You are on page 1of 7

FOR APPROVAL

A 11 Nov,14 Issue for Approval J.S. Lee H.S. Kim J. Son


REV. DATE DESCRIPTION DSGN CHKD APPD

PROJECT :

TWO(2) x 500 MW MONG DUONG 1 THERMAL POWER PLANT


EMPLOYER :

CONSULTANT :

CONTRACTOR :

DESIGNED BY DATE TITLE :

J.S. Lee 11 Nov,14 Site inspection & Test Procedure For AC/DC
CHECKED BY DATE Bus Duct of Excitation
H.S. Kim 11 Nov,14
APPROVED BY DATE PROJECT NUMBER DOCUMENT NUMBER REV.

J. Son 11 Nov,14 ADB/MD1-TPIP/EPC150911 MD1-0-T-060-05-00641 A


Site Inspection & Test Procedure
Document Number
ELECTRO ELECTRIC SYSTEMS
HHI-EES-W210-130701-A01

Contents

TITLE PAGE

1. SITE INSPECTION & TEST PROCEDURE 1-6


( )

1
Site Inspection & Test Procedure
Document Number
ELECTRO ELECTRIC SYSTEMS
HHI-EES-W210-130701-A01

1. INSPECTION & TEST PROCEDURE /

1.1 SCOPE /
This procedure covers the requirements for the test and inspection of the AC / DC
BUS DUCT for Mongduong1 #1, 2..
Mongduong1 #1, 2 AC/DC BUS DUCT
.

1.2 APPLICATION /
This procedure shall be applied to test and inspection of the AC/DC BUS DUCT
manufactured in accordance with the customer's technical specification.
AC/DC BUS DUCT
.

1.3 REFERENCE /
The requirement of this procedure are established in accordance with the Applicable
section of the followings.
.

1.3.1 IEC-62271-200 : Metal-Enclosed Bus


1.3.2 Specification ()
1.3.3 Approved ITP & DWG. ( )
1.3.4 Manufacture Standard( ) : HHIS-WW-116-A00
1.3.5 Test Report ()
1.3.6 Welding Procedure Specification ()

1.4 TEST AND INSPECTION ITEMS ( )

1.4.1 Insulation Resistance Check ()


1.4.2 High Voltage Test ()

1.5 TEST AND INSPECTION ( )


The test and inspection is carried out with following procedures.
( .)

2
Site Inspection & Test Procedure
Document Number
ELECTRO ELECTRIC SYSTEMS
HHI-EES-W210-130701-A01

1.5.1 Insulation Resistance Check /


The insulation resistance shall be confirmed between phase to phase and
each phase to ground before and after dielectric strength test.

.
Insulation resistance value shall be not less than 500 when tested with
1000V Megger Tester.
1000V 500 .

(Condition of ambient / )
1. Temp/ : Max./ 40
2. Humidity/ : between 7% to 90% (7% 90%)

1) Measurement of insulation resistance test AC (Main circuit) / AC

Result (M) / :

*BY 1000V(Main circuit) Megger / -1000V


*Ambient Temp./ ( ) / Humidity/ ( %)
*Acceptance criteria : above 500 M
Test Measurement Test Measurement Test Measurement
Test Point
Point Value Point Value Point Value
/
/ / / / / /

R - E M S - E M T - E M
Before
/
Main R - S M S - T M T - R M
circuit
/ R - E M S - E M T - E M
After/

R - S M S T M T - R M

Certification Signatures ()

Doosan : Date/ :

Owner : Date/ :

3
Site Inspection & Test Procedure
Document Number
ELECTRO ELECTRIC SYSTEMS
HHI-EES-W210-130701-A01

2) Measurement of insulation resistance test DC (Main circuit) / DC

Result (M) / :

*BY 1000V(Main circuit) Megger / -1000V


*Ambient Temp./ ( ) / Humidity/ ( %)
*Acceptance criteria : above 500 M
Test Measurement Test Measurement Test Measurement
Test Point
Point Value Point Value Point Value
/
/ / / / / /

P - E M N - E M - - -
Before
/
Main P - N M - - - - - -
circuit
/ P - E M N - E M - - -
After/

P - N M - - - - - -

Certification Signatures ()

Doosan : Date/ :

Owner : Date/ :

4
Site Inspection & Test Procedure
Document Number
ELECTRO ELECTRIC SYSTEMS
HHI-EES-W210-130701-A01

1.5.2 High Voltage Test /


High voltage assemblies shall be subject to dielectric strength test
Normal-frequency withstand tests shall be performed switchgear
assemblies to demonstrate the ability of the insulation system to
withstand rated voltage.

,
.

The wave shape shall be essentially sinusoidal and the frequency shall be
within 20% of the rated value 60Hz (IEC-62271-200)

IEC-62271-200
50Hz20% .

1) Procedure /

*The main circuit of assembly shall be subjected to dry condition only.


.

*The test voltage specified table 1&2 is to be increased gradually from


zero to reach the required test value.
Table 1&2 0 .

*The test voltage shall be held at rated value for 1 min.


1 .

*The test shall be made phase to phase and each phase to ground for
These tests.
.

2) Apply injection voltage standard /

*Table 1 ( AC Bus duct Dielectric Strength test ) / AC

Main circuit Dielectric Strength test /


(Test voltage is applied to 75%(14KV) of Factory test Voltage
according to ANSI-IEEE C37.23_2005 )

5
Site Inspection & Test Procedure
Document Number
ELECTRO ELECTRIC SYSTEMS
HHI-EES-W210-130701-A01

Max. Operating Duration Time Test Voltage Result


Voltage/ / / /

4.76 kV(r.m.s) 1 minute 14 kV(r.m.s)

ACCEPTANCE CRITERIA :
The test shall be considered to have passed if no disruptive discharge occurs
during each test.
Flash Over .

Certification Signatures ()

Doosan : Date/ :

Owner : Date/ :

*Table 2 (DC Bus duct Dielectric Strength test) / DC

Main circuit Dielectric Strength test /


(Test voltage is applied to 75%(14KV) of Factory test Voltage
according to ANSI-IEEE C37.23_2005 )

Max. Operating Duration Time Test Voltage Result


Voltage/ / / /

4.76 kV(r.m.s) 1 minute 14 kV(r.m.s)

ACCEPTANCE CRITERIA :
The test shall be considered to have passed if no disruptive discharge occurs
during each test
Flash Over .

Certification Signatures ()

Doosan : Date/ :

Owner : Date/ :