


1200

Control Cable Duct 250*250

800 290 800


Power Cable Duct 800*1000

57
SecoGear 3.3kV-27kV Air Insulated Switchgear

Detail of switchgear cable access cutout

17.5kV
1400

1330
350
30

614x28
C
A

70
200 70

650 545
Width A 650 800 1000
B 400 550 750 Power Cable Control Cable
C 470 620 820

27kV
1800
1700

4-15x20
A
B

54
Installation guide

144 358 190 130

Power Cable
Control Cable
Width A 800 1000
B 600 800
C 595 695

58
Greater China
Shanghai Taiwan
4F, Building 2, CTP, No.1 Hua Tuo Rd. Zhang Jiang Hi-Tech 6F, No. 8, Min Sheng E. Rd., Sec. 3, Taipei 10480
Park, Shanghai, China 201203 T : +886 2 2183 7000
T : +86 21 3877 7888 F : +886 2 2516 6829
F : +86 21 3877 7600

South East Asia


Malaysia Philippines Indonesia
Level 6, 1 Sentral, Jalan Travers, Kuala Lumpur Sentral 8F Net Cube Building, 30th Street, Corner 3rd Avenue, BRI II Tower, 27th floor, Jl. Jend. Sudirman No. 44-46
Kuala Lumpur, Malaysia 50470 Crescent West Park, Global City Taguig 1634 Jakarta 10210
T : +603 2273 9788 T : +63 2 877 7000 T: +62 21 573 0430
F : +603 2273 7988 F : +63 2 846 0629 F: +62 21 574 7089

Thailand Vietnam Singapore


25th floor, CRC Tower, All Seasons Place, 87/2 Wireless Saigon Centre, Unit 1, Floor 7, Le Loi Boulevard, District 1 240 Tanjong Pagar Road, #06-00 GE Tower
Road, Lumpini, Pathumwan, Bangkok 10330 HoChiMinh City Singapore 088540
T : +66 2 648 0240 T : +84 8 3914 6700 T : +65 6326 3718
F : +66 2 648 0200 F : +84 8 3827 8229 F : +65 6326 3015

India
India
Polt No. 42/1 & 45/14, Electronic City-Phase II
Bangalore-560100
T: (080) 41434000
F: (080) 41434199

Australia & New Zealand


Australia New Zealand
125-127 Long Street, Smithfield, Sydney, NSW 2164 Level 1, 8 Tangihua Street, Auckland, North Island
T : +61 2 8788 6911 T : +64 9 353 6706
F : +61 2 8788 7224 F : +64 9 353 6707

North Asia
Japan Korea
11F, Akasaka Park Bldg.,5-2-20, Akasaka, Minato-ku 3rd Floor, GE Tower, 71-3, Cheongdam-dong, Gangnam-gu
Tokyo 107-6111 Seoul, Korea 135-100
T : +81 3 3588 5288 T : +82 2 6201 4501
F : +81 3 3585 3010 F : +82 2 6201 4344

Europe & Middle East


Spain Italy Russia
P.I. Clot del Tufau, s/n, E-08295 Sant Vicen de Castellet Centro Direzionale Colleoni, Via Paracelso 16 27/8, Electrozavodskaya street, Moscow, 107023
T: +34 900 993 625 Palazzo Andromeda B1, I-20041 Agrate Brianza (MB) T: +7 495 937 11 11
T: +39 2 61 773 1
Belgium South Africa
Nieuwevaart 51, B-9000 Gent Netherlands Unit 4, 130 Gazelle Avenue, Corporate Park Midrand 1685
T: +32 (0)9 265 21 11 Parallelweg 10, Nl-7482 CA Haaksbergen P.O. Box 76672 Wendywood 2144
T: +31 (0)53 573 03 03 T: +27 11 238 3000
Finland
Kuortaneenkatu 2, FI-00510 Helsinki Germany United Arab Emirates
T: +358 (0)10 394 3760 Robert-Bosch Str. 2a, 50354 Hrth-Efferen 1101, City Tower 2, Sheikh Zayed Road,
T: +49 (0) 2233/ 9719-0 P.O. Box 11549, Dubai
France T: +971 43131202
Paris Nord 2, 13, rue de la Perdrix Portugal
F-95958 Roissy CDG Cdex Rua Camilo Castelo Branco, 805, Apartado 2770 United Kingdom
T: +33 (0)800 912 816 4401-601 Vila Nova de Gaia Houghton Centre, Salthouse Road, Blackmills,
T: +351 22 374 60 00 Northampton
Poland NN4 7EX
Ul. Odrowaza 15, 03-310 Warszawa Hungary T: +44 (0)800 587 1239
T: +48 22 519 76 00 Vaci ut 81-83. H-1139 Budapest
and T: +36 1 447 6050
Ul. Leszczyska 6, Bielsko-Biaa 43-300
T: +48 33 828 62 33

Latin America
Latin America Brazil
790 N.W. 107th Avenue, Suite 200, Miami, Fl 33172 USA Av. Mara Coelho Aguiar, 215, Bloco C - 6.Andar
T: +1 305 551 5155 Jd.So Luiz, 05804-900, So Paulo
T: +55 11 36141900
Chile
Vespucio Norte, Avenida Presidente Eduardo Frei Mexico
Montalva 6001, Edificio N 66 Av. Churubusco 3900 Nte, Col. Industrial Benito Jurez
Comuna: Conchal, Sector el Cortijo, Santiago Monterrey, N.L. 64517
T: (56 2) 928-4700 T: (01-800) 800-1968

North America
USA
41 Woodford Avenue, Plainville CT, USA 06062
and
12305 Kurland Drive, Houston, TX USA 77034
T: +1 800-431-7867
GE
Industrial Solutions

You may be interested in other MV Seco-family products


For more information, please visit www.geindustrial.com