Professional Documents
Culture Documents
1. Transmission
Rectifier and inverter stations in HVDC schemes, thyristor controlled static VA r
compensators .
In the supply system itself , transformers can generate harmonic at light load if the
transformer goes into saturation.
2. Industrial
Controlled and uncontrolled converters for rolling mills, etc. Arc furnaces, traction loads.
3. Domestic
Televisions, light dimmers etc.
4. Disturbance to:
Fig- 1
Each 6 pulse thyristor bridge supplied from its own converter transformer.
The action of the thyristor switching results in current waveforms on the AC system which
consist of blocks of current as shown below: -
Fig- 2
If a Fourier analysis is performed on these idealized waveforms the following results are
obtained: -
For
2 3 1 1 1
I I D [cos t cos 5t cos 11 t cos 13t .....]
5 7 13
For /
2 3 1 1 1
I I D [cos t cos 5t cos 11 t cos 13t .....]
5 7 13
If a Fourier analysis is performed on this idealized waveform the following results is obtained:
4 3 1 1 1 1
I I D [cos t cos 11t cos 13t cos 23t cos 25t ....]
11 13 23 25
Thus in a 12- pulse bridge, the harmonic order is 6n 1, n=1,3,5 are theoretically cancelled
leaving only characteristics 12-pulse harmonics, ie, 12n1, n=1, 2, 3 ..
The idealized wave form shown above will be modified by the reactance of the system ( mainly
the transformer reactance) to produce wave form as shown below.
Practical harmonic currents from HVDC converters
The harmonic current which occur in practice can be considered in three groups:
(a) Characteristic harmonic.
(b) Theoretically cancelled harmonic.
(c) Non-characteristic harmonic.
The bases of the harmonic filter can be explained with reference to the figure below
Where,
In is harmonic current from the disturbing loads.
Ifn is harmonic current in the filter.
Ifn is harmonic current in the supply system.
Zfn is harmonic impedance of the filter.
Zsn is harmonic impedance of the supply.
Z fn
I SN In
Z fn Z sn
Z fn Z sn
VSN In
Z fn Z sn
In order to calculate the harmonic performance and design the filters i.e. to find the value of Zfn
it is essential that the all detailed on the harmonic currents generated by the disturbing load (In),
and the harmonic impedance of the supply system (Zsn)