1 The design, installation and testing of Clean Agent Systems shall be in Applicable Codes
accordance with these regulations and the NFPA 2001. and regs
2 Only clean agents specifically approved by the Qatar Civil Defence shall be
used.
3 The use of CO2 is prohibited without specific approval from the QCD. Such
approval will only be granted on the basis of a formal engineering analysis that
concludes to the satisfaction of the QCD, that alternative clean agents are not
able to satisfactorily extinguish the fire.
4 Clean Agent storage containers shall not be stored within the protected Location of
enclosure. storage containers
They shall be easily accessible from the main entrance of the protected
enclosure.
5 A manual mechanical means of discharging the required agent shall be provided Mechanical
on the storage container. actuation
7 The Control Panel shall be located external to the protected enclosure and Control Panel
located near the main entrance to the protected enclosure.
The Control Panel shall be connected to the Buildings Main Fire Alarm Panel
and shall provide Alarm, Gas Discharged and Fault indications on the Main
Panel.
8 Gas discharge shall only occur after a predetermined time delay to be approved Gas discharge
by the QCD. delay timer to
The time delay shall be interrupted by the operation of the Abort Switch and allow occupants
shall re-commence on release of the Abort Switch. escape
The minimum delay shall be 20 seconds.
9 At least one Manual Release Push Button shall be provided external to the Manual Release
protected enclosure and mounted within 1.5m of the main entrance.
Subject to the size and configuration of the protected enclosure, more than one
Manual Release push button may be required.
Operation of the Manual Push Button shall cause instant release of the clean
agent.
8 An Abort Switch that interrupts the countdown delay timer shall be provided Abort Switch
within the protected enclosure and mounted within 1.5m of the main entrance.
Subject to the size and configuration of the protected enclosure, more than one
9 "DO NOT ENTER - GAS DISCHARGED" illuminated signs shall be external Gas Discharge
to the protected enclosure and mounted above all entrances so as to be visible to signage
any person entering.
The lettering shall be a minimum of 50mm high. It shall be visible at all times
of the day.
The illumination shall be activated by a pressure switch fitted to the discharge
piping.
10 All enclosures protected by clean agent systems that are required by code to be Enclosure
provided with an extinguishing system, in the absence of sprinkler protection, considerations
must be constructed from 2 hour fire resistant elements.
11 Subject to the location of the enclosure, its integrity (to be verified through
testing) and the type and nature of the clean agent used, ventilation system to
purge the gas after discharge may be required by the QCD. Due consideration
shall be given to this aspect of the system.