You are on page 1of 2

eSure Rectifier DC Power

for Business-Critical Continuity

R48-2000e

eSure Rectifier Description


-48 V DC, 2000 W The eSure R48-2000e rectifier converts standard AC supply voltages into stable
nominal-48V DC voltage adjustable to the needs of the application. The R48-
Features and Benefits 2000e is a constant power rectifier designed with the latest patented switch-
Optimized depth-reduced footprint mode technology using DSP (Digital Signaling Processor) functionality for
allows installation in short-depth racks efficient operation.
and cabinets
For a higher load capacity, rectifiers can be connected in parallel and intelligent
DSP (Digital Signaling Processor)-
means fewer components, optimized
control can be added with the help of a separate controller.
operation and active load sharing for
increased reliability
Compliant with global standards-
delivers quality, performance
and reliability no matter what the
application or location demands
High efficiency, near 97%-reduces
power consumption for lower
operating costs
Hot pluggable-facilitates future
extensions
Wide input voltage range-operates in
the most demanding environments
where input voltage changes
Wide temperature operating range R48-2000e
(-40C / -40 F to +80C / 176F) -meets
the harshest climatic environment
requirements
eSure Rectifier
R48-2000e

Technical Specifications, R48-2000e


AC Input R 48-2000e Output power vs.
Temperature at 290VVin176 Vac
Input Voltage, Nominal 200 to 250 V AC

% of output power
120
Input Voltage, Permitted Variation 85 to 300 V AC 100
Line Frequency 45 to 65 Hz 80
Max Input Current 13 A 60

Power Factor 0.99 40


20
THD (Total Harmonic Distortion) <5% from 50 to 100% of rated load
0
-40 -20 0 20 40 60 80 100
Temperature (C)
DC Output
Output Voltage, Adjustment Range -42 to -58 V DC
Output Power 2000W@Vout >48VDC R 48-2000e Output power vs. Input
voltage and Vo>48V at Temp55C
Output Power, Derated for Input Voltage See Diagram

% of output power
120
Output Current 41.7A@-48VDC
100
Output Current limit set Point 0 to 41.7A 80
Efficiency 96.5% peak 60
Psophometric noise (system) <2 mV typical 40

<38 dBrnc typical 20


0
Temperature Derating See diagram 0 50 100 150 200 250 300 350
Input voltage (VAC)

Control and Monitoring


Rectifier Alarm and Signaling Alarm and status reported via CAN bus to system Controller R48-2000e Output voltage v.s. Output current
Visual Indications Green LED = Normal operation; Yellow LED = Alarm; at max. Power
Red LED = Failure; Flashing red LED = Fan failure 60

Output Voltaqe(V)
50
40

Environmental 30
20
Temperature Range, Operating -40 to +80C, -40 to +176F
10
Temperature Range, Storage -40 to +70C, -40 to +158F 0
0 5 10 15 20 25 30 35 40 45
Relative Humidity 0 to 95% Output current(A)
Altitude 2000 m, 6560 ft at full power
EMC ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE class B
Safety IEC 60950, EN 60950, UL 60950 Efficiency Curve
97.0
96.5
Mechanics
Efficiency

96.0
Dimensions (HWD) 86 84.5272mm / 3.393.3310.71 inches 95.5
Efficiency
Weight 2.4kg/5.3lbs 95.0
94.5
94.0
0 500 1000 1500 2000 2500
Other parts Output Power
Controller Units See separate ACU/ACU+ and SCU/SCU+ datasheets

Ordering information
Description Product Code
Rectifier 48V,2000W 1R482000eXXX

AC Power Embedded Power Precision Cooling


Emerson Network Power.
Connectivity Infrastructure Management & Monitoring Racks & Integrated Cabinets
The global leader in enabling
DC Power Outside Plant Services
Business-Critical Continuity.
Embedded Computing Power Switching & Controls Surge Protection

www.emersonnetworkpower.com Business-Critical Continuity, Emerson Network Power


www.emersonnetworkpower.com/energysystems and the Emerson Network Power logo are trademarks
www.DCpowerefficiency.com and service marks of Emerson Electric Co.
2010 Emerson Electric Co.
Emerson Network Power reserves the right to alter without notice the specification, design or conditions of supply of any product or service. 2010.6