Professional Documents
Culture Documents
USERS MANUAL
SERS MANUAL
SIL_MANU_SILA_ING_R017.Docx
1. RECEPTION, HANDLING, INSTALLATION ............................................... 7
1.1. Unpacking ............................................................................................................................ 7
1.2. Reception of relays ............................................................................................................. 7
1.3. Handling electronic equipment .......................................................................................... 7
1.4. Installation, commissioning and service .......................................................................... 8
1.5. Storage ................................................................................................................................. 8
1.6. Recycling .............................................................................................................................. 8
2. DIMENSIONS AND CONNECTION DIAGRAMS ........................................ 9
2.1. SILA LPCT Model (SILAXX)-Adaptation A ........................................................................ 9
2.1.1. Equipment front view ......................................................................................................... 9
2.1.2. Equipment dimensions .................................................................................................... 10
2.1.3. Cut-out pattern ................................................................................................................ 11
2.1.4. Connection diagrams ...................................................................................................... 11
2.1.5. Terminals......................................................................................................................... 13
2.2. Standard SILA - Adaptation A .......................................................................................... 15
2.2.1. Equipment front view ....................................................................................................... 15
2.2.2. Equipment dimensions .................................................................................................... 16
2.2.3. Cut-out pattern ................................................................................................................ 17
2.2.4. Connection diagrams ...................................................................................................... 18
2.2.1. Terminals......................................................................................................................... 22
2.3. SILA LPCT model (SILAXX) - Adaptation B .................................................................... 26
2.3.1. Equipment front view ....................................................................................................... 26
2.3.2. Equipment dimensions .................................................................................................... 27
2.3.3. Cut-out pattern ................................................................................................................ 28
2.3.4. Connection diagrams ...................................................................................................... 28
2.3.5. Terminals......................................................................................................................... 30
2.4. Standard SILA - Adaptation B .......................................................................................... 32
2.4.1. Equipment front view ....................................................................................................... 32
2.2.2. Equipment dimensions .................................................................................................... 33
2.4.2. Cut-out pattern ................................................................................................................ 34
2.2.4. Connection diagrams ...................................................................................................... 35
2.4.3. Terminals......................................................................................................................... 39
3. DESCRIPTION .......................................................................................... 41
3.1. Introduction ........................................................................................................................ 41
3.2. Description ......................................................................................................................... 41
3.3. Functional Diagram ........................................................................................................... 47
3.4. Selection & Ordering data ................................................................................................ 48
3.5. Phase CT and neutral CT selection ................................................................................. 49
3.5.1. SIL-A/1 charge curve ...................................................................................................... 50
1.1. Unpacking
Relays must only be handled by qualified personnel and special care must be taken to protect all
of their parts from any damage while they are being unpacked and installed.
The use of good illumination is recommended to facilitate the equipment visual inspection.
The facility must be clean and dry and relays should not be stored in places that are exposed to
dust or humidity. Special care must be taken if construction work is taking place.
www.fanox.com 7/344
1.4. Installation, commissioning and service
The personnel in charge of installing, commissioning and maintaining this equipment must be
qualified and must be aware of the procedures for handling it. The product documentation should
be read before installing, commissioning or carrying out maintenance work on the equipment.
Personnel should take specific protection measures to avoid the risk of electronic discharge
when access is unlocked on the rear part of the equipment.
In order to guarantee safety, the crimp terminal and a suitable tool must be used to meet
isolation requirements on the terminal strip. Crimped terminations must be used for the voltage
and current connections.
It is necessary to connect the equipment to earth through the corresponding terminal, using the
shortest possible cable. As well as guaranteeing safety for the personnel, this connection allows
high frequency noise to be evacuated directly to earth.
The following checks must be performed before the equipment is supplied:
The rated voltage and polarity.
The power rating of the CT circuit and the integrity of the connections.
The integrity of the earth connection.
The equipment must be used within the stipulated electrical and environmental limits.
NOTE: current transformer circuits: Do not open a live CT secondary circuit. The high voltage
produced as a result could damage the isolation and threaten lives.
1.5. Storage
If the relays are not going to be installed immediately, they must be stored in a dust- and
humidity free environment after the visual inspection has been performed.
1.6. Recycling
Before recycling the equipment, the capacitors should be discharged through the external
terminals. All electrical power sources should be removed before performing this operation to
avoid the risk of electrical discharge.
This product must be disposed of in a safe way. It should not be incinerated or brought into
contact with water sources like rivers, lakes, etc
CUT-OUT
PATTERN
C2 Digital input 6
C3 Digital input 7
C4 Digital input 8
CUT-OUT
PATTERN
B2 Digital input 2
B3 Digital input 3
B4 Digital input 4
C1 Digital input 5
C2 Digital input 6
C3 Digital input 7
C4 Digital input 8
B4 Digital input 4
C1 Digital input 5
C2 Digital input 6
C3 Digital input 7
C4 Digital input 8
(*) When the model is chosen it is very important to choose the communications protocols
correctly. If RS485 port is chosen then E communications module is not available. If E
communications module is chosen then RS485 port is not available.
(*) When the model is chosen it is very important to choose the communications protocols
correctly. If RS485 port is chosen then E communications module is not available. If E
communications module is chosen then RS485 port is not available.
3.1. Introduction
Worldwide, the energy sector is currently undergoing a profound change as a result of high
levels of energy demand; more distribution lines and advanced supervision systems are
required. Given the need for creating intelligent infrastructure, FANOX has developed the SIL
family of products to carry out this function.
The SIL- A relay is designed to protect the secondary transformation and distribution centres of
electricity grids, using current functions. It is thought to work with a circuit breaker as element to
cut the power.
The protection functions can be enabled selectively by using both the front panel and the
communications links to the SIcom program, allowing for precise coordination with other
equipment.
Additional benefits include that all of the models have been designed to be supplied from an
external battery. This is aimed at facilitating event management and the commissioning of
centres, as well as allowing it to operate properly under adverse conditions.
3.2. Description
Power is supplied with an auxiliary voltage, and depending on the model, there are various
operation ranges. In models with Adaptation A it is possible to select an auxiliary voltage of 24-
48 Vdc or 90 -300 Vdc /110 -230Vac. In models with Adaptation B it is possible to select an
auxiliary voltage of 24-110 Vdc/48-230Vac. Apart from the overcurrent protection functions of a
line with a circuit breaker, instantaneous phase and neutral, and protection against phase and
neutral inverse time overcurrent, the relay provides phase imbalance and circuit breaker fault
functions as well as a thermal image protection.
As this is line protection, a re-closer is fitted. This automated control shall permit closure (up to
five attempts) with the possibility of programming each reclosing time. It can be blocked by
various means, from the keyboard with a separate key, to the remote communications.
Further functions have been included which support line protection, such as the cold load pickup,
or the trip circuit supervision.
All models include a circuit breaker management block, which monitors the state of the circuit
breaker, the number of openings and the accumulated amps. It generates an indication if these
are excessive, it determines whether or not an Opening fault has occurred and allows the circuit
breaker close and open commands from the HMI, with different keys, and via the
communications port (either locally or remotely).
Optionally, in models with Adaptation A, 49 protection function can be included. In models with
Adaptation B, apart from 49 protection function, 74CT, 37, 46BC and trip block for switch
disconnector functions can be selected as optional.
The SIL-A equipment has inputs and outputs that can be set by the user:
Adaptation A Adaptation B
The equipment has an LCD with two lines and twenty columns and a membrane keyboard with
six buttons. These allow the equipment status, the current measurements in the primary winding
and the events or incidents associated with the equipment to be seen, and adjustments to be
made to the protection criteria. Depending on the model, these events can be saved in a non-
volatile memory to keep them when there is no power.
As well as the 6 keys to navigate the menus, there are also special keys:
Reset. To reset the signals and events.
79 lock. This locks and unlocks the recloser.
Circuit breaker I/O. This serves to control the circuit breaker.
The SIL-A with Adaptation A is fitted with 8 front leds, of which 2 have reserved functions and the
other 6 can be set. The fixed function leds are as follows:
Circuit breaker status.
Recloser status.
The SIL-A with Adaptation B is fitted with 8 front leds, all of them configurable by the user.
The SIL-A with Adaptation A has storage for up to 500 events and SIL-A with Adaptation B for up
to 200 events, allowing any registered incidents to be analysed. As an option, the equipment can
be requested with a real time clock.
To facilitate problem solving, and as a wide range of fault events may arise (recloser and reverse
criteria) that may not be entirely detected by the oscillography as this is time limited, and as
event recording consists on more general information, with the possibility of fault specific
information being lost, the equipment includes a fault report record. This report allows the last 20
faults to be recorded with a capacity of 80 events per fault in case of SIL-A with Adaptation A and
24 events per fault in case of SIL-A Adaptation B.
In order to facilitate the analysis of events, it is fitted with oscillography records. SIL-A with
Adaptation A is fitted with 2 oscillographic registers, each one with 50 cycles (1 second at 50 Hz,
0.833 seconds at 60 Hz). 3 prefault cycles and 47 postfault cycles. The oscillography start can
be configured by the user. Each oscillography record shows the phase and neutral currents and
up to 80 digital channels, which include start-ups and trips, the protection functions, inputs,
outputs, etc. The COMTRADE format is used (IEEE C37.111-1991).
SIL-A with Adaptation B is fitted with 5 oscillographic registers, each one with 100 cycles (2
seconds at 50 Hz, 1.666 seconds at 60 Hz). 3 prefault cycles and 97 postfault cycles. The
oscillography start can be configured by the user. Each oscillography record shows the phase
and neutral currents and up to 48 digital channels, which include start-ups and trips, the
protection functions, inputs, outputs, etc. The COMTRADE format is used (IEEE C37.111-1991).
Adaptation A Adaptation B
Fault reports 20 fault reports /80 events in each 20 fault reports /24 events in each
Adaptation A Adaptation B
Setting-up a session allows four levels of access to be set up with passwords that can be
configured by the user.
The protective functions provided, easy-to-use interface, low amount of maintenance and simple
integration make the SIL-A a precise and practical solution for protecting both industrial and
public electrical grids and transformation and distribution centres. The SIL-A protection against
earthing faults is sensitive enough to be used on electric systems with low earthing fault currents.
It can be adjusted to 0.1 times the rated current and extremely low rated levels can be selected.
The main features of the equipment are listed below, and these features will be explained in the
rest of the manual:
Protection
1 through configurable
74TCS Trip circuit supervision 1 with specific inputs
inputs
Trip block Trip block for switch disconnector Not available Optional
Measurements
Configurable Inputs 8 6
5 outputs: 4 outputs:
Configurable outputs 2 (NO/NC) + 3 (NO) 2 (NO/NC) + 2 (NO)
Communication
LOCAL Communication
1 Local port RS232: ModBus RTU
(Optional) (Optional)
2 remote ports with 1 remote port with the following
the following options: options:
2 Remote port 1 Remote port RS485: ModBus RTU
RS485: ModBus or IEC 60870-5-103 (by general
REMOTE Communication RTU and IEC 60870- settings)
5-103
1 RJ45: IEC61850, DNP3.0 or IEC
1 Remote port 60870-104
RS485 ModBus RTU
and 1RJ45 port: IEC
61850, DNP3.0 or
IEC 60870-104
8 leds: 8 leds:
LED Indicators 6 configurable All configurable
2 non configurable
Power
24-48 Vdc
Auxiliary voltage . 24-110 Vdc./48-230 Vac
90Vdc300Vdc /110Vac230 Vac
Test menu
Self-diagnosis
Adjustments Table
By general settings
3 setting tables 4 setting tables
By Inputs
Mechanical
(**) LPCT model: 50N/G and 50/51N : calculated neutral; inStandard model: 50N/G and 50/51N/G: measured neutral
(1*) On SIL-AXX models( LPCT type), the accuracy of the measurement in the neutral is 8%
NOTE: LPCT model 50N/G and 50/51N: calculated neutral; Standard model 50N/G and
50/51N/G: measured neutral
PHASE NEUTRAL
0 Standard (In = 1A / 5A). Defined by General Setting
1 In = 1 A; (0,10 30,00 A)
5 In = 5 A; (0,50 150,00 A)
X X LPCT (Primary In = 50 800A). Defined by General Setting
NEUTRAL MEASUREMENT
0 Standard (In = 1A / 5A). Defined by General Setting
1 In = 1 A; (0,10 30,00 A)
5 In = 5 A; (0,50 150,00 A)
S Sensible (In = 0,1A / 0,5A). Defined by General Setting
X X LPCT: Internally Calculated.
NET FREQUENCY
0 (50Hz / 60Hz). Defined by General Setting
5 50 Hz
6 60 Hz
POWER SUPPLY
A 24-48 Vdc
B 90-300 Vdc / 110-230 Vac
C 24-110 Vdc/48-230Vac
ADDITIONAL FUNCTIONS
0 0 -
1 + 49
2 + 49 + 74CT + 37 + 46BC + Trip Block for switch
disconnector
REAR COMMUNICATIONS
0 RS485: ModBus + IEC 60870-5-103
1 FOP: ModBus + IEC 60870-5-103
2 FOC-ST: ModBus + IEC 60870-5-103
3 RJ45: IEC61850 + RS485: ModBus (not available in LPCT
model)
4
RJ45: DNP3.0 (TCP/IP) + RS485: ModBus(not available in
5 LPCT model)
RJ45: IEC 60870-5-104 + RS485: ModBus (not available in
LPCT model)
INPUTS-OUTPUTS
0 8 Inputs + 5 Outputs. Configurable
1 6 Inputs + 4 Outputs. Configurable.
MECHANICS
0 LPCT model: 4U x Rack
1 Standard model: 4U x Rack
2 LPCT & Standard: 4U x rack
LANGUAGE
A A English, Spanish and German
B B English, Spanish and Turkish
C C English, Spanish and French
D D English, Spanish and Russian
ADAPTATION
A -
B -
Residual phase
SIL-A55 CT 5 A 1-150 A 1-150 A
connection
Residual phase
SIL-A11 CT 1 A 0,2-30 A 0,2-30 A
connection
Adaptation B
Phase
Neutral nominal current
Model nominal Phase range Neutral range
current
Residual phase connection,
SIL-A00 1 A or 5 A 0,1 -30 A or 0,5-150 A 0,2-30A or 1-150A
1A or 5A
0,1-30 A or 0,5-150 A
Residual phase connection, or
SIL-A0S 1 A or 5 A 0,1-30 A or 0,5-150 A
0.5A or 0.1A 0,01-3A or 0.05-15A
0,05-15 A or 0,25-75 A
Residual phase connection, 1A or
SIL-AS0 0.5A or 2.5A 0,05-15 A or 0,25-75 A
or 5A 0,1-30 A or 0,5-150 A
0,05-15 A or 0,25-75 A
Residual phase connection, or
SIL-ASS 0.5A or 2.5A 0,05-15 A or 0,25-75 A
0.5A or 0.1A 0,01-3A or 0.05-15A
To ensure the relay functions correctly, a suitable current transformer must be used. The load of
the relays own measurement circuits and the load on the cables that connect the CTs and the
relay must be taken into account.
The SIL-XX unit is fitted with standard inputs in accordance with standard IEC 60044-8. This
standard established a rated voltage of 22.5mV for the rated current.
0,04
0,03
Average Voltage (V)
0,02
0,01
SILA/1 Circuito
SILA/1 de Medidacircuit
measurement
0,1
Average Voltage (V)
0,05
Permission - - YES/NO - No
50P_1
50P_2
Tap 0,10 30,00 0,01 Inominal 5,00
The operating time is independent from the operating current flowing through the equipment, so
if the phase current exceeds its predetermined value for an equal or greater amount of time than
this preset value, the protection function activates (trips) and does not reset itself until the
average value of the phase drops below the point of current pick-up.
The function activates at 100% of the preset input, and deactivates at 95%. The reset is
instantaneous.
The accuracy of the operating time is equal to the preset time 30 ms or 0.5%
Permission - - YES/NO - No
IEC Extrem.
Curve - - (1*) -
Inverse
50/51P
Dial 0,02 2,20 0,01 - 1,25
(1*) IEC Inverse, IEC Very Inverse , IEC Extremely Inverse , IEC long time inverse, ANSI Inverse, ANSI very inverse,
ANSI extremely inverse, Defined time
Permission - - Yes/No - No
50N/G_1
50N/G_2
Tap 0,10 30,00 0,01 Inominal 1,00
The operating time is completely independent from the operating current that flows through the
equipment, so if the neutral current exceeds its predetermined value for an equal or greater
amount of time than this preset value, the protection function activates (trips) and does not reset
itself until the average value of the phase drops below the point of current tap.
The function activates at 100% of the preset input, and deactivates at 95%. The reset is
instantaneous.
The accuracy of the operating time is equal to the preset time 30 ms or 0.5%
Permission - - Yes/No - No
IEC Extrem.
Curve - - (1*) -
Inverse
50/51N/G
Dial 0,02 2,20 0,01 - 1,25
(1*) IEC Inverse, IEC Very Inverse , IEC Extremely Inverse , IEC long time inverse, ANSI Inverse, ANSI very inverse,
ANSI extremely inverse, Defined time
If the option "Defined time" is selected for the curve setting, the unit behaves like an
instantaneous overcurrent unit. In this case, the unit operating time is adjusted by using the
parameter "Operating time".
If a curve (inverse, very inverse or extremely inverse) is selected for the curve setting, the
operating time depends on the curve, dial and tap settings.
If the unit operates as defined time, the function is activated at 100% of the set tap value, and it
deactivates at 95%.
If the unit operates with a curve, the function is activated at 110% of the set tap value, and it
deactivates at 100%. The reset is instantaneous in both cases.
The activation time is accurate to 5% or 30ms, whichever is higher, of the theoretical activation
time.
The curves used are IEC 60255-151 and ANSI IEE, which are described in their section.
Permission - - YES/NO - No
46
Tap 0,10 7,00 0,01 Inominal 1,00
The operating time is completely independent from the operating current that flows through the
equipment, so if the negative sequence current exceeds its predetermined value for an equal or
greater amount of time than this preset value, the protection function activates (trips) and does
not reset itself until the average value of the phase drops below the point of current tap.
The function activates at 100% of the preset input, and deactivates at 95%. The reset is
instantaneous.
The accuracy of the operating time is equal to the preset time 30 ms or 0.5%
Adaptation B
Permission - - YES/NO - No
IEC Extrem.
Curve - - (1*) -
Inverse
46
Dial 0,02 2,20 0,01 - 1,25
(1*) IEC Inverse, IEC Very Inverse , IEC Extremely Inverse , IEC long time inverse, ANSI Inverse, ANSI very inverse,
ANSI extremely inverse, Defined time
If the option "Defined time" is selected for the curve setting, the unit behaves like an
instantaneous overcurrent unit. In this case, the unit operating time is adjusted by using the
parameter "Operating time".
If a curve (inverse, very inverse or extremely inverse) is selected for the curve setting, the
operating time depends on the curve, dial and tap settings.
If the unit operates as defined time, the function is activated at 100% of the set tap value, and it
deactivates at 95%.
If the unit operates with a curve, the function is activated at 110% of the set tap value, and it
deactivates at 100%.
The reset is instantaneous in both cases.
The activation time is accurate to 5% or 30ms, whichever is higher, of the theoretical activation
time.
The curves used are IEC 60255-151 and ANSI IEE, which are described in their section.
2
= 100 x (I/It) x (1 e-t/) + 0 x e-t/
where:
I, maximum three phase r.m.s. current
It, adjusted tap current
, thermal constant
0, initial thermal status
Permission - - Yes/No - No
cooling 1 6 1 heating 1
Alarm 20 99 1 % 80
Th %
100%
75%
t
1 2 3 4
alarm
trip
We suppose that thermal image protection has and adjusted tap of 1,1 times the nominal current
and an alarm level of 75%.
Zone 1: The machine is deenergized for a long time. Therma image is 0%.
Zone 2: We supply the machine with the nominal current. Thermal image evolutions so as to get
2
the value of the thermal balance corresponding to one time the nominal current Th = (I/It) =
82%. The time that it takes in getting the thermal balance depends on the adjusted heating
constant.
Zone 3: Once reached the thermal image corresponding to the application of one time the
nominal current, we apply 1,2 times the nominal current. Therma image will evolutione so as to
2
get the thermal balance corresponding to 1,2 times the nominal current Th = (I/It) = 119%. This
would occur if we had the permission of the thermal function disabled. If the permission is
disabled, 49 protection function performs when the thermal image reachs the value of 100%.
Once tripped, current is cutted and thermal image is getting cool based on the cooling constant.
Zone 4: Before getting totally cool, nominal current is applied again and thermal balnace is
reached once passed the time determined by the heating thermal constant.
Thermal image protection alarm bit is active if the thermal image measurement is over the
adjusted alarm level.
Thermal image protection trip bit is active when the measurement of the thermal image is over
100% and it is reset when the measurement of the thermal image is under the adjusted alarm
level.
NOTE: The Maximum accumulated amperes adjustment units are M(A) (square mega
amperes) whilst the Accumulated amperes counter units are K(A) (square kilo amperes).
It is also necessary to assign the logical inputs 52a and/or 52b to a physical input.
This function provides information about the circuit breaker status and if any maintenance alarm
has been activated.
Start
Error
Open
Opening fault These are the different statuses of the circuit breaker automatic control
52 Closed
Closing time
Closing fault
No. of configured openings Activated if the counter that measures the number of openings exceeds the
exceeded "Maximum number of openings" setting
No. of configured
Activated if the accumulated amps counter exceeds "Maximum accumulated
accumulated (l2t) amps
amps" setting
exceeded
Activated the number of openings exceeds the setting in "Maximum
Repeated Trips repeated openings" for the time set in "Time of maximum repeated
openings"
If only the circuit breaker 52b contact is available, it should be wired to the corresponding
physical input. This physical input is then assigned to the "52b Input logical input. The 52a
logical input is calculated internally as the negative of 52b. The circuit breaker performance is
shown in the following finite state machine:
ERROR
52a & 52b 52a & 52b 52a & 52b
52a & 52b
Fallo
Fallo
Cierre
apertura
Trip
50BF
t>
Imax< 8% Inominal
Pickup
Run
50BF
INIT_50BF = 1
Imax< 8% Inominal
Reset
50BF
INIT_50BF = 0
Imax< 8% Inominal
When the 50BF init status is activated, a switch is made to the "50BF init" and time is counted.
If, following the adjusted open fault time, the switch is not detected to have open, the function
trips. The function is reset when the circuit breaker is detected to have opened, and the 50BF
init status has been reset.
To monitor the circuit breaker opening the current measurement via the three phases is used.
When the current via the three phases is less than 8% of the rated current, the circuit breaker is
considered to be open.
This
Function settings are as follows:
Reclosing device
Permission - - Yes/No - No
Number of reclosings 1 5 1 - 3
From the HMI. There is a specific key marked 79, plus a specific signal led, allowing recloser
operation, locking or unlocking it. In order that the command related to the key can run, the
menu must be in standby mode.
From the HMI. This command can be executed from the control menu.
From two pulse inputs. If the substation is equipped with a conventional remote control, two
pulse outputs are usually assigned, where one locks the recloser and the other locks it.
Via protocol. This is performed via any means of communication. This is carried out as if it
were a control, and the normal conditions of any control must be met. For example, if we are
operating from the HMI, it is understood that the relay is in local mode, whereby if a
Lock/Unlock command is received via remote control this shall be ignored.
From a level input. In this case the recloser monitors the status of the input. This may be of
use if the company has a handle with a key.
In the first four cases, the equipment stores the lock situation in the non-volatile memory, as the
last control must be know for a possible re-start.
The auto-reclosers start up is shown in the following figure: There are two stable conditions
here, Standby and Lockout, the other conditions are transient.
79 Init Input
Reclose Init
+
Configurable Init TimeOut
N=N+1 Reclose
Time
N > Max Number Shots
TimeOut
52 52 Close
Is Open?
No Hold Time
Hold
TimeOut
Time
Close
TimeOut
Time
Reclose Init
52 Close
Reset
TimeOut
Time
Permission - - Yes/No - No
Time to deactivate
CLP In < 10%
incrementing Time Out
Time Out
In > 10%
Cold Load
Pickup
Run
In < 10%
Time Out
Time Out
Time to activate
CLP
decrementing In < 10%
Adaptation B
The settings of this function are as follows:
Permission - - Yes/No - No
Setting group 1 4 1 - 4
The function operates according to the following automaton. The automaton consists of five
states, in three of those states the relay works with normal setting group (the table adjusted in
general settings), and in the other two, with the new settings group.
The relay uses the current level to determine the circuit breaker state (open or closed). If the
current is less than 10% of the rated level, it is understood that the line is open, with an
extremely low usage level (operating at night, or on weekends). In one case or the other Cold
Load is in working condition.
The relay usually operates with the settings in their active table. When the circuit breaker opens,
a timer No Load Time starts. After this time, the relay considers that the circuit breaker is open,
so the CLP function is in working conditions.
Permission - - Yes/No - No
If a current lower than 8% of the nominal current is detected in one phase during the adjusted
time, the trip occurs.
The reset is instantaneous when a current higher than 10% of nominal current is detected.
The accuracy of the operating time is equal to the preset time 30 ms or 0.5%
Permission - - Yes/No - No
The operating time is completely independent of the operating current through the equipment,
such that should the phase current gone down the set value during the same amount of time or
more than the set one, the protection function acts (trips) and there it is not restored until the
measured value of the phase exceeds the current set point.
The function pick up occurs at 100% of the adjusted input and the dropout at 105%. The reset
type is instantaneous.
The accuracy of the operating time is equal to the preset time 30 ms or 0.5%
Permission - - Yes/No - No
The function activates at 100% of the preset input, and deactivates at 95%. The reset is
instantaneous.
The accuracy of the operating time is equal to the preset time 30 ms or 0.5%
General Settings
Language - - - - English
Active table 1 3 1 - 1
1. Equipment Identifier. This is an ASCII text, for equipment identification. Normally protection
equipment is associated with a specific line or position, and this setting is used for this
identification. It is important that this field is filled in correctly, as the information regarding
events and oscillography are accompanied with this information.
2. The phase and neutral CT transformation ratio setting allows the measurements of the
primary values from the protection transformer to be viewed.
4. Language. The SIL equipment is capable of displaying their messages in four languages,
with English in all cases. Consult the list of models to find out which are available.
The other settings are grouped according to functions, to ease management. These groups are
subject to tables.
The equipment identifier setting can only be adjusted through communications.
The frequency setting is read only. The equipment frequency is selected from the list of models.
The rest of the settings can be changed either from the HMI or through communications.
Any change of settings, involves the reset of the functions, whether or not activated.
Adaptation B
General Settings
Frequency - - 60/50 Hz 50
Serial number - - - - 0
Language - - - - English
Modbus
IEC60870-5-
Remote Protocol - - RTU/IEC60870-5- -
103
103
4. Language. The SIL equipment is capable of displaying their messages in four languages,
with English in all cases. Consult the list of models to find out which are available
6. Nominal phase current: it is possible to select the secondary phase nominal current.
Depending on model the options are: 5 A, 1A, 0.5 A or 2.5 A
7. Nominal neutral current: it is possible to select the secondary neutral nominal current.
Depending on model the options are: 5 A, 1A, 0.5 A or 0.1 A
8. The phase and neutral CT transformation ratio setting allows the measurements of the
primary values from the protection transformer to be viewed.
9. Communication settings (address of front port and address and speed of rear ports): see
Communications
01 Table 1
10 Table 2
11 Table 3
In the zero position the active item is defined by the active table settings defined in the general
group. Regarding other options, regardless of that established by the settings, the inputs prevail
over the settings.
If the use of both inputs is not required, then one can be used, but depending on which is used,
operation can be done with table 1 or table 2.
Changing the active Table settings. In the general group there is a setting which establishes
which table is active (table 1, table 2, table 3 or table 4).
01 Table 1
10 Table 2
11 Table 3
Table 4 is not possible to be selected through inputs, only through general settings.
In the zero position the active item is defined by the active table settings defined in the general
group. Regarding other options, regardless of that established by the settings, the inputs prevail
over the settings.
If the use of both inputs is not required, then one can be used, but depending on which is used,
operation can be done with table 1 or table 2.
A D
t B D K
V Q
P
Where:
I
V
I adjusted
Parameters A P Q B K
Ext. Inverse 80 2 1 0 0
The curve can mode from its axis using the D time selection device, which the user can adjust.
Iadjusted is the initial operating current, set by the user.
A
t TD P B
V 1
Where:
I
V
I adjusted
Parameters A P B
The curve can move from its axis using the TD time selection device, which the user can adjust.
Iadjusted is the initial operating current, set by the user.
APPLICATION EXAMPLE 1
Starting from the following information:
Line details:
Transformation ratio of CT =100/1
Primary current: Ip=100 A
50/51 function settings
Curve type: IEC Inverse
Dial: 0.05
Tap: 1xIn
50 function settings
Tap: 11xIn
Operating time: 0.05 s
The figure below (Figure 2), shows the tripping curve of the relay:
APPLICATION EXAMPLE 2:
Line details:
Transformation ratio of CT =500/1
Primary current: Ip=500 A
50/51 function settings
Curve type: ANSI Extremely Inverse
Dial: 2.20
Tap: 1xIn
50 function settings
Tap: 14xIn
Operating time: 0.1 s
If overcurrent fault is 24xIn=12000 Ap, ANSI Extremely inverse curve defines a tripping value of
0.376 s (Figure 3) for 50/51 function. It is considered that this time is too high, so when current
fault reaches 24xIn, definite time overcurrent function will be work. 50 function tap is adjusted at
14xIn so definite time overcurrent function will trip when current fault is higher than 14xIn (50
function does not wait to reach 24xIn)
The figure below (Figure 4), shows the tripping curve of the relay:
In this example it is explained what occurs when it is selected in curve type parameter
DEFINITE TIME. In this case, 50/51 function works as 50 function.
Starting from the following information
Line details:
Transformation ratio of CT =100/1
Primary current: Ip=100 A
50/51 function settings
Curve type: Definite time
Tap 1xIn
Operating time: 5 s
50 function settings
Tap: 15xIn
Operating time: 1 s
Adaptation A
Phase r.m.s. currents (IA, IB, IC)
Neutral r.m.s. current (IN)
Negative sequence current (I2)
Thermal image
Adaptation B
Phase r.m.s. currents (IA, IB, IC)
Neutral r.m.s. current (IN)
Negative sequence current (I2)
Positive sequence current (I1)
Maximum current (Imax)
Thermal image (TI)
Adaptation A
They will have a rated current equal to 1 Ampere or 5 Amperes and they will have a
frequency equal to 50 or 60 Hz, and these values are not adjustable by user (they depend
on the selected model).
Current values are understood as secondary current:
SIL-A1* 0,2-30 A * 1A *
SIL-A*5 * 1-150 A * 5A
SIL-A*1 * 0,2-30 A * 1A
Adaptation B
They will have a rated current equal to 1 Ampere, 5 Amperes or sensitive model selectable
and they will have a frequency equal to 50 or 60 Hz selectable by general settings.
Current values are understood as secondary current:
In 50 A In 50A In 10A
dcba
In 100 A In 100A In 20A
dcba
In 150 A In 150A In 30A
dcba
dcba
In 250 A In 250A In 50A
dcba
In 300 A In 300A In 60A
dcba
In 350 A In 350A In 70A
dcba
In 400 A In 400A In 80A
dcba
In 450 A In 450A In 90A
dcba
In 500 A In 500A In 100A
dcba
In 550 A In 550A In 110A
dcba
In 600 A In 600A In 120A
dcba
dcba
In 700 A In 700A In 140A
dcba
In 750 A In 750A In 150A
dcba
In 800 A In 800A In 160A
To this end we start with an SILA.XX relay, i.e. the neutral units have the same range as
the phase units.
1. We set the rated current of the switchgear. To do this we set the equipments rear
switches to this configuration:
dcba
Which corresponds to 250 rated Amps. In this way we set the rated current range of the
cell to that of the relay.
2. We adjust the relay rated current. To this end 250 Amps shall be applied in the
general setting menu for the phase rated current, and 250 Amps for the neutral rated
current.
3. With this configuration, the relay understands that the rated current of the relay is 250
Amps, and as a result the protection unit starts settings shall be:
5.2. Counters
The following counters are provided:
1 Number of openings of the circuit breaker
3 Number of shots
4 Thermal Image
Group Status
Adaptation A Adaptation B
General status
Battery supply 50 Hz
Ready Ready
- Pickup
- Phase A Pickup
- Phase B Pickup
- Phase C Pickup
- Ground Pickup
- Phase A Trip
- Phase B Trip
- Phase C Trip
- Ground Trip
- 50P Trip
- 50N Trip
- Phase Trip
Adaptation A Adaptation B
50P_1 Trip
50P_2 Trip
50/51P Trip
Adaptation A Adaptation B
50N/G_1 Trip
50N/G_2 Trip
50/51N/G Trip
CLP Disable
52 Close
52 Open
CLP
CLP Activation 52 definitive Open
50BF Trip
46 Trip 46 Trip
Adaptation A Adaptation B
Reclosing device
79 Standby
79 Reclosing time
79 Open
79 Hold time
79 79 Closing time
79 Reset time.
79 Lock out
79 Safety time
79 Enabled
52 Start
52 Error
52 Open
52 Opening time
52 Opening fault
52 Closed
52
52 Closing time
52 Closing fault
52 Excessive openings
52 a Status
52 b Status
74TCS Alarm
Adaptation A Adaptation B
Thermal Image
49 49 Alarm
49 Trip
74CT Trip
46 Trip
Undercurrent
37 Phase A Pickup
37 Phase B Pickup
37 Phase C Pickup
37 Phase A trip
37 Phase B trip
37 Phase C trip
37 Trip
Phase a Block
Phase C Block
Phase Block
Adaptation A Adaptation B
Input 52 a 52 a
Input 52 b 52 b
Lock 79 79 Enable
Unlock 79 79 Block
Logical signal 1
Logical signal 2
Adaptation A Adaptation B
Digital inputs
Input 1 Input 1
Input 2 Input 2
Input 3 Input 3
Input 5 Input 5
Input 6 Input 6
Input 7 -
Input 8 -
Output 1 Output 1
Output 2 Output 2
Output 3 Output 3
Output 4 Output 4
Output 5 -
79 init -
50BF init -
Fault init -
Outputs
- Leds
ON Led Led 1
Led 1 Led 2
Led 2 Led 3
Led 3 Led 4
Led 4 Led 5
Led 5 Led 6
Led-52
Led-79
Adaptation A Adaptation B
Reset 86 Telecontrol
Reset
- Reset TI
Remote IEC60870-5-103
Lock 79 Lock 79
Remote com.
Unlock 79 Unlock 79
Telecontrol
- Reset
- Reset TI
Adaptation A Adaptation B
Local Modbus
Unblock 79 Unlock 79
Reset 86 Reset
- Reset TI
In conditions 52 and 79, a bit is assigned to each condition of the automaton, so that if the
oscillography must be observed, the evolution of this automaton can be seen.
A brief description of the general statuses is given below:
Trip: The equipment has tripped. This bit is the or of all the trips, of any functions, plus the
external trip input. Should it be required that a function does not generate a trip, this must
be prohibited individually. In the case of the external trip input, it is sufficient to not set it.
The Ready bit agglutinates correct relay operation and has the following logic:
Operation
Ready
Mesaurement error
Protection error
Default settings
ON(Activated) /OFF(Deactivated):
Value
an event is generated for Activation and deActivation
Year
Month
Day
Time
Minutes
Seconds
Milliseconds
The following list shows all of the conditions of the equipment and their associated events:
07 50 Hz network
bit-6 50 Hz network frequency Activation/Deactivation -
frequency
New Oscillography
- 30 New Oscillography record
record
- 46 Identification Identification
Bit-00 1 50P_1 Phase A pickup 50P_1 Phase A pickup Activation/Deactivation Phase A current
Bit-01 2 50P_1 Phase B pickup 50P_1 Phase B pickup Activation/Deactivation Phase B current
Bit-02 3 50P_1 Phase C pickup 50P_1 Phase C pickup Activation/Deactivation Phase C current
Bit-09 6 50P_1 Phase B trip 50P_1 Phase B trip Activation Phase B current
Bit-10 7 50P_1 Phase C trip 50P_1 Phase C trip Activation Phase C current
Bit-00 1 50P_2 Phase A pickup 50P_2 Phase A pickup Activation/Deactivation Phase A current
Bit-01 2 50P_2 Phase B pickup 50P_2 Phase B pickup Activation/Deactivation Phase B current
Bit-02 3 50P_2 Phase C pickup 50P_2 Phase C pickup Activation/Deactivation Phase C current
Bit-09 6 50P_2 Phase B trip 50P_2 Phase B trip Activation Phase B current
Bit-10 7 50P_2 Phase C trip 50P_2 Phase C trip Activation Phase C current
Bit-00 01 50/51P Phase A pickup 50/51P Phase A pickup Activation/Deactivation Phase A current
Bit-01 02 50/51P Phase B pickup 50/51P Phase B pickup Activation/Deactivation Phase B current
Bit-02 03 50/51P Phase C pickup 50/51P Phase C pickup Activation/Deactivation Phase C current
Bit-09 06 50/51P B phase trip 50/51P B phase trip Activation Phase B current
Bit-10 07 50/51P C phase trip 50/51P C phase trip Activation Phase C current
Recloser
Bit-11 12 52 a 52 a Activation/Deactivation -
Bit-12 13 52 b 52 b Activation/Deactivation -
Thermal image
Logical inputs
Digital inputs
Outputs
bit-8 - ON Led - - -
bit-9 - Led -1 - - -
bit-10 - Led -2 - - -
bit-11 - Led -3 - - -
bit-12 - Led -4 - - -
bit-13 - Led -5 - - -
Remote Modbus
bit-17 2 Open circuit breaker Open circuit breaker Activation Command identifier
bit-18 3 Close circuit breaker Close circuit breaker Activation Command identifier
IEC60870-5-103
Bit-00
- Remote communication. - -- -
Bit-18 2 Open circuit breaker Open circuit breaker Activation Command identifier
Bit-19 3 Close circuit breaker Close circuit breaker Activation Command identifier
Local communication
Bit-18 2 Open circuit breaker Open circuit breaker Activation Command identifier
Bit-19 3 Close circuit breaker Close circuit breaker Activation Command identifier
Bit-03 07 50 Hz - - -
Bit-16 49 Pickup - - -
- 57 Ground Trip - - -
- - Phase Trip - - -
Bit-14 30 - Fault report Activation Fault report NO.
Oscillography
Bit-00 1 50P_1 Phase A pickup 50P_1 Phase A pickup Activation/Deactivation Phase A current
Bit-01 2 50P_1 Phase B pickup 50P_1 Phase B pickup Activation/Deactivation Phase B current
Bit-02 3 50P_1 Phase C pickup 50P_1 Phase C pickup Activation/Deactivation Phase C current
Bit-09 6 50P_1 Phase B trip 50P_1 Phase B trip Activation Phase B current
Bit-10 7 50P_1 Phase C trip 50P_1 Phase C trip Activation Phase C current
Bit-00 1 50P_2 Phase A pickup 50P_2 Phase A pickup Activation/Deactivation Phase A current
Bit-01 2 50P_2 Phase B pickup 50P_2 Phase B pickup Activation/Deactivation Phase B current
Bit-02 3 50P_2 Phase C pickup 50P_2 Phase C pickup Activation/Deactivation Phase C current
Bit-09 6 50P_2 Phase B trip 50P_2 Phase B trip Activation Phase B current
Bit-10 7 50P_2 Phase C trip 50P_2 Phase C trip Activation Phase C current
Bit-00 01 50/51P Phase A pickup 50/51P Phase A pickup Activation/Deactivation Phase A current
Bit-01 02 50/51P Phase B pickup 50/51P Phase B pickup Activation/Deactivation Phase B current
Bit-02 03 50/51P Phase C pickup 50/51P Phase C pickup Activation/Deactivation Phase C current
Bit-09 06 50/51P B phase trip 50/51P B phase trip Activation Phase B current
Bit-10 07 50/51P C phase trip 50/51P C phase trip Activation Phase C current
Bit-01 - 52 Close - - -
Bit-02 - 52 Open - - -
Bit-12 02 Cold Load pickup Cold load Pickup Activation/Deactivation Phase current
Recloser
Bit-09 - 79 Enabled - - -
Bit-12 13 52 b 52 b Activation/Deactivation -
Negative sequence
Bit-04 01 46 pickup 46 pickup Activation/Deactivation
current
46
Negative sequence
Bit-12 02 46 Trip 46 Trip Activation/Deactivation
current
Thermal image
Undercurrent protection
Bit-00 01 37 Phase A pickup 37 Phase A pickup Activation/Deactivation Phase A current
Inputs
Outputs
Logic
Bit-13 18 52 a 52 a Activation/Deactivation -
Bit-14 19 52 b 52 b Activation/Deactivation -
Bit-17 02 Open circuit breaker Open circuit breaker Activation Command identifier
Bit-18 03 Close circuit breaker Close circuit breaker Activation Command identifier
IEC60870-5-103
Bit-00 IEC60870-5-103
- Communication - -- -
Bit-17 02 Open circuit breaker Open circuit breaker Activation Command identifier
Bit-18 03 Close circuit breaker Close circuit breaker Activation Command identifier
Local communication
Bit-17 02 Open circuit breaker Open circuit breaker Activation Command identifier
Bit-18 03 Close circuit breaker Close circuit breaker Activation Command identifier
5.6. Oscillography
Adaptation A
The SIL-A relay stores 2 oscillographic records, with a resolution of 16 samples/cycle and
a size of 50 cycles. The first three of these cycles correspond to pre-fault.
The oscillography is downloaded by communications through the front or rear port using
the Modbus protocol (the protocol is documented in this manual). The SICom
communications program allows the oscillograph to be downloaded and saved in
COMTRADE format (IEEE C37.111-1991).
The following information is included in each oscillographic record:
1 Phase A current
2 Phase B current
3 Phase C current
4 Neutral current
Oscillograph: 41458
Date/Time: 2008/10/15 11:29:11:85
Fault row = 15
***************************************************************
Oscillograph Events:
***************************************************************
An oscillography is started when the "fault init" state is activated; this is a configurable
logical signal. The default configuration is as follows:
1 Phase A current
2 Phase B current
3 Phase C current
4 Neutral current
***************************************************************
Cycles pre-fault = 3
Total cycles = 100
Analog channels = 4
Digital channels = 48
Oscillo = 1
Date/Time = 12/5/2014 - 09:52:18.570
****************************************************************
An oscillography is started when the "fault init" state is activated; this is a configurable
logical signal. The default configuration is as follows:
Not configured
52 a
52 b X
External trip
50P block
50N/G block
79 Pickup Input
79 Permission
Level 79 Lock
Pulse 79 Lock
Pulse 79 unlock
Table 1
Table 2
Reset
Continuity A
Continuity B
Logical signal 1
Logical signal 2
ADAPTATION A
LED 1
LED 2
LED 3
LED 4
LEDs LED 5
LED 6
Output 1
Output 2
Output 4
Output 5
Input 52 a
External Trip
50N/G block
Fault init
79 Init Input
79 Permission
Level 79 Lock
Pulse 79 lock
Pulse 79 unlock
Table 1
Table 2
79 Init
Fault Init
All the outputs (Leds, physical outputs and logical signals) are the result of a
PROGRAMMABLE LOGIC CONTROL which can be configured from HMI or from SICom
software.
For each output there is a LOGICAL GATE. It can perform a logical operation up to 16
binary states to obtain other binary result.
In V1of the PLC the LOGICAL GATES that are supported by SIL-A (adaptation A) are:
NOR_LACTH
LOGICAL
OUTPUT BINARY STATES
GATE
50P1 Trip
LED 2 OR_4 LATCH 50P2 Trip
51P Trip
50N1 Trip
LEDs LED 3 OR16_LACTH 50N2 Trip
51N Trip
General trip
PHYSICAL Local open breaker
OUTPUTS Output 4 OR16
Remote modbus open breaker
60870-5-103 open breaker
79 Close time
Local close breaker
Output 5 OR16
Remote modbus close breaker
60870-5-103 close breaker
50P Trip
51P Trip
50N Trip
79 init OR16
51N Trip
46 Trip
79 Pickup input
LOGICAL
50BF Pickup Input
OUTPUTS
HMI / Local Modbus opening
50BF Init OR16 ModBus opening
Remote opening
General trip
-
79 Init Input Not configured
LOGICAL
-
SIGNALS 79 Permission No configured
-
Level 79 Lock Not configured
-
Pulse 79 lock Not configured
-
Pulse 79 unlock Not configured
-
50BF Init Input Not configured
-
Table 1 Not configured
-
Table 2 Not configured
Logical signals are internal binary states result of the Programmable Logic Control. The
logical signal has a specific and defined meaning to be used by the rest functions of the
Device.
LED 1
LED 2
LED 3
LED 4
LEDs LED 5
LED 6
LED 52
LED 79
Output 1
Output 2
PHYSICAL OUTPUTS
Output 3
Output 4
52a
52b
External Trip
50BF start
Fault start
50P block
50N/G block
LOGICAL SIGNALS
Reset
Settings group 1
Settings group 2
Continuity A
Continuity B
Logical signal 1
Logical signal 2
In V3 of the PLC the LOGICAL GATES that are supported by SIL-A (adaptation B) are:
LOGICAL
OUTPUT BINARY STATES
GATE
50P1 Trip
LED 2 OR4_LATCH 50P2 Trip
51P Trip
50N1 Trip
LED 3 OR4_LACTH 50N2 Trip
51N Trip
LEDs
LED 4 OR4_LACTH 50BF Trip
79 Close time
Local close breaker
Output 2 OR4
Remote modbus close breaker
PHYSICAL 60870-5-103 close breaker
OUTPUTS
Output 3 OR4 50BF Trip
-
50G block Not configured
Local reset
OR4_PULSE
Reset Remote modbus reset
IEC60870-5-103 reset
-
Settings group 1 Not configured
-
LOGICAL Settings group 2 Not configured
SIGNALS
General trip
79 Init OR4
-
79 Enable Not configured
-
79 Block Not configured
-
Lock 79 Not configured
-
Unlock 79 Not configured
-
Continuity A Not configured
-
Continuity B Not configured
-
Logical signal 1 Not configured
-
Logical signal 2 Not configured
LOGICAL BINARY
OUTPUT DESCRIPTIONS
GATE STATES
Led On blinks when internal signal READY of
general state of the device is activated, this
LED 1 OR4_PULSES Ready
indicates that the device is working correctly
without any failures.
On the other hand, a default settings error indicates that the relay is operating with default
settings, whereby it will not trip (check that the relay alarm is activated with default
settings).
Remote com:
Modbus
Local Com.
HMI IEC 60870-5-103
ModBus
IEC61850
DNP 3.0
52 open
52 close
Lock 79
Unlock 79
Telecontrol YES -
NO telecontrol -
Reset 86
Adaptation B
Remote com:
Modbus
Local Com.
HMI IEC 60870-5-103
ModBus
IEC61850
DNP 3.0
52 open
52 close
Pulse Lock 79
Pulse Unlock 79
Local control -
Telecontrol -
Reset
Reset TI
5.13. Telecontrol
The equipment can only be set to telecontrol or local control from the HMI or through
communications software (SICOM).
If telecontrol is used, it is recommended to configure a led to display when telecontrol is
permitted and when it is not.
Instantaneous deactivation
Instantaneous deactivation
50/51P Dial: 0.05 to 2.20 (step 0.01) Dial: 0.02 to 2.20 (step 0.01)
Instantaneous deactivation
Operating time: Inverse curve, very inverse curve, Operating time: IEC Inverse curve, IEC very inverse
extremely inverse curve. curve,IEC extremely inverse curve IEC long time
inverse, ANSI Inverse curve, ANSI very inverse curve,
ANSI extremely inverse curve.
Instantaneous deactivation
Operating range: 0.10 to 1.00 xIn (step 0.01) Operating range: 0.10 to 7.00 xIn (step 0.01)
Operating time: 0.02 to 300 s (step 0.01 s) Curves IEC 60255-151 and ANSI
Instantaneous deactivation
Function Pickup configurable: Equipment trip, activation of the opening fault input, circuit breaker open control
activation.
Number of reclosings: 1 to 5
Operating time: 0.02 to 300 s (step 0.01 s) Operating time: 0.02 to 300 s (step 0.01 s)
50N/G_1 Multiplier range: 1 to 5 Cold load Time: 0.02 to 300 s (step 0.01 s)
86 Allows to latch (lock out) the contact trip due to programmable logic (PLC: LATCH).
Trip time curves are valid under 20 times the adjusted tap. With currents higher than 20 times the adjusted tap, trip
time and thermal image value are truncated to 20 times the adjusted tap.
Instantaneous reset
16 samples/cycle 16 samples/cycle
20 fault reports with 80 events each one 20 fault reports with 24 events each one
Fault reports
Same voltage as the auxiliary power supply Same voltage as the auxiliary power supply
Configurable inputs
8 configurable inputs 6 configurable inputs
Phase current (IA, IB, IC), neutral (IN), positive sequence (I1),
Phase current (IA, IB, IC), neutral (IN), and
negative sequence(I2), maximum current (Imax) and thermal
negative sequence(I2).
image (TI)
Real RMS
Current
measurement Sampling: 16 samples/cycle
2% Accuracy over a band of 20% over the nominal current and 4% over the rest of the range
LOCAL COMMUNICATION
1 Local port RS232: ModBus RTU
REMOTE COMMUNICATION (*) REMOTE COMMUNICATION (*)
2 remote ports with the following options : 1 remote port with the following options :
Communications
2 Remote port RS485: ModBus RTU 1 Remote port RS485: ModBus RTU or IEC 60870-5-
and IEC 60870-5-103 103 (by general settings)
1 Remote port RS485 ModBus RTU 1 RJ45 port: IEC 61850, DNP3.0 or IEC 60870-104
and 1RJ45 port: IEC 61850, DNP3.0 or
IEC 60870-104
Measurement 3 or 4 CT /5 or /1
Transformers
Measurement 3 LPCT (current transformers with voltage output)
Metallic box
Panel mounted.
Mechanical
Characteristics
1/2Rack 4 U 1/4Rack 4 U
IP-54 on pannel
1.5. Radiated radiofrequency IEC 60255-26 Level 3, Test field strenght 10V/m, Frequency
electromagnetic fields IEC 61000-4-3 80MHZ - 1000MHz and 1400MHz - 2000MHz,
AM Modulation 80% for 1KHz carrier
sinusoidal signal
1.6. Electrical fast transients IEC 60255-26 Level 4, Power supply to Earth terminals 4kV,
IEC 61000-4-4 Signal and control terminals 2kV. Repetition
frequency 5KHz, Burst duration 75s.
1.7. Surge IEC 60255-26 Level 4, Line to earth for all terminals 4kV.
IEC 61000-4-5 Line to Line for all terminals excepts
Communication port 2kV
1.8. Conducted disturbance IEC 60255-26 Level 3, Applied voltage 10V, Frequency
induced by radio frequency fields IEC 61000-4-6 0.15MHz - 80 MHz, AM Modulation 80% for
1KHz carrier sinusoidal signal, Dwell time 1s.,
Test duration >10s.
1.9. Voltage dips, short IEC 60255-26 DC Voltage Dips: 40%, 130ms and 70%,
interruptions and voltage variations IEC 61000-4-11 100ms, 3 times every 10s.
DC Voltage Interruption: 100ms, 3 times every
IEC 61000-4-29
10s.
1.10. Ripple on DC input power IEC 60255-26 Level 4, Ripple 15%, 50Hz and 100Hz
port IEC 61000-4-17
1.11. Power frequency magnetic IEC 60255-26 Level 5, Continuous field strenght 100 A/m.
field IEC 61000-4-8 Short field strenght for a duration of 3s. 1000
A/m. Frequency 50Hz.
1.12. 100KHz damped oscillatory IEC 61000-4-18 Class 3, Repetition frequency 40Hz, Duration
waves of each application 3s. Common mode:
2.5kV. Differential mode: 1kV
2.3. Insulation resistance IEC 60255-27 500V applied between each group to earth
IEC 60255-5 and with rest of the groups in short-circuit
2.4. Protective bonding IEC 60255-27 Test current 2xIn, Test voltage 12Vac during
resistance 60s. Resistance shall be less than 0.1 ohm
3. Burden
3.1. AC burden for CT IEC 60255-1 Declared on manual
3.2. AC burden for VT
3.3. AC, DC burden for power
supply
3.4. AC, DC burden for binary
inputs
4. Contact performance
IEC 60255-27
5. Communication
requirements
ModBus RTU
IEC 61850
IEC 60870-5-103
IEC 60870-5-104
DNP 3.0
6.3 Change of temperature IEC 60068-2-14 Change of Temperature Nb, Upper temp
+70C, Lower temp -25C, 5 cycles, Exposure
time 3h, Transfer time 2 min.
6.4 Damp heat IEC 60068-2-30 Damp Heat Cyclic Db, Upper temp +40C,
Humidity 93%, 2 cycles. Relay energized
7.4. Seismic IEC 60255-21-3 Single Axis Sine Sweep, Class 1, X Axis: 1 to
9Hz, 3.5mm and 9 to 35Hz, 1gn; Y Axis: 1 to
IEC 60068-21-3
9Hz, 1.5mm and 9 to 35Hz, 0.5gn
8. Electrical environmental
requirements
8.1. CT Input continuous IEC 60255-27 3xIn without damage for continuous operation
overload
8.2. CT Input short time IEC 60255-27 70xIn without damage for 1s short time
overload overloading
8.3. VT Input continuous IEC 60255-27 Declared on manual, without damage for
overload continuous operation
8.4. VT Input short time IEC 60255-27 Declared on manual, without damage for 10s
overload short time overloading
9. Enclosure protection
Permission to:
Read-only permission: Permission to: Permission to
Change settings Permission to:
ACCESS Status and measurements Execute Change
Download and Delete the Change
LEVEL Settings Commands Protected
Events buffer Configuration
Events Settings
2 YES YES NO NO NO
3 YES NO YES NO NO
Four passwords and their associated levels of access are set up when the equipment is
configured using the SIcom program. Four passwords and their associated levels of
access are set up when the equipment is configured using the SIcom program. It is
possible to change the passwords The password must have 4 characters. By default, the
equipment is programmed with the following passwords and their associated levels:
2222 2
3333 3
4444 4
5555 5
Adaptation A
SILA555C2A12BB
0.00 0.00 0.00 0.00
Adaptation B
If any error is detected by the self-diagnosis, an error message appears in the second line
(instead of the currents) on the main screen, which can show any of the following information:
(see inside self-diagnosis section).
PROTECTION ERROR
MEASUREMENT ERROR
EEPROM ERROR
EVENt ERROR
Trip 50P1
07/01/15 13:51:44825
Even is auxiliary power is lost, when the SIL-B regains power, it will retain information on the
last trip. The last trip screen will only disappear when the RESET button is pressed and held
down.
OK C
01/01/2000 01:43
Adaptation A
From the "sleep" mode screen, press the key to access the fault report menu. Using
the and keys we can move onto the report we wish to display, and, pressing OK
provides access to the events each fault report contains.
1/9: 535
OK C
New Osc. Regist
Adaptation B
From the "sleep" mode screen, press the key to access the fault report menu. It is
possible to access to fault report menu navigating throug main menus too. Using the
and keys we can move onto the report we wish to display, and, pressing OK
provides access to the events each fault report contains.
07/01/15 12:08:58828
OK C
51N Pickup
Trip 51P
C
07/01/15 10:01:11661
Adaptation A
serial number:
C
0
Adaptation B
From the default screen, press and hold key to access to communications parameters:
LOCAL Settings
1 19200-8-N-1
(*) REMOTE COM parameters depend on model ( the protocol that it is used can be IEC61850,
DNP3.0 or IEC60870-5-103 depending on model)
OK
Set Password C
SILA000C2A12BB
-> 0 0.00 0.00 0.00 0.00
Set Password C
-> 5555
OK
TEST MENU
C
SILA000C2A12BB
0.00 0.00 0.00 0.00
OK
Led-1: C
not activated
OK
Led-1:
<<ACTIVATED>>
Led-2:
C
not activated
Led-3: C
not activated
OK
Led-3:
<<ACTIVATED>>
Led-4:
C
not activated
OK
Led-4:
<<ACTIVATED>>
Led-5:
C
not activated
Led-5:
OK
<<ACTIVATED>>
Led-6:
C
not activated
Led-6:
OK
<<ACTIVATED>>
Led-79:
OK
<<ACTIVATED>>
Led-52:
C
not activated
OK
Led-52:
<<ACTIVATED>>
Output 1:
C
not activated
Output 1:
OK
<<ACTIVATED>>
Output 2: C
not activated
OK
Output 2:
<<ACTIVATED>>
OK
Output 3:
<<ACTIVATED>>
Output 4: C
not activated
Output 4:
OK
<<ACTIVATED>>
Output 5: C
not activated
Output 5:
OK
<<ACTIVATED>>
STATES
C
SETTINGS GEN
C
T.A=1 COM
EVENTS
C
There are 5
COUNTERS
C
COMMANDS
C
Press the OK key to access the second level from the main screen. Use the and keys to move from one menu section to another in the second
level. Use the C key to return to a higher level.
Adaptation A
MEASUREMENTS SILA555B1001BA
OK C
0.00 0.00 0.00 0.00
I-A 1/6
OK
0.00 *A
I-B 2/6
C
0.00 A
I-0 4/6
C
0.00 A
I-2 5/6
C
0.00 A
TI 6/6
C
20
Adaptation B
MEASUREMENTS SILA000C2A12BB
OK C
0.00 0.00 0.00 0.00
I-A 1/8
OK
0.00 *A
I-B 2/8
C
0.00 A
I-0 4/8
C
0.00 A
I-2 5/8
0.00 A
I-1 6/8
C
0.00 A
IMax 7/8
0.00 A
TI 8/8
C
20
STATES SILA555B1001BA
C
0.00 0.00 0.00 0.00
Phase B Pickup:
C
not activated
Phase C Pickup:
C
not activated
Phase Pickup:
C
not activated
Phase A Trip:
C
not activated
Phase C Trip:
C
not activated
Phase Trip:
C
not activated
Phase B Pickup:
C
not activated
Phase C Pickup:
C
not activated
Phase Pickup:
C
not activated
Phase A Trip:
C
not activated
Phase C Trip:
C
not activated
Phase Trip:
C
not activated
Phase B Pickup:
C
not activated
Phase C Pickup:
C
not activated
Phase Pickup:
C
not activated
Phase B Trip:
C
not activated
Phase C Trip:
C
not activated
Phase Trip:
C
not activated
Ground Trip:
C
not activated
STATES
Sta. 50N2 C
Ground Trip:
C
not activated
Ground Trip:
C
not activated
Sta. 46 STATES
C
Pickup: Sta. 46
OK C
not activated
Trip:
C
not activated
Sta. 49 STATES
C
Pickup: Sta. 49
OK C
not activated
Trip:
C
not activated
Battery Supply:
C
not activated
50 Hz:
C
<<ACTIVATED>>
Measure error:
C
not activated
Setting changed:
C
not activated
Set Date/Time:
C
not activated
No Telecontrol:
C
not activated
FactorySetting:
C
not activated
Eeprom error:
C
not activated
Event error:
C
not activated
I. 52b:
C
not activated
I. 50P block:
C
not activated
I. 50G/50N block:
C
not activated
I. Ext Trip:
C
not activated
I. 79 Init:
C
not activated
I. 79 Enable:
C
not activated
I. 79 Block:
C
not activated
I1-Sett Table:
C
not activated
I2-Sett Table:
C
not activated
Lock 79:
C
not activated
Unlock 79:
C
not activated
I. 50BF Init:
C
not activated
Input 2:
C
not activated
Input 3:
C
not activated
Input 4:
C
not activated
Input 5:
C
not activated
Input 6:
C
not activated
Input 7:
C
not activated
Input 8:
C
not activated
Continuity A:
C
not activated
Continuity B:
C
not activated
LedON:
OK C
not activated
Led1:
C
not activated
Led2:
C
not activated
Led3:
C
not activated
Led4:
C
not activated
Output 1:
C
not activated
Output 3:
C
not activated
Output 4:
C
not activated
Output 5:
C
not activated
79 Init:
C
not activated
50BF Init:
C
not activated
Sta. 79 STATES
C
Standby:
OK C
not activated
Reclose Time:
C
not activated
79 Is 52 Open?:
C
not activated
79 Hold Time:
C
not activated
79 Close Time:
C
not activated
79 Reset Time:
C
not activated
79 Lockout:
C
not activated
79 Manual Open:
C
not activated
Sta. 52 STATES
C
>52 Open Error
52 Startup:
OK C
not activated
52 Error:
C
not activated
52 Open:
C
not activated
52 Open Time:
C
not activated
52 Open Error:
C
<<ACTIVATED>>
52 Close Time:
C
not activated
52 Close Error:
C
not activated
I2t Alarm:
C
<<ACTIVATED>>
52A contact:
C
not activated
52B contact:
C
not activated
74TCS Alarm:
C
not activated
Command Select:
C
not activated
Open Breaker:
C
not activated
Close Breaker:
C
not activated
Block Recloser:
C
not activated
Reset 86
not activated
STATES
Sta. REMOTE C
Command Select:
C
not activated
Open Breaker:
C
not activated
Close Breaker:
C
not activated
Block Recloser:
C
not activated
UnBlock Reclos:
C
not activated
MMI Activity:
C
<<ACTIVATED>>
Local Ctrl.:
C
not activated
Command Select:
C
not activated
Open Breaker:
C
not activated
Close Breaker:
C
not activated
UnBlock Reclos:
C
not activated
No Telecontrol:
C
not activated
Telecontrol Yes:
C
not activated
Reset 86
not activated
STATES SILA000C2A12BB
C
0.00 0.00 0.00 0.00
50 Hz:
C
<<ACTIVATED>>
TripBlck Enab.:
Not activated
Measure error:
C
not activated
Ready:
not activated
Setting changed:
C
not activated
Local Ctrl.:
C
not activated
FactorySetting:
C
not activated
Eeprom error:
C
not activated
Eeprom changed:
C
not activated
Event error:
C
not activated
Reset:
C
not activated
Pickup:
C
not activated
Phase A pickup:
C
not activated
Phase C pickup:
C
not activated
Ground pickup:
C
not activated
Phase A Trip:
C
not activated
Phase B Trip:
C
not activated
Phase C Trip:
C
not activated
Ground Trip:
C
not activated
50P Trip:
C
not activated
Phase Trip:
C
not activated
Phase B Pickup:
C
not activated
Phase C Pickup:
C
not activated
Phase Pickup:
C
not activated
Phase A Trip:
C
not activated
Phase B Trip:
C
not activated
Phase Trip:
C
not activated
Phase B Pickup:
C
not activated
Phase C Pickup:
C
not activated
Phase Pickup:
C
not activated
Phase A Trip:
C
not activated
Phase C Trip:
C
not activated
Phase Trip:
C
not activated
Phase B Pickup:
C
not activated
Phase C Pickup:
C
not activated
Phase Pickup:
C
not activated
Phase A Trip:
C
not activated
Phase C Trip:
C
not activated
Phase Trip:
C
not activated
Ground Trip:
C
not activated
STATES
Sta. 50N2 C
Ground Pickup:
OK C Sta. 50N2
not activated
Ground Trip:
C
not activated
Sta. 46 STATES
C
Pickup: Sta. 46
OK C
not activated
Trip:
not activated
52 Open:
C
not activated
52 Def. open:
C
not activated
Close CLP:
C
not activated
Open CLP:
C
not activated
CLP:
C
not activated
Trip:
C
not activated
Alarm: Sta. 49
OK C
not activated
Trip:
C
not activated
Sta. 79 STATES
C
>Lockout
Standby: Sta. 79
OK C
not activated >Lockout
Reclose Time:
C
not activated
79 Is 52 Open?:
C
not activated
79 Hold Time:
C
not activated
79 Reset Time:
C
not activated
79 Lockout:
C
not activated
79 Security T.:
C
not activated
79 Manual Open:
C
not activated
Sta. 52 STATES
C
>52 Error
52 Startup: Sta. 52
OK C
not activated >52 Error
52 Error:
C
not activated
52 Open:
C
not activated
52 Open Error:
C
<<ACTIVATED>>
52 Close:
C
not activated
52 Close Time:
C
not activated
52 Close Error:
C
not activated
I2t Alarm:
C
<<ACTIVATED>>
52B contact:
C
not activated
74TCS Alarm:
C
not activated
74CT Alarm:
C
not activated
Phase B Pickup:
C
not activated
Phase C Pickup:
C
not activated
Phase Pickup:
C
not activated
Phase A Trip:
C
not activated
Phase B Trip:
C
not activated
Phase C Trip:
C
not activated
Phase Trip:
C
not activated
Trip:
C
not activated
Phase B block:
C
not activated
Phase C block:
C
not activated
Phase block:
C
not activated
Input 2:
C
not activated
Input 3:
C
not activated
Input 4:
C
not activated
Input 5:
C
not activated
Input 6:
C
not activated
Output 2:
C
not activated
Output 3:
C
not activated
Output 4:
C
not activated
Led2:
C
not activated
Led4:
C
not activated
Led5:
C
not activated
Led6:
C
not activated
Led-52:
C
not activated
Led-79:
C
not activated
Ext Trip:
C
not activated
50BF Init:
C
not activated
Fault Init:
C
not activated
Blck. 50P:
C
not activated
Blck. 50N:
C
not activated
Reset:
C
not activated
SettingsG1:
C
not activated
79Init:
C
not activated
79 Enable:
C
not activated
L Lock 79:
C
not activated
P Lock 79:
C
not activated
P Unlock 79:
C
not activated
74TCS A:
C
not activated
74TCS B:
C
not activated
Logic Sig2:
C
not activated
HMI Activity:
C
<<ACTIVATED>>
Open Breaker:
C
not activated
Close Breaker:
C
not activated
P Lock 79:
C
not activated
P Unlck 79:
C
not activated
Telecontrol:
C
not activated
Reset:
C
not activated
Reset TI:
C
not activated
Open Breaker:
C
not activated
Close Breaker:
C
not activated
P Unlck 79:
C
not activated
Local Ctrl.:
C
not activated
Telecontrol:
C
not activated
Reset:
C
not activated
Reset TI:
C
not activated
NOTE: REMOTE COM can be ModBus, IEC60870-5-103, IEC61850, DNP3.0 or IEC60870-5-104 depending on model
Adaptation A
Select table
C
2
Select table
C
3
Set Password
-> 5555
Function Enable
OK
NO -> NO
Function Enable
NO -> YES
Function Enable
OK
NO > YES y/n
SETTING CHANGED
OK
Function Enable
Function Enable
OK
YES
Current Tap
C
1.00 xIn
Operating Time
C
0.02 s
Current Tap
C
0.20 xIn
Operating Time
C
5.00 s
Curve type
C
Def Tim
Time Dial
C
0.05
Operating Time
C
5.00 s
Settings 50N1 SETTINGS GEN
C
T.A.=1 COM
Current Tap
C
0.50 xIn
Operating Time
C
1.00 s
Settings 50N2 SETTINGS GEN
C
T.A.=1 COM
Current Tap
C
0.30 xIn
Settings 51N SETTINGS GEN
C
T.A.=1 COM
Curve type
C
Def Tim
Time Dial
C
0.05
Current Tap
C
0.20 xIn
Operating Time
C
5.00 s
Settings CLP SETTINGS GEN
C
T.A.=1 COM
Multiplier 50P1
C
1.00
Multiplier 50P2
C
1.00
Multiplier51P
C
1.00
Multiplier 50G1/50N1
C
1.00
Multiplier 50G2/50N2
C
1.00
Multiplier 51G/51N
C
1.00
No Load Time
C
15 s
Operating Time
C
0.02 s
Settings 46 SETTINGS GEN
C
T.A.=1 COM
Current Tap
C
0.20 xIn
Operating Time
C
0.02 s
Settings 49 SETTINGS GEN
C
T.A.=1 COM
Current Tap
C
1.00xIn
z Heating constant
C
3 min
z Cooling constant
C
1
Alarma Level
C
80
Settings 79 SETTINGS GEN
C
T.A.=1 COM
Hold Enable
C
NO
Recloser Number
C
1
Reclose 2 Time
C
0.02 s
Reclose 3 Time
C
1.00 s
Reclose 4 Time
C
1.00 s
Reclose 5 Time
C
1.00 s
Hold Time
C
1.00 s
Reset Time
C
1.00 s
Settings 74TCS SETTINGS GEN
C
T.A.=1 COM
Press the key to access the general settings from the "SETTINGS" screen.
The general setting "Equipment name" can be viewed from the HMI, but it can only be modified by using the SICom program.
The value of the "CT Phase ratio and CT Neutral ratio general settings is the result given by dividing the number of turns on the primary winding by the
number on the secondary winding. For example: With TI 500/5, the setting would be 100 in standard models. In LPCT models this settings correspond to
the primary phase cuarrent and the primary neutral current.
The frequency is selected by means of an internal equipment selector, which can be accessed by removing the rear selector access cover in LPCT
models or by model in standard SILA. The value is read only.
CT Phase Ratio
C
10
CT Neutral Ratio
C
10
VT Ratio
C
100
Language
C
ENGLISH
Active Settings T.
C
1
Remote baudrate
C
(*)
ModBus Address
19200
ModBus BaudRate
19200
(*) Parameters in Remote communication depend on the protocol (IEC60870-5-103, IEC61850 or DNP3.0 depending on model)
It is necessary to enter a password to change a setting for the first time. The settings can be changed after entering the password, until returning either
manually or automatically to the standby mode screen. The system returns automatically to the standby mode screen if no key is pressed for five
minutes.
Adaptation B
Select group
C
2
Select group
C
3
Select group
4
Set Password
-> 5555
Function Enable
OK
NO -> NO
Function Enable
NO -> YES
Function Enable
OK
NO > YES y/n
SETTING CHANGED
OK
Function Enable
Function Enable
OK
YES
Current Tap
C
1.00 xIn
Current Tap
C
0.20 xIn
Time Delay
C
5.00 s
Curve type
C
Def Tim
Current Tap
C
0.20 xIn
Time Delay
C
5.00 s
Sett(1) 50N1 SETTINGS GEN
C
COM "
Current Tap
C
0.50 xIn
Time Delay
C
1.00 s
Sett(1) 50N2 SETTINGS GEN
C
COM "
Time Delay
C
2.00 s
Curve type
C
Def Tim
Time Dial
C
0.05
Current Tap
C
0.20 xIn
Time Delay
C
5.00 s
Curve type
C
Def Tim
Time Dial
C
0.05
Current Tap
C
0.20 xIn
Time Delay
C
5.00 s
Sett(1) CLP SETTINGS GEN
C
COM "
No Load Time
C
15 s
Sett(1) 50BF SETTINGS GEN
C
COM "
Time Delay
C
0.02 s
Sett(1) 49 SETTINGS GEN
C
COM "
Current Tap
C
1.00xIn
z Cooling constant
C
1
Alarma Level
C
80
Sett(1) 79 SETTINGS GEN
C
COM "
Hold Enable
C
NO
Recloser Number
C
1
Reclose 1 Time
C
0.02 s
Reclose 3 Time
C
1.00 s
Reclose 4 Time
C
1.00 s
Reclose 5 Time
C
1.00 s
Hold Time
C
1.00 s
Reset Time
C
1.00 s
Sett(1) 52 SETTINGS GEN
C
COM "
Sett(1) 74TCS SETTINGS GEN
C
COM "
Time Delay
C
0.02 s
Time Delay
C
0.02 s
Current Tap
C
0.20 xIn
Time Delay
C
0.02 s
Current Tap
50%
Time Delay
0.02 s
Current Tap
7xIn
Press the key to access the general settings from the "SETTINGS" screen.
The general setting "Equipment name" can be viewed and modified from the HMI and from SICom software.
The frequency can be 50 or 60 Hz.
Serial number is a read only setting.
The value of the "CT Phase ratio and CT Neutral ratio general settings is the result given by dividing the number of turns on the primary winding by the
number on the secondary winding. For example: With TI 500/5, the setting would be 100 in standard models. In LPCT models this settings correspond to
the primary phase cuarrent and the primary neutral current.
Frequency
C
50Hz
Serial number
C
0
Language
C
ENG.
Active Setting G.
C
1
N. Nominal Current
C
1 A
CT Phase Ratio
C
1.0
CT Neutral Ratio
C
1.0
Remote Address
C
3
Remote Baudrate
C
19200
Remote Protocol
C
MODBUS
EVENTS SILA000C2A12BB
C
There are 5 0.00 0.00 0.00 0.00
Set Password
C
-> 5555
Confirm
OK C
Erased Events y/n?
EVENTS
OK C
There are 1
Associated
Time Event number measurement
Date
01/01/00 00:54:18600 1/120 measurement
EventsErased EventsErased
Activated or
Not activated
Event Description
Adaptation A
COUNTERS SILA555B2001BA
C
0.00 0.00 0.00 0.00
Accumulated Amps
C
14011325 k(A2)
Reclosing Numbers
C
25
Thermal Image
C
75
COUNTERS SILA5000C2A12BB
C
0.00 0.00 0.00 0.00
Accumulated Amps
C
0 k(A2)
Reclosing Numbers
C
0
COMMANDS SILA555B2000BA
C
0.00 0.00 0.00 0.00
COMMANDS
OK
COMMANDS
OK
COMMANDS
OK
COMMANDS
OK
COMMANDS
OK
COMMANDS
OK
COMMANDS
OK
Adaptation B
COMMANDS SILA000C2A12BB
C
0.00 0.00 0.00 0.00
4
OK
In progress
COMMANDS
4
OK
In progress
COMMANDS
4
OK
In progress
COMMANDS
4
OK
In progress
COMMANDS
4
OK
In progress
COMMANDS
4
OK
In progress
COMMANDS
4
In progress
COMMANDS
OK
4
In progress
COMMANDS
OK
DEMAND SILA000C2A12BB
C
0.00 0.00 0.00 0.00
08/01/15 13:56
C
1.50 0.00 0.0 1.50 1.50
Dedicated fault report menu is only available in SIL-A with adaptation B. Apart from this it is possible to acces to faul reports by pressing key from dtandby
screen. This second option is available in both adaptations (adaptation A and adaptation B)
NOTE: Only in adaptation B, if fault report is configured to a situation that does not cause trip screen then the fault report is identified with the number of
report (example in the flowchart Fault report 77). If fault report is configured to a situation that originates a trip screen the the fault report is identified with the
trip (example in the Trip 51N)
Adaptation A
To assign a logical input to a physical input, go to the INPUT STATUS menu. If OK is pressed from the screen that displays the inputs status
(activated or deactivated), the current status of the logical input will disappear and the physical input that it is associated with will be displayed. To
change the associated logical input, press OK and use the and keys to find the desired physical input. Confirm the choice by pressing OK.
Go up through the menu levels by pressing the "C" key.
I. 52a:
OK C Sta. INPUTS
not activated
I. 52a I. 52a:
OK C
Not Asigned not activated
I. 52a
OK
Do not Asign y/n
I. 52a
Set to Input 1 y/n?
I. 52a
Set to Input 2 y/n?
I. 52a
C Sta. INPUTS
Set to Input 4 y/n?
Configuration
OK
Processing...
I. 52a
OK
Asigned to Input 4
I. 52a
Set to Input 5 y/n?
Phase A Pickup:
OK C Sta. 50P1
not activated
Phase B Pickup:
C Sta. 50P1
not activated
Phase B Pickup:
C Sta. 50P1
> LedON y/n?
Configuration
OK
Processing...
Phase B Pickup:
> Led1 y/n?
Phase B Pickup:
RESET
> Led1 y/n?
Phase B Pickup:
> Led2 y/n?
Phase B Pickup:
> Led3 y/n?
Phase B Pickup:
> Led4 y/n?
Phase B Pickup:
> Led5 y/n?
Phase B Pickup:
> Output 1 y/n?
Phase B Pickup:
> Output 2 y/n?
Phase B Pickup:
> Output 4 y/n?
Phase B Pickup:
> Output 5 y/n?
Phase B Pickup:
> 79 Init y/n?
Phase B Pickup:
> 50BF Init y/n?
Phase B Pickup:
> Osc Init y/n?
To view or remove the instantaneous statuses assigned to a physical output, go to the OUTPUT STATUS" menu. When the output current status
(activated or deactivated) is displayed, press the "OK key to replace this current status reading with the first instantaneous status that is associated with
the output, along with its index number from 1 to 16. The and keys can be used in this menu to browse all of the statuses (up to 16) that are
associated with a physical output.
Press and hold the RESET key while viewing any of the instantaneous statuses associated with the output and its index number from 1 to 16 to remove
the association with the physical output.
Phase B Pickup:
C
not activated
Configuration
OK
Processing...
Phase B Pickup:
> Led 2 y/n?
Phase B Pickup:
> Led 2 y/n?
Phase B Pickup:
> Led 2 y/n
Phase B Pickup:
> & Led 2 y/n?
Phase B Pickup:
> $ Led 2 y/n?
Phase B Pickup:
> Led 2 y/n?
Phase B Pickup:
> O Led 2 y/n?
Phase B Pickup:
> P Led 2 y/n?
Phase B Pickup:
> Q Led 2 y/n?
Phase B Pickup:
> o Led 2 y/n?
Phase B Pickup:
> p Led 2 y/n?
Phase B Pickup:
> q Led 2 y/n?
Phase B Pickup:
> r Led 2 y/n?
Phase B Pickup:
> Led 3 y/n?
Phase B Pickup:
> Led 4 y/n?
Phase B Pickup:
> Led 5 y/n?
Phase B Pickup:
> Led 7 y/n?
Phase B Pickup:
> Led-52 y/n?
Phase B Pickup:
> Led-79 y/n?
Phase B Pickup:
> Output 1 y/n?
Phase B Pickup:
> Output 2 y/n?
Phase B Pickup:
> Output 3 y/n?
Phase B Pickup:
> Output 4 y/n?
CUSTOMER 1 byte Each device on a communication bus must have a unique address,
ADDRESS otherwise two different units could reply simultaneously to the same
request. All ports of the relay will use this address which can be set a
value between 1 and 247. When the master transmits a frame with
the slave address to 0 indicates a Broadcast. All the slaves in the
communications bus will carry out the requested action, but no one
will reply to the master. The Broadcast will only be accepted to write,
as it makes no sense to make a read request in the Broadcast, as no
one will reply this request.
FUNCTION 1 byte This is one of the function codes supported by the equipment. In this
CODE case, the only function codes supported are 3 to read and 16 to write.
When the slave has to reply with an exception one of these frames, it
is indicated by putting 1 in the most important bit of the correspondent
function. Thus, an exception for the function 3, will be indicated with a
83 as a function code; and an exception for the function code 16 or
0x10 in hexadecimal, will be indicated with an 0x90.
DATA N bytes This part consists of a variable number of bytes, depending on the
function code. It may include: addresses, data lengths, settings,
commands or exception codes sent by the user.
CRC 2 bytes Control code of two bytes. The ModBus/RTU includes a 16 bit CRC in
each frame, to detect errors. If the slave detects an erroneous frame,
based on a CRC that is not correct, it wont take any action, nor will
reply anything to the master. The management of the CRC is LSB-
MSB.
DEAD TIME Necessary A frame is terminated when nothing is received for a period of 3,5
time to bytes. It means:
transmit 3,5 15 ms at 2400 bps
Bytes 2 ms at 19200 bps
...etc.
HEX
DEC MODBUS NAME DEFINITION COMMENT
CODE
0x03 Read Holding Reading of Any Value This function allows the master to read
1 or more consecutive addresses of a
3 Registers relay. The registers always are of 16
bits, with the most important byte at
first. The maximum number of
registers to be read in a package are
60.
The slave does not support any function with the function code
01 ILLEGAL FUNCTION
received in this message.
The slave has detected that the value sent by the master is not
03 ILLEGAL DATA VALUE
valid.
06 SLAVE DEVICE BUSY The slave is busy and unable to perform the required operation.
Integer without sign of 16 bits. Each of the values that the integer can be will have a
correspondence in the auxiliar list of the database. I this list is the correspondence chain
ENUM 1 which must be shown for each of the values. Memory will only receive an integer value.
E. g.: 0, 1 Correspondence to CLOSED, OPEN
String: In length variable character chain. Final of String marked with \0.
ASCIIxx xx/2 E. g.: ABC 0x41x42x43x00....
CONT 13 Directory(UINT).Value(DWORD).Description(ASCII20)
EVENTO 10 Antiquity(UINT).Event(EVENT)
When the data format takes up more than one BYTE, the most important BYTE is sent
through the communications first, and the least important BYTE is sent last.
Pickup Number of
Function Description Format
address registries
See commands
16 Confirmation of Command 201 1 UINT map
See commands
16 Write the Directory of Event 400 1 UINT map
See protection
03 Read of the Protection States 501 61 PEST status map
Write-Confirmation of a
16 5001 2 See Settings map
Setting
4 Thermal Image
6 Reset 86
1 IA
2 IB
3 IC
4 IN
5 I2
6 Thermal Image
Criteria
Criteria Directory Criteria denomination
Number
2 50*256+5+32 50P_2
3 51*256+7 50/51P
4 150*256+5 50N/G_1
5 150*256+5+32 50N/G_2
6 151*256+7 50/51N/G
8 24*256+1 50BF
12 255*256+4 Measurements
13 253*256+8 Inputs
14 254*26+14 Outputs
15 79*256+1 79 (Auto-recloser)
16 52*256+1 52 (Breaker)
17 74*256+1 74TCS
bit-3 Pickup
50P_1
bit-8 Phase A trip
bit-11 Trip
bit-3 Pickup
50P_2
bit-8 Phase A trip
bit-11 Trip
bit-3 Pickup
50/51P
bit-8 Phase A trip
bit-11 Trip
bit-4 Pickup
50N/G1
bit-12 Trip
bit-4 Pickup
50N/G2
bit-12 Trip
bit-4 Pickup
50BF
bit-12 Trip
bit-4 Pickup
46
bit-12 Trip
bit-4 Alarm
49
bit-12 Trip
bit-0 Trip
General:
Bit-1 External Trip Input
bit-16 Ready
bit-11 Lock 79
bit-12 Unlock 79
bit-17 Input -2
bit-18 Input -3
bit-19 Input -4
bit-20 Input -5
bit-21 Input -6
bit-22 Input -7
bit-23 Input -8
bit-25 A continuity
bit-26 B continuity
bit-0 Output - 1
bit-1 Output - 2
bit-2 Output - 3
bit-3 Output - 4
bit-4 Output - 5
bit-5 79 Init
bit-8 ON Led
bit-9 Led -1
bit-10 Led -2
bit-11 Led -3
bit-12 Led -4
bit-13 Led -5
bit-4 Pickup
74TCS
bit-12 Trip
bit-20 Unlock 79
bit-24 Reset 86
bit-19 Lock 79
bit-20 Unlock 79
bit-24 Reset 86
bit-20 Unlock 79
bit-21 Telecontrol No
bit-24 Reset 86
1 50 Pickup up A
2 50 Pickup up B
3 50 Pickup up C
4 50 Pickup up P
50P_1
5 50 Trip A
6 50 Trip B
7 50 Trip C
8 50 Trip P
1 50 Pickup up A
2 50 Pickup up B
3 50 Pickup up C
4 50 Pickup up P
50P_2
5 50 Trip A
6 50 Trip B
7 50 Trip C
8 50 Trip P
1 50/51 Pickup up A
2 50/51 Pickup up B
3 50/51 Pickup up C
4 50/51 Pickup up P
50/51P
5 50/51 Trip A
6 50/51 Trip B
7 50/51 Trip C
8 50/51 Trip P
1 50 Pickup up N/G
50N/G_1
2 50 Trip N/G
1 Pickup
CLP
2 Activation
1 Pickup
50BF
2 Trip
1 Pickup
46
2 Trip
1 Alarm
49
2 Trip
1 General Trip
7 General 50Hz
17 General Ready
22 General Telecontrol NO
46 General identification
49 Neutral pick-up
50 Phase A pick-up
51 Phase B pick-up
52 Phase C pick-up
53 General pick-up
54 Phase A trip
55 Phase B trip
56 Phase C trip
57 50N/G trip
58 50P trip
1 Input 52 a
2 Input 52 b
7 Input init 79
8 Input enable 79
9 Input Locking 79
Inputs
10 Input 1 select table
12 Lock 79
13 Unlock 79
17 Input1
18 Input2
19 Input3
20 Input4
22 Input6
23 Input7
24 Input8
25 Control voltage
26 Coil A continuity
27 Coil B continuity
1 Output1
2 Output2
3 Output3
4 Output4
Outputs
5 Output5
6 79 Init
7 50BF Init
8 Fault Init
1 Status 79 Standby
3 Status 79 Open
7 Status 79 Lockout
1 Status 52 Inicio
2 Status 52 Error
52
3 Status 52 Open
12 Status 52-A
13 Status 52-B
1 Pickup
74TCS
2 Activation
1 Command select
4 Lock 79
ModBus
5 Unlock 79
6 Telecontrol NO
7 Telecontrol YES
9 Reset 86
1 Command select
4 Lock 79
Remote
5 Unlock 79
6 Telecontrol NO
7 Telecontrol YES
9 Reset 86
4 Lock 79
Local Modbus
5 Unlock 79
6 Telecontrol NO
7 Telecontrol YES
9 Reset 86
in ModBus
Maximum
Minimum
Category
Function
ModBus
Type
Step
Unit
Equipment
3001 5001 ASCII20 General -
identifier
Phase CT
3006 5006 LONG General 1 2000 1 -
Ratio
Neutral CT
3007 5007 LONG General 1 2000 1 -
Ratio
DENUM
3008 5008 5060Hz
General Frequency 0 1 1 Hz
DENUM
3009 5009 LANGUAGE
General Language 0 3 1 -
Value Curve
3 Definite time
Number
H Pickup L Pickup Number of Number of checksum checks
address function of Password
address address H registers L registers H um L
Bytes
01 10 00 A8 00 02 04 35,35,35,35 30 F4
01 10 00 A8 00 02 04 29 93
01 03 05 79 00 08 95 19
And the SIL-A will reply with the IA, IB, IC and I0 measurements in FLOAT format:
Number
Measurement Measurement Measurement Measurement checksum checksum
address function of
IA IB IC IN H L
Bytes
01 03 10 00,00,00,00 00,00,00,00 00,00,00,00 00,00,00,00 E4 59
01 03 01 F5 00 3D 95 D5
00,00,00,01,00,00,00,00,.,7C,B1,0A,AF,DD 3B 1D
CUSTOMER 1 byte Each device on a communication bus must have a unique address,
ADDRESS otherwise two different units could reply simultaneously to the same
request. All ports of the relay will use this address which can be set a value
between 1 and 247. When the master transmits a frame with the slave
address to 0 indicates a Broadcast. All the slaves in the communications
bus will carry out the requested action, but no one will reply to the master.
The Broadcast will only be accepted to write, as it makes no sense to make
a read request in the Broadcast, as no one will reply this request.
FUNCTION 1 byte This is one of the function codes supported by the equipment. In this case,
CODE the only function codes supported are 3 to read and 16 to write. When the
slave has to reply with an exception one of these frames, it is indicated by
putting 1 in the most important bit of the correspondent function. Thus, an
exception for the function 3, will be indicated with a 83 as a function code;
and an exception for the function code 16 or 0x10 in hexadecimal, will be
indicated with an 0x90.
DATA N bytes This part consists of a variable number of bytes, depending on the function
code. It may include: addresses, data lengths, settings, commands or
exception codes sent by the user.
CRC 2 bytes Control code of two bytes. The ModBus/RTU includes a 16 bit CRC in each
frame, to detect errors. If the slave detects an erroneous frame, based on a
CRC that is not correct, it wont take any action, nor will reply anything to the
master. The management of the CRC is LSB-MSB.
DEAD TIME Necessary A frame is terminated when nothing is received for a period of 3,5 bytes. It
time to means:
transmit 3,5 15 ms at 2400 bps
Bytes 2 ms at 19200 bps
...etc.
HEX
DEC MODBUS NAME DEFINITION COMMENT
CODE
0x03 Read Holding Reading of Any Value This function allows the master to read
1 or more consecutive addresses of a
3 Registers relay. The registers always are of 16
bits, with the most important byte at
first. The maximum number of
registers to be read in a package are
60.
The slave does not support any function with the function code
01 ILLEGAL FUNCTION
received in this message.
The slave has detected that the value sent by the master is not
03 ILLEGAL DATA VALUE
valid.
06 SLAVE DEVICE BUSY The slave is busy and unable to perform the required operation.
Integer without sign of 16 bits. Each of the values that the integer can be
will have a correspondence in the auxiliar list of the database. I this list is
ENUM 1 the correspondence chain which must be shown for each of the values.
Memory will only receive an integer value.
E. g.: 0, 1 Correspondence to CLOSED, OPEN
String: In length variable character chain. Final of String marked with \0.
ASCIIxx xx/2 E. g.: ABC 0x41x42x43x00....
Year(UINT).month(UCHAR).day(UCHAR).hour(UCHAR).minutes(UCHAR
FH 5 ).seconds (UCHAR).hundredth(UCHAR).thousandth(UINT)
CONT 13 Directory(UINT).Value(DWORD).Description(ASCII20)
EVENTO 10 Antiquity(UINT).Event(EVENT)
Number of Meassure(UINT).Descriptive
CMED 8 text(ASCII7).Unit(ASCII3).Primary Unit(ASCII5).Number of
decimals(UCHAR)
When the data format takes up more than one BYTE, the most important BYTE is sent
through the communications first, and the least important BYTE is sent last.
Start Number of
Function Description Format
address registries
Setting DENUM
03 and 16 618 2 Phase nominal current
CURRENT
Setting DENUM
03 and 16 620 2 Neutral nominal current
CURRENT
Setting DENUM
03 and 16 760 2 Protocol
PROTOCOL
4 Pulse Lock 79
5 Pulse Unlock 79
6 Local control
7 Telecontrol
9 Reset
Number
H Pickup L Pickup Number of Number of checksum checks
address function of Password
address address H registers L registers H um L
Bytes
01 10 00 A8 00 02 04 35,35,35,35 30 F4
01 10 00 A8 00 02 04 29 93
01 03 05 79 00 08 95 19
And the SIL-A will reply with the IA, IB, IC and I0 measurements in FLOAT format:
Number
Measurement Measurement Measurement Measurement checksum checksum
address function of
IA IB IC IN H L
Bytes
01 03 10 00,00,00,00 00,00,00,00 00,00,00,00 00,00,00,00 E4 59
01 03 01 F5 00 3D 95 D5
10.
00,00,00,01,00,00,00,00,.,7C,B1,0A,AF,DD 3B 1D
X RS-485
Transmission speed
X 4800 bits/s
X 9600 bits/s
X 19200 bits/s
X 38400 bits/s
Transmission parameters
parity EVEN
Stop bits 1
<5> Power on
<23> Characteristic 1
<24> Characteristic 2
<25> Characteristic 3
<26> Characteristic 4
<78> Zone 1
<79> Zone 2
<80> Zone 3
<81> Zone 4
<82> Zone 5
<83> Zone 6
<144> Measurement I
<145> Measurement I, V
<116> 79 init
<119> 79 Enabled
<17> 32 Trip
<18> 32 Start
<19> 32 Trip
<20> 32 Start
<21> 32 Trip
<22> 32 Start
<23> 32 Trip
<32> 37 Start A
<33> 37 Start B
<34> 37 Start C
<35> 37 Start P
<36> 37 Trip A
<37> 37 Trip B
<38> 37 Trip C
<96> 67 Start N
<97> 67 Trip N
<98> 67 Start N
<99> 67 Trip N
<100> 67 Start A
<101> 67 Start B
<102> 67 Start C
<103> 67 Start P
<104> 67 Trip A
<105> 67 Trip B
<106> 67 Trip C
<107> 67 Trip P
<108> 67 Start A
<110> 67 Start C
<111> 67 Start P
<112> 67 Trip A
<113> 67 Trip B
<114> 67 Trip C
<115> 67 Trip P
<8> 27 Start A
<9> 27 Start B
<10> 27 Start C
<11> 27 Start P
<12> 27 Trip A
<13> 27 Trip B
<14> 27 Trip C
<15> 27 Trip P
<16> 27 Start A
<17> 27 Start B
<18> 27 Start C
<20> 27 Trip A
<21> 27 Trip B
<22> 27 Trip C
<23> 27 Trip P
<24> 59 Start N
<25> 59 Trip N
<26> 59 Start N
<27> 59 Trip N
<28> 59 Start A
<29> 59 Start B
<30> 59 Start C
<31> 59 Start P
<32> 59 Trip A
<33> 59 Trip B
<34> 59 Trip C
<35> 59 Trip P
<36> 59 Start A
<37> 59 Start B
<38> 59 Start C
<39> 59 Start P
<40> 59 Trip A
<41> 59 Trip B
<43> 59 Trip P
<48> 81 Start
<49> 81 Trip
<50> 81 Lockout
<51> 81 Start
<52> 81 Trip
<53> 81 Lockout
<54> 81 Start
<55> 81 Trip
<56> 81 Lockout
<57> 81 Start
<58> 81 Trip
<59> 81 Lockout
ADAPT ADAPT
FUN INF Description TYP COT
A B
This section describes the implementation of IEC 61850 protocol in standard SILA.
IEC 61850 protocol defines a way of structuring the available information in each device,
that is reflected in the Data Model and a way of managing and sending this information
through communications using specific Services.
SILA device will be known as a Server IED (Intelligent Electronic Device), which services
will be available using the Ethernet through its default IP (192.168.0.121)
MMS will be the used Ethernet protocol for the Client-Server communication and 102 will
be the used port.
GOOSE fast messages is not a Client-Server communication like TCP/IP but a Multicast
communication that sends messages directly to the Link Layer using MAC directions as
destination directions for publishing the GOOSE.
Adaptation B includes:
System Functions:
DATASETS
A Dataset is a grouping of information from the data model of the IED:
These groupings can be used by other services for the sending of information (GOOSE,
RCB, BRC).
The definition of Datasets has to be made in a IEC61850s file with extension .ICD (IED
Capability Description) that is provided with the device.
By default there are 4 Datasets, grouped according the functionality (Trips, Measures,
Events and Goose):
Trips, with the name of Trips and the following data objects:
Events, with the name of Events and the following data objects:
REPORTS
The Report service is used for the sending of values from elements of a Dataset to a
communication client that enables the report service (Central unit of Substation, remote
unit o software application).
The use of Reports optimizes the communication when the information of the
associated Dataset is only sent when there is a change of value, when is requested or
time integrity is enabled.
Standard SILA device is pre configured with 10 URCB associated to the Measures
Dataset:
GOOSE
Goose service allows the Multicast sending (to multiple devices) of the existing information
in a Dataset.
Goose message is an Ethernet message that is continuously cast to the Ethernet and
every device can analyze it.
Standard SILA disposes by default a Goose message associated to the Goose Dataset:
This message is sent to the Ethernet with a latency time of 30 seconds till one of the
values of the element of the Dataset changes, then the message is sent immediately in a
repeating way in a short time, increasing till reaching the latency time.
10.3. Operation
Standard SILA is pre configured with a sample configuration to be integrated in an IEC
61850 system.
It disposes all the Data model with all the functionallity available via MMS (using a
software application like IEDScout) or via Reports (with their Event, measure or Trip
Datasets) in case a client needs to receive information from the device.
To retrieve the data model from the device to a PC with an IEC 61850 tool, it is only
required the IP of the device (by default 192.168.0.121).The tool has to be able of asking
the data model automatically.
The name of the IED is by default TEMPLATELD1 and below it there is the data model
with its logical nodes, data objects and data attributes according IEC 61850.
The common way to integrate a new IED in a SCADA is using reports and the ICD files
from SILA provided for this purpose.
From the ICD file of SILA, the client device has to select a Report with the associated
Dataset. This way, client will have a list of signals that will use to configure its own
database. Once client device is configured, the communication between server could be
initiated by the client by enabling the report and receving the existing information from the
report.
Each client has different ways of configuring, so it will be necessary referring to
IEC61850s configuration chapter from the clients manual.
Goose message is activated by default and is published with the information from the
Goose dataset (General Trips and Starts) into the net.
One IED that requires the information from a Goose has to be configured using the ICD
file from SILA. In this file appears the default parameters of the Goose message.
DNP V3.00
DEVICE PROFILE DOCUMENT
This document must be accompanied by : Implementation Table and Point List.
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited
quantity), and 17 and 28 (index) are supported. Static object requests sent with qualifiers
07, or 08, will be responded with qualifiers 00 or 01.
16-bit, 32-bit and Floating Point Analog Change Events with Time may be requested.
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
None None
Fixed at ____________________ Configurable
Configurable, from _0_ to _255_
Default, 3
Requires Data Link Layer Confirmation:
Never
Always
Sometimes. If 'Sometimes', when? ____________________________________________
Configurable as Never, Only for multi-frame messages, or Always. Default Never
Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Queue Never
Clear Queue Never
_______________________________________________________________________
Attach explanation:
All points support the same Function Codes :Direct Operate and Direct Operate-No ACK
All points support the same Control Codes : Pulse ON, Latch ON, Latch OFF, Pulse OFF
and Trip-Pulse ON.
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events
specific variation requested: when no specific variation requested:
Never Never
Only time-tagged Binary Input Change With Time
Only non-time-tagged Binary Input Change With Relative Time
Configurable to send both, one or the Configurable (attach explanation)
other (attach explanation)
Function Codes 7 6 5 4 3 2 1 0
Index Size Qualifier Code
1 Read
2 Write
3 Select Index Size Qualifier Code
4 Operate
5 Direct Operate 0- No Index, Packed 0- 8-Bit Start and Stop Indices
6 Direct Operate-No ACK 1- 1 byte Index 1- 16-Bit Start and Stop Indices
13 Cold Start 2- 2 byte Index 2- 32-Bit Start and Stop Indices
14 Warm Start 3- 4 byte Index 3- 8-Bit Absolute address Ident.
20 Enable Unsol. Messages 4- 1 byte Object Size 4- 16-Bit Absolute address Ident.
5- 2 byte Object Size 5- 32-Bit Absolute address Ident.
21 Disable Unsol. Messages 6- 4 byte Object Size 6- No Range Field (all)
23 Delay Measurement 7- 8-Bit Quantity
129 Response 8- 16-Bit Quantity
130 Unsolicited Message 9- 32-Bit Quantity
11-(0xB) Variable array
REQUEST RESPONSE
OBJECT
(BCD will parse) (BCD will respond)
Func Qual Func Qual
Obj Var Description Codes Codes Codes Codes Notes
(dec) (hex) (dec) (hex)
1 0 Binary Input All variations 1 6
Assigned to
1 1 Binary Input 129 1 Class 0.
20,21 6
20,21 6
20,21 6
0
80 1 Internal Indications 2
index=7
-- -- No Object (Cold Start) 13
In SIL-A relay, the value of the currents IL1, IL2 and IL3 have valid values, the other
measures remain with value 0.
Each current value is in the range 0 4095 where 4095 corresponds to 1,2*In
e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A
In SIL-A relay, the value of the currents IL1, IL2 and IL3 have valid values, the other
measures remain with value 0.
Each current value is in the range 0 4095 where 4095 corresponds to 1,2*In
e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A
Application Confirm Timeout: Specifies how long the slave DNP device will wait for an
application layer confirmation from the master.
Source Address: Destination address of the Master device to which the unsolicited responses
are to be sent.
Unsolicited Retry Delay: Specifies the time to delay after an unsolicited confirm timeout before
retrying the unsolicited response.
Unsolicited Max. Retries: How many times should this slave resend Unsols before declaring
the station offline
Unsolicited Offline Retry Delay: How often to retry unsolicited responses after maxRetries
attempts
12.1. Identification:
Date: .
Official: .
Substation: ...
Circuit: .
Model: .
Serial no.: ..
Software Versions:
LPCT setting
OFF ON OFF ON
50 A
100 A
Phase A
200 A
+ 400 A
OFF ON
750 A
+ 50 A
OFF ON
Phase C
50P_1
Permission Permitted Forbidden
Current pick-up xIn
Defined Time s
50P_2
Permission Permitted Forbidden
Current pick-up xIn
Defined Time s
50/51P
Permission Permitted Forbidden
Current pick-up . xIn
Curve type Inverse IEC Very inverse IEC Extr. Inverse IEC
LT Inverse IEC Inverse ANSI Very Inverse ANSI
Extr Inverse ANSI Defined time
Dial .
Defined Time s
50N/G_1
Permission Permitted Forbidden
Current pick-up .. xIn
Defined Time s
50N/G_2
Permission Permitted Forbidden
Current pick-up .. xIn
Defined Time s
50/51N/G
Permission Permitted Forbidden
Current pick-up .. xIn
Curve type Inverse IEC Very inverse IEC Extr. Inverse IEC
LT Inverse IEC Inverse ANSI Very Inverse ANSI
Extr Inverse ANSI Defined time
Dial ..
Defined Time . s
50BF
Permission Permitted Forbidden
Operating time: .. s
46
Permission Permitted Forbidden
Time dial:
Curve type Inverse IEC Very inverse IEC Extr. Inverse IEC
LT Inverse IEC Inverse ANSI Very Inverse ANSI
Extr Inverse ANSI Defined time
49
Permission Permitido Prohibido
Current TapxIn
heatingmin
cooling.. heating
Alarm%
79
Permission Permitted Forbidden
Hold permission Permitted Forbidden
Number of reclosings .
st
1 reclose time s
nd
2 reclose time s
rd
3 reclose time s
th
4 reclose time s
52
Maximum number of openings .
Maximum number of accumulated amperes
Maximum opening time ...
Maximum closing time
Time / openings number: Number of openings
Time period min
74TCS
Permission Permitted Forbidden
Operating time: ..s
74CT
Permission Permitted Forbidden
Operating time: ..s
37
Permission Permitted Forbidden
Current pick-up .. xIn
Defined Time s
46BC
Permission Permitted Forbidden
Tap .. %
Defined Time s
Logical inputs In1 In2 In3 In4 In5 In6 In7 In8
52 a
52 b
50P block
50N/G block
Fault init
79 Init
79 Permission
Level 79 Lock
Pulse 79 Lock
Pulse 79 unlock
50BF Init
Reset
Table 1
Table 2
External trip
Continuity A
Continuity B
Logical signal 1
Logical signal 2
Output 1
Output 2
Output 3
Output 4
Output 5 (*)
79 Init (*)
Led On
Led 1
Led 2
Led 3
Led 4
Led 5
Led 52
Led 79
ON
50P/51P
50G/51G
50BF
46
74TCS
Tel. + 34 94 471 14 09
Fax + 34 94 471 05 92
fanox@fanox.com
www.fanox.com