You are on page 1of 7

1

Travelling Wave Based Fault Location for Teed


Circuits
Cansn Y. Evrenosoglu, Student Member, IEEE, and Ali Abur, Fellow, IEEE

Abstract This paper describes a fault location algorithm for order to determine the faulted region prior to fault location
three terminal lines using wavelet transform of the fault initiated estimation. A single ended fault location method is proposed
transients. The results presented in [1] are extended to the case of in [9] for two and three terminal lines where the voltages
three terminal configuration and a new single ended procedure is
developed for teed circuits. The algorithm gives accurate results and currents are estimated by solving the travelling wave
for the case of three terminal lines including series compensated equation and then different criteria are used to determine the
branch, mutual coupled line section and different values of fault location. More recently, in [1], the use of the discrete
fault resistances. The performance of the algorithm is tested on wavelet transform (DWT) of the modal components of the
different scenarios by using ATP/EMTP program and MATLAB fault initiated travelling waves is proposed in order to estimate
Wavelet Toolbox.
the location of the fault.
Index Terms Fault Location, Wavelet Transform, Electro-
magnetic Transients Simulations, Teed Circuits, Series Compen- L AT L BT
sation, Mutual Coupled Lines, Frequency Dependent Line Model
T
A B
I. I NTRODUCTION
L CT

D UE to the superimposed reflections of the fault signal


from the T-node and the fault point, fault location in
teed circuits (Figure 1) presents unique challenges. In addition
Fig. 1.
C

Three Terminal Power Transmission System

to the impedance based fault location techniques, there are


various types of fault location methods proposed for teed The presence of parallel transmission lines with mutually
circuits using either phasor based or travelling wave based coupled line sections makes the fault location problem more
models. difficult in transmission lines. Two different algorithms for
The post fault differential currents from each terminal is different types of faults are developed in [10] and [11] by
used in [2] in order to locate the fault in multi terminal applying the Z-transform to the loop equations and using
transmission lines. A fault location technique using the pre- Newton Raphson method to solve the nonlinear equation. One
fault load flow for phase alignment is described in [3] by ended data with the simplified line model is used by neglecting
utilizing the multi end phasor measurements in order to the shunt capacitance. Another phasor based single ended fault
determine the fault location. The post fault synchronized location technique is proposed in [12] where post and pre fault
phasor measurements are used to solve the system differential data are used with zero sequence current from a healthy line in
equations for fault location in multi terminal lines in [4]. The order to solve the algebraic equation. A similar approach to [6]
use of negative sequence multi-ended measurements for fault is used in [13] by introducing the synchronized measurements.
location in three terminal lines is proposed in [5]. Recently a A complex and nonlinear equation is derived from the nodal
new fault locator for three terminal lines is described in [6] equations and solved by Newton Raphson iterative scheme in
using phasor measurement units in order to solve the travelling [14]. The technique is validated for a parallel transmission line
wave differential equations. with a teed circuit, using a lumped line model and for single
Travelling wave based fault location for transmission lines phase to ground faults only.
is initially formulated in [7] by defining a discriminator that Another source of difficulty in fault location problem is
combines the wave characteristics and its first derivative. A the presence of series capacitors which are widely used in
travelling wave technique for teed circuits is introduced in power systems in order to improve the transfer capability and
[8] considering the cross correlation between the forward and increase the stability margins. Metal Oxide Varistor (MOV) is
backward travelling waves and a polarity change criterion in the most popular protection device which is connected across
the capacitor. The existing fault location techniques have to
Partial support provided by the NSF grant ESC-9821090 and the Electric be adapted in order to cope with the complexity introduced
Power and Power Electronics Institute of Texas A&M University are gratefully
acknowledged. by the nonlinear V-I characteristics of the MOV. Different
C.Y. Evrenosoglu is a graduate student in the Department of Electrical solutions including the use of Artificial Neural Networks [15],
Engineering, Texas A&M University, College Station, TX, 77843, USA (e- single ended [16] and multi-ended [17] measurements have
mail: yaman@ee.tamu.edu).
A. Abur is with the Department of Electrical Engineering, Texas A&M been proposed.
University, College Station, TX, 77843, USA (e-mail: abur@ee.tamu.edu). In this paper, a travelling wave based fault location tech-
2

Middle C
nique which is developed earlier in [1] will be extended A F1 F2 T

to the three terminal circuits with mutually coupled line


segments and MOV protected series capacitors. Preliminary
results [18], [19] indicate that this approach can overcome the t 11
B

challenges presented by such topologies. The performance of t 12


t 21
the proposed fault location algorithm is tested by introducing
t 22
random errors representing the quantization error introduced
by A/D converters, to the simulated signals and using various
fault resistances. t 23

II. FAULT L OCATION P ROCEDURE Fig. 2. Lattice diagram [22] for faults at line segment A-T
The following assumptions are made in developing the fault
location procedure:
Three terminal measurements are available
of the aerial mode W T C 2 is due to the backward travelling
The measurements need not be synchronized
wave arriving at bus A at time t11 . The second peak is due
An open communication channel is available between the
to the reflected backward travelling wave arriving at bus A at
terminals time t12 . The fault location is given by [1]:
There is no injection or load at the tee point.

The procedure consists of three stages. In the first stage, v t


x = (1)
the modal transformation is applied to the measured voltage 2
signals. Clarke [20] transformation matrix is used as: t = t12 t11

1 1 1
where v is the aerial mode propagation velocity in scale-1.
V1 Va
V2 = 1 1
2 2
1
Vb Now consider a fault close to the T-node, shown as F2 in
2 Figure 2. The backward travelling wave arrives at bus A at
V3 3 3 3 Vc
0
2
2

time t21 while the forward travelling wave arrives at bus A at
where Va , Vb and Vc are phase voltages, V1 is ground mode time t22 . The fault location can then be determined as in [1]:
voltage and V2 , V3 are aerial mode voltages. In the second
stage, the discrete wavelet transform (DW T ) is applied to t v
0

the modal voltages and the squares of the wavelet transform x = (2)
2
coefficients (W T C 2 ) are obtained in order to determine the 0 2L
instant when the energy of the signal reaches its maximum t = t
v
value. Daubechies-4 [21] mother wavelet is used for wavelet t = t22 t21
transformation. Then in the final stage, ground mode W T C 2 s
in scale-1 are observed in order to determine the fault type where L is the total length of the line segment A T and v is
(whether the fault is grounded or not) and aerial mode W T C 2 s the aerial mode propagation velocity in scale-1. Fault location
in scale-1 are processed based on the Bewley lattice diagram can also be determined by using the third peak of the aerial
[22] of the fault initiated travelling waves in order to determine mode W T C 2 which arrives at bus A at time t23 . The following
the fault location. In the following sections the last stage of equation is used for the calculations [18]:
the fault location procedure is described in detail for various
possible cases. v t
x= (3)
2
A. Fault Location in Teed Circuit t = t23 t21

Fault location in teed circuits involves two basic steps. Nevertheless, as the fault location moves closer to the
In the first step the faulted line segment is identified and T-node, the second peak gradually decreases, coming very
in the second stage the fault location along the faulted line close to the first peak and eventually the two becoming
segment is determined. The aerial mode W T C 2 s are compared indistinguishable. The difficulty of identifying the second peak
at each bus in order to identify the faulted line segment. when the fault is in the second half, can be overcome by using
The magnitude of the first peak of the aerial mode W T C 2 s (3) instead of using (2) to calculate the fault location.
obtained at the sending end of the faulted line segment will The faulted half of the line is determined by comparing
be significantly higher than those obtained at the sending ends the time difference t0 , between the arrival time instants of
of the other non-faulted line segments. Once the faulted line the aerial mode and the ground mode W T C 2 s with the time
segment is known, the location of the fault is determined difference, tm , obtained for a fault located right at the middle
by using a modified version of the single ended algorithm of the line.
proposed in [1] as described below. Since the ungrounded and symmetric faults do not produce
A grounded fault is assumed to occur at the first half of the remote end reflections, (1) will be used in order to locate the
line segment A T , at point F1 in Figure 2. The first peak fault independent of the half in which the fault occurs.
3

B. Fault Location in a Teed Circuit with MOV Protected Series ground mode signals are then calculated using the wavelet
Capacitor transform. The W T C 2 s of the aerial mode voltages in scale-
The most popular and widely used device for protecting 1 for both cases with and without the MOV are given in
series capacitor against high voltage during faults is the Metal Figures 6 and 7. It is observed that both the shape and the
Oxide Varistor (MOV), which is installed directly across the peak arrival instants of the wavelet transform coefficients of
series capacitor as shown in Figure 3, and has a nonlinear I-V the aerial mode voltages for each case, are identical for a
characteristics: certain period after the fault. This period extends well beyond
 q the needed duration for the successful application of the fault
V location procedure described in the previous section.
i=I (4)
Vref 2
WTC of Aerial Mode Voltage at Bus A w/o MOV

The nonlinear characteristics given in (4) allows no current 18

to flow through the MOV under normal operating conditions. 16

14

In case of fault, when the voltage across the capacitor reaches 12

2 7
WTC *10
10

the threshold Vref , MOV clamps the voltage and starts to 8

conduct. The voltage recorded at the sending end will have a 6

different waveform because of this clamping action compared 2

with the waveform obtained without using the MOV. 20.3 20.4 20.5 20.6
time [msec]
20.7 20.8

C Fig. 6. W T C 2 of the aerial mode voltage, without MOV


A

T 2
WTC of Aerial Mode Voltage at Bus A with MOV

MOV B
18

16

14

12

2 7
Fig. 3. Teed Circuit with MOV protected series capacitor WTC *10 10

Assume that a single phase to ground fault occurs on the 4

line segment A T and voltage transients are recorded at the 2

0
20.3 20.4 20.5 20.6 20.7 20.8

sending end of the line segments A-T, B-T and C-T in Figure time [msec]

3. These signals are not synchronized. The voltage signals of Fig. 7. W T C 2 of the aerial mode voltage, with MOV
the faulted phase are presented in Figures 4 and 5 for the
cases with or without the MOV in order to show the effect
of the varistor. Note that in Figure 5, after the fault occurs
C. Fault Location in a Teed Circuit with Mutually Coupled
the phase voltage is clamped between 200 kV thanks to the
Line Section
MOV protection.
A partially coupled teed circuit is studied as shown in Figure
Faulted Phase Voltage at Bus A w/o MOV
1000
8. The detailed interpretation of the lattice diagram in [19]
500 shows that the end point of the mutually coupled section,
M , behaves like a discontinuity where multiple reflections
Voltage [kV]

500
occur during a fault. Because of this complexity introduced by
the coupled section the following situations must be studied
1000

depending on where the fault occurs:


Fault is in the coupled section, A M
1500
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
time [sec]

In the first half of the coupled section


Fig. 4. Faulted phase voltage, without MOV
In the second half of the coupled section
Fault is beyond the coupled section, M T
Faulted Phase Voltage at Bus A with MOV
400

300

A C
200

100
M T
Voltage [kV]

100
B
200

300
L
400
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
time [sec]
Fig. 8. Teed Circuit with mutually coupled line section
Fig. 5. Faulted phase voltage, with MOV
In order to specify the faulted section (coupled or un-
The simulated voltage signals at each bus are subsequently coupled), the difference between the arrival time instants of
transformed into the modal domain. Discrete wavelet trans- the W T C 2 s peaks of the aerial mode and the ground mode
form coefficients (WTC) of different scales for the aerial and voltages are calculated. Then the calculated value is compared
4

2
WTC of Aerial Mode Voltage at Bus A

with the time difference obtained for a fault right at the end
5

of the coupled section.


4
In case a grounded fault occurs in the coupled line section,

WTC2*105
the algorithm described in the previous section will be valid, 3

and the equations (1) and (3) will be used in order to locate 2

the fault. 1

A F C 0
21 21.2 21.4 21.6 21.8 22 22.2 22.4 22.6
time [msec]

B
Fig. 11. W T C 2 of the aerial mode voltage at bus A, XF = 160 mi

2
WTC of Aerial Mode Voltage at Bus A

t1

5
WTC *10
3
t2

2
2

0
21 21.2 21.4 21.6 21.8 22 22.2 22.4 22.6 22.8
time [msec]
tj

Fig. 12. W T C 2 of the aerial mode voltage at bus A, XF = 180 mi


Fig. 9. Lattice diagram for a fault in the uncoupled section

When the fault is in the uncoupled section as shown in where L is the total line length. As a result, either one of the
Figure 9, the first peak of the aerial mode W T C 2 which is equations (5) or (6) can be used in order to locate the fault.
due to the backward travelling wave, arrives at bus A at time Alternatively, their average value can be used to minimize any
t1 and the jth peak which is due to the backward travelling estimation errors.
wave that is first reflected from bus A, will arrive at bus A
at time tj . It is observed that, the W T C 2 peak (jth) which D. Fault Location in a Teed Circuit Using Synchronized
has the largest magnitude after the first two W T C 2 peaks Measurements At Three Terminals
is due to the backward travelling wave which is reflected
Now assume that the measurements are synchronized at
from the fault point. As can be seen from the Figures 10 to
each bus and voltage transients are recorded at buses A, B
12, the arrival time of the W T C 2 peak due to the reflected
and C as shown in Figure 1. After the faulted line segment is
backward travelling wave increases (from fifth to tenth) as the
identified by comparing the W T C 2 s of each bus as described
fault location approaches the T node. The fault location can
above, the double ended fault location algorithm described in
be calculated by the following equation:
[1] is used to locate the fault. The aerial mode voltage W T C 2 s
v t obtained at the sending ends of the faulted line segment and
x= , t = tj t1 (5)
2 one of the un-faulted line segments are used in this algorithm
as follows:
WTC2 of Aerial Mode Voltage at Bus A
LT v t
9
x= (7)
8 2
7
where t is the time difference between the arrival times of the
5

6
WTC *10

aerial mode W T C 2 s of the voltages recorded at the sending


2

4
ends of the faulted line segment and the chosen un-faulted
line segment. LT is the total line length of the faulted line
3

1
20.6 20.8 21 21.2 21.4 21.6 21.8
segment and the chosen un-faulted line segment. Assume that
time [msec]
line segment C T is the faulted line segment and ta , tb and
Fig. 10. W T C 2 of the aerial mode voltage at bus A, XF = 110 mi tc are the arrival time instants of the initial peaks of the aerial
mode voltage W T C 2 s at the buses A,B and C respectively.
Provided that the fault location is not too close to the T- Then the fault location will be calculated as follows:
node, an alternative and simpler procedure can be used as
follows [1]: LC + Lj v (tj tC )
x= (8)
2
t v
0 where j = A (or B) as the chosen un-faulted line segment.
x = (6)
2
0 2L III. S IMULATION R ESULTS
t = t All simulations are carried out by using ATP/EMTP pro-
v
t = t2 t1 gram and MATLAB with a sampling time interval of 3 sec.
5

The fault occurrence time is chosen as 0.02 sec. The tower yields 0.006 msec which is less than the one obtained for a
configuration of 220 kV transmission line is given in [18] and fault at the middle of the line. The arrival times of the first
[19]. The frequency dependent transmission line model is used two aerial mode W T C 2 peaks at bus A are t1 = 20.283
throughout the simulations. All the line segments are assumed msec and t2 = 20.817 msec yielding a time difference of
to be fully transposed. The aerial mode propagation velocity t = 0.534 msec. The fault location can thus be determined
is calculated as 1.85882 105 mi/sec in scale-1 corresponding by using Equation (1) as:
to the frequency interval of 75 kHz - 150 kHz. The studied
systems are simulated under various types of faults along 1.85882 105 0.534 103
different line segments. Line segment lengths are chosen x= = 49.63 mi
2
as LAT = 200 miles, LBT = 180 miles and LCT = 170
Note that the arrival times of the peaks of aerial mode
miles. Simulation results for one phase to ground fault in line
voltage W T C 2 s are same with those obtained in the previous
segment A T with a very small fault resistance (1 m) are
section implying that MOV has no effect on the proposed fault
presented.
location algorithm.

A. Fault Location in a Teed Circuit C. Fault Location in a Teed Circuit with Mutually Coupled
It is assumed that a single line to ground fault occurs at 50 Line Section
miles away from bus A. After the recorded transient voltages In this case, the system shown in Figure 8 is studied where
are transformed into modal domain and W T C 2 s of the aerial the length of the coupled section is 80 miles. It is assumed that
mode is obtained, the faulted line segment is identified by the fault occurs within the coupled section A T , 50 miles
comparing the magnitudes of the W T C 2 s of the aerial mode away from bus A. The fault is declared to be in the region
voltages at each bus. The W T C 2 s at bus A is shown in close to the end point M of the coupled section by using the
Figure 13, while the coefficients at other buses are insignificant arrival time differences between the initial peaks of aerial and
indicating that the fault is in line segment A T , the ground mode W T C 2 s. The first peak arrives at bus A at
WTC2 of Aerial Mode Voltage at Bus A
time t1 = 20.283 msec and the third peak arrives at bus A at
2.5
time t3 = 20.829 msec. The fault location is determined by
2
using Equation (3) as:
WTC2*108

1.5

1 1.85882 105 0.546 103


x= = 50.74 mi
0.5 2
20.3 20.4 20.5 20.6
time [msec]
20.7 20.8 Next, the fault is assumed to be within the second half of
the uncoupled section, 180 miles away from bus A as shown
Fig. 13. W T C 2 of the aerial mode voltage at bus A in Figure 9. The first peak of the aerial mode W T C 2 s arrives
at bus A at t1 = 20.985 msec while the second one arrives
After the faulted line segment is identified as A T , the at t2 = 21.20 msec. The aerial mode W T C 2 peak which has
faulted half of the line is determined by comparing t0 and the largest magnitude after the first two peaks arrive at bus
tm . In this example t0 = 0.0059 msec where tm = A at t10 = 22.935 msec as shown in Figure 12. The fault
0.024 msec indicating that the fault is located at the first half location is determined by using Equation (5):
of the line A T . The arrival times of the first and second
peaks of the aerial mode W T C 2 at bus A are t1 = 20.283 1.85882 105 1.95 103
msec and t2 = 20.817 msec respectively. Equation (1) is used = 181.23 mi
2
to calculate the fault location as follows:
Alternatively, one can use Equation (6), which yields:

1.85882 105 0.534 103


x= = 49.63 mi 2 200 0.215 103 1.85882 105
2 = 180.02 mi (9)
2
B. Fault Location in a Teed Circuit with MOV Protected Series The differences between the two results are attributed to the
Capacitor sampling errors and are not considered significant.
The configuration shown in Figure 3 is simulated. A series
compensation rate of 80 % is used for the line A T . The D. Fault Location in a Teed Circuit Using Synchronized
MOV parameters I, q and Vref of Equation (4) are chosen as Measurements At Three Terminals
200 A, 23 and 70 kV respectively. The faulted line segment is The same examples in the previous sections are worked out
identified by comparing the aerial mode W T C 2 s recorded at in order to be able to illustrate the simplicity of the algorithm
each bus. The faulted section of the line segment for a phase to with a fully synchronized measurement system.
ground fault located at 50 miles away from bus A is estimated Assume that the fault occurs 50 miles away from bus A
by calculating the difference between the arrival times of the in the system shown in Figure 3. The arrival times of the
peaks for the aerial and ground mode W T C 2 s at bus A. This initial peaks of the aerial mode W T C 2 s at bus A, B and C
6

2
WTC of Aerial Mode Voltage at Bus A w/ Random Error

are tA = 20.283 msec, tB = 21.783 msec and tC = 21.74 9

msec respectively. The fault location is simply determined by 7

Equation (7): 6

WTC2 * 104
5

5
(200 + 170) 1.85882 10 1.457 10 3 2

x = 1

2 0
20.6 20.8 21 21.2 21.4 21.6 21.8

x = 49.59 mi time [sec]

Fig. 14. W T C 2 of the aerial mode voltage at bus A, with Random Error
where the recorded transients at the sending terminals of the
faulted line segment, namely bus A and bus C are used for
the calculations.
It is observed that the random error has no effect on the peak
Next, the fault is assumed to occur within the coupled
arrival instants of the W T C 2 s. Also the magnitudes of the co-
section 50 miles away from bus A as shown in Figure 8. The
efficients due to the random errors are insignificant compared
arrival times of the initial peaks of the aerial mode W T C 2 s
to the coefficients which are due to the fault initiated transients
at bus A, B and C are tA = 20.283 msec, tB = 21.789 msec
as shown in Figure 14. The choice of 12 as the number of
and tC = 21.735 msec respectively. The fault location is then
bits of the A/D converter is rather conservative. Availability of
determined by Equation (7):
higher resolution converters will certainly decrease the already
insignificant effects of random errors to a minimum.
(200 + 180) 1.85882 105 1.506 103
x =
2
x = 50.03 mi IV. C ONCLUSIONS
This paper presents a fault location procedure for teed
where the recorded transients at the sending terminals of the
circuits. The procedure is based on processing of travelling
faulted line segment, i.e. bus A and bus B are used for the
waves by wavelet transform in order to extract the arrival
calculations.
times of fault initiated waves reflected from the discontinuities.
The fault location algorithm is shown to be insensitive to
E. The Effect of Fault Resistance the existence of series capacitors, fault resistance, fault type
and any existing mutual coupling between the lines while
All the simulations are repeated by replacing the fault
the accuracy of the algorithm is proportional to the sampling
resistance by Rf = 400 . It is observed that the initial peaks
frequency. Simulation results show good correlation between
of the square of aerial mode wavelet coefficients are smaller
the actual and estimated fault locations for all the studied
than those obtained by using no fault resistance, however
cases.
the shape and peak arrival instants of the waveforms remain
the same. The fault location results obtained with zero fault
resistance, match closely with those obtained by using 400 R EFERENCES
fault resistance. Based on this limited set of experimental
[1] F.H. Magnago and A. Abur, Fault Location Using Wavelets, IEEE
results, it is believed that the algorithm performance will Transactions on Power Delivery, Vol. 13, No. 4, Oct. 1998, pp. 1475-
remain insensitive to variations in the fault resistance. 1480.
[2] T. Nagasawa, M. Abe, N. Otsuzuki, T. Emura, Y. Jikihira and
M. Takeuchi, Development of a New Fault Location Algorithm For Multi-
F. The Effect of Random Error Terminal Two Parallel Transmission Lines, IEEE Transactions on Power
Delivery, Vol. 7, No. 3, July 1992, pp.1516-1532.
The performance of the fault location algorithm is tested by [3] A.A. Girgis, D.G. Hart and W.L. Peterson, A New Fault Location Tecnique
introducing random error to the simulated voltage signals. A For Two and Three Terminal Lines, IEEE Transactions on Power Delivery,
Vol. 7, No. 1, Jan. 1992, pp.98-107.
gaussian noise is generated with zero mean and standard [4] Q. Gong, Y. Chen, C. Zhang and Z. Wang, A Study of the Accurate Fault
deviation which is equal to the 30 % of the quantization Location System for Transmission Line Using Multi-Terminal Signals,
error (0.3 q). The basic formulation of the quantization error IEEE PES Winter Meeting, Vol. 4, Jan. 2000, pp.2533-2538.
[5] D.A. Tziouvaras, J.B. Roberts and G. Benmouyal, New Multi-Ended Fault
introduced by A/D converters is given below [23] : Location Design For Two or Three Terminal Lines, IEE Developments in
Power System Protection, No. 479, 2001, pp.395-398.
[6] Y. Lin, C. Liu, C. Yu, A New Fault Locator for Three Terminal Trans-
q = 2N V (10) mission Lines- Using Two Terminal Synchronized Voltage and Current
Phasors, IEEE Transactions on Power Delivery, Vol. 17, No. 2, April
where N (= 12) is the number of the bits of the A/D converter 2002, pp. 452-459.
and V is chosen as the rms value of the voltage signal in steady [7] H.W. Dommel and J.M. Michels, High Speed Relaying Using Traveling
state. Wave Transient Analysis, IEEE PES Winter Meeting, NY, Jan. 1978.
[8] S. Rajendra and P.G. McLaren, Traveling Wave Tecniques Applied to
All the simulations are repeated by introducing the random the Protection of Teed Circuits:Multi- Phase/Multi-Circuit System, IEEE
error to the simulated voltage signals. The simulation results of Transactions on Power Apparatus and Systems, Vol. PAS-104, No. 12,
the most complicated case because of the multiple reflections Dec. 1985, pp.3351-3557.
[9] A.O. Ibe and B.J. Cory, A Travelling Wave-Based Fault Locator For Two
is presented here where a fault occurs in the uncoupled section, and Three Terminal Networks, IEEE Transactions on Power Systems, Vol.
110 miles away from bus A, as shown in Figure 9. PWRD-1, No. 2, April 1986, pp. 283-288.
7

[10] Z. Qingchao, Z. Yao, S. Wennan, Y. Yixin and W. Zhigang, Fault


Location of Two-Parallel Transmission Line for Non-Earth Fault Using
One-Terminal Data, IEEE Transactions on Power Delivery, Vol. 14, No.
3, July 1999, pp.863-867.
[11] Z. Qingchao and D.W.P. Thomas, Accurate Fault Location Algortihms
for Two-Parallel Transmission Line Using One-End Data, Transmission
and Distribution Conference and Exposition IEEE/PES, Vol. 1, 2001, pp.
527-530.
[12] J. Izykowski and R. Kawecki, Location of Faults in Partially Parallel
Transmission Networks, Power Tech Conference, Sep. 2001, Vol. 3, pp.
6.
[13] C. Chen, C. Liu and J. Jiang, A new Adaptive PMU Based Protection
Scheme for Transposed/Untransposed Parallel Transmission Lines, IEEE
Transactions on Power Delivery, Vol. 17, No. 2, April 2002, pp. 395-404.
[14] S. Kang, S. Lee, Y. Kwon, Y. Kang, A fault Location Algorithm for
Parallel Transmission Line with a Teed Circuit, IEEE PES Summer
Meeting, Vol. 2, 2001, pp. 921-926.
[15] B. Bachmann, D. Novosel, D. Hart, Y. Hu and M.M. Saha, Application
of Artificial Neural Networks for Series Compensated Line Protection,
Intelligent Systems Applications to Power Systems, 1996, pp. 68-73.
[16] M.M. Saha, J. Izykowski, E. Rosolowski and B. Kasztenny, A New
Accurate Fault Locationg Algorithm for Series Compensated Lines, IEEE
Transactions on Power Delivery, Vol. 14, No. 3, July 1999, pp.789-797.
[17] J. Sadeh, N. Hadjsaid, A.M. Ranjbar and R. Feuillet, Accurate Fault
Location Algorithm for Series Compensated Transmission Lines, IEEE
Transactions on Power Delivery, Vol. 15, No. 3, July 2000, pp.1027-1033.
[18] C.Y. Evrenosoglu and A. Abur, Fault Location for Three Terminal Lines
Using Traveling Waves, North American Power Symposium, Oct. 2002.
[19] C.Y. Evrenosoglu and A. Abur, Fault Location for Teed Circuits with
Mutually Coupled Lines and Series Capacitors, Power Tech Conference,
June 2003.
[20] E. Clarke, Circuit Analysis of AC Power Systems, Symmetrical and
Related Components,John Wiley & Sons, NY, 1943
[21] I. Daubechies, Ten Lectures on Wavelets, SIAM, Pennsylvania, 1992
[22] L.V. Bewley, Travelling Waves on Transmission Systems, John Wiley &
Sons, NY, 1951
[23] A.G. Phadke, J.S. Thorp, Computer Relaying for Power Systems, John
Wiley & Sons, NY, 1988

Cansn Y. Evrenosoglu (S00) received his B.S. and M.S. degrees


from Istanbul Teknik Universitesi, Turkey in 1998 and 2001 respec-
tively. He is currently a Ph.D. student at the Department of Electrical
Engineering at Texas A&M University, College Station, Texas.

Ali Abur (F03) received his B.S. degree from Ortadogu Teknik
Universitesi, Turkey in 1979, M.S. and Ph.D. degrees from The Ohio
State University, Columbus, Ohio, in 1981 and 1985 respectively. He
is currently a Professor at the Department of Electrical Engineering
at Texas A&M University, College Station, Texas.

You might also like