You are on page 1of 20

S No. Page No. Clause No.

Description
Architectural design and detail engineering
1 1013 7.10 FFL

2 1014 7.20 Steps/Ramps

3 1014 7.30 wall

4 1015 7.40 Doors

5 1015 7.50 windows/ventilators


6 1016 7.60 canopy/over hang
7 1016 7.80 parapet

8 1018 7.18 toilet


9 1019 7.23 plinth protection
Packaged equipment
1 1023 4.10 chain pulley block

2 1023 4.20 electric wire rope hoist


3 1023 4.30 EOT & HOT CRANE
ELECTRICAL
1 1030 4.00 control-protection-metering
2 1034 5.00 sub station design
3 1035 6.40 transformers
4 1036 6.80 control supply voltage
5 1036 6.90 motors
6 1037 6.15 cables
7 1038 7.10 cable details
8 1038 7.20 cable laying philosophy
9 1039 9.20 control philosophy
10 1040 11.00 cable sizes for 415V motors
11 1041 13.00 spare parts
Instrumentation
1 1048 1.20 control room requirements
2 1049 1.30 type of control and monitoring
3 1051 3.00 station control system requirements

4 1053 5.10 units of measurement


4 1053 5.10 units of measurement

5 1057 6.00 other instrumentation and systems


SCADA SYSTEM
1 1060 1.00 type of fluid handled in STP & SPS
2 1061 8.00 system operating system
3 1063 10.00 functional requirements
Geo-technical data
1 1067 5.00 ground water table

2 1067 6.10 major foundations

3 1068 7.00 under groung piping

4 1068 11.00 backfilling


Surface preparation and protective coating system for STP
1 1075 3.00 Paint materials
2 1076 4.00 coating systems
3 1076 5.00 coating application
Job specification(Architecture)
1 1087 5.20 internal finishes
2 1091 6.2.2 cement concrete granolithic flooring
3 1091 6.2.3 heavy duty cement concrete flooring
4 1092 6.2.5 tile work

5 1093 6.2.6 kota stone flooring


6 1094 6.2.7 acid resistant tiles flooring
7 1095 6.30 doors & windows
8 1103 6.40 plastering & wall finishing
Piping material specification
1 1146 Class-A3A
2 1153 Class-A91S
Job specification ELECTRICAL

1 1158 3.00 site conditions

2 1161 4.70 high voltage cables


Job specification instrumentation
1 1176 3.2.16.3 trenches

2 1148 4.20 field transmitters


2 1148 4.20 field transmitters

1 1211 Pump-non clog submersible pump 1

2 1212 Pump-non clog submersible pump 2

3 1213 inlet chamber

4 1214 coarse screen chamber

5 1217 wet well

6 1219 fine screen chamber feed pump

7 1220 stilling chamber

8 1222 fine screen chamber feed pump

9 1225 grit removal unit

SBR(INFLUENT)

10 1127
SBR(INFLUENT)

10 1127
SBR(EFFLUENT)

SBR(DESIGN CRITERIA)

11 12131 SBR AIR BLOWERS

12 1232 SBR RAS pumps

13 1233 SBR SAS PUMP

14 1234 ClO2 contact tank

15 1235 Sludge sump

16 1237 Thickner feed pump

17 1238 sludge thickner


17 1238 sludge thickner

18 1240 thickened sludge sump

19 1242 sludge sump air blower

20 1243 centrifuge feed pump

21 1244 centrifuge

22 1246 FeCl3 dosing tank

23 1248 FeCl3 dosing pump

24 1249 DWPE dosing tanks

25 1250 DWPE dosing agitators


25 1250 DWPE dosing agitators

26 1251 DWPE dosing pump

27 1252 NaClO2 bulk storage

28 1254 sodium chlorite unloading pumps

29 1255 sodium chlorite dosing pump

30 1256 HCl bulk storage tanks

31 1258 HCl unloading pump

32 1259 HCl dosing pumps

33 1260 ClO2 generator

34 1262 chemical house

35 1264 dilution water pump

36 1265 belt filter press


36 1265 belt filter press

37 1267 combo units


Specifications
n and detail engineering

tread>=260mm
riser<=175mm
slope of ramp<= 1:6
ratio of tread and riser=(2tread+1riser)=600-650mm
no. of risers per flight<=15
blast proof & rain water shaft wall>=230mm thick RCC wall
external walls>=230mm thick brick wall
internal partition wall=230/115 mm thick brick wall
fire wall>=345mm thick brick wall
entrance door size>=1500x2100mm
bath cubicle door=800x2100mm
other doors>=1000x2100mm
total openable area of windows>=15% of floor area
size of overhang>=900mm
non approachable ht.of wall>=300mm
approachable ht. of wall>=900mm
ht. of ceiling=2500-3000mm
min width of 1000mm around building
d equipment
load=0.5MT-5MT & lift<5m
if two in no. each of 75% capacity of total weight shall be provided
load>=5MT & lift>5m

CTRICAL

mentation

flow liquid- MLD@(ambient &15C)


density-Kg/m3
viscosity-centistoke
level-%
pressure-Kg/cm2*(acc. Due to gravity)
temperature- C

A SYSTEM
sewage water

chnical data
designed GWL=existing ground level(egl)
width>=1m

under wind & seismic forces increase net.safe bearing capacity in shear by 25%
E=120Kg/cm2
density of moist soil=1800Kg/m3
K=0.19
layer thickness<=150mm
otective coating system for STP

ion(Architecture)

overall thickness=40mm(25mm base+ 15mm wearing course)


overall thickness=50mm(35mm base+ 15mm wearing course)
size of ceramic tile=300x300x8mm for flooring
size of ceramic tile=100x200x6mm or 300x200x6mm for walls

rial specification

tion ELECTRICAL
max ambient temperature=50C
min ambient temperature=3C
design ambient temperature=40C
altitude above MSL<1000M
11KV shall be three cored
on instrumentation
buried trenches shall have min width of 600mm and depth of 1000mm

transmitter range between 1Kg/cm2*(acc. Due to gravity) - 100Kg/cm2*(acc.


Due to gravity) over range pressure=130Kg/cm2*(acc. Due to gravity)
transmitter range 100Kg/cm2*(acc. Due to gravity) and above over range
2
pressure=210Kg/cm *(acc. Due to gravity) or 130% of max range whichever is
higher

flow rate=350 m3/hr


solids in suspension max size =100mm
discharge pressure =2Kg/cm2*(acc. Due to gravity)
2
differential pressure =2Kg/cm *(acc. Due to gravity)
differential head=20m
2
design pressure=3.2Kg/cm *(acc. Due to gravity)
design temp=65C
solids in suspension max size =100mm
3
flow rate=635m /hr
discharge pressure =3Kg/cm2*(acc. Due to gravity)
differential pressure =3Kg/cm2*(acc. Due to gravity)
differential head=30m
design pressure=4.8Kg/cm2*(acc. Due to gravity)
design temp=65C
min residence time @ peak flow=60sec
no. of compartmens =1
min velocity across the screen=0.6m/sec & max velocity =1.2m/sec
angle of inclination=75
opening of each bar=20mm
thickness of bar=10mm
min residence time @ avg flow=30min
no. of compartmens =1
max size of solid particles=20mm
design pressure=4.5Kg/cm2*(acc. Due to gravity)
min residence time @ peak flow=60sec
min free board =0.5m
min velocity across the screen=0.6m/sec & max velocity =1.2m/sec
opening of each bar=6mm(mechanical)/10mm(manual)
thickness of bar=2mm(mechanical)/8mm(manual)
angle of inclination=45
min detention time @peak flow=60sec
SG of grit=2.65
dia of particle removed=150
type-vortex grit removal
BOD3days,27C=250mg/l
COD=450mg/l
TSS=450mg/l
TVS=200mg/l
TKN=50mg/l
Total Phosphorus=6mg/l
pH=6.5-8
Total alkalinity as CaCO3=460mg/l
BOD3days,27C<=10mg/l
TSS10mg/l
ammoniacal nitrogen10mg/l
total nitrogen10mg/l
Phosphorus2mg/l
pH=6.5-8
F/M ratio(max)=0.12
Min Sludge age=10days
MLVSS =3500mg/l
Oxygen supplied/kg BOD=1.2 (minimum)
Oxygen req /kg ammoniacal Nitrogen =4.6 minimum
min oxygen transfer rate@ field condition =2kg/kg BOD (minimum)
excess DO to be maintained in tank =2mg/l
composition-79%N2 &21% O2
ratio of specific heat K=1.4
compressibility factor=1
operating blowers as standby=min 33% of no. of blowers
liquid density=1050kg/m3
liquid handled - biosludge
solids in suspension-yes,1.3%
dynamic viscosity at pumping temp=1cp
design pressure =3.5Kg/cm2*(acc. Due to gravity)
3
liquid density=1050kg/m
liquid handled - biosludge
solids in suspension-yes,1.3%
dynamic viscosity at pumping temp=1cp
2
design pressure =3.5Kg/cm *(acc. Due to gravity)
3
liquid density=1000kg/m
liquid handled - decanted water from SBR
holding period of tank=60min
dynamic viscosity at pumping temp=1cp
no. of tanks=1
type - open rectangular
liquid handled - biosludge
residence time=4hrs
shape - rectangular/square
3
liquid density=1050kg/m
liquid handled - sludge
solids in suspension-yes
no. of pumps=2(1W+1SB)
2
design pressure =3.5Kg/cm *(acc. Due to gravity)
fluid handled - sludge
suspended solid content at inlet(max)=1%by wt.
suspended solid content in underflow(min)=4%by wt.
suspended solid content in overflow(max)=100mg/l
pH=6.5-7.5
density=1050kg/m3
viscosity=1cp
solid loading(max)=30kg/m2/day
bottom slope=1:8
sludge feeding-from top
type of inlet - centre of feed well
type of overflow arrangement- V-notch
fluid handled -thickened sludge
total residence time(min)=16hr
type of sump-open
no. of compartment-2
gas handled-air
composition-79%N2 &21% O2
ratio of specific heat K=1.4
compressibility factor=1
no. of blowers=2(1W+1S)
liquid handled-thickened biosludge
3
liquid density =1100kg/m
solids in suspension-yes
fluid handled- thickened sludge
pH=6.5-7.5
solids recovery(min)=97% by wt.
solid content(max)=500mg/l
no. of units=2(1W+1SB)
operating cycles=8hr/day
dosing strength=0.1%
liquid handled =10% FeCl3 solution
holding period of tank(min)=12hr
no. of tanks =2
type-closed with removable lids
liquid handled =10% FeCl3 solution
presence of corrosive/toxic components-FeCl3
no. of pumps =2(1W+1SB)
liquid handled -0.1%DWPE solution
nature of liquid-corrosive
holding period of each tank(min)=12hr
no. of tanks=2
type-closed with removable lids
purpose-mixing
operation - batch
solubility-medium
abrasion-low
setteling-nil
degree of agitation-medium
corrosive products-yes
liquid handled -0.1%DWPE solution
no. of pumps=2(1W+1SB)
liquid handled-sodium chlorite
design vacuum pressure-50mm WC
no. of tanks=2
type-circular fixed roof
liquid handled=25-31% NaClO2
corrosive components - yes
solids in suspension-no
no. of pumps =2(1W+1SB)
liquid handled=25-31% NaClO2
presence of corrosive/toxic components-NaClO2
no. of pumps =2(1W+1SB)
liquid stored-30%HCl
SG of liquid at storage temp=1.156
design vacuum pressure-50mm WC
No. of tanks = 2
Type - circular,fixed cone roof
liquid handled =30%HCl
liquid density=1156 kg/m3
no. of pumps =2(1W+1SB)
liquid handled =30%HCl
presence of corrosive/toxic components-HCl
no. of pumps =2(1W+1SB)
solids in suspension-no
liquid handled <1gm/L ClO2 solution
viscosity-1cs
liquid density=1000kg/m3
ClO2 yield =90% (min)
no. of units=2(1W+1SB)
size of cut-out(min)=1.2X1.2m
lime pit details(min)=2
overhead service watertank capacity=5m3
capacity of weighing machine=100kg
drinking water loft tank capacity =1m3
liquid handled - treated sewage
liquid density =1000kg/m3
presence of corrosive/toxic components-ClO2
no. of pumps =2(1W+1SB)
fluid handled-thickened sludge
type and nature of sludge-biological
pH=6.5-7.5
solids recovery(min)=97% by wt.
solid content(max)=500mg/l
no. of units=2(1W+1SB)
operating cycle=8hr/day
duty-intermittent
fluid handled-sludge
type and nature of sludge-biological
influent flow rate(max)=1m3/hr
pH=6.5-7.5
solid recovery(min) = 97%bz wt.
solid content(max)=500mg/l
no. of units=2(1W+1SB)
operating cycles =8hr/day
duty-intermittent
stages-gravity belt thickner+belt filter press combined unit