You are on page 1of 3

Electrical Engineering

Measurement of zero sequence impedance for


three-winding transformers
Using actual measurements from a
reputable transformer manufacturer, Xos As
Er. Lee Wai Meng explains the Secondary
Ap Xop
required connection scheme and
Primary K XoT AT
associated calculations.
Tetiary
Bp
A three-winding transformer has the BT BS
following specifications: Zero bus
Primary winding of 300 MVA, 230
kV, star connected with the neutral
accessible, and connected to the local Figure 1 - Zero sequence impedance
grid.
Secondary winding of 300 MVA,
132 kV, star connected with the neutral
accessible, and connected to the load of Configuration of Windings Status of Switch
the consumer.
Tertiary winding of 90 MVA, 15.75 AP, AS, or AT BP, BS, or BT
kV, delta connected, and not connected
to any load. The sole purpose of the 1) Delta Open Closed
tertiary winding is to allow the flow
of zero sequence current during fault
conditions. 2) Star with neutral connected to ground Closed Open

Model for zero sequence 3) Star with neutral NOT connected to ground Open Open
A three-winding transformer has zero
sequence impedance for the primary,
secondary, and tertiary windings. With the combinations of the switches in 2A to 5A show the connection schemes.
XOP = zero sequence various open and closed states, the values Figures 2B to 5B show the zero sequence
impedance of the primary winding of XOP, XOS and XOT can be calculated impedance diagram for the connection
XOS = zero sequence from measurements of injected voltage schemes in Figures 2A to 5A.
impedance of the secondary winding and induced current at the primary, The test source can be connected either
XOT = zero sequence secondary and tertiary terminals of the at the primary or secondary windings. The
impedance of the tertiary winding transformers. test source is a single phase AC source,
and there is no need for a three phase AC
The equivalent circuit for the zero Connection scheme source for the measurement of the zero
sequence impedance is illustrated in In order to solve for the three unknowns sequence impedance. The measurement
Figure 1. It is important to recognise (XOP, XOS and XOT), at least three equations of the positive sequence impedance will
that point K in Figure 1 is a fictitious or three measurements are needed. Figures however require a three phase AC source.
point and does not represent the
neutral point of the transformer. Connection Scheme Zero Sequence Impedance
The connection of the zero sequence
impedance to the system is determined Figure 2A XOP + XOT
by imaginary switch AP, AS, AT, BP, BS,
and BT. Switch AP, AS, or AT will be
closed if the winding is star connected Figure 3A XOP +
and with the neutral connected to
ground. Switch AP, AS, or AT will be
opened if the winding is star connected Figure 4A XOS + XOT
and with the neutral not connected
to ground. Switch BP, BS, or BT will
be closed only if the winding is delta Figure 5A XOS +
connected.

26 THE SINGAPORE ENGINEER Jan 2010


Electrical Engineering
Tetiary Tetiary

Primary Secondary
Primary Secondary

3Io
3Io Io
Test
Io Source,
Test
Vo
Source,
Vo

Figure 3A - Test source at Primary, XOP + Xos XOT


Xos + XOP
Figure 2A - Test source at Primary, XOP + XOT

Xos Xos As Secondary


As
Ap Secondary Ap Xop
Xop
XOT AT XoT AT Tetiary
Test Test
Tetiary
Source, Bp Source, Bp
BT BS BT BS
Vo Vo Zero bus
Zero bus

Figure 2B - Zero sequence impedance, XOP + XOT


Figure 3B - Zero sequence impedance, XOP + XoS XOT
XOS + XOT

Tetiary Tetiary

Primary Secondary

Primary Secondary
3Io
Io
Test
3Io
Source,
Io Vo
Test
Source,
Vo

Figure 5A - Test source at Secondary, XOS + XoT XOP


XoT + XOP

Figure 4A - Test source at Secondary, XOS + XOT

Xos As Xos As
Ap Xop Ap Xop
Primary Primary XoT Tetiary
XOT AT Tetiary Test AT Test
Source, Source,
Bp Bp
BT BS Vo BT BS Vo

Zero bus Zero bus

Figure 4B - Zero sequence impedance, Xos + XOT Figure 5B - Zero sequence impedance, Xos + XoT XOP
XoT + XOP

THE SINGAPORE ENGINEER Jan 2010 27


Electrical Engineering
Measurement results Connection Measured Measured Calculated Calculated
The measurement results in the table Scheme Voltage in kV Current in Impedance Impedance
on the right have been obtained from Ampere in ohm per in %
a reputable transformer vendor for an phase
installation at a customers facility in
Jurong Island. Figure 2A 10.95 424 77.5 44
For the connection scheme in Figure
2A, the impedance recorded by the test Figure 3A 10.19 676 45.2 26
source will be (10950 / 424) or 25.8 ohm.
The equivalent zero sequence impedance Figure 4A 2.61 1034 7.5 13
will be (3 x 25.8) or 77.5 ohm per phase
or XOP + XOT = 77.5 ohm per phase. Figure 5A 1.52 1027 4.4 7
To convert the ohm per phase to the
equivalent % value, the base impedance The base values are 300 MVA, 230 kV or 300 MVA, 132 kV
at the primary winding must be calculated,
and this is equal to (230 x 230) / 300 or
176 ohm. The % impedance value will be of zero sequence impedance are across where
(77.5 / 176) or 44%. The calculations for the physical terminals of the primary, Vo is the pre-fault phase to neutral
Figure 3A are similar to that for Figure secondary, and tertiary windings. voltage
2A because the test source is connected at These physical values of zero sequence X1 is the positive sequence impedance
the primary winding. impedance are X2 is the negative sequence impedance
For the connection scheme in Figure XO_PS = XOP + XOS = 27% X0 is the zero sequence impedance
4A, the impedance recorded by the test XO_PT = XOP + XOT = 33% IF is the three phase fault current
source will be (2610 / 1034) or 2.5 ohm. XO_ST = XOS + XOT = 13%
The equivalent zero sequence impedance In most applications, X1 = X2 and
will be 3 x 2.5 or 7.5 ohm per phase or XOS Zero sequence impedance hence the single phase to ground
+ XOT = 7.5 ohm per phase. To convert The measurement of the zero sequence fault current will be
the ohm per phase to the equivalent impedance for transformers is seldom
% value, the base impedance at the done for small transformers, and is done of the three phase fault current, where
secondary winding must be calculated, only for large transformers. It is common
and this is equal to (132 x 132) / 300 or to assume that the zero sequence K =
58 ohm. The % impedance value will be impedance of the transformer is equal to
(7.5 / 58) or 13%. The calculations for the positive sequence impedance which When XO = X1, the single phase
Figure 5A are similar to that for Figure is the transformer leakage impedance. to ground fault current equals the three
4A because the test source is connected at The exceptions to this are the three phase fault current.
the secondary winding. phase transformers with three limbs for When XO is less than X1, the single
the core. This type of construction does phase to ground fault current is more
Calculation results not provide the return path for the zero than the three phase fault current.
From the measurement results, we have sequence flux through the core of the When XO is greater than X1, the
the following: three limbs. The return path for the single phase to ground fault current is
XOP + XOT= 44% zero sequence flux is through the metal less than the three phase fault current.
body of the transformer tank. Therefore
XOP + = 13% the zero sequence impedance will not be Therefore measurement of the zero
equal to the positive sequence impedance, sequence impedance of a transformer
XOS + XOT= 26% and typical values are 85% to 90% of the is important when the transformer is of
positive sequence impedance. large MVA size because of the possibility
XOS + = 7%
that the single phase to ground fault
Single phase to ground fault current is greater than the three phase
The single phase to ground fault will fault current.
Solving the equations, we will have depend on the positive, negative, and
XOP = 29% zero sequence impedance. [Er. Lee Wai Meng is Principal
XOS = - 2% Consultant/Director of J.M. Pang & Seah
XOT = 15% Single Phase to Ground Phase = (Pte) Ltd, an electrical and mechanical
consultancy. A Singapore-registered
XOP, XOS and XOT, are fictitious zero = professional engineer, he has a 230 kV
sequence impedances and hence may switching licence from Energy Market
have negative values. The physical values Authority (EMA)].

28 THE SINGAPORE ENGINEER Jan 2010

You might also like