You are on page 1of 16

GA DRAWING FOR LOCAL CONTROL PANEL

FOR AREA BF, HM1, HM2, LD,


CH, OP, SP, SM, CO & RM BULDING

01 OF 16
PANEL PANEL
DOOR LOCKS MTG. LUGS
(4Nos.) (4Nos.)

R Y B
DEGREE OF PROTECTION IP-52
INDOOR TYPE APPLICATION
MCCB MCCB MCCB TIC HIC FABRICATION MATERIAL:- CRCA SHEET
ON OFF TRIP
AS PER GTS STANDARD
ON OFF ON OFF ON ON
M1 M2 M3

0-500V 0-100A
H1 H2 H3 H4 H5 H6 BUSBAR :- 100A TPN ALUMINIUM BUSBAR-50KA-1SEC.
PAC-1 PAC-2 HTR HUMD
PAC-1 PAC-2 ON OFF 25 x 5mm AL. PHASE
V A
SS2 SS3 25 x 5mm AL. NEUTRAL
ON OFF
25 x 5mm AL. EARTHING
PB1 PB2
PAC-1/2
ON OFF TRIP ON OFF TRIP COLOUR:- POWDER COATED RAL-7035
VSS ASS H7 H8 H9 H10 H11 H12 CABLE ENTRY:- BOTTOM
PUMP-1 PUMP-2
PUMP-1 PUMP-2

1250
ON
SS4 OFF

PB3 PB4
PUMP-1/2
ON OFF TRIP ON OFF TRIP
100A, TPN
MCCB H13 H14
CT-1
H15 H16 H17
CT-2
H18

INCOMER ON OFF ON OFF

PB5 PB6 PB7 PB8


CT-1 CT-2
CONTROL
ON
SS1

CHANGE OVER
SWITCH
100A TPN
50

400 800
300
1200

FRONT ELEVATION SIDE VIEW


PANEL
EARTHING
CONN.
(2Nos.)
300

GLAND PLATE
200 300 300 300 300 x 70 X 3mm Thk.
=

BOTTOM VIEW 02 OF 16
R R
Y Y
B B
N N
S1
0-100A
S3 A
S5
S A
CT S
100/5A
CL-1 CTS

100A, TPN MCCB


INCOMER

MCCB MCCB
AUX. TRIP
CONTACT CONTACT
INCOMER CIRCUIT DIAGRAM
M1 M2 M3
CF-1-3
2A
R
0-500V
Y V
B S V
100A TPN S
ALUMINIUM BUS BAR N
WITH H.S. SLEEVE NL-1
50KA-1Sec.
R Y B

CHANGE OVER
SWITCH
R Y B N 100A R Y B N 03 OF 16

INCOMER-1 INCOMER-2
R
3.6.A Y
5.1.A
B
N

MPCB-1 MPCB-2 MCB


20-25A 20-25A 10A-3P

6.3.E 6.4.E 6.4.E

C1 C2 C3

N N N

HEATER
(As per Location
Requirement)
PAC-1 PAC-2
11 TR/5.5 TR 11 TR/ 5.5 TR

CONTROL CIRCUIT DIAGRAM 04 OF 16


4.8.A
9.1.A

MPCB-3 MPCB-4 MPCB-5 MPCB-6


4-6.3A 4-6.3A 1-1.6A 1-1.6A MCB MCB
4A-2P 10A-2P

7.3.D 7.3.D 7.4.D 7.5.D 6.1.A 6.1.A

220V. AC
C5 C6 C7 C8

N N N N
C9 C9

10.7.D 10.7.D

DAMPER DAMPER
CONTROLLER CONTROLLER

FD-1 FD-2

PUMP-1 PUMP-2 COOLING COOLING


2.2 KW 2.2 KW TOWER-1 TOWER-2
0.55 KW 0.55 KW

CONTROL CIRCUIT DIAGRAM 05 OF 16


PHASE
5.8.B 7.1.A
SS1

INTERLOCK
PLC

OFF

PLC
STOP

ON PLC R1

10.4.B TIC-1 C1 C2

SS2

PAC-1 PAC-2

R3 R4
8.3.D 8.4.D

R1 C1 C2 C3
PAC-1 PAC-2 HEATER
11 TR/ 11 TR/ (As per Location
5.5TR 5.5TR Requirement)
5.8.B 7.1.E

CONTROL CIRCUIT DIAGRAM 06 OF 16


6.6.A
10.1.A
PHASE

R2 MPCB-5 MPCB-6

SS4
STOP PUMP-1 PUMP-2 STOP STOP

PLC PLC PLC


STOP STOP STOP

MPCB-3 MPCB-4
PLC PLC PLC
START R2 C7 C8
START START START START
START

R5 R6
8.6.D 8.7.D

R2 C5 C6 C7 C8
COOLING COOLING
TOWER-1 TOWER-2
6.6.F
10.1.D
NEUTRAL

CONTROL CIRCUIT DIAGRAM 07 OF 16


9.2E +
24V. DC

9.2E _
FROM PS1
FLOW FLOW LEVEL LEVEL
SWITCH SWITCH SWITCH SWITCH
PACKAGE PACKAGE C/T-1 C/T-2
UNIT-1 UNIT-2

R3 R4 R5 R6

CONTROL CIRCUIT DIAGRAM 08 OF 16


5.8.A
11.1.A

6A-MCB-2P 6A-MCB-2P 2A-MCB-2P 2A-MCB-2P

220V. AC 220V. AC 220V. AC 220V. AC

DC POWER DC POWER
PS1 SUPPLY PS2 SUPPLY

24V. DC 24V. DC

+ _ + _

8.1.A 8.1.A 10.1.D 10.1.D

CONTROL CIRCUIT DIAGRAM 09 OF 16


7.6.A 12.1.A

9.5.D 9.7.D MCB 2A-2P

+ 6.2D + 11.5.C
TIC-1 HIC-1
_ 6.2.D
_ 11.5.C SIGNAL
FROM
FIRE
SYSTEM
TIC HIC

9.5.D
9.7.D

FROM PS2
9.4.E +
24V. DC 4 TO 20mA
9.4.E
_
C9
TEMPERATURE
& RH SENSOR

7.6.E 12.1.D

TEMP./RH CONTROLLER CIRCUIT DIAGRAM

10 OF 16
9.8.A

MCB-6A-3P
SS3
MCB-6A-2P
OFF ON

LEVEL SWITCH THERMOSTAT-1

C4

10.6.B HIC-1
THERMOSTAT-2 500W-HEATER

HEATER
(As per Location
Requirement)

IN HUMIDIFIER TERMINAL BOX

HUMIDIFIER CIRCUIT DIAGRAM


11 OF 16
10.8.E
10.8.A
PHASE
2A
CF

NL-1
220V. AC

NEUTRAL
CONTROL SUPPLY C1

H1
PACKAGE UNIT-1 ON
C1

H2
PACKAGE UNIT-1 OFF
C2

H3
PACKAGE UNIT-2 ON
C2

H4
PACKAGE UNIT-2 OFF
C3

H5
HEATER - ON
C4

H6

HUMIDIFIER - ON
C5

H7

PUMP-1 ON

INDICATION LAMP CIRCUIT DIAGRAM


H8
C5

PUMP-1 OFF
H9

PUMP-1 TRIP
MPCB-3
C6

H10

PUMP-2 ON
C6

H11

PUMP-2 OFF
H12

PUMP-2 TRIP
MPCB-4
C7

H13

C/T-1 ON
C7

H14

C/T-1 OFF
H15

C/T-1 TRIP
MPCB-5
C8

H16

C/T-2 ON
C8

H17

C/T-2 OFF
H18

C/T-2 TRIP
MPCB-6
12 OF 16
TERMINAL
220V.AC TO FIRE
TO C9 PANEL
O/L-1 PAC-1

24V DC TO TEMP/RH SENSOR


+ TEMP + TEMP
+ RH + RH
TO TIC/HIC FROM TEMP/RH SENSOR
- (COM) - (COM)
O/L-2 PAC-2
SPARE
TERMINALS
+24V DC
PAC-1 FS
TO R3
+24V DC
O/L-3 PUMP-1 PAC-2 FS
TO R4
+24V DC
CT-1 LS
TO R5
+24V DC
O/L-4 PUMP-2 CT-2 LS
TO R6
PAC-PLC
INTERLOCK
O/L-5 COOLING PAC-PLC STOP
TOWER-1
PAC-PLC START

COOLING PUMP 1/2


O/L-6
TOWER-2 PLC-STOP
PUMP 1/2
PLC-START
C3 TO STRIP
CT-1
PLC-STOP
TO PLC TERMINAL DIAGRAM
HEATER
N CT-1
PLC-START
CT-2
PLC-STOP
C4
TO CT-2
N HUMIDIFIER PLC-START
4-20mA, +
MCB FROM TIC -
4-20mA, +
DC-1 FD-1 SUPPLY FROM HIC -

DC-2 FD-2 SUPPLY


13 OF 16
- NC CONTACT
A - AMMETER

- CONTACTOR COIL
V - VOLTMETER

- PUSH BUTTON
- INDICATING LAMP LED TYPE
WITH NO LEMENT

- PUSH BUTTON
- PUSH BUTTON
WITH NC LEMENT
- CURRENT TRANSFORMER

- CT SHORTLINK TERMINALS
- AUTO / MANUAL
SELECTOR SWITCH
- AUX RELAY
- TPN MCCB
- HUMIDITY IND. CONTROLLER
HIC

- CONTROL FUSE
- TEMP. IND. CONTROLLER
TIC

- O/L RELAY

- NEUTRAL LINK
LEGEND
- NO CONTACT

14 OF 16
NMDC ELECTRICAL BOQ FOR AC BUILDINGS
S. NO. ITEM DESCRIPTION RATING MAKE QTY .
CHANGE OVER SWITCH TPN/4POLE 100 Amp. C&S/SCHNEIDER/L&T
1 1
WITH ROTARY HANDLE
MCCB TPN /4-POLE (50KA FOR1Sce.) WITH 1C/O
2 100 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 1
AUX. CONTACT, TRIP CONTACT (LV510487)
3 ROTARY HANDLE FOR MCCB - SCHNEIDER/L&T/BCH/ SIEMENS 1
4 SPREADER TERMINALS FOR MCCB - SCHNEIDER/L&T/BCH/ SIEMENS 2-SET
5 MPCB, WITH 1NO+1NC FRONT CONTACT 20-25 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
6 MPCB, WITH 1NO+1NC FRONT CONTACT 4-6.3 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
7 MPCB, WITH 1NO+1NC FRONT CONTACT 1-1.6 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
8 MCB, 3-POLE 10 Amp. SCHNEIDER/L&T/SIEMENS 1
9 MCB, 3-POLE 6 Amp. SCHNEIDER/L&T/SIEMENS 1
10 MCB, 2-POLE 10 Amp. SCHNEIDER/L&T/SIEMENS 1
11 MCB, 2-POLE 6 Amp. SCHNEIDER/L&T/SIEMENS 3
12 MCB, 2-POLE 4 Amp. SCHNEIDER/L&T/SIEMENS 1
13 MCB, 2-POLE 2 Amp. SCHNEIDER/L&T/SIEMENS 3
CONTACTOR, 3-POLE (AC-3 DUTY) COIL 240V AC 40 Amp. SCHNEIDER/L&T/SIEMENS/BCH
14 2
WITH 2NO+2NC AUX. CONTACT
CONTACTOR, 3-POLE (AC-3 DUTY) COIL 240V AC 25 Amp. SCHNEIDER/L&T/SIEMENS/BCH
15 6
WITH 2NO+2NC AUX. CONTACT
CONTROL (AUX.) CONTACTOR COIL 240V AC 4 Amp. SCHNEIDER/L&T/SIEMENS/BCH
16 1
WITH 2NO+2NC CONTACT
17 SELECTOR SWITCH 2POLE, 2-WAY SALZER/KAYCEE 4
18 VOLT METER SELECTOR SWITCH SALZER/KAYCEE 1
19 AMP. METER SELECTOR SWITCH SALZER/KAYCEE 1
20 INDICATION LAMP-RED LED TECNIC/L&T/SIEMENS/BCH 8
21 INDICATION LAMP-YELLOW LED TECNIC/L&T/SIEMENS/BCH 6
22 INDICATION LAMP-GREEN LED TECNIC/L&T/SIEMENS/BCH 9
23 INDICATION LAMP-BLUE LED TECNIC/L&T/SIEMENS/BCH 1
24 PUSH BUTTON START SCHNEIDER/L&T/SIEMENS/BCH 4
25 PUSH BUTTON STOP SCHNEIDER/L&T/SIEMENS/BCH 4
26 RELAY MODULE, 24V, 8-WAY/2C/O REPUTED MAKE 1
27 AMMETER ANALOGUE TYPE 100 Amp. AE/MECO 1
28 VOLTMETER ANALOGUE TYPE 0-500 V AE/MECO 1
1200 x 1250 BCH/VENUS/MEDITRON/
29 PANEL SCHNEIDER/SEN &SINGH 1
x 300
30 BUS BAR ALUMINIUM 50KA FOR 1Sec. 25 x 5 mm REPUTED MAKE 1-Lot
31 220 V. AC TO 24 V. DC SUPPLY 2 Amp. SCHNEIDER/SIEMENS 2
32 CT, CL-1 100/5 Amp. KAPPA/PRAGATI/REPUTED 3
33 CONTROL FUSE WITH BASE 2 Amp. CONNECT WELL/REPUTED 4
34 CT SHORTING TERMINAL REPUTED MAKE 4
35 FIRE DAMPER CONTROLLER SYSTEM AIR 2
36 TEMPURATURE/RH CONTROLLER 96x96mm MASIBUS/PEPL/HONEYWELL/CHINO 2
37 NEUTRAL LINK REPUTED MAKE 4
38 WIRE FOR CONTROL CIRCUIT WIRING POLYCAB/KEI/BCH 200Mtr.
39 WIRE FOR POWER CIRCUIT WIRING POLYCAB/KEI/BCH 100Mtr.
40 TERMINALS CONNECT WELL/ WAGO/ELMEX 36
41 TERMINALS CONNECT WELL/ WAGO/ELMEX 64
42 LUG TERMINAL, INSULATOR PANEL HARDWARE - REPUTED 1-LOT

15 OF 16
NOTES:-
1. THE PANEL SHALL BE SINGLE FRONT, OPERATION & MAINTENANCE ON FRONT SIDE.
2. THE PANEL SHALL BE DUST & VERMIN PROOF. (DEGREE OF PROTECTION IP-52)
3. THE LOAD BEARING SECTION, FRAME SHALL BE FABRICATED OUT OF 2.0MM, NON LOAD
BEARING SECTION DOORS, COVERS & PARTITIONS SHALL BE FABRICATED OUT OF 1.6MM
THICK & GLAND PLATES SHALL BE FABRICATED OUT OF 3.0MM THICK MS. CRCA SHEET.
4. THE PANEL SHALL BE POWDER COATED RAL-7035
5. ALL DOOR & COVER WILL BE FULLY GASKET WITH NEOPRENE RUBBER.
6. ALL THE DOORS SHALL BE EARTHING WITH 2.5 SSQ.MM Cu. WIRE.
7. THE SIZES FOR THE WIRING SHALL BE AS FOLLOWS:-
(a) AC POWER WIRING (415V AC) - BLACK - AS PER RATING.
(b) AC CONTROL WIRING (230V AC.) -PHASE-GREY, NEUTRAL - BLACK - 2.5 SQ.MM. ,1100V.
(c) CT WIRING - GREY - 2.5 SQ.MM.
(d) EARTHING WIRING - GREEN - 2.5 SQ.MM.
8. ALL TERMINATING WIRE ENDS OF CONTROL WIRING SHALL BE PROVIDED WITH THE
SLEEVE AND FERRULE NUMBER ON IT FOR WIRE IDENTIFICATION.
9. INSPECTION & TESTING:-
(a) PHYSICAL CHECKING.
(b) INSULATION RESISTANCE (100 MEGGER ).
(c) FUNCTIONAL TESTS INCLUDING CONTROL & INTERLOCK FUNCTIONS.
10. AREAS COVERED FOR ELECTRICAL PANELS BF,HM1,HM2,
LD,CH,OP,SP,SM,CO & RM BUILDING.

12. MCCB & CONTACTOR RATING SHALL BE AS PER TYPE 2 COORDINATION CHART.

16 OF 16