This document provides technical specifications for HVAC systems for buildings in a refinery expansion project. It lists the requirements for air cooled chillers, chemical filtration units, and their proposed specifications. For the chillers, it specifies brands, models, capacities, dimensions, and other details. For the filtration units, it outlines design criteria, flow rates, dimensions and other key particulars. Overall this summary outlines the HVAC equipment needs and proposed solutions for various buildings in a refinery project.
This document provides technical specifications for HVAC systems for buildings in a refinery expansion project. It lists the requirements for air cooled chillers, chemical filtration units, and their proposed specifications. For the chillers, it specifies brands, models, capacities, dimensions, and other details. For the filtration units, it outlines design criteria, flow rates, dimensions and other key particulars. Overall this summary outlines the HVAC equipment needs and proposed solutions for various buildings in a refinery project.
This document provides technical specifications for HVAC systems for buildings in a refinery expansion project. It lists the requirements for air cooled chillers, chemical filtration units, and their proposed specifications. For the chillers, it specifies brands, models, capacities, dimensions, and other details. For the filtration units, it outlines design criteria, flow rates, dimensions and other key particulars. Overall this summary outlines the HVAC equipment needs and proposed solutions for various buildings in a refinery project.
BUILDINGS LIST: SUBSTATION AND RACK ROOM 42-R-101 SUBSTATION AND RACK ROOM 44-R-101 SATELLITE OPERATOR BUILDING 44-R-105
REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)
Offer XXXXX dated XXXXXXXX
as per 071973C-G00-JSD-3400.01 (hereafter
1. General Design Criteria referred to as "JSD") NOTED
as per 071973C-G00-JSS-3480.01 (hereafter
2. Minimum Requirements for Fabrication referred to as "JSS") NOTED
3. EQUIPMENT
3.1. General requirements
Applicable Stds. as per JSD, sect.2. and JSS, sect.2. NOTED Electric data 380 VAC / 3ph./ 50 Hz NOTED
3.2. Protection against harsh environment
as per JSS, sect. 3.1., EDS-B-3 "GENERAL SPECIFICATION FOR COATING AND General PAINTING" and 071973C-G00-JSD-2300-01 "JOB DESIGN SPECIFICATION FOR PAINTING" NOTED tin coated copper piping with copper fins shall be Air cooled condensers and AHUs cooling in general selected, or other well-proven coils (if not protected by a chemical filtration equivalent coating provisions (world-main system) Brands patented/guaranteed) such as Heresite, High silver coating, or others NOTED
3.3. Air cooled water chillers
3.3.1. Common features
Brand name & model carrier &30XA aquaforce Construction features as per JSS sect. 3.2.2. Compressors type scroll or semi-hermetic type NOTED R134a or other ozone friendly type, complying Refrigerant with the local phase-out policy NOTED Minimum performance as per JSS sect. 3.2.1. NOTED Notes
Offer XXXXX dated XXXXXXXX Working unit weight 6300 kg 4313 KG Overall dimensions (lxwxh) 5 x 2,5 x 2,5 m 4798x2253x2295 mm
3.3.3. Service SUBSTATION AND RACK ROOM 44-R-101
Acronym ACWC-ES-44-01 A/B Quantity no. 2 (1 duty, 1 stand-by) NOTED Cooling capacity (each unit) 618 kW 702 kw Electrical power input (each unit) 310 kW 278 kw Working unit weight 7600 kg 6640 kg Overall dimensions (lxwxh) 6 x 2,5 x 2,5 m 7186x2253x2297mm
3.4. Chemical filtration units
3.4.1. Common features
Brand name & model Construction features as per JSS sect. 3.2.5. level G1 according to ISA S71.04 (outdoor: H2S Values of pollutants at outlet of filter levels 5 ppm - level GX ) Fans no. 2 (1 duty, 1 stand-by) Notes fans motors provided with VFD
3.4.2. Service SUBSTATION 42-R-101 WE WILL PROVIDE LATER
Acronym PFU-ES-42-01 Quantity no.1 Fresh air flow rate 1950 l/s Full load input power 3 kW Working unit weight Overall dimensions (lxwxh) 3,0 x 2,0 x 2,0 m
3.4.3. Service RACK ROOM 42-R-101
Acronym PFU-RR-42-01 Quantity no.1 Fresh air flow rate 524 l/s WE WILL PROVIDE LATER Full load input power 1,5 kW Working unit weight Overall dimensions (lxwxh) 2,5 x 1,0 x 1,2 m
3.4.4. Service SUBSTATION 44-R-101
Acronym PFU-ES-44-01 Quantity no.1 Fresh air flow rate 2961 l/s WE WILL PROVIDE LATER Full load input power 4 kW Working unit weight Overall dimensions (lxwxh) 4,0 x 2,5 x 2,0 m
3.4.5. Service RACK ROOM 44-R-101
Acronym PFU-RR-44-01 Quantity no.1 Fresh air flow rate 784 l/s WE WILL PROVIDE LATER Full load input power 1,5 kW Working unit weight Overall dimensions (lxwxh) 3,0 x 1,5 x 1,5 m
10/09/2017 - page 2 of 6 file name:368203201.xls
NESTE OIL - SINGAPORE HVAC TECHNICAL DATA
REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)
Offer XXXXX dated XXXXXXXX
3.4.6. Service SATELLITE OPERATOR BUILDING 44-R-105
Acronym PFU-SOB-01 Quantity no.1 Fresh air flow rate 136 l/s WE WILL PROVIDE LATER Full load input power 0,75 kW Working unit weight Overall dimensions (lxwxh) 2,5 x 0,6 x 1,2 m Notes chemical filter section to be included
3.5. Air handling units
3.5.1. Common features
Brand name & model carrier &39 HQM SERIES-KSA Construction features as per JSS sect. 3.2.4. and 3.2.8.
3.5.2. Service SUBSTATION 42-R-101
Acronym AHU-ES-42-01 A/B Quantity no. 2 (1 duty, 1 stand-by) NOTED Supply air flow rate (each unit) 11027 l/s 11470 L/S Fresh air flow rate (each unit) 1950 l/s WE WILL PROVIDE LATER Cooling coil capacity (each unit) 324 kW WE WILL PROVIDE LATER Full load input power (each unit) 22 kW WE WILL PROVIDE LATER Working unit weight Overall dimensions (lxwxh) 5,0 x 2,4 x 2,2 m WE WILL PROVIDE LATER
3.5.3. Service RACK ROOM 42-R-101
Acronym AHU-RR-42-01 A/B Quantity no. 2 (1 duty, 1 stand-by) NOTED Supply air flow rate (each unit) 2664 l/s 2800 L/S Fresh air flow rate (each unit) 524 l/s WE WILL PROVIDE LATER Cooling coil capacity (each unit) 74 kW WE WILL PROVIDE LATER Full load input power (each unit) 7,5 kW WE WILL PROVIDE LATER Working unit weight Overall dimensions (lxwxh) 3,5 x 1,2 x 1,2 m WE WILL PROVIDE LATER n.1 self-contained steam humidifier to be Notes provided NOTED
3.5.4. Service SUBSTATION 44-R-101
Acronym AHU-ES-44-01 A/B Quantity no. 2 (1 duty, 1 stand-by) NOTED Supply air flow rate (each unit) 17432 l/s 17118 L/S Fresh air flow rate (each unit) 2961 l/s WE WILL PROVIDE LATER Cooling coil capacity (each unit) 506 kW WE WILL PROVIDE LATER Full load input power (each unit) 35 kW WE WILL PROVIDE LATER Working unit weight Overall dimensions (lxwxh) 7,0 x 3,0 x 3,0 m WE WILL PROVIDE LATER
Offer XXXXX dated XXXXXXXX Fresh air flow rate (each unit) 784 l/s WE WILL PROVIDE LATER Cooling coil capacity (each unit) 112 kW WE WILL PROVIDE LATER Full load input power (each unit) 11 kW WE WILL PROVIDE LATER Working unit weight Overall dimensions (lxwxh) 4,0 x 1,5 x 1,5 m WE WILL PROVIDE LATER n.1 self-contained steam humidifier to be Notes provided NOTED
3.6. Electric driven water pumps
3.6.1. Common features
Brand name & model Construction features as per JSS sect. 3.2.10. NOTED
Chilled water distribution - SUBSTATION AND
3.6.2. Service RACK ROOM 42-R-101 Quantity no. 2 (1 duty, 1 stand-by) NOTED Water flow rate (each unit) Full load input power (each unit) Notes included in the hydronic module of chillers NOTED
Chilled water distribution - SUBSTATION AND
3.6.3. Service RACK ROOM 44-R-101 Quantity no. 2 (1 duty, 1 stand-by) NOTED Water flow rate (each unit) Full load input power (each unit) Notes included in the hydronic module of chillers NOTED
3.7. Exhaust air fans
3.7.1. Common features
Brand name & model Construction features as per JSS sect. 3.2.9. NOTED
3.7.2. Service All Bldgs NOTED
Quantity Air flow rate (each unit) Full load input power (each unit) fans for battery rooms shall be suitable for Notes local hazardous area characteristics NOTED
3.8. Electrical type duct heaters
3.8.1. Common features
Brand name & model Construction features as per JSS sect. 3.2.7. NOTED
Brand name & model Construction features as per JSS sect. 3.2.6. and 3.2.8. NOTED Minimum performance as per JSS sect. 3.2.1. NOTED n.1 self-contained steam humidifier to be Notes provided NOTED
SATELLITE OPERATOR BUILDING 44-R-105 -
3.9.2. Service Operator room Acronym SSAC-SOB-01 A/B Quantity no. 2 (1 duty, 1 stand-by) NOTED Overall cooling capacity (each unit) 11 kW NOTED Electrical power input (each unit) 5 kW NOTED Working unit weight External unit: overall dimensions (lxwxh) 1,0 x 0,4 x 1,5 m WE WILL PROVIDE LATER N.2 indoor units: overall dimensions -each 1,2 x 0,3 x 0,4 m (lxwxh) WE WILL PROVIDE LATER Notes dual split-type: n.2 indoor units NOTED
SATELLITE OPERATOR BUILDING 44-R-105 -
3.9.3. Service Dining room Acronym SSAC-SOB-02 A/B Quantity no. 2 (1 duty, 1 stand-by) NOTED Cooling capacity (each unit) 4 kW NOTED Electrical power input (each unit) 2 kW NOTED Working unit weight External unit: overall dimensions (lxwxh) 1,0 x 0,4 x 1,0 m WE WILL PROVIDE LATER Indoor unit: overall dimensions (lxwxh) 1,2 x 0,3 x 0,4 m WE WILL PROVIDE LATER
4. Electric power & control panels
4.1. Common features
Brand name & model as per Project Vendor List NOTED Construction features as per JSS sect. 3.5.2. NOTED
4.2. Service All Bldgs NOTED
Quantity n.3 NOTED Overall dimensions (lxwxh)
5. Electric power & control cables and cable trays/conduits
5.1. Common features
Brand name & model as per Project Vendor List NOTED Construction features as per JSS sect. 3.5.1. NOTED
5.2. Service All Bldgs NOTED
Quantity Notes
10/09/2017 - page 5 of 6 file name:368203201.xls
NESTE OIL - SINGAPORE HVAC TECHNICAL DATA
REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)
Offer XXXXX dated XXXXXXXX 6. Ductwork and insulation Quantity Construction features as per JSS sect. 3.4. NOTED Notes
7. Diffusers, dampers, grilles, louvers, fire dampers, blast valves
Brand name Construction features as per JSS sect. 3.4. NOTED Notes
8. Piping, insulation, valves, pressurized tanks, water treatment systems
Brand name Construction features as per JSS sect. 3.2., 3.3. and 3.6. NOTED Notes
9. Regulation & control systems
Brand name Construction features as per JSS sect. 3.7. NOTED Notes