ENVHCMC Specification

LOAD BREAK SWITCH 22kV - 630A - 3P OUTDOOR


V. DATA SHEET :
No Description Unit Requirements Tendered
1. Manufacturer
Tenderer must state
2. Country Tenderer must state
3. Common requirements expressed in Yes YES
common requirements document
4. Standards of quality
Tenderer must state ISO 9001
management
5. Member approve of certificate of
Tenderer must state (*)
management
6. Standards of factory and test IEC 60265 or IEC 62271-103
equivalent
7. Warranty period since the date of 2,3,4,5 years
issuance Minutes of acceptance for the (Atleast 2 years)
2
last delivery. More than 02 years
is priority
Operating condition:
Outdoor used in HCM city area (*)
Maximum altitude Yes
Less than 1000m
Max. ambient temperature 400C Yes
Average ambient temperature 350C Yes
Relative humidity 95% Yes
Climate Tropical Yes
Solar radiation 1000W / m2 Yes
Max. Wind speed 34m/s Yes
Number of storm days per year 120 days Yes
Construction :
8. Type Yes
Silver-plated contact,
for outdoor
installation
9. The switch is manufactured as a 3 pole Yes Yes
unit gang-operated for outdoor service,
suitable for horizontal mounting on the
centrifugal concrete electrical pillar of
12m.
10. Insulating medium SF6 gas SF6 gas
11. Interrupting medium SF6 gas or vacuum SF6 gas
12. The terminals of switch can be connected Yes Yes

A6-DCB58 11/11/2014 4/6


ENVHCMC Specification
LOAD BREAK SWITCH 22kV - 630A - 3P OUTDOOR
with Aluminium lugs by bolt M22
13. LBS has included functions SCADA-
SUPERVISORY CONTROL AND
DATA ACQUISITION in case IEC 60870- Protocol is
motor and control box installed later 5-101, IEC ok, but Fiber
on. 60870-5-104 optical is
+ Standard of SCADA protocols: Fiber optical needed the
- IEC 60870-5-101, IEC 60870- detailed
5-104 (obligatory) information.
- IEC 61850 (not obligatory)
+ Fiber optical (single mode)
- The manufacturer shall provide a
full range catalogs and Type test
report to demonstrate control box of
manufacturer has SCADA functions
ensures protocol as specified in
above.
Technical data :
14. Rated voltage kV 22 (24) Yes
15. Frequency Hz 50 Yes
16. Rated continuous current (In) A 630 Yes
17. Rated breaking current A 630 Yes
18. Rated short time withstand current kA 25/1 or 20/3 It needs
rms/s additional test
19. Rated peak withstand current kA 62.5kA (for rated It needs
short time withstand additional test
current 25kA/1s) or
50kA (for rated short
time withstand
current 20kA/3s)
20. Rated cable-charging breaking current A 16 25
21. Rated no load transformer breaking A 1% In 1% In
current
22. Rated lightning impulse withstand kV 125 150
voltage
23. Rated power - frequency withstand kV
voltage :
+ Dry for 1 minute 50 60
+ Wet for 10 seconds 50 50
24. Minimum creepage distance mm/ 25 25
kV
25. Close-opening operations for test duty 1 times 400 400
according to IEC 60265

A6-DCB58 11/11/2014 5/6


ENVHCMC Specification
LOAD BREAK SWITCH 22kV - 630A - 3P OUTDOOR
Mechanical endurance class times 2.000 5.000

26. Accessories :

A6-DCB58 11/11/2014 6/6


ENVHCMC Specification
LOAD BREAK SWITCH 22kV - 630A - 3P OUTDOOR
- 01 Manual operating mechanism, Yes
completed with 8m linkage rod and Additional
detachable lever, suitable for horizontal explanation is
mounting of load break switch on the required.1)
centrifugal concrete electrical pillar of
12m.
- 06 connectors for ACSR 240mm. Yes Yes
- 01 set of bracket + boulons + nuts + Yes ?
rondells suitable for horizontal mounting
of load break switch on the centrifugal
concrete electrical pillar of 12m at fixed
position as the attached drawing 12m
concrete pole layout
1)
Does the 8m linkage rod mean an operating rod for manually manipulating the LBS on the
ground?
(*) : Important requirements

A6-DCB58 11/11/2014 7/6


ENVHCMC Specification
LOAD BREAK SWITCH 22kV - 630A - 3P OUTDOOR
Data point list required for SCADA (to be tested for Accepteance test)

Status Points Regular Points Tendered


Point Name
No
Description Single Double Three
1 LBS open/closed status Open/Closed 1 1 Yes
2 Local/ Remote Switch Local/Remote 1 1 Yes
3 Switch status Alarm/Normal 1 Yes
4 Enclosure Door Open Alarm/Normal 1 Yes
5 Gas low (SF6) Alarm/Normal 1 Yes
6 Battery Alarm/Normal 1 Yes
7 AC power Alarm/Normal Yes
8 Charger Alarm/Normal 1 Yes
9 Operating Handle Locked/Unlcok 1 Yes
10 Fault indicator Alarm/Normal 1 Yes
Measurement points
8 Current Measurement Measurement 1 Yes
9 Voltage measurement Measurement 1 Yes
10 Operation counter Measurement 1 Yes
Control Outputs: Digital Output
1 Open Command 1 Yes
2 Close Command 1 Yes
3 Reset Fault 1 Yes
4 Battery test 1 Yes
Auxiliary contacts: 2 DI with NO Yes
2 DO with NO
RTU
Communication: IEC 60870-5- Yes
101, 104.
Port: USB Yes
RS232,
ETHERNET.

** If there is a specified Point Map, we will obey it. The table above is a partial revision.