You are on page 1of 2

Specification

Nominal Voltage 12V


Number of cell 6
Nominal Capacity 100Ah@10hr-rate (10.0A to 1.80V/cell @25)
Weight Approx.31.5Kg
Terminal M6,=14&18

Container Material ABS (UL94-HB), Flammability resistance Introduction


of UL94-V1 can be available upon request.
The Vision UPS Systems batteries designed
102.8Ah 20hr-rate (5.14A to 1.80V/cell @25) with 15+ years service life. The SOLID-GEL
100.0Ah 10hr-rate (10.0A to 1.80V/cell @25) system can avoid corrosion and stratification.
Rated Capacity 83.0Ah 5hr-rate (16.6A to 1.75V/cell @25) The special separator can properly prevent
61.2Ah 1hr-rate (61.2A to 1.60V/cell @25) short-circuit. It can offer high deep discharge
Max. Discharge Current ability, super thermal stability, good recovery-
500A(5sec)
ability after deep discharging. The deep dis-
Internal Resistance Approx.3.5m(Fully charged) charge cycles of GEL-TECH batteries can be
more than 50% compared with other normal
Discharge: -40~60 AGM batteries.
Operating Temp. Range Charge : -20~50
Storage : -40~60 Applications
Charging Current:20.0A Auto control system &ATM machine
Cycle Use Voltage:14.2V ~14.4V Electronic apparatus and equipment
Temperature compensation:-30mV/ Emergency light & Emergency backup
power supply & Alarm/Security system
Charging Current:No limit
Standby Use Voltage:13.6V ~13.8V Power generation system (solar and
Temperature compensation:-20mV/ wind power system,etc.)
Communication power & DC power
Self-Discharge less than 1% at 25 oC Electric Power System(EPS)
Design Life 15 years (floating charge) Uninterruptable Power System (UPS)

Dimensions 329

5
Length 3291mm (12.95 inches)
216
222
174

Width 1741mm (6.85 inches) M6


Heigth 2161mm (8.50 inches) POS NEG

Total Heigth 2221mm (8.74 inches)


Unit: mm

Constant Current Discharge Characteristics: A (25)


F. V/Time 5min 10min 15min 30min 1h 2h 3h 4h 5h 8h 10h 20h
1.60V/cell 331.1 2 37.3 1 7 2 .7 1 08.4 61.26 34.97 2 4 .6 0 20.36 1 7 .1 4 12.17 1 0.48 5.543

1.65V/cell 322.3 2 25.8 1 6 9 .1 1 06.6 60.98 34.71 2 4 .5 0 20.26 1 7 .0 4 12.07 1 0.38 5.442

1.70V/cell 303.7 2 17.8 1 6 6 .5 1 05.7 60.41 34.45 2 4 .3 2 20.17 1 6 .9 4 11.97 1 0.28 5.341

1.75V/cell 272.7 2 01.0 1 5 8 .5 1 03.0 59.85 34.18 2 4 .2 2 19.98 1 6 .7 4 11.87 1 0.18 5.241

1.80V/cell 246.1 1 83.3 1 4 6 .1 9 8.49 58.43 33.57 2 3 .5 6 19.51 1 6 .4 4 11.68 1 0.08 5.140

1.85V/cell 214.3 1 63.8 1 3 1 .0 9 2.27 55.51 32.08 2 2 .5 3 18.57 1 5 .7 3 11.18 9 .7 7 6 4.837

Constant Power Discharge Characteristics: W (25)


F. V/Time 5min 10min 15min 30min 1h 2h 3h 4h 5h 8h 10h 20h
1.60V/cell 3 451 252 3 1858 12 23 7 00.6 4 0 2 .3 2 83.9 2 3 5 .2 198.5 1 4 1 .2 117.9 6 2 .2 5

1.65V/cell 3 380 241 0 1819 12 08 6 97.2 4 0 0 .7 2 83.3 2 3 4 .7 197.3 1 4 0 .6 116.6 6 1 .6 5

1.70V/cell 3 191 233 0 1795 11 94 6 92.2 3 9 7 .1 2 81.6 2 3 3 .5 196.6 1 3 9 .4 116.0 6 1 .0 4

1.75V/cell 2 873 215 3 1711 11 67 6 85.4 3 9 3 .4 2 79.9 2 3 1 .9 194.8 1 3 8 .3 114.8 6 0 .4 4

1.80V/cell 2 585 195 5 1572 11 13 6 68.4 3 8 7 .6 2 73.1 2 2 5 .6 191.8 1 3 5 .3 113.6 5 9 .8 3

1.85V/cell 2 231 173 6 1404 10 43 6 33.3 3 6 9 .7 2 59.6 2 1 4 .9 182.1 1 3 0 .5 110.0 5 7 .4 2

1
Discharge Characteristics Curve Charging Characteristics Curve

Temperature:25
(V/cell) Constant Voltage Change Characteristic
Charge Charge (2.23V/Cell,25) Charging
2.16
Volume Voltage Current
% (V)
Terminal Voltage(V)

130
2.00
120 2.40 0.1
110 Charged Volume
1.84 100
2.30 0.08
0.1C 0.05C 90
0.4C 0.2C 80 Charging voltage
1.68
0.6C 70 2.20 0.06
3C 2C 1C 60 After 50% Discharge
1.52 After 100% Discharge
50 2.10 0.04
40
1.36 30
2.00 0.02
20
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 10 Charging Current
0 0
min h 0 4 8 12 16 20 24 28 32 36 40

Discharge Time Charging Time(h)

Cycle life in relation to depth of Discharge Temperature effects on Capacity

120 120

100 100 A
0 .1 C

Capacity(%)
80 A
0 .2 C
Capacity(%)

80

60 60
100% 80% 50%
DOD DOD DOD A
1 .0 C 2 .0 C
A
40 40 A
3 .0 C
Testing condition(25)
20 Charging volume:120% of discharged capacity 20

0 400 800 1200 1600 2000 2400 2800 0


-20 -10 0 10 20 30 40 50

Number of cycles Temperature()

Relationship between charging voltage and temperature Self-discharge Characteristics


V/Cell

No supplementary
100 charge required
(Carry out supplementary
10 charge before use if 100%
Remaining Capacity(%)

2.6
capacity is required.)
80
CYCL
2.5 E US 20
E
Supplementary charge
60
required before use.
2.4
S TA N 40 30
DBY 40
2.3 USE
Supplementary charge
may fail to recoverthe
2.2 20 capacity.The battery should
never be left standing till
this is reached
0
-40 -20 0 10 20 30 40 60 0
2 4 6 8 10 12
Ambient Temperature() Storage time(months)

Temperature effects on Float life Life Characteristics of Standby use

120
Life expectancy (years)

100
Charging voltage:2.23V/Cell
Capacity(%)

20 80
Testing condition
60 Floating voltage:2.23V/Cell
10 Ambient temperature:25

40

5 20

0 10 20 30 40 50 0 3 6 9 12 15
Temperature () Life expectancy (years)