You are on page 1of 13

Supplemental

Operation and Maintenance


Instructions Manual
for

CLARKE PLD ENGINE MODELS

Clarke UK, Ltd. Clarke Fire Protection Products, Inc.


Unit 1, Grange Works 3133 E. Kemper Road
Lomond Road Cincinnati
Coatbridge Ohio
ML5 2NN 45241
United Kingdom United States
TELE: +44(0)1236 429946 TELE: +1.513.771.2200 Ext. 427
FAX: +44(0)1236 427274 FAX: +1.513.771.5375

www.clarkefire.com

10/11
C131042 rev L
CONTENTS
SUBJECT PAGE
1. OVERVIEW AND PRINCIPLES OF OPERATION 2
1.1 IDENTIFICATION/NAMEPLATE 3
1.2 PLD ENGINE MODELS 3
2. INSTALLATION INSTRUCTIONS 3
2.1 CONNECTIONS 3
2.1.1 Supply 3
2.1.2 Drain 4
2.2 START-UP INSPECTION INSTRUCTIONS 6
2.2.1 Closing-Off the Speed Control System 6
2.2.2 Initial Start Up 6
2.2.3 Bleeding the Speed Control System 6
2.3 OPERATION 6
2.3.1 Freeze Protection 6
2.3.2. Failure Mode 6
Light (on Clarke engine gauge panel) 7
Reset Switch (on Clarke engine gauge panel) 8
2.3.3 Adjustments 9
3. ENGINE SYSTEMS 9
3.1 ELECTRICAL SYSTEM 9
3.1.1 Wiring Diagram 9
4. MAINTENANCE 10
4.1 STRAINERS Inspect every 6 months and may require more frequent depending
upon the quality of the sprinkler system water supply 10
4.2 THROTTLE LINKAGE - Inspect weekly 10
4.3 DAMPER FLUID Inspect weekly. Refill with Dot 5 Silicone Brake Fluid 10
4.4 WEEKLY EXERCISE Record pump shutoff pressure and engine RPM 10
5. TROUBLESHOOTING 10
5.1 DAMPER FLUID RISE 10
5.2 DAMAGED BOOT 10
5.3 CYLINDER LEAK 10
5.4 CONTACT INFORMATION 10
Appendix A 11,12
NOTE
The information contained in this book is intended to assist operating personnel by providing information on the characteristics of the
purchased equipment.

It does not relieve the user of their responsibility of using accepted practices in the installation, operation, and maintenance of the
equipment.

NOTE: CLARKE FPPG Reserves the right to update the contents of this publication without notice.

Page 1 of 12
1. OVERVIEW AND PRINCIPLES OF Note: With most pressure control systems there
OPERATION is some pressure overshoot upon start up (see
figure #1).
The Pressure Limiting Driver (PLD)
incorporates a Speed Control System used to
limit the total discharge system pressure by
reducing the pump driver speed from the rated
speed. When activated, this Speed Control
System continuously senses system discharge
pressure via a dedicated line and will reduce the
engine speed as necessary to limit system
discharge pressure from a pre-determined set
point. Figure #2 shows a typical sprinkler Figure #1
system performance curve with and without the
PLD Speed Control System activated. With the During the brief (1-2 second) period of pressure
PLD Speed Control System activated, and the overshoot, the main relief valve will pop open
engine running, there may be a continuous water discharging some water and there-by relieving
flow from the PLD device to a suitable drain. this pressure. This is best accomplished by
The hydro/mechanical PLD Speed Control setting the pressure relief valve 5-10 psig above
System requires additional engine installation the sprinkler system design working pressure.
steps, start-up inspection checks, and has its
own maintenance requirements.

Figure #2

Page 2 of 12
This supplemental operators manual only 50 = A power rating code
pertains to the PLD features of the Clarke P1 = Suffix to signify a PLD equipped
Engine. This manual should be used in Engine
conjunction with the following manuals:
Smart p/n Clarke internal p/n to establish
JU/JW Models engine bill of material
Operators Manual - C13960
Technical Catalog - C13965 Mfg S/N = Engine S/N
VM Models
Operators Manual C13217 Rated Speed = Engine Rated Speed
Technical Catalog C131024
Rated Power = Engine Rated HP
1.1 IDENTIFICATION/NAMEPLATE
Control Pressure=
In addition to the information on a standard Factory Set Point Pressure. Engine will
engine nameplate, the PLD equipped Clarke begin to slow down once this system
Engine models are also identified by a specific pressure is exceeded.
engine model number on the Clarke nameplate.
The Clarke nameplate also includes: Control System Max. Pressure=
Pressure Set Point, System Maximum Pressure, Maximum Working Pressure of the
Variable Speed Pressure Limiting Control Sprinkler System.
(VSPLC) Rating, and Minimum Operating
Speed. (Ref. Fig #3). VSPLC Rating, Z=
Variable Speed Pressure Limiting
Control Rating Z Factor. This Z
value, when multiplied by the pump
differential shut-off pressure, gives the
maximum pressure trimming capability
of the PLD equipped engine.

Minimum Operating Speed=


Minimum reduced speed the PLD
equipped engine can operate at.

1.2 PLD ENGINE MODELS

Refer to appendix A on page 11 & 12 of this


Figure #3 manual for PLD equipped Clarke Engine
Example: Models.
Model: JU6H-UF50-P1
J = John Deere base engine prepared by 2. INSTALLATION INSTRUCTIONS
Clarke
U = base engine series (4.5 liter, 4 2.1 CONNECTIONS
cylinder or 6.8 liter, 6 cylinder)
6 = number of cylinders 2.1.1 Supply
H = Heat Exchanger cooled
UF = Underwriters Laboratories Listed/ Engine is provided with a single connection
Factory Mutual Approved block for pressure sensing, incorporating
supply and drain connections. Connections
Page 3 of 12
are labeled appropriately. Supply suitable drain. (NOTE: The drain line must
connection from the sprinkler system must not be connected to the engine cooling loop
be made between the pump discharge flange drain.) A (12.7mm) nominal size inside
and the discharge check valve. (NOTE: diameter pressure line shall be used.
The supply line must not be connected to the
engine cooling loop.) A (12.7mm) CAUTION: The highest point in the
nominal size inside diameter pressure line drain line should not be any higher than
shall be used. Supply line must be rated for 6 above the engine drain line
the maximum potential system pressure. connection block on the engine.
(See Figure #4).
(NOTE: Under normal operating conditions
2.1.2 Drain the maximum flow through this drain line
should not exceed 2 GPM). (See figure #4).
Drain line must run from connection block
on engine to atmosphere, terminating near a

Page 4 of 12
Figure #4

Page 5 of 12
2.2 START-UP INSPECTION NOTE: The purpose of this
INSTRUCTIONS indicating, shut-off valve is to allow
for testing of the pump with the PLD
2.2.1 Closing-off the PLD Speed Control Speed Control System de-activated.
System This only occurs during initial start-
up and during the annual pump test.
System has 3 drain cocks that must be
closed, and 2 strainer plugs, shipped loose, 2.2.3 Bleeding the PLD Speed Control
that must also be installed. System

2.2.2 Initial Start Up At initial start-up, with the PLD Speed


Control System activated (Section 2.2.2),
Verify damper fluid level per Figure and the engine running, open the drain cock
6. Do not overfill. at the top of the cylinder (See Figure #4) to
De-activate the PLD Speed Control bleed out any air.
System by closing the indicating
shut-off valve (See figure #4). 2.3 OPERATION
Close the sprinkler system main
discharge valve and then start the 2.3.1 Freeze Protection
engine. (Note: Refer to engine
operators manual to assist with start Protect the unit from freezing.
and stopping instructions for the
engine.) 2.3.2 Failure Mode
Set engine rated speed with pump
operating at rated flow (GPM). In the event that the PLD Speed Control
Record the discharge pressure and System fails, the system will de-activate
engine speed at shutoff (0 GPM) for itself and return the engine to rated speed.
future reference. When this failure occurs, an indicating light
Activate the PLD Speed Control will illuminate on the engine instrument
System by opening the indicating panel (See Figure #5). Investigate the cause
shutoff valve. (See Figure #4). and make necessary corrections before
You may or may not observe a lifting the cover and pressing the PLD
reduction in speed. The greatest failure reset switch(See figure #5).
speed reduction will occur with the
pump running at shut-off (0 GPM). NOTE: This operation must be completed
Reduce flow back to shut-off and to allow the PLD Speed Control System to
record the change in discharge be re-activated.
pressure and engine RPM from
values recorded above. In no case Operational Note (See figure #4 detail):
should the discharge pressure be Normal operating pressures with-in the PLD
greater than the maximum allowed cylinder connected to the engine throttle
system pressure. range from 0-25 psig. The normally open
The normal position of the indicating contact of the pressure switch at the top of
shut-off valve, that is part of the PLD the PLD cylinder is rated to close at 75 psig.
Speed Control System (See Figure When the pressure switch contacts close, the
#4), is in the open position. It is 3 way solenoid valve will be switched
recommended that a tamper proof, allowing flow through the PLD over speed
locking device be used to maintain emergency drain, which removes the
this valve in this position. pressure in the PLD cylinder, which returns
the engine throttle to rated speed.
Page 6 of 12
Page 7 of 12
Figure # 5
1 Emergency Operating Instructions 5 Warning Light
2 Automatic Manual Mode Selector 6 Overspeed Verification
3 Manual Crank Controls 7 PLD Over-pressure Failure Light
4 Overspeed Reset 8 PLD Over-pressure Reset Switch
2.3.3 Adjustments

There are no field adjustments; other than


fine tuning the throttle adjustment when
setting the engine rated speed with pump
operating at rated flow (Section 2.2.2).

3. ENGINE SYSTEMS

3.1 ELECTRICL SYSTEM

3.1.1 Wiring Diagram


Refer to Figure #6 for the wiring
diagram that shows the additional
circuits added to a PLD equipped
engine. Note, for the standard engine
wiring diagram refer to the appropriate
technical catalog as listed in section 1.0
of this manual.

Page 8 of 12
Figure #6

Page 9 of 12
4. MAINTENANCE (Note: It will be necessary to reset the
throttle during rated flow test.)
4.1 STRAINERS Inspect every 6 months.
May require more frequent inspections 5.4 CONTACT INFORMATION
depending upon the quality of the www.clarkefire.com
sprinkler system water supply. Phone (513) 771-2200 Ext. 427
Fax (513) 771-5375
4.2 THROTTLE LINKAGE Inspect E-Mail: parts@clarkefire.com
weekly.

4.3 DAMPER FLUID Inspect weekly.


Refill damper fluid reservoir with Dot 5
Silicone Brake Fluid if fluid level drops.
Maintain fluid level per Figure #7.

Damper Fluid Reservoir Oil Level Range


Figure #7

4.4 WEEKLYWEEKLY EXERCISE


Record pump shutoff pressure and
engine RPM. Maintain weekly
readings in a log for future reference.

5. TROUBLESHOOTING

5.1 IF DAMPER FLUID RISES Damper


fluid level will rise and fall during the
course of normal engine operation. If
maintenance level has increased after
normal operation, replace cylinder.

5.2 IF BOOT ON CYLINDER ROD IS


DAMAGED - Replace boot.

5.3 IF WATER SEEPS OUT ALONG


CYLINDER ROD - Replace cylinder

Page 10 of 12
Appendix A
VSPLC VSPLC VSPLC
No. of Speed Rating - Z (1) Rating - Z (1) Rating - Z (1)
Model Cylinders (RPM) HP (HP) (100 psi) (2) (170 psi) (3) (240 psi) (4)
JU4H-UF10-P1 4 1760 41 0.34 0.26 0.34
2100 51 0.56 0.50 0.56
2350 55 0.66 0.61 0.66
JU4H-UF12-P1 4 2350 55 0.66 0.61 0.66
2600 59 0.73 0.59 0.72
JU4H-UF20-P1 4 1760 60 0.34 0.26 0.34
2100 67 0.56 0.50 0.56
2350 72 0.66 0.61 0.66
JU4H-UF22-P1 4 2350 72 0.66 0.61 0.66
2600 75 0.73 0.59 0.72
JU4H-UF30-P1 4 1760 64 0.34 0.26 0.34
2100 79 0.56 0.50 0.56
2350 85 0.66 0.61 0.66
JU4H-UF32-P1 4 2350 85 0.66 0.61 0.66
2600 85 0.73 0.59 0.72
JU4H-UF40-P1 4 1760 94 0.34 0.26 0.34
2100 105 0.56 0.50 0.56
2350 106 0.66 0.61 0.66
JU4H-UF42-P1 4 2350 106 0.66 0.61 0.66
2600 106 0.73 0.59 0.72
JU4H-UF50-P1 4 1760 110 0.34 0.26 0.34
2100 130 0.56 0.50 0.56
2350 127 0.66 0.61 0.66
JU4H-UF52-P1 4 2350 127 0.66 0.61 0.66
2600 127 0.73 0.59 0.72
JU6H-UF30-P1 6 1760 140 0.35 0.35 0.35
2100 160 0.55 0.56 0.55
2350 160 0.64 0.66 0.64
JU6H-UF32-P1 6 2350 160 0.64 0.66 0.64
2600 160 0.71 0.68 0.66
JU6H- 6 1760 173 0.35 0.35 0.35
UFABL0-P1 2100 173 0.55 0.56 0.55
2350 173 0.64 0.66 0.64
JU6H-UF50-P1 6 1760 183 0.35 0.35 0.35
2100 210 0.55 0.56 0.55
2350 210 0.64 0.66 0.64
JU6H-UF52-P1 6 2350 210 0.64 0.66 0.64
2600 210 0.71 0.68 0.66
JU6H-UF60-P1 6 1760 200 0.35 0.35 0.35
2100 240 0.55 0.56 0.55
2350 240 0.64 0.66 0.64
JU6H-UF62-P1 6 2350 240 0.64 0.66 0.64
2600 240 0.71 0.68 0.66

Page 11 of 12
Appendix A (contd)
VSPLC VSPLC VSPLC
No. of Speed Rating - Z (1) Rating - Z (1) Rating - Z (1)
Model Cylinders (RPM) HP (HP) (100 psi) (2) (170 psi) (3) (240 psi) (4)
JWH-UF30-P1 6 1760 265 0.34 0.34 0.34
2100 275 0.50 0.41 0.50
2350 275 0.62 0.47 0.61
JWH-UF40-P1 6 1760 290 0.34 0.34 0.34
2100 300 0.50 0.41 0.50
2350 300 0.62 0.47 0.61
JWH-UF50-P1 6 1760 300 0.34 0.34 0.34
2100 340 0.50 0.41 0.50
2350 350 0.62 0.47 0.61
JWH-UF60-P1 6 1760 360 0.34 0.34 0.34
2100 375 0.50 0.41 0.50
2350 360 0.62 0.47 0.61
VMFP-04HN-P1 4 2800 55 0.63 0.63 0.63
3000 56 0.69 0.69 0.69
3300 56 0.75 0.75 0.75
3600 60 0.68 0.69 0.69
VMFP-04HT-P1 4 2800 80 0.63 0.63 0.63
3000 83 0.69 0.69 0.69
3300 86 0.75 0.75 0.75
3600 87 0.68 0.69 0.69
VMFP-06HT-P1 6 2800 104 0.63 0.63 0.63
3000 115 0.69 0.69 0.69
3300 120 0.75 0.75 0.75
3600 115 0.68 0.69 0.69
VMFP-T6HT-P1 6 2800 135 0.63 0.63 0.63
3000 140 0.69 0.69 0.69
3300 143 0.75 0.75 0.75
3600 145 0.68 0.69 0.69
VMFP-L6HR-P1 6 2800 155 0.63 0.63 0.63
3000 160 0.69 0.69 0.69
3300 163 0.75 0.75 0.75
3600 165 0.68 0.69 0.69
VMFP-T6HR-P1 6 2800 160 0.63 0.63 0.63
3000 175 0.69 0.69 0.69
3300 180 0.75 0.75 0.75
3600 185 068 0.69 0.69

Notes:

1. Z Factor value shown is the maximum pressure trimming capability. The actual Z Factor, as shown on the
nameplate, may be less than this maximum published value. Associated with the Z Factor is a minimum operating
speed which is also shown on the nameplate. Each engine has a minimum RPM it can operate at. Minimum RPM is
based upon several factors, therefore in order to determine if the Clarke PLD equipped engine can trim enough
pressure for a particular installation, it will be necessary to run Clarkes PLD Calculator program. This can be
accessed through Clarkes website, www.clarkefire.com or by consulting the factory.
2. 100 psi factory set point (100 110 psi control range).
3. 170 psi factory set point (170 175 psi control range).
4. 240 psi factory set point (240 250 psi control range).

Page 12 of 12