Professional Documents
Culture Documents
TH1
~21d National Research Comeil national
no. 910
cop 2
I$ Council Canada de recherches Canada
E3Llb~.
by RLD. Cane
Published in
ASHRAE Journal
VoL 21, No. 9, September 1979
p. 60.63
SOMMAIRE,
- -
- -
- -
-
L
REQUIREMENTS OF RESIDENTIAL AIR SOURCE HEAT PUMPS
R.L.D. Cane*
ABSTRACT
The bin method outlined in the ASHRAE Handbook (Systems 1976 - Chapter
43) overestimates the amount of purchased heating energy needed in
reasonably well insulated dwellings because it erroneously assumes that
purchased heat is needed whenever the outside temperature is below 18.3OC
(6SF). The "modified" bin method presented here treats internal and
solar heat gains separately from heat loss and thereby determines the
"break even" temperature below which the heating system needs to operate
This will automatically lead to elimination of the bin hours that occur
in the non-heating months of the year.
+ . . . . . . . . . . . . . . l o ( At,) -1
.(Tindoor-Tmean (i) 1
The SHLRF applies to all above-grade portions of walls including doors
W
and foundation. For below-grade portions of walls and the basement
floor the SHLRF is assumed equal to 1. The seasonal heat loss reduction
factors for walls, windows and ceilings are shown in Fig. 2.
The final equation for the adjusted heat loss rate is:
..... + Hfloor -1 + H
cei1ing
*SHLRF
c
+ H
window
1
In the previous section, the SHLRF for windows was set equal to 1
for the purpose of calculating the total heat loss rate. In this
s e c t i o n , t h e s o l a r h e a t g a i n w i l l be c a l c u l a t e d s e p a r a t e l y .
--
"g a i n
S
a l l wiidows ( gain
S
A window 1
j
j
Before the solar and internal gains can be incorporated into a bin
analysis, the length of the heating season must be determined. As a first
step, the months of June, July and August can be excluded. The remaining
months can then be used to calculate the building break even temperature
as follows: L&P--- = kA
TBE = T
indoor
H =
gain [Hgains + (HgainI) en] - ( 7 3 0 an)-'
The calculated value for the TBE can then be compared with the mean
monthly temperatures for a locale. If the number of months with a mean
monthly temperature less than the T equals the assumed value for n, the
BE
value for H is correct. Otherwise, the value for n is changed and a
gain
new value for H is calculated.
gain
Solar heat gains through windows and the internal heat gains remain
to be considered. For this example the useful solar heat gain during the
heating season (Col. 4) is 2230 kW-h. Recall that the internal heat gain
(occupancy and electricity consumed within the heated space) was
calculated to be 925 kW*h/month.
For the Ottawa area, the months of June, July and August are non-
heating months. The total extraneous heat gain (assumed to be constant
over the entire heating season) can be calculated using equation (5).
H
gain
=1.6 kW -
= (2230 kW*h + 925 kW*h/month x 9 months) x (730 hour/month x 9 months)-'
7,,
21.1 -
' b $ ~ d .i'.71*1
7
- 7 -
C, ec;k. +U L f i L n L (W + 9.& (L5.f
+d ,Lwu-L rrl
ww
*
a c t
- h p k
b5'~).
.- .
The next step is fa,compare the new method with the procedure
\
Conclusions
The proposed bin method using SHLRFs and a separate accounting for
solar and internal gains provides an accurate estimate of heat loss and
hence heat pump energy consumption in well insulated residential
construction.
Acknowledeement
2 2
A
window
- n e t a r e a o f window j (m or ft )
j
- design h e a t l o s s r a t e f o r c e i l i n g (kW)
H
gain
- t o t a l monthly i n t e r n a l h e a t gain ( e l e c t r i c a l and occupancy)
I
(kW0h/month)
2
H - u s e f u l s o l a r h e a t gain f o r window j (kW-h/m )
gain
S
j
H
gain
- average h e a t gain ( i n t e r n a l and s o l a r ) assumed c o n s t a n t (kW)
- design h e a t l o s s r a t e by i n f i l t r a t i o n (kW)
n - l e n g t h of h e a t i n g season (months)
4, (i) - a d j u s t e d h e a t l o s s r a t e , b i n i (kW)
SHLRFc - seasonal h e a t l o s s r e d u c t i o n f a c t o r f o r c e i l i n g
SHLRFI - seasonal h e a t l o s s r e d u c t i o n f a c t o r f o r i n f i l t r a t i o n
SHLRF
W
- seasonal h e a t l o s s r e d u c t i o n f a c t o r f o r wall
- s o l a r a b s o r p t i v i t y of s u r f a c e
References
1. G.P. Mitalas. Net Annual Heat Loss Factor Method for Estimating Heat
Requirements of Buildings. Nat. Res. Council of Canada, Div. Bldg. Res.
Bldg. Res. Note 117, 1976.
3. G.T. Tamura and A.G. Wilson. Air Leakage and Pressure Measurements of
Two Occupied Houses. ~ S H ~ AJournal,
E Vol. 5, No. 12, 1963.
8. C.E. Bullock and W.R. Reedy. Heat Pump Cyclic Performance and Its
Influence on Seasonal Operation. Procs. 3rd Annual Heat Pump
Technology Conference. April 10-11, 1978, Oklahoma State Univ.,
Stillwater, Oklahoma.
E
1.9
1.2
I n s u l . Door
Plus Storm
"
5.8
(Total)
O.gl [ 0.96(0.61)
0.84(0.39)
5.3
Lnur
v*+*L~
i % ~
jy
L~,,.,,
- =I79
'
51.k
$v~.8
-
(0.75 a. c / h r ) - (0.3 a . c / h r ) r
y*.
T o t a l h e a t loss
r a t e , W/*C
2
rn 2 \
I
I Basement slab*** 52.0 nil 5 . 4 W/m 1.0 5.4 W/m 1 58
Basement w a l l f * * 2~79- \I, - I 0.95
(below-grade) 62.3 R1.8 10.75 IT 1. O 10.75 I'
'3 2 3 0
% -
.q
s3
p ~ a p w . 4b.3)
1
ht&% & X I 1 4 1
$
.c-J- @
,
!A '3.L"
f < (;.. 1
.J-F
TABLE 2
MODIFIED BIN METHOD
k,!
Energy Heating
Adjusted Below Ave . Energy
Outdoor Heat Grade Building Ave . Power Consumed
Consumed
by
Energy
Temp. Loss Supp 1i e d
Number Heat Heat Heating Heat Pump Input t o by
Range, of ( 6 L / ~ t D xY d ~LOSS,
~ Gain, Required, Capacity, Heat Pump, Resistance by
Heat Pump, Heaters, System,
O F
Hours* k~ kW kW kW kW kW kW*h kW*h kW-h
65-69 215 0.20 hi 0.0 12.6 4.2 0 0 0
60-64 293 0.53 0.0 11.7 4.0 0 0 0
55-59 398 0.87 0.22 10.8 3.8 31 0 87
50-54 475 1.20 0.55 9.9 3.7 98 0 261
45-49 491 1.53 0.88 9.1 3.4 161 0 432
40-44 554 1.87 1.22 8.2 3.3 272 0 676
35- 39 668 2.20 1.55 7.3 3.1 440 0 1035
30- 34- _ 728 - 2.53
1.88 6.6 3.0 622 0 1369
,Z-29 _ - 5SIj 2.7, , 0,25 1.60 2.22 6.0 2.9 - 575 D - - 1190
20-24 46 7 3.20 2.55 5.6 2.8 595 0 1191
15- 19 383 3.53 2.88 5.2 2.7 573 0 1103
10-14 348 3.87 3.22 4.8 2.6 607 0 1120
5-9 2 75 4.20 3.55 4.3 2.6 590 0 976
0-4 210 4.53 3.88 3.9 2.5 522 0 815
-5 - -1 145 4.87 4.22 3.3 2.4 348 133 6 12
-10 - -6 83 5.20 4.55 2.7 2.3 191 153 378
-15 - -11 41 5.53 4.88 2.3 2.1 86 106 200
-20 - -16 15 5.87 5.22 2.0 1.9 28 48 78
Y \ 5739 440 11523
6325
2.87+ '9s - 1.10 2 2 ;r
2 2 2 , 5 3 ( 0 = 1\90 k v L Heating Energy S u p p l i e d by System
J
55 Loku i> 2,l--f- SPF = = 1.9
-
\iqo
b
\, ,1.9 kd =r 575 k'+JL Energy Consumed+ Energy Consumed
by Heat Pump by R e s i s t a n c e H e a t e r s
*Months o f J u n e , J u l y
and August excluded
k
-
NO; ,&dU'L-
A& +-*
4I 1
TABLE 3
I
ASHRAE B I N METHOD
n
1292 ~3%;
+,o~&!3'?=
5 5.63
H e a t i n g Energy S u p p l i e d by System 2+4
5.03n2to = b5L kwt* SPF = = 2.2
- 3.9
h,?. r&?'o - gJqkuh
%'- 1 0 5 b - S I 9 =231 kvk
Energy Consumed + Energy Consumed
3.9lco~= 2.5 by Heat Pump by R e s i s t a n c e H e a t e r s
~ . 5 ~ 2 1=, 3525 kwh 1322k
Energy Saving o v e r R e s i s t a n c e Heating = 11116 kW-h
* A l l 12 months i n c l u d e d
Z
This publication is one of a s e r i e s of r e p o r t s produced by the
Division of Building Research, National R e s e a r c h Council of
Canada. No abridgement of thie r e p o r t m a y be published with-
out the written authority of the Division. E x t r a c t s m a y b e pub -
lished f o r purposes of review only.
Copies of thie and other publications of the Division may b e ob-
tained by mailing the appropriate remittance (a Bank. E x p r e e s ,
o r PostOffice Money Order, o r acheque, made payable to the
Receiver General of Canada, c r e d i t NRC) to the Publications
Section, Division of Building Research, National R e s e a r c h
Council of Canada, Ottawa. K1A OR6. Stamps a r e not accept-
able.
A l i s t of the publications of DBRJNRC i e available, on r e q u e s t ,
f r o m the Publications Section of the Division.