You are on page 1of 10

Generator Protection

7UM515 Generator protection relay (Version V3)

Scope of functions

64 81

64R 64W

59/81

59

27

Fig. 1
7UM515 generator protection relay

Application Functions Serial interfaces


The 7UM515 unit is a numerical genera- The unit contains the following integrated The relay is equipped with two serial in-
tor protection relay. It is a protection sys- protection functions: terfaces.
tem for large generators which rounds  100 % stator earth-fault protection The interface at the front is suitable for
off the 7UM511, 7UM512 and 7UT51 connection of an AT-compatible personal
 Sensitive rotor earth-fault protection
range. Some functions can be used to computer. An operating and analysis soft-
provide redundant protection.  Stator earth-fault protection (evaluation
ware DIGSI is available for convenient
of the neutral voltage) and clear setting, evaluation of fault re-
Construction  Overexcitation protection cords and data, as well as for commis-
The unit is of compact construction and  Overvoltage protection sioning.
comprises all components for: The interface on the rear of the unit is
 Undervoltage protection
 Measured value acquisition and either an isolated V.24 interface or an
 Overfrequency protection
evaluation 820-nm fibre-optic interface. It is used
 Underfrequency protection either as a system interface for connect-
 Operation and display
 Interturn protection ing to the SINAUT LSA substation control
 Indication and command output
and protection, i.e. to a protection data
 Direct coupling (for separate protection
 Acquisition of binary signals master unit (protocol acc. to VDEW/ZVEI
equipment)
 Serial data transmission recommendation, company-specific), or
 Tripping circuit monitoring as an operating interface for connecting a
 Auxiliary voltage supply
PC.
The unit is supplied with housings for Measurement method
flush and surface mounting. The model The influences of superimposed har- Settings
for panel flush mounting or cubicle monics, high-frequency transients, tran- All setting parameters are input either via
mounting has rear connection terminals sient DC current components and differ- the integrated operator and display panel
and can be supplied with or without a ing CT saturation levels is suppressed to or via a personal computer. The operator
glass cover. The model for panel surface a large degree by the use of a powerful is guided through the setting process.
mounting has 100 screw terminals ac- microprocessor and complete digital sig- The parameters are written into non-vola-
cessible from the front. nal processing (measured value acquisi- tile memories so that the settings remain
tion, measured value conditioning and secure even when the supply voltage is
measured value processing). disconnected.
Precise measurement of the voltage over
a wide frequency range of 10 to 68 Hz is Selfmonitoring
achieved by adapting the sampling rate. All important hardware and software
Some protection functions make use of components are monitored continuously.
the symmetrical current component. A Any irregularities in the hardware or in
change in the phase sequence, which the program sequence are detected and
can occur when the direction of rotation alarmed. This significantly improves the
is reversed in a pumped-storage power security and the availability of the protec-
plant, is taken into account by the protec- tion system.
tion relay 7UM515. The phase sequence
is also signalled to the protection relay as
a binary indication.

Siemens LSA 2.5.4 . February 1997  Siemens AG 19971


Generator Protection

7UM515 Generator protection relay (Version V3)

100% stator earth-fault protection The protection function evaluates the


(ANSI 64) rms value of the fundamental of the
This protection function detects earth three voltages. It has two stages.
t
faults in the machine and all galvanically
connected components of the station.
The protection criterion is the phase-to-
Thermal trip
earth resistance. With this principle,
stage
earth faults can be detected at any point
in the station, even at the machine neu-
tral point. For the measurement, a
20 Hz AC voltage is fed into the primary
equipment as a neutral voltage and the
magnitude of the 20 Hz current is calcu-
lated. The protection function has an Thermal alarm
alarm stage and a tripping stage. stage
Independently of detection of the earth
resistance, the protection function evalu-
ates the magnitude of the 50 Hz current tV/f>
flowing. There is a further stage for earth
faults with which the displacement volt-
age and therefore the evaluated current
exceeds a certain magnitude. V/f> V/f

Sensitive rotor earth-fault protection


(ANSI 64R) Fig. 2
This protection function detects earth Tripping characteristic of the overexcitation protection
faults in the exciter circuit.
It can be adjusted to be sensitive and
therefore detects high-resistance earth
faults. To calculate the resistance, an t
auxiliary voltage is interposed between
the field circuit and the earth potential.
The current flowing is a measure of the
earth resistance. To eliminate interfer-
ence from currents flowing through the
rotor-earth capacitance when the field
voltage changes, the polarity auxiliary
voltage is constantly reversed. With this
principle, calculation of the resistance is
also independent of the location of the
earth fault.

Stator earth-fault protection (evalua-


tion of the displacement voltage)
(ANSI 64)
With this protection function, the earth
faults in the stator circuit of machines
are detected by measuring the displace-
ment voltage. The protection range Vpos sequence
achieved depends on the fault quantities
present during operation. It can be up to
95% of the stator winding. Fig. 3
The function can be used redundantly for Tripping characteristic of the undervoltage protection
the earth-fault protection function. Be-
cause it has a separate voltage input, the The protection criterion is the quotient of This protection function evaluates the
function can also be assigned to any pri- the voltage and the frequency, which is rms value of the fundamental component
mary transformer. proportional to the flux density. A replica of the three voltages. It provides two
of the thermal characteristics of the pro- stages.
Overexcitation protection (ANSI 59/81) tected object is held in the protection Undervoltage protection (ANSI 27)
relay using a mathematical homogeneous
Overexcitation protection protects the model. The characteristic curve of the Undervoltage protection compares the
transformers from excessive magnetic protection relay can be adapted to the positive-sequence component of the volt-
flux density, which causes saturation of protected object by entering 6 points. ages with a lower limit value. This func-
the iron core, eddy currents and therefore tion is used for induction motors and
thermal loading of the transformer. Overvoltage protection (ANSI 59) pumped storage motor-generators and
Power plant transformers are at risk if prevents instability due to voltage.
they are disconnected from the network The protection prevents insulation faults
To stabilize the voltage during a power
at full load. due to an excessive voltage. Overvoltage
deficiency, the undervoltage protection
can be caused by a fault in the voltage
function can be used for load shedding.
controller or by maloperation.

2 Siemens LSA 2.5.4 . February 1997


Generator Protection

7UM515 Generator protection relay (Version V3)

The tripping time of the protection func-


tion is a function of the magnitude of the
voltage measured. The characteristic
used is entered by defining five points.

Frequency protection (ANSI 81)


The 7UM515 protection relay contains a
four-stage frequency protection. Each
stage can be used as either an overfre-
quency or underfrequency protection.
The algorithm filters out the fundamental
reliably even from distorted voltages and
performs a fast and precise frequency
calculation.

Interturn protection (ANSI 64W) High-voltage cable


(non-steel-armoured)
The principle of this protection function is
shown in Fig. 2.
The protection criterion (for an interturn
fault) which the 7UM515 evaluates is the
neutral voltage of the phase-to-neutral
Vo Turn
voltages. The necessary sensitivity is
7UM515
achieved using a special input and digital
filter algorithms.
Fig. 4
Direct coupling Block diagram of interturn short-circuit protection
Direct coupling functions are functions of
Fault recording Indication memory
the 7UM515 that are used for acquisition
of binary information. This binary informa- In the protection relay, instantaneous or The unit provides detailed data for the
tion is entered in the fault indication rms values are implemented depending analysis of faults and for checking states
memory. Such information can actuate on your selection. The recording duration during operation. All the indication fault
LEDs, alarm relays and command relays. is up to 5 s for instantaneous values and memories listed below are protected
Each direct coupling can delay the ef- up to 60 s for rms values. In the 7UM515 against power supply failure.
fect of the binary information by an indi- protection relay, primary values of up to  Time
vidual timer. The direct coupling func- eight faults can be stored. The total num- The unit has a battery-backed clock
tion is used for processing of information ber depends on the duration of each fault that can be synchronized with a binary
from the Buchholz relay or generator and the parameterized longest recording signal or via the system interface. All
commands. duration. Setting a leading and trailing indications are assigned a time and
time and the start event (start on activa- date.
Tripping circuit monitoring tion or on trip) permits adaptation to dif-
 Fault indications
ferent requirements. The fault data can
The 7UM515 protection relay is able to The indications of the last three faults
be transferred to the SINAUT LSA
monitor two tripping circuits (circuit- can be retrieved at any time.
substation control and protection or to a
breaker coils including incoming cables)  Operational indications
PC and evaluated there.
for correct functioning. All indications that are not directly
Trip matrix/trip circuits associated with a fault are stored in
Operational measurement the operational indication buffer.
The unit is equipped with five trip relays.
The values acquired and calculated by the
These can be arbitrarily assigned to the
unit can be displayed on the LC display or Assignable alarm relays, LEDs and
above-mentioned protection functions by
a PC. These include: Phase voltages (pri- binary inputs
parameterization (software matrix).
mary and secondary), the largest of the For user-specific output and display of
phase-to-phase voltages, the positive-se- Furthermore, each protection function
can be switched ON or OFF via the indications, alarm relays and LEDs can be
quence components of the voltages, fre- assigned as required. Information dis-
quency, neutral voltage, neutral voltage operator panel. A third Blocked mode
permits commissioning of the unit with played with the LEDs can be stored so
at the input of the interturn protection, that a start or trip can be displayed after
20 Hz voltage of the stator circuit, stator- the local annunciations and the alarm
relay circuits operative, but without trip- it has been released. Auxiliary voltage
earth resistance (secondary and primary), failure has no effect on the information
cycle duration of the rotor-earth voltage, ping of the circuit-breakers.
stored.
amplitude of the rotor-earth voltage, rotor With the many parameterizing possibili-
earth-fault measurement current (resis- ties provided, testing of and alterations to All binary inputs can be operated either
tive component for measurement from the circuit-breaker operation can be per- as make circuits or as break circuits.
unit; measurement current for rotating formed during commissioning, as well as They can also be assigned as defined by
measured value transmission), charge of during normal operation without the need the user. The signal input at a binary input
a pole reversal process (rotor earth fault), for rewiring. can be logically combined with several
rotor-earth resistance, excitation V/f, protection functions.
overtemperature calculated from
(over)excitation, and the thermal losses
(overexcitation protection).

Siemens LSA 2.5.4 . February 1997 3


Generator Protection

7UM515 Generator protection relay (Version V3)

Technical data
Input circuits Rated current 1 or 5 A
Rated voltage, can be parameterized 100 to 125 V AC
Rated frequency, can be parameterized 50/60 Hz
Thermal overload capability
in voltage paths 140 V AC
in earth voltage path 140 V AC, 300 V AC for  30 s
isolating amplifier 60 V DC
Power consumption
in voltage path at VN = 100 V <0.3 VA

Voltage supply Rated auxiliary voltage Vaux 24 V, 48 V DC or


via integrated DC/DC converter 60 V, 110 V, 125 V DC or
220 V, 250 V DC
Permissible tolerance of the rated auxiliary voltage 20 to + 15 %
Power consumption max. 20 W

Setting ranges
100 % stator earth-fault protection Alarm stage RSEF < 20 to 500 2
(ANSI 64) Trip stage RSEF << 10 to 300 
Earth current stage SEF >> 0.02 to 0.8 A
Trip delay, reset delay 0 to 32 s
Reset ratios Approx. 1.2 to 1.7
Failure monitoring 20 Hz generator
V20 0.3 to 15 V
20 5 to 40 mA




Correction angle 30 to +30




Sensitive rotor earth-fault protection Alarm stage RE ALARM 5 to 80 k
(ANSI 64R) Tripping stage RE TRIP 1 to 10 k






Trip delay, reset delay 0 to 32 s

Reset ratio 1.25


Response time 1 to 1.5 s




Response threshold of fault indication 1) QC< 0.01 to 1 mAs




Reset ratio 1) 1.2 or 0.01 mAs
Permissible rotor-earth capacitance1) 0.15 to 4 F




Stator-earth fault protection




Neutral voltage V> 5 to 100 V

(ANSI 64) Trip delay, reset delay 0 to 32 s




Reset ratio 0.7
Response time 50 ms




Overexcitation protection




Overexcitation V/f> 1 to 1.5 V

(ANSI 59/81) Trip delay, reset delay 0 to 32 s


Reset ratio Approx. 0.98;




Approx. 0.99 thermal alarm stage




Response time 250ms
Characteristic value pairs for thermal characteristic




V/f 1.02 to 1.6
t 1 to 98 s




Time factor 1 to 8




V/f basic value (limit value for previous load acquisition) 0 to 1




Overvoltage protection (ANSI 59) Voltage V>, V>> 30 to 180 V
Trip delay, reset delay 0 to 32 s




Reset ratio 0.98
50 ms




Response time

Undervoltage protection (ANSI 27) Characteristic value pairs




V< 20 to 100 V
t 0 to 32 s






Reset delay 0 to 32 s

Reset ratio Approx. 1.05


Response time Approx. 50 ms

1) Not for rotating measured-value transmission

4 Siemens LSA 2.5.4 . February 1997


Generator Protection

7UM515 Generator protection relay (Version V3)




Technical data (continued)




Setting ranges (continued)
Frequency protection (ANSI 81) Number of stages 4




Frequency f1, f2, f3, f4 40 to 65 Hz




Number of measurement repetitions 2 to 10 000
(one measurement requires a time of 3/f)




Reset difference Approx. 20 mHz
Response time 100 ms + time for measurement






Undervoltage blocking V< 40 to 100 V

Reset ratio of blocking 1.05




Interturn protection (ANSI 64W) Displacement voltage Vwin> 0.3 to 130 V
Trip delay, reset delay 0 to 32 s




Reset ratio Approx. 0.6




Response time v50ms




Direct coupling Number 4
Trip delay t1, t2, t3, t4 0 to 32 s




Reset delay t1, t2, t3, t4 0 to 32 s



Response time <15 ms

Switchover of the rotating field direction Response time 200 ms (requirements I < 0.1 x IN and



V < 0.1 x VN)



Response tolerances under nominal Stator earth-fault protection Resistance 5 % or 2 
conditions Current 3 % or 3 mA





Rotor earth-fault protection Resistance

Voltage (voltage and earth-fault protection)


5 % or 0.5 k at 0.15 F v CE < 1 F
10 % or 0.5 k at 1 F v CE v 4 F
v3 % of the setting value or 1 V



Voltage (interturn protection) v3 % of the setting value or 0.1 V



Frequency at f = fN 10 mHz
Times 1 % or 10 ms



Operational measured values



Display of the values
Voltage VPH1N, VPH2N, VPH3N, Vmax PH, VPOS,
V0, VWIN



Frequency f



Stator earth-fault protection
Voltage VSEF rms
ISEF rms



Earth current
Stator resistance RSEF, RSE p



Rotor earth-fault protection
Cycle duration Tg



Voltage amplitude Vg
Measured current Ig



Charge QC
Rotor-earth resistance RREF



Overexcitation protection
Excitation (flux density) V/f



Overtemperature V/fth.
Thermal losses th. loss



Frequency f



Fault data acquisition Either instantaneous values (12 values per cycle) vPH1N, vPH2N, vPH3N, v0, vWIN, vSEF,
iSEF, vREF


3 V
Or calculated values (one value per cycle) POS, Vmax PH, V 0, VW, V SEF


ISEF, RSEF, ffN

Contacts Potential-free trip contacts (3 x 2, 2 x 1) NO contacts


(total of 5 TRIP relays)
Switching capacity make 1000 W/VA
break 30 W/VA
Permissible current, continuous 5A
0.5 s 30 A
Switching voltage 250 V DC
Alarm contacts 13
Switching capacity make/break 20 W/VA
Permissible current 1A
Switching voltage 250 V DC

Displays, signal inputs LED displays on the front of the unit 16


Optocoupler 8
for 24 to 250 V DC
Current consumption independent of voltage Approx. 2.5 mA

Siemens LSA 2.5.4 . February 1997 5


Generator Protection

7UM515 Generator protection relay (Version V3)

Technical data (continued)


CEconformity, standards This product is in conformity with the directives of the Council of Conformity is proved by tests performed
the European Communities on the approximation of the laws of by Siemens AG in line with article 10 of the
the Member States relating to the electromagnetic compatibility Council Directives in accordance with the
(EMC Council Directive 89/336/EEC) and concerning electrical generic standards EN 50081 and EN 50082
equipment for use within specified voltage limits (low voltage for the EMC directive 89/336/EEC and
directive 73/23/EEC). The product conforms with the international standard 602556 for the low voltage di-
standard IEC 255 and the national standard DIN 57 435 part 303 rective.
(corresponding to VDE 0435 part 303).
The relay is designed for use in an industrial environment, for
installation in standard relay rooms and compartments so that
with proper installation electromagnetic compatibility (EMC) is
ensured.

Insulation tests Voltage test (routine test) all circuits except the auxiliary voltage 2 kV (rms value), 50 Hz
IEC 255-5, VDE 0435 Part 303 Voltage test (routine test), for auxiliary voltage only
Impulse voltage test (type test), all circuits, class III DC 2.8 kV
5 kV (peak value), 1.2/50 ms, 0.5 J,
3 positive and 3 negative impulses at inter-
vals of 5 s

EMCtests; immunity (type test) High frequency test with 1 MHz interference 2.5 kV (peak), 1 MHz,  = 15 ms,
Standards: IEC 2556, IEC 25522 IEC 255221, class III and VDE 0435 part 303, class III 400 shots/s, duration 2 s
(international product standard) Electrostatic discharge 4 / 6 kV contact discharge, 8 kV air dis-
EN 500822 (generic standard) IEC 255222, class III and IEC 100042, class III charge, both polarities, 150 pF, Rl = 330 W
VDE 0435 part 303 (German Radiofrequency electromagnetic field, nonmodulated 10 V/m, 27 to 500 MHz
product standard) report IEC 255223, class III
Radiofrequency electromagnetic field, amplitude modulated 10 V/m, 80 to 1 000 MHz, AM 80 %, 1 kHz,
IEC 100043, class III
Radiofrequency electromagnetic field, puls modulated 10 V/m, 900 MHz, repetition frequency
ENV 50204, class III 200 Hz, duty cycle 50 %
Fast transients 2 kV, 5/50 ns, 5 kHz, burst length = 15 ms,
IEC 255224 class III, IEC 100044 class III repetition rate 300 ms, both polarities,
Rl = 50 W, duration 1 min
Conducted disturbances induced by radiofrequency fields, 10 V, 150 kHz to 80 MHz, AM 80 %, 1 kHz
amplitude modulated
IEC 100046, class III
Power frequency magnetic field 30 A /m, continuous, 300 A /m for 3 s, 50 Hz
IEC 100048, class IV 0.5 mT; 50 Hz
IEC 2556

EMCtests; emission (type test) Conducted interference voltage, auxiliary voltage 150 kHz to 30 MHz, group 1
Standard: EN 500812 (European generic CISPR 11, EN 55011 and VDE 0875 part 11 class A
standard for use in industrial Interference field strength 30 to 1 000 MHz, group 1
environment) CISPR 11, EN 55011 and VDE 0875 part 11 class A

Climatic conditions Permissible ambient temperature during service 5 to + 55C


during storage 25 to + 55C
during transport 25 to + 70C
Humidity class Annual average: 75 % relative humidity;
on 30 days/year up to 95 % relative humid-
ity; condensation not permissible

Mechanical stress tests Permissible mechanical stress during service 10 Hz to 60 Hz: 0.035 mm amplitude
IEC 255211, IEC 682 60 Hz to 500 Hz: 0.5 g acceleration
during transport 5 Hz to 8 Hz: 7.5 mm amplitude
8 Hz to 500 Hz: 2 g acceleration

Construction For panel surface mounting in housing 7XP20 401


Weight Approx. 12 kg
For panel flush mounting, cubicle mounting in housing 7XP20 402
Weight Approx. 10,5 kg
Degree of protection acc. to EN 60 529 IP 51

6 Siemens LSA 2.5.4 . February 1997


Generator Protection

7UM515 Generator protection relay (Version V3)

Selection and ordering data


Order No.
7UM515 generator protection relay 7UM515 0   B 0 1 0  A 0
Rated auxiliary voltage
24 V, 48 V DC 2
60 V, 110 V, 125 V DC 4
220 V, 250 V DC 5
Construction
for panel surface mounting, with screw terminals B
for panel flush mounting or cubicle mounting C
for panel flush mounting or cubicle mounting without glass cover E
Rear serial interface (suitable for station control and DIGSI operating program)
electrical B
optical C

Accessories
Rotor earth-fault protection
Series coupling unit, impulse generator (W x H x D in mm) 298 x 220 x 253 7XT70000B
(100/110 V AC; Weight 2.5 kg)
Coupling unit in housing 3PP1346 Insulation voltage 4.5 kV or 7XR6002
Coupling unit in housing 3PP1346 Insulation voltage 6 kV 7XR6003
Stator earth-fault protection
20 Hz generator (100/110 V AC; weight 15 kg) (W x H x D in mm) 390 x 222 x 312 7XT31101
Band-pass filter (weight 23 kg) 240 x 270 x 200 7XT32000
Miniature C.T. (weight 0.5 kg) 58 x 100 x 70 4NC12252CK20
Voltage divider 500 V/100 V 196 x 300 x 146 3PP13361CZ013001

Operation software
DIGSI program (suitable for all protection relays 7UM..., 7UT..., 7SJ..., 7SA..., ...) German 7XS50200AA00
English 7XS50201AA00
Test version: German 7XS50210AA00
English 7XS50211AA00
Connecting cables for protection relays (25-pin) PC (9-pin); (other variations supplied on request) 7XV51002

Documentation
German
Katalogblatt LSA 2.5.4: Maschinenschutz 7UM515 (Version V3) E50001K5752A141A2
Handbuch: Maschinenschutz 7UM515 C53000G1100C1111
English
Catalog LSA 2.5.4: 7UM515 Generator protection (Version V3) E50001K5752A141A27600
Manual: 7UM515 Generator protection C53000G1176 C1111

Siemens LSA 2.5.4 . February 1997 7


8
Version for panel surface mounting
Network

Fig. 5
L1 L2 L3
Unit auxilary supply Version for panel flush mounting/cubicle mounting
L1 9 3B1
L2 V L1
7B1 65 100% stator earthfault
L3 10 3B2
Alarm relay 1 8B1 64
11 3B3
V L2 6B1 63
12 3B4 7B2 68 Rotor earthfault RE <
V L3 13 2B1 8B2 67
Alarm relay 2 66
14 2B2 6B2
VN 7B3 71
VO Ve 31 2B3 8B3 70
OverexitationV/f, V/f 
Alarm relay 3
2B4 6B3 69


V n 32 7B4 86
33 1B1 Earthfault VO >
V O win 34 8B4 85
1B2 Alarm relay 4
6B4 84
35 1B3
Generator Protection

3D1 87 OvervoltageV >


V SEF 36 1B4 Alarm relay 5 4D1 88
3D2 89 OvervoltageV >>
V L1  SEF 8 1D2 Alarm relay 6 4D2 90
V L2 7UM515 3D3 91
V L3 4 1D1 Alarm relay 7 Undervoltage V <
VN 4D3 92
53 8A2 3D4 93
Binary Underfrequency f1< , f2 <
54 Alarm relay 8 4D4 94
Ve 8A1 input 1 3C1 95

Connection diagram of the 7UM515 generator protection relay


55 Underfrequency f4 <
8A4 Alarm relay 9 4C1 96
56 Binary 3C2 43 V/f Alarm
Vn 8A3 input 2 Alarm relay 10 4C2 44
7UM515 Generator protection relay (Version V3)

57 7A2 3C3 45
7XT32 Group alarm trip
Binary Alarm relay 11 4C3 46
7XT31 Band pass 58 7A1
input 3 47
filter 3PP1336 3C4
20 Hz generator 59 7A4
R.e.f.. R E Alarm
Voltage Alarm relay 12 4C4 48
5 3 1 Binary L + (M2)
1 divider 60 7A3 input 4 6A3 19
2 G 61 8D2
20Hz Unit malfunction 6A1 18 L + (M1)
3 62 8D1 Binary alarm 6A2 17
6 input 5 Internal failure
78 8D4
e 8 1) 9 5B1 74
79 8D3 Binary 99 L+
input 6 Command 5B3
K L RL 80 7D2 relay 1 5B4 100 Trip command 1
n Binary 75
81 5B2 L
k l 7D1 input 7 72
5A1
82 7D4 5A3 L+
4NC1225 Binary Command 97
83 7D3 input 8 relay 2 5A4 98 Trip command 2
7XR6002 39 2C3 5A2 73
Resistor unit 20 L
6D1
V control.REF 40 2C4 6D3 22 L+
3 40k 2 Command
37 2C1 relay 3 6D4 23 Trip command 3
7XT70 V mes.REF 38 6D2 21
2C2 5D1 24 L
Excitation Coupling unit 1 6 7 L+
G system 15 4B1 L + Command 5D2 25
14 relay 4 Trip command 4
Power supply 16 4B2 L 5D3 49
1 40k 15 100V Command L+
5D4 50 Trip command 5
relay 5
2
4A1 4A3 76
3 RxD 51 V.24 interface, 2kV isolated TxD
MR 52 4A2 coupling to central unit 4A4 77 MT Optional V.24
5 or fibreoptic
Fibreoptic interface
1) Loss of 20 Hz voltage coupling to central unit
26
Binary inputs, 1 to 6 alarm relays,
command relays, LEDs are
marshallable

Siemens LSA 2.5.4 . February 1997


Generator Protection

Dimension drawings in mm

7.3 206.5
220 30 172 29.5 13.2 180

5.4
Diam. 5 or M4

255.8
Fibreoptic

244

266

245
interface
1.5
10

Diam. 6

225 221
231.5

Front view Side view Panel cutout

Fig. 6
7UM515 in 7XP20402 housing (for panel flush mounting and cubicle mounting)

234
7.5 27 29.5
51 ..... 75
76 ..... 100

Cutout 20 x 60
(without paint)
280
344

266
40

39 1.5
Fibreoptic interface

1 ..... 25
26
..... 50 Z
71
219 260

Front view Side view Detail Z:

Fig. 7
7UM515 in 7XP20401 housing (for panel surface mounting)

Siemens LSA 2.5.4 . February 1997 9


Generator Protection

Conditions of Sale and Delivery S Export Regulations S Trademarks S Dimensions

Conditions of Sale and Delivery


Subject to the J
General Conditions of Supply and Delivery The technical data, dimensions and We reserve the right to adjust the prices
for Products and Services of the weights are subject to change unless and shall charge the price applying on
Electrical and Electronic Industry otherwise stated on the individual pages the date of delivery.
and to any other conditions agreed upon of this catalog.
with the recipients of catalogs.
The illustrations are for reference only.
A 9.91 a

Export Regulations
In accordance with present provisions of An export licence may however be requi- Relevant are the criteria stated in the de-
the German Export List and the US Com- red due to countryspecific application of livery note and the invoice.
mercial Control List, export licences are the products.
not required for the products listed in this Subject to change without notice.
catalog.

Trademarks Dimensions
All product designations used are trade- All dimensions in this catalog are given in
marks or product names of Siemens AG mm.
or of other suppliers.

Siemens online!
The Power Transmission and Distribution
Group can also be found in the Internet:
http://www.ev.siemens.de

Responsible for
Technical contents: Dr. HansJoachim Hermann,
Siemens AG, EV S V13, Nrnberg
General editing: Roland Reichel/Claudia KhnSutiono,
Siemens AG, EV S SUP22, Nrnberg/EV BK T, Erlangen

Bereich
Energiebertragung und -verteilung Power
Geschftsgebiet Sekundrsysteme
P. O. Box 48 06 Transmission
D-90026 Nrnberg and Distribution
10
Siemens Aktiengesellschaft Order No.:Siemens
E50001-K5752A141-A27600
LSA 2.5.4 . February 1997
Printed in Germany
KG K 0297 2.0 SD 10 En 321510 6101/U528

You might also like