Professional Documents
Culture Documents
09-15-17
BSCHE-V
Experimental Study
the cooling water flow rate. In this heating/cooling scheme, the inlet flowrate
of cooling water and the input power to the heater is the manipulated inputs.
T
RTD
T
N2 Gas
T
RTD
Reactor
Heater
Coolant
Control Strategies
1. FEEDFORWARD CONTROL
value of the controlled output from its desired set point. On the other hand, a
appropriate control action in order to eliminate its effect on the process output.
Consider the distillation column shown in Fig (1) The control objective
(disturbance) and adjusts the reflux ratio appropriately. Fig (b) shows the
2. CASCADE CONTROL
corrective action for disturbances does not begin until after the controlled
variable deviates from the setpoint. In other words, the disturbance must be
felt by the process before the control system responds. Feedforward control
offers large improvements over feedback control for processes that have large
BOSE, JUDY ANN D. 09-15-17
BSCHE-V
time constant and/or delay. However, feedforward control requires that the
3. RATIO CONTROL
disturbances are measured and their ratio is held at a desired set point by
controlling one of the streams. The other uncontrolled stream is called wild
stream. Figure shows the schematic of a ratio controller. The ratio of flow rates
of two streams are being held at a desired ratio by controlling the flow rate of
one stream. The flow rates are measured through flow transmitters (FTs).
BOSE, JUDY ANN D. 09-15-17
BSCHE-V
The chemical process industries have various applications for ratio controllers.
4. OVERRIDE CONTROL
destruct the process or its personnel. In such case the normal operation should
purpose switch can be used that can take preferential instruction from one
controller over the others to manipulate the final control element in such a
way that the dangerous situation can be averted. This is called override
Consider a boiler shown in the Fig. It has one water inlet and one steam
outlet. The steam outlet is regulated by the valve in the discharge line that
takes the control signal from the control mechanism in Loop1 (pressure
regulated on the basis of its pressure desired in the supply line elsewhere.
However, the water is boiled using a heating coil that needs to be always
submerged below the water level so that the heating coil does not burn out.
Hence, in order to ensure a certain minimum level of water inside the boiler,
the control Loop 2 is set in place that contains a level transducer and a level
BOSE, JUDY ANN D. 09-15-17
BSCHE-V
controller. Both level controller and pressure controller give the control signal
to the valve through an intermediate switch LSS (Low Selection Switch) that
takes the preferential signal from the level controller. In other words, Loop 2
remains inactive during the normal operation and the Loop 1 regulates the
process. Nevertheless, at critical situation when the water level drops below
the minimum allowable limit, the Loop 2 takes over and takes corrective
measures.
5. AUCTIONEERING CONTROL
regulated through a single control action. Thus it is evident that the said
Consider a tubular reactor shown in the Fig. The reaction is exothermic and
hence the temperature inside the reactor needs to be regulated. However, the
temperature varies along the length of the tube and if the corrective action,
i.e. the coolant flow rate, is taken on the basis of highest temperature
measurement, it will ensure that the other temperature zones are also
When there are more than one manipulated inputs available for one
single controlled output then Split Range Control scheme can be implemented.
Consider a reactor shown in the Fig . The pressure inside the reactor
needs to be controlled. The control valve is available in both inlet and outlet
lines. Hence the control action can be coordination between two valves. When
the pressure is low, inlet valve should be FULLY OPEN and when the pressure
is high, outlet vale should be FULLY OPEN In either care the other valve needs
action.
7. ADAPTIVE CONTROL
for a process is very much domain specific. First the model of the process is
linearized around a certain nominal point and the controller is designed on the
BOSE, JUDY ANN D. 09-15-17
BSCHE-V
basis of that linearized model and finally implemented on the process. Hence,
the controller is applicable for certain domain around the nominal operating
Adaptive control
K overall K c K p K m K f
K overall
Kc
K p KmK f
BOSE, JUDY ANN D. 09-15-17
BSCHE-V
When the process is poorly known, one cannot rely much on the correctness
self adaptive controllers are Model Reference Adaptive Control (MRAC) and
8. INFERENTIAL CONTROL
Often the process plant has certain variables that cannot be measured
Inferential Control
y1 G y1u u G y1d d
y 2 G y 2u u G y 2 d d
1 G
d y 2 yzu u
Gy d Gy d
z z
And hence,
1 G
y1 G y1u u G y1d y 2 yzu u
G yz d
Gy d
z
G y1d G y1d
y 2 G y u G y u u
Gy d
1 Gy d z
z z
BOSE, JUDY ANN D. 09-15-17
BSCHE-V
in this case).