Professional Documents
Culture Documents
Instruction Bulletin
6065-14
04/2012
Retain for future use.
Hazard Categories and Special Read these instructions carefully and look at the equipment to become
Symbols familiar with the device before trying to install, operate, service or maintain
it. The following special messages may appear throughout this bulletin or on
the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of either symbol to a Danger or Warning safety label
indicates that an electrical hazard exists which will result in personal injury if
the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not
avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not
avoided, can result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The
safety alert symbol is not used with this signal word.
Please Note Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this material.
6065-14 Outdoor Vacuum Circuit Breaker, Type EOX with Spiral Spring Operating Mechanism
04/2012 Table of Contents
3
2012 Schneider Electric All Rights Reserved
Outdoor Vacuum Circuit Breaker, Type EOX with Spiral Spring Operating Mechanism 6065-14
Table of Contents 04/2012
Section 1Introduction This bulletin contains instructions for the installation, operation, and
maintenance of the Type EOX circuit breaker from Schneider Electric.
Type EOX vacuum circuit breakers are three-pole, stored-energy, outdoor
circuit breakers manufactured and tested according to IEEE/ANSI
standards. They have been designed and built to operate under normal
service conditions (as defined in Table 2 on page 9), allowing reliable
closing and interrupting functions.
The enclosure allows for easy access to all breaker controls. It has
height-adjustable, galvanized steel legs to suit customer needs.
Read and understand this bulletin completely before performing the
installation, operation, and maintenance steps provided. Electrical
equipment should be installed and serviced only by qualified personnel.
Qualified personnel should establish procedures that ensure the safety of
personnel and equipment.
Catalog Numbers The following drawing is an example and Table 1 is an explanation of the
catalog numbering system:
Catalog NumberEOX 15 25 12
Identification The rating nameplate is located on the inside of the rear low-voltage door
and includes the following information:
Section 2Safety
Precautions DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
Only qualified personnel familiar with medium voltage equipment are to
perform work described in this set of instructions. These personnel must
understand the hazards involved in working with or near medium
voltage circuits and perform such work only after reading and
understanding all of the instructions contained in this bulletin.
Turn off all power supplying this equipment before working on or inside
equipment.
Always use a properly rated voltage sensing device to confirm power is off.
All maintenance must be performed by qualified personnel in
accordance with local codes and under the following conditions:
The circuit breaker must be isolated from all power sources.
Control voltage must be removed from the control circuits.
The circuit breaker must be in the open (O) position.
All circuit breaker springs must be discharged.
Handle this equipment carefully and install, operate, and maintain it
correctly in order for it to function properly. Neglecting fundamental
installation and maintenance requirements may lead to personal injury,
as well as damage to electrical equipment or other property.
Do not make any modifications to the equipment or operate the system
with interlocks or panels removed. Contact your local Schneider Electric
sales representative for additional instructions if the equipment does not
function as described in this manual.
Use lock-out/tag-out tags and padlocks when working on equipment.
Leave tags in place until the work is completed and the equipment is
ready to be put back into service.
Carefully inspect your work area and remove any tools and objects left
inside the equipment.
Replace all devices, doors, and covers before turning on power to this
equipment.
All instructions in this manual are written with the assumption that the
customer has taken these measures before performing maintenance or
testing.
Section 3Receiving, Each vacuum circuit breaker is completely assembled, inspected, and
tested in the factory prior to shipment. The total weight depends on the
Handling, and Storage circuit breaker rating, but is in the range of 22002350 lbs. ( 9981066 kg).
Receiving Upon receipt, inspect the equipment for damage that may have occurred in
transit. Check all items against the packing list provided. Immediately notify
the carrier and Schneider Electric of any damages or shortages.
For details concerning claims for equipment shortages and other errors,
refer to Schneider Electrics Terms and Conditions of Sale.
Handling
Lifting The Type EOX circuit breaker is shipped with the breaker contacts in the
closed position. Before lifting the circuit breaker, view the circuit breaker
position indicator (Figure 4 on page 12) to verify the mechanism/breaker is
in the closed position. If it is not, perform a close operation before lifting the
circuit breaker (see Closing the Circuit Breaker on page 23).
Lifting eyes (Figure 1 on page 8) are provided on the roof of the circuit
breaker for lifting by crane. A spreader bar is required.
NOTE: Handle the equipment with care. Protect the high voltage (HV)
bushings from rough treatment to avoid chipping.
WARNING
TOP HEAVY LOAD / DAMAGEABLE COMPONENTS
If lifting the circuit breaker by forklift:
Stabilize the circuit breaker with a safety strap to reduce the possibility
of tipping.
Lift only from the side to prevent damage to the operating mechanism.
Do not lift from the front or rear.
If lifting the circuit breaker by forklift, place the forklift forks underneath the
low voltage compartment from either side (Figure 1 on page 8), and secure
the circuit breaker to the forklift with a strap. The floor of the low voltage
compartment is reinforced to support the weight of the circuit breaker. If
another handling method is necessary, contact Schneider Electric to make
special preparations.
48.00
(1219)
Spreader bar
(not supplied with
circuit breaker)
21.30 HV compartment
(541)
LV compartment
52.00
(1321)
Inches
49.50 Dual Dimensions: (mm)
(1257)
Storage If the circuit breaker is stored prior to installation, keep it in an area that
provides protection from damage.
Remove all plastic wrap from the circuit breaker.
Space heaters are furnished with each breaker; energize them from an
external source. (Refer to the schematic and wiring diagrams located in
the LV control compartment for the connection point and for voltage and
power requirements.)
Verify that the heater thermostats are set to at least 75 F (24 C). Adjust
the settings, as necessary, to prevent condensation within the circuit
breaker enclosure.
Inspect the circuit breaker regularly when it is stored for prolonged periods.
Section 4Description The Type EOX circuit breaker is designed for outdoor applications and has
two separate compartments (high voltage and low voltage). The circuit
breaker is supplied fully assembled and is equipped with a spiral spring
operating mechanism.
2
3 4
6
5
8
Right
Side
Front
Left
Side 9
16
Legend
The normal service conditions for operation of the circuit breaker are
described in Table 2. For dimensions, refer to the outline drawings located
in the LV control compartment.
Condition Range
Operating temperature -22 to +104 F (-30 to +40 C)
Relative humidity 0100%
Altitude 3,300 ft. (1,000 m) or lower
Circuit Breaker Components The Type EOX circuit breaker has the following components:
high voltage (HV) compartment
low voltage (LV) compartment
mechanism compartment
current transformers (CTs)
porcelain bushings
vacuum interrupter
control equipment for circuit breaker operation
High Voltage Compartment The HV compartment houses the bushings, CTs, and three vacuum
interrupter poles that are mechanically linked to operate simultaneously.
Low Voltage Compartment The LV compartment houses the control equipment specific to customer
specifications. Most circuit breakers have some means of controlling the
breaker locally and remotely via terminal board connections. For
convenience, the terminal board is located on the rear surface of the LV
compartment. In some cases, components are mounted on the internal
sides. The shorting terminal blocks for the CTs can be found in these areas.
Mechanism Compartment The EOX circuit breaker uses a stored-energy operating mechanism
(Figure 3 on page 11) in which a charged spiral spring opens and closes the
circuit breaker. The operating mechanism is equipped with the necessary
electrical control components and interlocks. The mechanism is mounted in
a separate compartment so it can be easily accessed for inspection and
servicing.
The spiral spring operating mechanism has a single mechanical output
which simultaneously operates the three vacuum interrupter poles. The
mechanism is particularly suited to the short travel and low operating energy
required by the vacuum interrupters.
The spiral spring stores the energy required to perform a fast
OPEN-CLOSE-OPEN reclosing cycle if required. It accelerates the main shaft
and cam, which transforms the rotary movement into a transverse
momentum. The standard duty cycles are:
O -15s - CO (open - 15-second spring charge - close - open)
O - 0.3s - CO - 15s - CO (open - 0.3-second pause - close - open -15-
second spring charge - close - open
In the resting position, the drive shaft roller levers bear on either the closing
latch or the tripping latch. The circuit breaker is closed and opened by
applying a voltage to the corresponding coils, or by manually operating the
OPEN and CLOSE push buttons mounted in the mechanism compartment.
At the end of each closing operation, the spiral spring is rewound so that the
energy required to perform a complete reclosing cycle is available.
The spiral spring operating mechanism (Figure 3 on page 11) is equipped
with:
close and trip coils
operation counter
anti-pumping relay
auxiliary contact block for circuit breaker position indication
manual spring-winding handle
Optional:
under-voltage release coil
motor overcurrent protection
remote indication of local I/O operation
additional auxiliary contacts
4 5 1 6 7
2
1
11 10 9 8
16
Legend
1 Roller levers 7 Close coil
2 Main shaft 8 Spring winding handle
3 Cam 9 Emergency trip
4 Spiral spring 10 Motor
5 Trip coil 11 Trip latch
6 Close latch
4 6
2
1
5
3
16
Legend
1 Circuit breaker position indicator (Open/Closed)
2 Trip push button
3 Close push button
4 Spring position indicator (Charged/ Discharged)
5 Operations counter
6 Opening for manual spring-charging handle
Current Transformers When specified by the customer, current transformers (CTs) are mounted
around the bushings on the inside of the roof (Figure 5). CT circuit wiring
extends from the CT case to the shorting type terminal blocks located in the
low voltage compartment. The CTs are selected based on the electrical
needs of each application.
Current
transformer
Bushing
Heat sink
Flex
connector
Porcelain Bushings Porcelain bushings are provided on all Type EOX circuit breakers through
the ranges of operating currents of 1200 or 2000 A, 125 kV BIL. These
ratings are dependent on operating voltages. Refer to the circuit breaker
nameplate(s) for information on circuit breaker, bushing, or CT ratings.
Vacuum Interrupter The vacuum interrupter (Figure 6) is bolted onto the upper copper
connection and mounted inside the insulating enclosure. A sliding contact is
mounted on the lower part of the interrupter and makes contact with a
silver-plated copper tube. The copper tube is attached to the lower
connection. This assembly reduces mechanical stresses on the interrupter
and its ceramic enclosure.
The vacuum interrupter consists of an insulating and sealed enclosure
containing copper contacts. One of these contacts is fixed, while the other is
moved through a metal bellows. A metal shield surrounding the contact area
collects metal vapor created by arcing and prevents it from condensing on
the insulating surfaces.
1
6
2 8
9
3
4
10
16
Legend
1 Upper connection 6 Fixed contact
2 Vacuum interrupter 7 Metal shield
3 Insulating enclosure 8 Ceramic enclosure
4 Sliding contact 9 Moving contact
5 Lower connection 10 Metal bellows
magnetic field is applied to the arc. This magnetic field is created by the
current itself and the design of the contacts. As a consequence, the arc is
maintained in the diffuse mode. This has been demonstrated for currents
over 10,000 A.
The low arc energy associated with a uniform distribution over the entire
contact surface considerably enhances deionization of the contact gap. This
rapidly restores the dielectric strength when the current passes through zero
and the arc extinguishes.
The high speed at which the dielectric strength recovers makes it possible
to withstand the transient recovery voltage occurring after current
interruption. Using an axial magnetic field for arc control allows a higher
number of short-circuit current interruptions with only minimal contact
erosion. This limited contact wear results in the mechanical and electrical
characteristics of the circuit breaker being maintained.
Section 5Technical Data The curve in Figure 7 shows the typical number of interruptions against
breaking current.
10,000
Number of Interruptions
1,000
100
10
0 5 10 15 20 25 30 35 40
Section 6Installation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
This equipment must only be installed and serviced by qualified
electrical personnel who are familiar with medium voltage circuits.
Turn off all power supplying this equipment before working on or inside
equipment.
Always use a properly rated voltage sensing device to confirm power is off.
Replace all devices, doors, and covers before turning on power to this
equipment.
Installation of the EOX circuit breaker should be carried out following the
instructions included in this manual. Care should be taken when lifting or
transporting the equipment to prevent damage to the porcelain bushings.
Construction work above the circuit breaker should be completed prior to
installation.
The drawings for this equipment can be found inside the LV control
compartment. These drawings will include a general layout, dimensions, high
voltage connections, and entry points for low voltage control connections.
Preparing the Foundation The Type EOX circuit breaker is designed for installation on a concrete pad.
The finished floor area of the pad should be level (not sloping by more than
1/8 in. (3 mm) for every 8 ft. (2.5 m) of run) and should extend a minimum of
8 in. (200 mm) beyond the foundation anchor points in all directions.
Figure 8 on page 17 shows the plan view and anchoring details for the
Type EOX circuit breaker. Refer to the outline drawings located in the LV
control compartment for detailed information on the location of the
foundation anchor points.
8.00
Foundation pad (203) 8.00
(203)
5.00 Leg
(127)
14.00
(356) 3/4 in. (19 mm) hex
49.50 nut and flat washer
(1257)
3/4 in. (19 mm) bolt
46.50 Conduit
(1181) opening
7/8 in. (22 mm)
hole (typical)
Foundation
38.00 pad
(965) 41.00
(1041)
Front Side
Inches
Dual Dimensions: (mm)
LV compartment
Maximum
Front Side height
shown
Foundation pad
Wiring Connections
Ground Connection
Connect the circuit breaker to the system ground using the two grounding
Figure 9: Ground Connection Details pads (NEMA 2-hole pattern) located on the lower enclosure corners
diagonally opposite each other (Figure 2 on page 9 and Figure 9). These
Side of circuit
breaker pads are connected internally via ground bus. Once installed, any ground
Ground pad
connections from the control cables can be made using the ground bus
located inside the low voltage compartment.
Ground
connector
Cable Connection
The Type EOX circuit breaker is connected to the primary circuit through
Figure 10: Cable Connection Details aerial lugs which are not included unless specified by the customer. Follow
the instructions below when attaching the aerial lugs to the circuit breaker
Connector
bushing studs.
NOTICE
Bushing
HAZARD OF EQUIPMENT DAMAGE
BE CAREFUL NOT TO OVERTIGHTEN. It is critical that the aerial lug is
not overtightened. Always loosen the aerial lug counter-clockwise to align
the lug pad properly.
Top of circuit
breaker Failure to follow this instruction can result in equipment damage.
Low Voltage Wiring Connect all control circuits and secondary connections of CTs according to
the wiring diagram located in the LV control compartment.
NOTE: If the ambient temperature is under 14 F (-10 C), turn on the
equipment heaters a minimum of two hours before performing any
mechanical tests on the circuit breaker.
Section 7Start-Up NOTE: Perform the tests outlined in this section after the circuit breaker has
been installed, but before it is energized.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
This equipment must be installed and serviced only by qualified
personnel.
Turn off all power supplying this equipment before working on or inside
equipment.
Always use a properly rated voltage sensing device to confirm power is off.
Isolate and ground both the line and the load side of the circuit breaker.
Make sure the circuit breaker is in the OPEN position before inspecting
this equipment or connecting the circuit breaker to your system.
Replace all devices, doors, and covers before turning on the power to
this equipment.
Mechanical Operation Test Operate the equipment several times to ensure the operating mechanism,
trips, auxiliary switches, circuit breaker, and linkage operate satisfactorily
(see Section 8Operation on page 22).
1. Charge the spring electrically using the spring charging motor or
manually by turning the spring winding handle (Figure 11 on page 22).
2. Close and open the circuit breaker one time using the mechanical push
buttons (Figure 11 on page 22).
3. Electrically close and open the circuit breaker five times using local
and/or remote controls.
Electrical Test
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When performing the hi-pot (dielectric) test:
Do not exceed the voltages specified in Table 4 on page 20.
Keep all persons at least 6 ft (1.8 m) away from the circuit breaker being
tested.
Discharge the HV bushings to ground after each test. These areas can
retain a static charge after a hi-pot test.
WARNING
HAZARD OF RADIATION (X-RAY) EXPOSURE
This device may emit X-rays if voltage higher than the rated maximum is
applied across the open contacts. In such a case, personnel must be
protected with appropriate shielding.
4. Verify that the circuit breaker withstands the specified voltage without
flashover for one minute. If it does not, inspect the insulators for leakage
paths. If necessary, clean the surface of each insulator and repeat steps
13. If test results continue to differ from the specified voltage, DO NOT
place the equipment into service. Contact your local Schneider Electric
sales representative.
5. After each hi-pot test, discharge the HV bushings to ground.
Contact Resistance Measurement With the circuit breaker closed, measure the contact resistance of the
primary path from the top of the line side bushings to the top of the load side
bushings (cable connections are not included). Using a DC current source
with the current not less than 10 A, the contact resistance should not
exceed the values shown in Table 5. Repeated unacceptable test results
may be due to a loose connection or may indicate the vacuum interrupter is
at the end of its life and should be replaced. Contact Schneider Electric for
the replacement procedure.
Maximum Resistance
Continuous Current
Short Circuit Rating Measurement
Rating
(as new)
1200 A 90 ohms
2031.5 kA
2000 A 60 ohms
Final Inspection Perform a final inspection of the equipment before placing it into service.
1. Reconnect any control wiring disconnected during testing.
2. Check and record contact wear (Figure 13 on page 27).
3. Make sure all covers are in place and properly secured.
4. Check ground bars for continuity.
5. Make sure all fuses and links are inserted.
6. Verify that padlocks are in place and locked.
7. Make sure all insulation surfaces in the LV control compartment are
clean and dry.
8. Operate the circuit breaker electrically and manually to ensure it is
functional.
9. Place the circuit breaker in the OPEN position.
Section 8Operation
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
This equipment must only be installed and serviced by qualified
electrical personnel who are familiar with medium voltage circuits.
Turn off all power supplying this equipment before working on or inside
equipment.
Always use a properly rated voltage sensing device to confirm power is off.
Replace all devices, doors, and covers before turning on power to this
equipment.
4 6
2
1
5
3
16
Legend
1 Circuit breaker position indicator (Open/Closed)
2 Trip push button
3 Close push button
4 Spring position indicator (Charged/ Discharged)
5 Operations counter
6 Opening for manual spring-charging handle
Charging the Spring The spiral operating spring is located inside the mechanism. The spring can
be manually charged by inserting the manual spring-charging handle and
turning it counter-clockwise until the CHARGED/DISCHARGED indicator
reads CHARGED.
Manual Operation Open the mechanism compartment door and press the CLOSE (I) push
button to close the circuit breaker.
Electrical Operation
Manual Operation Open the mechanism compartment door and press the OPEN (O) button to
open the circuit breaker.
Electrical Operation
1 The LOCAL/REMOTE selector switch is an optional device. If it is left in the LOCAL position,
remote operation of the circuit breaker will not be permitted.
2 The LOCAL/REMOTE selector switch is an optional device. If it is left in the LOCAL position,
remote operation of the circuit breaker will not be permitted.
Emergency Trip Button The emergency trip button provides additional operator protection.
Push to tripthe mechanism is locked (blocking electrical operations)
Pull to resetthe mechanism is unlocked
Doors
Padlock
provisions
Emergency
trip button
Operating Mechanism
LV Compartment
Section 9Inspection and This section contains the inspection and maintenance procedures
recommended by Schneider Electric.
Maintenance
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
Only qualified personnel familiar with medium voltage equipment are to
perform work described in this set of instructions. These personnel must
understand the hazards involved in working with or near medium voltage
circuits and perform such work only after reading and understanding all
of the instructions contained in this bulletin.
Turn off all power supplying this equipment before working on or inside
equipment.
Open the circuit breaker and discharge all springs by pressing the OPEN
and CLOSE push buttons in the order OPEN-CLOSE-OPEN.
Always use a properly rated voltage sensing device to confirm power is off.
All maintenance must be performed by qualified personnel in
accordance with local codes and under the following conditions:
The circuit breaker must be isolated from all power sources.
Control voltage must be removed from the control circuits.
The circuit breaker must be in the open (O) position.
All circuit breaker springs must be discharged.
Handle this equipment carefully and install, operate, and maintain it
correctly in order for it to function properly. Neglecting fundamental
installation and maintenance requirements may lead to personal injury,
as well as damage to electrical equipment or other property.
Do not make any modifications to the equipment or operate the system
with interlocks and barriers removed. Contact your local Schneider
Electric sales representative for additional instructions if the equipment
does not function as described in this manual.
Use lock-out/tag-out tags and padlocks when working on equipment.
Leave tags in place until the work is completed and the equipment is
ready to be put back into service.
Carefully inspect your work area and remove any tools and objects left
inside the equipment.
Replace all devices, doors, and covers before turning on power to this
equipment.
All instructions in this manual are written with the assumption that the
customer has taken these measures before performing maintenance or
testing.
Checking Contact Wear Contact wear is checked with the circuit breaker in the CLOSED position.
Wear is measured on the vacuum interrupter vacuum chamber shaft. To
measure the contact wear, use a set of feeler gauges or a drill bit set.
Vacuum Interrupter Removal and Prior to any maintenance work being carried out in this area, the circuit
Installation breaker must be de-energized (circuit breaker open and spring discharged).
1. From the fixed end of the vacuum interrupter assembly, use a 10 mm
hex key to loosen the middle set screw (Figure 14).
Figure 14: Loosening Middle Set Screw
2. Using a 6 mm hex key, loosen the two outer set screws (Figure 15).
Figure 15: Loosening Outer Set Screws
3. With the vacuum interrupter chamber opened, remove the spring clip
and right-hand plate (Figures 16 and 17).
Figure 16: Spring Clip and Plates
Spring clip
Right-hand plate
Pivot pin
4. Remove the left-hand plate assembly by using a small punch to push the
pivot pin through its die-cast housing (Figure 17 on page 29 and
Figure 18). Once the left-hand plate assembly has been completely
removed, the vacuum interrupter will close with a dull clunk.
Figure 18: Removing the Left-Hand Plate Assembly
Wear
block
Copper
conductor
5. Place the two plates and pivot pin to one side and note the orientation of
the plates in relation to the other two interrupter assemblies.
6. Go back to the fixed end side of the assembly and lightly tighten the
middle set screw (Figure 14 on page 28).
7. Completely remove the two outer set screws (Figure 15 on page 28) and
carefully remove the interrupter assembly. A small amount of force
(6 in-lbs [0.68 Nm]) may be required at this point.
NOTE: While removing the interrupter assembly, take care that the wear
block does not catch against the copper conductor on the moving end of
the assembly (Figure 18).
9. Remove the snap ring and slide out the pin to disconnect the
phase-spring subassembly from the interrupter.
Figure 21: Disconnecting Phase-Spring Subassembly
Snap ring
Pin
NOTICE
HAZARD OF TWISTING INTERRUPTER BELLOWS
Do not use excessive force to remove the screw located inside the bore
of the connector link. This will damage the interrupter bellows, which will
affect the life span of the interrupter.
10. Using hand tools only, remove the socket screw located inside the bore
of the connector link.
Figure 22: Connector Link Bore
Socket screw
Connector link
Insulating pole
Trip/Close Coil Removal and Prior to any maintenance work being carried out in this area, the circuit
Installation breaker must be de-energized (circuit breaker open and spring discharged).
The process for removing the trip and close coils is identical. The
photographs used in these instruction are of the close coil.
1. Remove the mechanism cover to show the drive components.
2. Locate the coil bracket and disconnect the coil wiring (Figure 24).
3. Using a 3 mm Allen wrench and a standard 7 mm open ended wrench,
remove the two bracket screws and slide the assembly away from the
mechanism.
Figure 24: Coil Bracket
Coil
bracket
screws
4. Moving the assembly will reveal a plunger (Figure 25). The plunger will
remain attached to the operating mechanism. Ensure the plunger is
clean of debris.
Figure 25: Plunger
Plunger
Charging Motor Removal and Prior to any maintenance work being carried out in this area, the circuit
Installation breaker must be de-energized (circuit breaker open and spring discharged).
1. Remove the operating mechanism cover (Figure 27).
Figure 27: Mechanism Cover Removed
Screw A
Screw B
3. Unhook the operations counter spring and remove the motor mounting
bracket screws (Figure 29). One screw is located in front of the motor
and one is behind it (not shown).
Figure 29: Operations Counter Spring and Bracket Mounting Screws
Mounting
Spring
screw
5. Using an Allen wrench, remove the two socket screws securing the
motor to the bracket and pull the motor away from the mounting bracket
(Figure 31).
Figure 31: Removing Motor from Bracket
Socket screws
Groove
Torque Values
Table 7: Fastener Torque Values
Lubrication The Type EOX circuit breaker operating mechanism and related
components have been factory lubricated for the life of the unit under
normal operating conditions. If for any reason lubrication must be removed
and reapplied, specific lubrication must be applied in specific areas.
The following lubricants are approved for use in Type EOX circuit breakers:
Dow Corning Molykote PG-54 Plastislip silicone grease
Klber Unimoly GL 82 high-performance grease
Klbersynth LI 44-22 synthetic, low-temperature grease
NOTE: Do not mix any of the lubricants.
Operations
Date Counter Actions
Reading
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
Schneider Electric USA, Inc. personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
9870 Crescent Park Drive the use of this material.
West Chester, OH 45069 USA
1-888-778-2733 6065-14 04/2012
www.schneider-electric.us 2012 Schneider Electric All Rights Reserved