You are on page 1of 6

Technology Report

February, 2003

VAV Fume Hood Energy Savings and Safety Considerations


Sash Closure vs. Automatic Face Velocity Setback

This report addresses the potential energy savings implementing face velocity setback center around
and safety considerations associated with Variable whether 60 fpm will provide adequate fume
Air Volume (VAV) fume hood control systems that containment even if no one is in front of the fume
offer automatic face velocity setback. Recall that the hood.
purpose of a VAV fume hood control system is to
Research has revealed that room air currents or
control fume hood exhaust as a function of the sash
cross currents in the vicinity of the fume hood can be
opening in order to maintain a constant face velocity.
very detrimental to effective fume hood containment.
By maintaining a constant face velocity, fume hood
Even relatively mild air currents passing a fume
air consumption is reduced whenever the sash
hood sash opening can draw out fumes from the
opening is reduced, thereby saving ventilation
hood interior. Figure 1 illustrates chemical fumes
system energy. VAV fume hood air consumption and
being drawn out of the fume hood by room air
ventilation system energy usage is minimized
currents (shown by dark arrows) passing the open
whenever the sash is fully closed.
sash. This phenomenon can result when the room
This contrasts with Constant Air Volume (CAV) fume air currents are horizontal, vertical, or even angular.
hoods, which do not change overall fume hood air Thus, all room air currents pose the potential for
consumption in relation to the sash position. Thus, compromising effective fume hood containment.
CAV fume hoods consume significantly more
ventilation system energy than VAV fume hoods.

Automatic Face Velocity Setback


Aside from maintaining a constant face velocity at all
sash positions, some VAV fume hood control
systems incorporate a type of user detection sensor
to enable initiating an automatic reduction in face
velocity when the user is not at the fume hood. The
claim is made that when no one is at a fume hood, a
face velocity of 60 feet per minute (fpm) in lieu of the
commonly accepted 100 fpm will still provide
adequate fume containment. And subsequently, by ROOM AIR ROOM AIR
reducing the face velocity from 100 fpm to 60 fpm, FUME
FUME
fume hood air consumption will be reduced to about ROOM AIR ROOM AIR
60% of what it would be at 100 fpm. FUME
E
FUM
ROOM AIR
ROOM AIR
Safety Considerations
Before addressing the potential energy savings
claim, the safety issues associated with automatic
face velocity setback should be the first
consideration. Although face velocity setback has
been promoted for a number of years it continues to
be a subject of controversy within the laboratory Figure 1. Room Air Currents Can Draw Out
ventilation industry. The reservations against Fumes from the Interior of the Fume Hood.
Siemens Industry, Inc. Page 1 of 6
Document No. 149- 976
To minimize these effects ANSI/AIHA Z9.5 states NFPA 45 also requires that laboratory occupants be
that room air velocities should be less than one-half trained and reminded as a safety practice to close
and preferably less than one-third of the face fume hood sashes since the sash provides a
velocity 1 . Standard NFPA 45 also states that room physical shield or barrier much like a face shield.
air currents should ideally be less than 30% of the Leaving a fume hood sash open even when no one
fume hood face velocity. 2 is in front of a fume hood constitutes an unsafe
practice and exposes all occupants of a laboratory
Therefore, to use a face velocity setback of 60 fpm
room to needless hazards. Chemical processes or
and be in accord with the foregoing safety
experiments can generate large volumes of noxious
standards, one must be sure that room air currents
or hazardous fumes that may not be contained with
at the fume hood will be less than one-half and
a 60 fpm face velocity. Gasses, flammable liquids, or
preferably less than 30% of the face velocity. This
vapors in a fume hood may ignite and result in a fire.
means that for a 60 fpm face velocity setback, room
In actual instances, explosive chemical reactions
air currents must be less than 30 fpm and preferably
have fractured glassware and propelled fragments
less than 18 fpm respectively. 3
and chemicals throughout the room.
These are very slow rates of air movement and are
A guide document published by OSHA for its field
comparable to the rate that smoke rises from a
inspectors specifically states that the laboratory
smoldering candle in a calm room. With such low
facility chemical hygiene plan should include the
room air velocity requirements, it is understandable
provision whereby fume hoods shall be kept closed
why many fume hood safety professionals express
at all times that do not require that the hood be
admonition against reducing the face velocity to
open 5 .
such a low level.
The U.S. Occupational Safety and Health
Administration (OSHA) recommends that a fume Face Velocity Setback and User
hood's face velocity range from 60 to 100 fpm, which Safety Training
places 60 fpm at the extreme low end of their Having an automatic provision to reduce face
recommendation. OSHA also recognizes the velocity when a user moves away from the hood
problems with room air currents and cautions that may convey a message that conflicts with safety
airflow throughout the entire laboratory room should practices. It infers that fume hood users are not
be uniform and without higher velocity air currents. really expected to close fume hood sashes, and thus
Standard AIHAs Z9.5 specifically recommends that weakens the effort to maintain and enforce
the face velocity be at least 80 fpm. 4 laboratory safe working practices. If a laboratory
accident or mishap is ultimately attributed to a
needlessly open fume hood sash, an automatic face
The Sash Closure Alternative velocity setback provision might be construed as
An important safety consideration is expressed in evidence that safety practices were not being
Standard NFPA 45 (Paragraph 6.8.3) which states: enforced. This would substantially increase the
"Laboratory hood sashes shall be kept closed liability on the part of the laboratory facility and
whenever possible. When a fume hood is probably also on the laboratory ventilation system
unattended, its sash shall remain fully closed." designer. As a matter of logic, if strict sash closure
practices are enforced, there is no benefit from an
1. American National Standard for Laboratory Ventilation automatic face velocity setback provision, since it
ANSI/AIHA Z9.5, 5.2.2: "Supply air distribution shall be would not be needed.
designed to keep air jet velocities less than half, preferably
less than one-third of the capture velocity or the face velocity
of the laboratory chemical hoods at their face opening."
2. National Fire Protection Association, Standard NFPA 45: A- Energy Savings
6-3.5: Room air current velocities in the vicinity of fume The claim is made that a typical fume hood user will
hoods should be as low as possible, ideally less than 30
always leave the fume hood sash open even though
percent of the face velocity of the fume hood.
they only need access to the fume hood interior for
3. One-half of 60 fpm is 30 fpm. 30% of 60 fpm is 18 fpm.
short periodsperhaps an hour or two a day. Thus,
4. American National Standard for Laboratory Ventilation
ANSI/AIHA Z9.5, 3.3.1: "Design face velocities for laboratory
an assumption is made that with a 60 fpm face
chemical hoods in the range of 80100 FPM (0.410.51m/s)
will provide adequate face velocity for a majority of chemical 5. Reference: Occupational Safety and Health Administration,
hoods." "This is the range recommended for a majority of Philadelphia Regional Instruction STD 1-23,1
laboratory chemical hoods." February 11, 1991, Office of Technical Support
Page 2 of 6 Siemens Industry, Inc.
Document No. 149- 976
velocity rather than 100 fpm, an automatic face communicates to the users that they are not
velocity setback provision will provide a near 40% 6 expected to close sashes. Compare this to a room
reduction in fume hood ventilation energy for most of equipped with a lighting control arrangement that
the time. shuts off the lights when no one is in the room.
Persons are less likely to make an effort to turn the
However the actual energy savings are diminished
lights off when they know it will happen
if:
automatically.
1. Users close their sashes when they no
With fume hoods, the concern is primarily worker
longer need immediate access to the fume
safety and not just with energy savings. To obtain
hood interior. VAV fume hood ventilation
the cooperation of fume hood users for keeping
energy savings will then attain the maximum
sashes closed the following suggestions are offered:
reduction of approximately 80% when the
sash is closed. 7 Avoid impersonal and authoritative approaches
2. Fume hoods are actively used for more than since these are unlikely to generate enthusiastic
the short usage times often claimed. cooperation. An ineffective example would be a
sternly worded notice such as:
3. Facilities use a fume hood sash stop to
restrict how far sashes may be opened. If a
NOTICE TO ALL LABORATORY PERSONNEL:
vertical sash can only be opened 18 inches
Effective immediately, all fume hood sashes may be open
rather than 28 inches, the fume hood
only when absolutely necessary. At all other times, sashes
ventilation energy is reduced by nearly 35% 8 shall remain closed!
without the need for any face velocity
setback. In such situations, face velocity Conduct periodic safety training by a skilled
setback does not add significant savings. professional safety trainer or consultant,
4. Room air currents in front of the fume hood preferably from outside of the facility. People are
require that the automatic face velocity set more likely to heed an outside expert than
back needs to maintain a higher face another facility person.
velocity than 60 fpm, thus reducing the
savings 9 . Post instructional posters or signage to educate,
encourage and remind workers of safe work
practices. For VAV fume hoods also provide
Attaining Fume Hood Sash Closure information indicating the difference in energy
consumption between open and closed sashes.
The argument for automatic face velocity reduction
Figure 2 provides examples of signs that help
is based upon the assumption that fume hood users
reinforce the importance of safe work practices
do not and will not close their sashes. However
and energy consciousness.
implementing automatic face velocity reduction is
likely to only make this situation worse since it

6. 100 fpm 60 fpm = 40% less.


7. The 80% air reduction figure is based upon the AIHA Z9.5
and NFPA 45 recommendation that VAV fume hoods
maintain a minimum exhaust airflow rate of 25 cfm per
square foot of internal work surface when the sash is fully
closed (Paragraph 3.3.1 in AIHA Z9.5 & Paragraph A.6.4.6
in NFPA 45). This enables reducing a VAV fume hood's air
consumption by approximately 80% of maximum when a
constant face velocity of 100 fpm is maintained.
8. For an 18-inch vertical sash opening rather than 28 inches,
the sash open area is reduced to about 65% (18 in. 28 in.)
and, thus, only requires 65% of the maximum ventilation
airflow. This results in the 35% reduction in air American
National Standard for Laboratory Ventilation ANSI/AIHA
Z9.5, 2002 5.2.2, consumption.
9. Since room air current velocities will not be known until after
the room is constructed and the ventilation system is put into
operation, the permissible face velocity setback value cannot
be determined beforehand.
Siemens Industry, Inc. Page 3 of 6
Document No. 149- 976
STOP
100

DID YOU REMEMBER


AN OPEN SASH
TO CLOSE YOUR SASH ?
IS A HAZARD !

FUME HOOD
ANNUAL ENERGY COST
SI ZE SASH OPEN SASH CLOSED

5Foot $5,00000 $1,00000


6Foot $6,25000 $1,25000
KEEP FUME HOOD SASHES 8Foot $8,50000 $1,70000
CLOSED 10Foot $10,75000 $2,15000

Figure 2. Example Signage for Reminding Laboratory Workers to Close Fume Hood Sashes.

Sash Closure Technology the sash. The variables of this feature including
the sash opening limit, elapsed time since last
Various means can also be implemented to help
movement, audible alert volume, time between
attain sash closure and thus enhance safety and
successive chirps, and so forth are assigned by
energy reduction without the potential problems of
authorized personnel.
automatic face velocity reduction.
Central Monitoring of SashesBuilding
Open Sash AlertThis feature uses the automation systems which network into VAV
electronic logic of the VAV fume hood controller fume hood control systems are capable of
to also monitor the extent the fume hood sash is monitoring all fume hood sash positions and
open and the time since the sash was last providing this data at designated locations. This
repositioned. If a fume hood sash opening can include alerts when sashes are left open in
exceeds a preset limit and has not been excess of a preset time period. Also, many
repositioned for a certain time period, it is different summary printouts of the cumulative
probable that the user is no longer at the fume time that individual sashes remain open over
hood and has failed to close the sash. The fume daily, weekly and monthly periods are available.
hood monitoring panel will then begin a series of This information may be used to identify the
periodic audible chirps as a reminder to close
Page 4 of 6 Siemens Industry, Inc.
Document No. 149- 976
Conclusion
Automatic Sash Closure Mechanisms This paper has presented a factual discussion on
Mechanisms may be added to fume hoods to the ramifications of implementing automatic face
slowly close the sash after a pre-designated velocity setback. In general, the application of an
period in which there is no sash movement. automatic face velocity setback provision requires,
Such devices typically incorporate appropriate as a minimum, the assurance that room airflow
safety features to ensure against personal injury conditions meet very stringent requirements. In
and exerting excessive closing force on flexible addition, fume hood users must be well aware of the
hoses, electrical cords, or other apparatus that need to keep all chemicals and apparatus well inside
may extend into the sash opening. The use of of the fume hood sash and not to create harmful air
these mechanisms is dependent on individual currents due to their movements within the
facilities and may not be suitable for every laboratory. Fume hood users must also be made
instance. aware that automatic face velocity setback is not a
substitution for closing the sash whenever possible.
However, if the fume hood users maintain safe work
practices and keep fume hood sashes closed
whenever possible, they will maintain a safe work
environment and maximize the reduction of
ventilation energy without the need for face velocity
setback.

Siemens Industry, Inc. Page 5 of 6


Document No. 149- 976
Product or company names mentioned herein may be the trademarks of their respective owners. 2009 Siemens Industry, Inc.
Siemens Industry, Inc. Printed in the USA
Building Technologies Division Document No. 149-976
1000 Deerfield Parkway Page 6 of 6
Buffalo Grove, IL 60089-4513
USA

You might also like