TABLE OF CONTENT
PART 1 - GENERAL
PART 2 - PRODUCTS AND SYSTEMS
2.1. COMPONENTS AND ACCESSORIES
2.2. LAMPS
PART 3 - FIELD AND INSTALLATION WORK
3.1. INSTALLATION
3.2. INSPECTION AND TESTS ON SITE
PART 4-SCHEDULE OF LIGHT FITTINGS
PART 1 - GENERAL
1.3 FIXTURE DESIGN AND STANDARDS: the Specification and the Drawings is a
guide to the selection of lighting characteristics and lighting fixtures, giving general
features of construction, materials, method of installation and conditions of
operation. Unless otherwise specified, fixtures are to be manufacturers standard
series, designed and manufactured for the purpose and application required,
generally in accordance with the Schedule of Lighting Fixtures and complying with
IEC 598 and CISPR 15.
1.4 DESIGN LAYOUT: fixture layout has been determined from photometric data
of specified fixtures to achieve desired level and uniformity of illumination.
Reflected ceiling plans are to be checked to ensure exact positions of fixtures with
respect to structural members, ducts pipes, other installations and ceiling
panels/tiles, where required. Certain fixtures are shown in provisional positions,
pending preparation of final equipment layout drawings. Such fixtures are to be
located in coordination with final equipment layout so that illumination is as intended
by the design.
1.5 EQUIPMENT DATA: submit data for approval including, but not limited to, the
followings:
C. Photometric data for lighting calculations including polar light distribution curves,
coefficient of utilization, glare classification, efficiency, depreciation factors etc.
D. Wiring details, circuit and panel board references, special lighting control
arrangements etc.
E. Log sheets submittals, shop drawings, method of statements, and approvals shall be
submitted by the contractor.
1.7 SAMPLES: submit fully equipped sample of each fixture type, modified if
required, together with color and texture samples of each fixture.
A. Fluorescent Lamps: Quantity equal to 3 percent of amount of each type installed, but
not less than six unit of each type.
C. High Intensity Discharge Lamps: Quantity equal to 5 percent of amount of each type
installed, but not less than three unit of each type.
E. Lighting Control Gear (any type): Quantity equal to 2 percent of amount of each
type installed, but not less than 2 unit of each type.
1.9 WARRANTY
A. General Warranty: The special warranty specified in this Article shall not deprive the
Owner of other rights the Owner may have under other provisions of the Contract
Documents and shall be in addition to, and run concurrent with, other warranties
made by the Contractor under requirements of the Contract Documents.
C. SHEET STEEL HOUSINGS: to be not less than 0.6 mm thick, and thicker when
required by the Specification or the Standards.
M. WIRING INSIDE FIXTURES: to be not less than 1.5 mm2, and insulated for 240 V
VOLUME II Part 3 Page No. 5 of 20
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16575: General Lighting Requirements
application. All wiring inside light fixture and wiring used for connection must be
rated to 105 Deg.C temperature.
N. HINGES: fixtures with visible frames and hinged diffusers are to have concealed
hinges and catches, and stainless steel retaining clips. Other alternative equally
durable products may be submitted for approval.
E. BALLAST PROTECTION: Each ballast is to have one-time external fuse and fuse
holder rated in accordance with manufacturers instructions. Electronic ballasts are to
have built-in overload and short circuit protection.
F. BALLAST TYPE (except for clod cathode): electronic or electronic high frequency
dimmable type, as stated in fixture description and as shown on the drawings, power
VOLUME II Part 3 Page No. 6 of 20
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16575: General Lighting Requirements
H. CAPACITORS: to IEC 566, having snap-type connectors and fastening, bolt type
M8, for fixing to fixture.
I. STARTERS, if required, are to comply with IEC 155, and are to be selected in
conjunction with respective ballast and lamp.
A. TYPE: fixture are to be complete units including integral ballasts (and igniters for
HPS lamps where indicated) and lamps of required number and type, and are to have
lighting distribution characteristics equivalent to model and manufacturer indicated in
the fixture description.
A. General: Comply with relevant IEC standards. Unless otherwise indicated, features
include the following:
2.2. LAMPS
A. Lamps are not limited to the following; special lamps shall be subject to
lighting fixture manufacturer recommendations and supervising consultant approval.
E. Lamps are to be type PLC as manufactured by Osram, Philips or other equal and
approved, with warm color impression.
VOLUME II Part 3 Page No. 8 of 20
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16575: General Lighting Requirements
3.1. INSTALLATION
B. FIXTURE SUPPORT: provide fixture and/or fixture outlet boxes with hangers,
brackets and flanged bolted fittings, as necessary, to support weight of fixture.
Submit details of hangers etc. and method of fastening for approval. Rigidly secure
fixture mounted on outlet boxes to fixture studs. Install hooks or extension pieces,
when required, for proper installation. Provide one point of support in addition to
the outlet box fixture stud for individually mounted fixtures longer than 600 mm.
C. STEM HANGERS: provide two stem hangers for individually mounted pendant
fixtures. Stems are to have suspension aligners and are to be suitable length for
suspending fixtures at required height.
G. COVER PLATES: install cover plates over fixture outlet box or opening in ceiling
VOLUME II Part 3 Page No. 9 of 20
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16575: General Lighting Requirements
K. TIGHTNESS: ensure that enclosed fixtures are reasonably insect/ dust tight when
installed, and completely weather-proof for installations subject to weather conditions.
D. ELECTRICAL DATA: measure power factor, current and voltage at start for
installations with discharge lamps.
Certain manufacturers lighting units are specified to be supplied an installed with the
intention that the shape, finish, and illumination of these units shall match each other
and match the overall aesthetic concept. No deviation from these specified
requirements will be allowed unless otherwise specifically approved by the Engineer.
If so approved, the Contractor shall submit alternative luminaries having equivalent
architectural and technical feature. The Contractor shall provide all the information as
directed by the Engineer to prove the equivalency of the proposed alternative
luminaries.
Provide standard bi- pin fluorescent tube lamp, white 4000k unless otherwise
indicated.
Provide PL, PL-C, 2D or other compact fluorescent lamp white 3500K unless
otherwise indicated.
VOLUME II Part 3 Page No. 10 of 20
DEWAN Building - UAQ Electrical Specifications
Block 1, Sector 8 Plot 6, Al Khor 1, UAE Section 16575: General Lighting Requirements
- End of Section -