Integrated Transformers for ACS 2000 Frequency Converters


ACS2000

Project: Indonesia BOSOWA project

Main electrical data

Typical connection diagrams

No. of p.
Issued Yonggang.Li 2015.05.19 ACS 2000
Check / rel. Xuqiang.Qin 2015.05.19 Int. Transformer Specification 4
Resp. dept. MV Drives
Document No. Lang. Rev. ind. Page

ABB Beijing Drive Systems Co., Ltd 2UBB010680 EN/CN - 1


01. Quantity 3

02 Rated voltage HV (r.m.s. value, phase to phase) UL 11000V

03 Network Voltage tolerance Ul +10% / -10%

04 Rated power of HV winding (IEC 61378-1) SR 2100 kVA


(Remark: supply undervoltage considered in power calculation)

05. Tappings at HV winding: None

Intended for off-circuit, off-load or on-load tapp-changing

06. Rated voltage LV (r.m.s. value, phase to phase) UL 1850 V


( , )
07. Rated frequency fL 50 Hz

Tolerance +2% / -2%

08. Type of transformer: dry-type (see IEC 60076-11) or oil Dry type
immersed (see IEC 60076-2)

09. Winding materials Cu.

10. Duty cycle: (converter current ISN) 10 1 110%


ISN
11. External cooling medium

- Maximum temperature of cooling medium 40.0 [C]

The ambient temperature of integrated transformer


may be continuously 40C
40C
12. Conditions on site: indoor / outdoor, altitude, climatic Indoor
zone
If earthquake proof: acceleration due to gravity for all
directions 2000 m a.s.l.

Document No. Lang. Rev. ind. Sheet

ABB Beijing Drive Systems Co., Ltd 2UBB010680 EN/CN - 2


13. Insulation class & temperature rise H

14. Cooling type Air Force

15 Dimension 2UBB001853

16. Transformer accessories

a) general 1pc PT100 per phase for


winding temperature sensor
b) additional for dry-type or oil-immersed type
PT100

17. Comments, appended documents:

1. General transformer specifications 2UBB001875 Rev. H

Fig.1: Typical Connection Diagrams


1

Fig.1: Based on: 2UBB001875 Rev. H


1 2UBB001875 Rev. H

Document No. Lang. Rev. ind. Sheet

ABB Beijing Drive Systems Co., Ltd 2UBB010680 EN/CN - 3


Revision
Rev. ind. Description Date / Status
First issue 2015.05.19/Final

Document No. Lang. Rev. ind. Sheet

ABB Beijing Drive Systems Co., Ltd 2UBB010680 EN/CN - 4