Professional Documents
Culture Documents
November 2009
Volume 37
In this issue...
Selecting Isolated Enclosures for COTS Electronics (part 1): Shock conditions,
enclosure types and equipment requirements - by Herb Lekuch
stiffeners. Base and top panels may have have to remain fixed with respect to the 2010 “Open” Courses
openings for air entry and cable penetrations. motion of the vehicle and operator’s platform. Wayne Tustin will teach
Rear and side panels are removable and This enables the operator to continue Fundamentals of Random
may also have opening for cable penetrations controlling and properly using the electronics.
Vibration and Shock
and air discharge. The front door is usually Military warfare displays are an example of
Testing, Measurement,
full opening with air entry via louvered water this - in some cases multiple displays can be
barrier sub-panels. EMI weather gaskets are a part of console design and the operator has Analysis, Calibration,
used at panel and door closure surfaces. to be attentive to each screen. However, if HALT, ESS and HASS at
Construction can be from formed or extruded vehicle vibration caused the isolated displays the following locations:
components, assembly is welded or bolted. to jitter, image definition and resolution could February 23-25, 2010
Special gussets are sometimes used at be degraded and inspection or surveillance
Santa Barbara, California
corner connections for strength where capabilities significantly reduced. Enclosure
bending moments are greatest and to carry designs can include hard mounted outer April 5-7, 2010
the reaction loads directly into the isolators. shells and internal compartments for College Park, Maryland
Flexing and twisting of the frame is reduced equipment, some of which are isolated and
through deep sections of the columns and others directly attached. The more fragile
stiffened top and bottom covers. The isolators (or unknown) equipment such as COTS
can be attached by means of a ‘sandwiched’ would be isolated and the rugged equipment Steve Brenner will teach
plate assembly for easy change out and hard mounted. Two levels of shock control Military Standard
replacement. A typical rack is 22 inches wide. would then be established and equipment 810G (MIL-STD-810G)
moved from one compartment to another as Testing - Understanding,
The Internally Isolated enclosure takes newer designs or next generation equipment Planning and Performing
a different approach. The enclosure became available. It is also possible to install Climatic and Dynamic
becomes an adjunct to the foundation and the equipment in modular compartments that Tests on the following
the electronics are installed in a stiffened would then be installed into the console at a dates and locations:
frame or platform that is supported and later time. This can result in quicker assembly
isolated from the outer rack by means of and shorter maintenance cycles since November 16-19, 2009
multiple mounts. In one design base and equipment can be integrated and checked to Bohemia (Long Island, NY)
side stabilizers are used. In newer designs, a relatively high level before final installation.
the platform is suspended with isolators February 8-11, 2010
only at the sides. Because the outer rack is Construction features of certain class of Fullerton, California
fixed in-place, the overall space is defined consoles involve machined end plates for the March 15-18, 2010
and no sway space or movement of the structural frame and isolated compartments Montreal, Canada
rack occurs. Shock isolation and relative in the lower space. Provisions are made for
displacement is entirely inside the enclosure. dynamic balance and physical separation of
This design can actually ‘package’ more the compartments to avoid resonance of the
electronics in the same overall space since isolation sections. Otherwise amplification Kevin Howard will teach the
there is no upward movement or sway that at the predominant modes can increase the new course in “Distribution,
has to be accommodated. Also the air can be dynamic loads transmitted into the hardened Packaging and Testing”
distributed completely around the equipment compartments during vibration and shock
and cabling run in the side clearances. test. Racks can also be configured with March 2-4, 2010
Enclosures can be kept to only 24 inches isolated and hard compartments. Relative Santa Barbara, California
width. Outer rack construction is generally deflection has to be checked between modular
strengthened with heavier column sections compartments to avoid impact during shock or
and corner restraints, stainless steel is often at resonance dwell in vibration.
used for the platform. Larry J. Bogatz will teach
Why Each Type of Enclosure Requires The Fundamentals of
Partially Isolated – Not all equipment has to Different Isolation Sealing and Fastening
be isolated but because of its rugged design The shock performance of the isolation system February 16-18, 2010
and need for stability can be hard mounted. is primarily a function of the mount stiffness Santa Barbara, California
That is, in normal use the equipment may to payload mass ratio and the duration of the
shock pulse. Amplification of 1.5 to 2.0 times Comparison of Test Specifications Take advantage of our
the input will occur for a moderately damped Comparing a commercial disk specification early-bird discounts and
system if they are closely coupled. These are versus military test shock levels shows how save up to $200 when
shown in the well known Mindlin curves for much more severe the specifications levels your enrollment and
response when subjected to velocity shock. are than the manufacturer’s ratings. Using payment reach ERI one
Close coupled frequency response of the rack the no loss data criteria, the disk limit is 15 month before the course
with the input can also amplify the measured g, half sine pulse, 5 ms duration. Mil Std 810 starts. Sign up now!
response of a COTS unit installed within the for ground equipment is 40 g’s, 6 to 9 ms, in
rack above the isolators. other words nearly 3 times the shock peak
and nearly twice the duration. Also the pulse Learned Vibration Testing
The stiffness k characteristics of mounts shapes are different. The barge is even more
by trial…
are axis dependent - generally stiffest in severe reaching 50-60 g’s, 30 to 35 ms for
compression/tension and more compliant in the 14 hz deck test. Isolation designed to The following is an exact
shear and roll. External quotation from a recent
isolated enclosures e-mail, commenting
usually have mounts at favorably upon Wayne's
the base in compression random vibration text.
and stabilizers in roll
or shear. Four to six “As I said before, I learned
base mounts and two vibration testing more or
stabilizers normally less by trial and error. This
handle up to 1200 gives me a more "academic"
lb payload which approach in talking to my
includes the 600 lb department here and to our
weight of the cabinet. customers. Now I have the
Example – 1200 lbs
accepted vocabulary and
and 4 mounts each at
theory to make my points
900 lbs/in stiffness in
compression, 300 lbs/ and discussions. I wish I
in in shear. The effective had gotten it sooner.”
shock response Those four sentences
frequency is: don’t surprise me. Many
shaker operators have
f (shock resp) = 3.13 (4 x
Figure 4 learned that way.
900 / 1200)^0.5 = 5.42 hz
Too bad about burning
In the internal isolation design, there may be reduce the Mil 810 level to 15 g’s might still out the shaker driver coil.
eight mounts at the sides (four each side) be inadequate to be effective at the 14 hz Too bad about some over-
and the isolated weight is only 600 lbs. Rack levels thus isolated equipment containing testing that led to product
weight is excluded. Although they are only these disks might satisfactorily operate to a
redesign. Too bad about
0.3 to 0.5 the compression stiffness, using ground test but fail the Navy test.
some under-testing, that
the same base mounts of type [1] would be
unsatisfactory in this case for the internally Figure 4 compares these in a bar chart led to some field failures
isolated rack in shear and an unacceptable form, the height of the vertical bar depicts and warranty expense.
amount of shock response g’s could occur the shock in g’s, the width of the same bar Unaware of what’s been
due to having a stiffer system. The frequency indicates the pulse duration. The impulse is a happening “down in the
with same mounts in shear is: finction of the force in g’s and pulse duration lab,” some company
thus its descriptive of how much more severe
executive will say, “No,
f (shock resp) = 3.13 (8 x 300 / 600)^0.5 = 6.26 hz the barge test conditions are. The disk drive
I don’t believe we need
limits in this example are below both Mil Std
810F and Mil S 901D levels. any vibration test training.
Bill is doing just fine.”
Equipment Reliability Institute tustin@equipment-reliability.com
1520 Santa Rosa Avenue Phone: (805) 564-1260 http://www.equipment-reliability.com
Santa Barbara, CA 93109 Fax: (805) 966-7875
Equipment Reliability Institute
November 2009
Volume 37
Contamination Mechanism 1 of small particles may be very low When will one of the US
Agglomeration with regard to the air volume near that builders of electrodynamic
Aside from the problems due to movement tool, yet sufficient to reduce yield to an shakers factory assemble
of lithography components, building unacceptably low level. The small particles three or more ED shakers
vibrations can also cause airborne that are generated may deposit on a into a deliverable system?
particulate contamination that is difficult surface that vibrates. Vibration results in Overseas ED shaker firms
to detect with normal cleanroom particle agglomeration of the small particles to have shown the way.
measurement. Even low-level vibration can produce agglomerate particles that can
cause release into the air of particles that be as large as ten to one hundred times
have settled upon surfaces. These particles the size of the initial small particles. This
can be in the nanometer and larger size phenomenon was noted in a recent paper³ 80th Shock & Vibration
ranges and in small quantities. If the settled that examined the behavior of fine particles Symposium
particles are retained on a surface only by on a surface under ultrasonic vibration. Wayne tutored on fixture
the effects of gravity, then vibration can
design, fabrication and
cause the original particles to agglomerate, Contamination Mechanism 2
usage last October 26, at
forming particles that can be much larger Relative Motion Between Walls, Floor
than the particles originally deposited and Ceiling SAVIAC’s 80th Shock &
on the surface. Even so, many of the How was your cleanroom constructed? Vibration Symposium. The
discrete particle counters used to classify Quite possibly plasterboard panels were event met in San Diego,
cleanrooms in the low concentration levels screwed or nailed or stapled to a wood CA, October 25-29, 2009.
of the present US Federal Standard 209 or metal framework. Joints between
Wayne also spoke on
are close to the limits of their particle plasterboard panels were taped and the
“Simultaneous Multiaxis
detection sensitivity levels. Statistically room was painted. One of the unfortunate
valid data for the ISO 14644-1 cleanroom results of building vibration, however Shaking”, recently blessed
standard² are difficult to procure for ISO caused, is relative motion along the edges by a new Test Method
level 1. The particles that must be sized of those panels, releasing paper and 527 in the October
and counted for both documents at their plaster particles into the air. 2008 "G" revision to
lowest classification size level are defined Military Standard 810.
as being equal to and larger than 0.1 µm Contamination Mechanism 3
Wayne's SAVIAC
in diameter. The US Federal Standard 209 Relative Motion Between Clean Room
presentation (also shown
specifies that the cleanest classification And Equipment
level shall have no more than 350 particles What equipment? Let us commence with at the Aerospace Testing
per cubic meter or 9.9 particles per cubic air conditioners on the roof and work our Seminar at Manhattan
foot of air equal to and larger than 0.1 µm way downward between rooms, noting Beach, CA), have been
in diameter. ISO 14644-1 specifies that ductwork for heating and cooling, a posted at ERI's website.
the cleanest classification level shall have furnace, blowers, pumps. Inside the various
no more than 10 particles equal to and cleanrooms are wall-mounted and floor
larger than 0.1 µm in diameter per cubic supported cabinets, wall-mounted and
meter of air. Statistical requirements result ceiling-mounted light fixtures. Is Environmental Test Lab
in the need to count at least 20 particles Safety Training Needed?
per measurement in order to provide Another unfortunate result of building
an acceptable confidence level to in? vibration, however caused, is relative Do you recall any on-
reported data. These requirements result in motion between equipments, releasing the-job injuries to your
excessive instrument operating time for to particles into the air. folks who use climatic
acquire? acceptable data. test chambers? Shakers?
Contamination Mechanism 4 Shock test machines?
Unfortunately, many state-of-the-art high Loss Of Particulate Uniformity Any near misses? Please
technology devices are extremely sensitive In the pharmaceutical industry, many e-mail Wayne about what
to small particles that are generated at medical processes involve blending of you remember along with
locations that may be "upwind" of the particulate materials, each with specific your advice on need for
device processing tool. The quantity properties needed for a particular product laboratory safety training.
to satisfy a medical need. Quite often, it is Cleanup Procedures; Effect On Vibration with
necessary to blend particulate materials in Production
Minimal Math
different size ranges to produce a product Depending on the severity of vibration
with the desired properties. The mixing that has previously occurred, some Yes, Wayne Tustin's
process is designed to blend these materials areas in the cleanroom may no longer vibration text (picture
so that the batch of powder contains the be adequately clean to meet either the below) weighs 4+ pounds,
correct quantities of each of the initial process cleanliness requirements or the but the math is less than 1
particulate materials. Vibration can cause regulatory agency requirements as the ounce. In a 3-day course,
smaller particles to settle downward in pharmaceutical industry is always required Wayne or Steve Brenner
into? spaces between the larger particles. to do. If a requirement is present that
or Herb LeKuch spends
Al - is this agglomeration? What had specifies a cleanroom classification level
perhaps 15 minutes using
been uniformly blended powder is no that must always be maintained, then
longer uniform and the batch may require procedures are written out in detail in the any branch of mathematics.
additional mixing with a possible decrease ISO 14644-1 and ISO 14644-2 documents. Their emphasis is on the
in uniformity. Maybe delete final 3 sentences ISO 14644-1 specifies procedures to verify practical aspects of vibration
that don't seem to relate to vibration. the cleanroom classification level. These and shock measurement
procedures involve verifying the integrity of and testing, along with
A Specific Stimulus, an Earthquake the final filter system, ensuring that the air ESS, HALT and HASS.
Immediately after an earthquake or other flow rate is acceptable and that the integrity
major stimulus, check for particles that of the cleanroom enclosure is verified by
may have been generated and/or moved leak testing.
into the cleanroom. Inspect the cleanroom
area and the tools operating in and about For a large ballroom type cleanroom, this
that area. For large tools, inspect product operation may require that production be
component entrance areas in particular, stopped for as long as one or two weeks.
but do not ignore any of the tool interiors Profitability of a 300 mm wafer fab can be
where in-process products may be exposed severely affected if one or two weeks of
to "fallout" from particles generated by tool production is not carried on. ISO 14644-2
motion during the earthquake. Inspect all specifies procedures for continuous and/or
cleanroom filters, especially those in ceiling frequent monitoring in the cleanroom and
ducts. During that inspection, examine the for ensuring compliance with ISO 14644- Who witnesses your Tests?
filter seals to ensure that the earthquake 1 If continuous or frequent monitoring
has not caused filter movement sufficient is carried out, then reverification of the When your hardware goes
to cause an opening in the seal area. An cleanroom class can be extended from to "the lab" for a vibration
opening can permit significant quantities of a period of 6 months to a period of 24 test or a shock test, who
contaminated air to bypass the filter medium months. In a two year time, availability of observes the test? (This
and act as a local area contamination three "extra" work weeks production is very applies to tests at your
source. During the cleanroom inspection, important to the profit of the facility. own lab at your facility, and
make sure that small local contaminant also applies to tests at an
sources have been produced as an effect Consider monitoring your entire cleanroom "outside" or commercial
of the movement caused by the motion of for atypically high particle concentrations. If testing laboratory).
the tool or storage where in-process product production rates must remain high, monitor
components are stored. several locations in your processing Does the test witness
area, especially where anomalous airflow understand what's
Remember that many of the less-dramatic patterns may have been recorded in the happening?
vibration sources listed under "STIMULI" past. If you find excessive contamination
Often he/she does not.
may intermittently or continuously shake in those areas, trace the particle "plume"
your cleanroom structure. At certain of the to its generation source and take the At least that is what many
structure's natural frequencies, the resulting necessary actions to remedy the problem. shaker operators have
magnified vibration can shake particles As cleanroom manager, you might also told us. That is why ERI
loose into cleanroom air. consider setting up a monitoring program developed Course No.
V&S 502 Witnessing
Equipment Reliability Institute tustin@equipment-reliability.com
1520 Santa Rosa Avenue Phone: (805) 564-1260 http://www.equipment-reliability.com
Santa Barbara, CA 93109 Fax: (805) 966-7875
Equipment Reliability Institute
November 2009
Volume 37
for particle count and for air flow patterns used to protect the product from effluents Vibration and Shock
at critical locations. Procedures for such generated by the environment or by the Tests. Would you like a
activities can be seen in the Institute of operating personnel. This is particularly copy? Just e-mail Wayne.
Environmental Science and Technology's true in areas where viable bacterial
Recommended Practices. IEST-RP 006.2, contamination is a potential problem.
"Testing Cleanrooms", is recommended
as a guide for characterizing the References Whom do you know?
cleanroom. IEST-RP-CC018.2, "Cleanroom ¹ Amick, H., & Bayat, A., "Meeting the Whom do you know that
Housekeeping-Operating and Monitoring Vibration Challenges of Next-Generation
needs a basic understanding
Procedures" recommends procedures for Photolithography Tools" Proc. 47th Annual
of vibration or shock testing,
monitoring cleanrooms. IEST can also Technical Meeting and Exposition of the
supply the ISO cleanroom documents Institute of Environmental Sciences and measurement, analysis,
referenced herein. Technology, Phoenix, AZ, April 22-25, calibration, isolation, etc?
(2001) Please tell him or her about
Cocoons ERI's website, newsletter,
When cleanrooms were smaller, their ² ISO14644-1 "Classification of Airborne short courses, etc.
natural frequencies were higher and the Particulate Cleanliness for Clean Rooms
ERI offers a commission
movements were smaller. At this time and Clean Air Devices"
some cleanrooms are ballroom-sized, or a course discount to
with relatively low natural frequencies ³ Matsusaka, S., Nakamura, S. and individuals who refer new
and relatively large motions, leading to an Masuda, H. "Behavior of Fine Particles on students or consulting
increase in particle contamination. One a Plate Under Ultrasonic Vibration" KONA, clients to us. Please contact
solution is a "cocoon" inside the large not- 18, 213-219, (2000) Wayne for more information.
so-clean room. Not only does the cocoon
have relatively high natural frequencies, but ISO14644-2 "Test Schedule to
it can "float" on soft springs or air cushions. Demonstrate Compliance with ISO14644-1"
There are a number of companies that Consider joining LinkedIn
produce such devices. These can be ISO14644-3 "Metrology and Test Methods" Sign up at LinkedIn
to exchange ideas,
opportunities and
This article has been published in the October 2001 issue of A²C² magazine (now
information with other many
Controlled Environments).
professionals. Search for
Wayne Tustin, ERI’s president, can be reached by e-mail or phone (805) 564-1260. ERI’s Vibration and Shock
Group. You can comment
Ray Schneider is the Chair of the Department of Construction Science and Management at on multiaxis vibration
Clemson University. He can be reached at www.practicaltechonline.com. testing, on hammers for
repetitive shock (as in
The late Alvin Lieberman wrote over 100 technical publications dealing with particulate ESS, HALT & HASS).
systems and contamination measurement and control, co-edited a 1997 book on liquid-
borne particle measurement and was sole author of a 1992 book on cleanrooms and
contamination control. He developed many standards for particle measurements,
instruments and cleanrooms, including Federal Standart 209. What are your Reliability
Problems?
ERI is vitally interested
Lock in 2009 fees for 2010 courses in the reliability problems
If we receive your course registration and payment by December 30th, 2009, you get you face. Will you, as an
to lock in the 2009 fee in addition to our usual early-bird discounts. It's savings up to individual, share those
$700! So don't delay and sign up now! problems with us and with
other readers? We won't