ELECTRICAL INSTALLATION

FINAL SUB CIRCUIT POINT WIRING

Supply, wire, install and commission of following items as per


the latest IEE regulations.

The wiring shall be in full rigid PVC conduits with the conduit
system providing a continuous and effective means of protection
for the wiring. The conduit system shall be concealed in the
building fabric and where provided under a roof the conduit shall be
clipped to the roof members.

A. Supply all material and provide final sub circuit point wiring only for
the following outlets with 1 way switch and 3 plate ceiling rose.
Including lamp fitting fixing charges with other materials required to
make complete installation.

Excluding the cost of fitting. Wiring shall be in 1.0mm2 PVC/CU


cables + E as specified and as shown in the electrical drawings.

1 Pendent Lamp

1.1 Ground Floor 62 Nr 1,446.00

1.2 First Floor 65 Nr 1,446.00

1.3 Typical Floors 02nd to 08th 448 Nr 1,446.00

1.4 Roof top (Terrace) 15 Nr 1,446.00

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

A. Supply all material and provide final sub circuit point wiring only for
the following outlets with 1 way switch and connectors. Including
lamp fitting fixing chargers with other materials required to make
complete installation. Excluding the cost of fitting. Wiring shall be in
1.0mm2 PVC/CU cables + E as specified and as shown in the
electrical drawings
1 Wall Lamp

1.1 Ground Floor 05 Nr 1,446.00

1.2 First Floor 88 Nr 1,446.00

1.3 Typical Floors 02nd to 08th 658 Nr 1,446.00

1.4 Roof top (Terrace) 28 Nr 1,446.00

2 Emergency Wall Lamp

Supply all material and provide final sub circuit point wiring only for
the following outlets.
Including connectors , lamp fitting fixing chargers with other
materials required to make complete installation.
Excluding the cost of fitting. Wiring shall be in 1.0mm2 PVC/CU
cables + E as specified and as shown in the electrical drawings.

2.1 1 st floor to 8 th floor 48 Nr 2,250.00

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

A. Supply all material and provide final sub circuit point wiring only for
the following outlets with 1 way switch and connectors. Including
lamp fitting fixing chargers with other materials required to make
complete installation. Excluding the cost of fitting. Wiring shall be in
1.0mm2 PVC/CU cables + E as specified and as shown in the
electrical drawings
1 Recessed or Ceiling Mounted Type Lamp
1.1 Ground Floor 15 Nr 1,446.00
1.2 First Floor 31 Nr 1,446.00
1.3 Typical Floors 02nd to 08 th 224 Nr 1,446.00

2 Spot Lamp
2.1 Ground Floor 04 Nr 1,446.00
2.2 First Floor 04 Nr 1,446.00
3 Garden Lamp (External)
Supply, install , terminate and glanding 4 Core, 3C and 2C, 2.5mm2
CU/XLPE/SWA/PVC under ground Cables as specified and as
shown in electrical drawings for the external garden lighting system.
Including cost of cable trench excavating ,cable tiels , warning tape,
sand & any other items required to make complete installation.
Excluding cost of garden lamp fittings.
3.1 Ground Level 12 Nr 15,643.00

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

A. Supply all material and provide final sub circuit point wiring only for
the following outlets with 2 way / intermediate switch and
connectors. Including lamp fitting fixing charges with other materials
required to make complete installation. Excluding the cost of fitting
wiring shall be in 1.0mm2 PVC / Cu cables + E as specified and as
shown in the electrical drawings.
1 Wall Lamp

1.1 Ground Floor 02 Nr 1,446.00

1.2 First Floor 08 Nr 1,446.00

1.3 Typical Floors 02nd to 08 th 56 Nr 1,446.00

1.4 Roof top (Terrace) 02 Nr 1,446.00

2 Recessed or / Ceiling Mounted Type Lamp


2.1 Ground Floor 02 Nr 1,446.00

2.2 First Floor 03 Nr 1,446.00

2.3 Typical Floors 02nd to 08 th 21 Nr 1,446.00

2.4 Roof top (Terrace) 02 Nr 1,446.00

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

A. 13A Socket Outlets Ring


Supply and install 2.5mm2 PVC cu cable and 2.5 mm2 earth Cu
conductor with all accessories required to make complete
installations and wire 230 volts, 13 Amp. single switch soket outlet in
ring circuit as specified specifications & illustrated in the electrical
drawings. (including switch socket outlet)

i. Ground Floor 17 Nr 3,000.00

ii. First Floor 153 Nr 3,000.00

iii. Typical Floors 02nd to 08 th 1113 Nr 3,000.00

iv. Roof top (Terrace) 04 Nr 3,000.00

B. 15A Socket Outlets Direct


Supply and install 2.5mm2 PVC cu cable and 2.5 mm2 earth Cu
conductor with all accessories required to make complete
installations and wire 230 volts, 15 Amp. single switch soket outlet in
direct circuit as specified specifications & illustrated in the electrical
drawings. (including switch socket outlet)

i. Ground Floor 01 Nr 4,661.00

ii. First Floor 06 Nr 4,661.00


iii. Typical Floors 02nd to 08 th 42 Nr 4,661.00

iv. Roof top (Terrace) 01 Nr 4,661.00

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

A. 20A , DP Swicth with 15 A Socket Outlets for AC

Supply and install 2.5mm2 PVC cu cable and 2.5 mm2 earth Cu
conductor with all accessories required to make complete
installations and wire 230 volts, 20 A, DP swicth with 15 Amp. single
swicth socket outlets for split type Air Conditioners as specified
specifications & illustrated in the electrical drawings (including
20A,DP switch and 15A socket outlet).

i. First Floor 23 Nr 4,913.00

ii. Typical Floors 02nd to 08 th 161 Nr 3,171.00

B. 20A , DP Swicth with 15 A Socket Outlets for Geazers

Supply and install 2.5mm2 PVC cu cable and 2.5 mm2 earth Cu
conductor with all accessories required to make complete
installations and wire 230 volts, 20 A, DP swicth with 15 Amp. single
swicth socket outlets for split type Geazers as specified
specifications & illustrated in the electrical drawings (including
20A,DP switch and 15A socket outlet).
i. First Floor 17 Nr 5,154.00
ii. Typical Floors 02nd to 08 th 119 Nr 2,946.00

To Collection
ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

A. Call Bell and Bell Press Switch

Supply and install 230v call bell, weatherproof bell press switch and
all accessories required to make complete installations as specified
specifications & illustrated in the electrical drawings. (Including
associated wiring works in concealed conduits, call bell,
weatherproof bell press swicth .)

i. First Floor 06 Nr 2,946.00

ii. Typical Floors 02nd to 08 th 42 Nr 1,982.00

B. Shaver Socket Outlets

Supply and install 1mm2 PVC / CU cable with 2.5mm2 earth Cu


conductor and wire for shaver socket outlets as per the
specifications and illustrated in the electrical drawings. Including
shaver Shaver socket outlet and its sunk box with all accessories
required to make complete installations.

i. First Floor 07 Nr 4,286.00

ii. Typical Floors 02nd to 08th 49 Nr 3,964.00

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

A. Cooker Control Unit

Supply and install 4 mm2 PVC / CU cable with 2.5mm2 earth Cu


conductor and wire for 230V, 35 KA Cooker Control Unit (35KA,DP
swicth with neon indicator + 13 A socket outlet + swicth) as per the
specifications and illustrated in the electrical drawings. Including
cooker control unit with all accessories required to make complete
installations.
i. First Floor 05 Nr 11,796.00

ii. Typical Floors 02nd to 08th 35 Nr 7,377.00

B. Ceiling Fan Outlets

Supply and install 1 mm2 PVC/Cu cable and 2.5mm2 earth Cu


conductor and wire, for ceiling fan outlets as per the specifications
and illustrated in the electrical drawings. Including connectors
,hooks ,control swicthes or regulators and other all accessories
required to make complete installation. ( Excluding cost of ceiling fan
fitting ).
i. First Floor 33 Nr 1,971.00

ii. Typical Floors 02nd to 08th 231 Nr 1,757.00

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

A. DISTRIBUTION BOARDS

1 Supply and install following flush mounted type, 02 row, plastic or


powder coated metal distribution boards, shall be consisted flush
metal clad or all insulated fitted with

32A, 4P, Isolator 01 Nos.


32A, 2P, RCCB (30mA) 01 Nos.
10A, SP, MCB 03 Nos.
16A, SP, MCB 02 Nos.
20A, SP, MCB 05 Nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.
1 XA - DB1 (9 way) 08 Nr 11,893.00

2 XB - DB1 (9 way) 08 Nr 11,893.00

3 ZC - DB1 (10 way) 07 Nr 11,893.00

4 ZD - DB1 (9 way) 07 Nr 11,893.00

5 XE - DB1 (9way) 08 Nr 11,893.00

6 1Ca - DB1 (9 way) 1 Nr 11,893.00

7 1Da - DB1 (9 way) 1 Nr 11,893.00

X=1:8
Z=2:8

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

DISTRIBUTION BOARDS (Cont'd)

A. Supply and install following flush mounted type, 02 row, plastic or


powder coated metal distribution boards, shall be consisted flush
metal clad or all insulated fitted with

32A, 3P, Isolator 01 Nos.


32A, 2P, RCCB (30mA) 02 Nos.
10A, SP, MCB 05 Nos.
20A, SP, MCB 05 Nos. and other materials
required to make complete installation according to the
specified specifications and illustrated in the electrical drawings.

1 XA - DB2 (9 way) 08 Nr 14,464.00

2 XB - DB2 (9 way) 08 Nr 14,464.00

3 ZC - DB2 (10 way) 07 Nr 14,464.00

4 ZD - DB2 (9 way) 07 Nr 14,464.00

5 XE - DB2 (9 way) 08 Nr 14,464.00


6 1Ca - DB2 (9 way) 01 Nr 14,464.00

7 1Da - DB2 ( 9 way) 01 Nr 14,464.00

X=1:8

Z=2:8

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

DISTRIBUTION BOARDS (Cont'd)

A. Supply and install following flush mounted type, 02 row, plastic


or powder coated metal distribution boards, shall be consisted
flush metal clad or all insulated fitted with

40A, 2P isolator 01 nos.


40A, 2P, RCCB (30mA) 01 nos.
10A, SP, MCB 03 nos.
16A, SP MCB 01 nos.
20A, SP MCB 05 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.

1 XF - DB 08 Nr 10,071.00

X=1:8

B. Supply and install flush mounted type, 02 row, plastic or powder 01 Nr 14,518.00
coated metal distribution board , shall be consisted flush metal
clad or all insulated fitted with

63A, 4P, isolator 01 nos.


63A, 4P, RCCB (100mA) 01 nos.
40A, SP, MCB 03 nos.
32A, TP, MCB 01 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings. ( G-E MDB )
To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

DISTRIBUTION BOARDS (Cont'd)

A. Supply and install flush mounted type, 02 row, plastic or powder 01 Nr 12,000.00
coated metal distribution board , shall be consisted flush metal clad
or all insulated fitted with

40A, 4P, isolator 01 nos.


40A, 4P, RCCB (100mA) 01 nos.
40A, SP, MCB 03 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.
( 1E-MDB )

B. Supply and install flush mounted type, 02 row, plastic or powder 01 Nr 14,304.00
coated metal distribution board , shall be consisted flush metal clad
or all insulated fitted with

63A, 4P, isolator 01 nos.


63A, 4P, RCCB (100mA) 01 nos.
40A, TP, MCB 01 nos.
40A, SP, MCB 02 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.

( 8E- MDB )

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

DISTRIBUTION BOARDS (Cont'd)


A. Supply and install flush mounted type, 02 row, plastic or powder 02 Nr 16,232.00
coated metal distribution boards , shall be consisted flush metal
clad or all insulated fitted with

40A, 2P, isolator 01 nos.


32A, 2P, RCCB (100mA) 02 nos.
10A, SP, MCB 09 nos.
20A, SP, MCB 10 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.
( G-EDB-R ,G-EDB-B )

B. Supply and install flush mounted type, 02 row, plastic or powder 06 Nr 10,714.00
coated metal distribution boards , shall be consisted flush metal
clad or all insulated fitted with

40A, 2P, isolator 01 nos.


40A, 2P, RCCB (30mA) 01 nos.
10A, SP, MCB 04 nos.
20A, SP, MCB 04 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.
( G-EDB-Y ,1-EDB-R , 3-EDB-Y , 5-EDB-B ,
7-EDB-R , 8-EDB-Y )

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

DISTRIBUTION BOARDS (Cont'd)

A. Supply and install flush mounted type, 02 row, plastic or powder 01 Nr 13,286.00
coated metal distribution board , shall be consisted flush metal
clad or all insulated fitted with

40A, 4P, isolator 01 nos.


40A, 2P, RCCB (100mA) 01 nos.
10A, SP, MCB 04 nos.
20A, SP, MCB 02 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.
( RT-EDB1)

B. Supply and install flush mounted type, 02 row, plastic or powder 01 Nr 11,732.00
coated metal distribution board , shall be consisted flush metal
clad or all insulated fitted with

40A, 3P, isolator 01 nos.


40A, 2P, RCCB (100mA) 02 nos.
10A, SP, MCB 08 nos.
20A, SP, MCB 04 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.
( RT-EDB2 )

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FINAL SUB CIRCUIT POINT WIRING (Cont'd)

DISTRIBUTION BOARDS (Cont'd)

A. Supply and install flush mounted type, 01 or 02 row, plastic or 01 Nr 15,214.00


powder coated metal distribution board , shall be consisted flush
metal clad or all insulated fitted with

40A, 4P, isolator 01 nos.


40A, 2P, RCCB (30mA) 01 nos.
40A, SP, MCB 02 nos.
6A, SP, MCB 04 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.
( H-EMDB )

B. Supply and install flush mounted type, 01 or 02 row, plastic or 02 Nr 8,786.00


powder coated metal distribution boards , shall be consisted flush
metal clad or all insulated fitted with

40A, 2P, isolator 01 nos.


40A, 2P, RCCB (30mA) 01 nos.
6A, SP, MCB 06 nos. and other materials
required to make complete installation according to the specified
specifications and illustrated in the electrical drawings.
( H-EDB1 , H-EDB2 )

To Collection

ELECTRICAL INSTALLATION (Cont'd)

A. MAIN DISTRIBUTION BOARD

1 Gen. Panel (Emergency)

Floor mounted metal clad powder coated, hinged lockable door type
Gen. Panel (Emergency) incoming panels fitted with the following
accessories, and other all materials required to make complete
installation as per the specifications and electrical drawing, Including
inter connection wiring and etc.

1.1 4 pole, 200Amp., Auto and Manual changeover switch. (1 nos.)

1.2 Incoming MCCB, 4 pole, 200Amp., or higher frame size with a rated
breaking capacity of not less than 22KA at 400V, 4 pole fitted with
thermal over - load, earth leakage & magnetic short circuit trips. The
thermal overload trip shall be adjustable over the range of 75 to 100%
of 200Amp. Earth leakage trip shall be operated via shunt trip and
shall be adjustable in the range 1 - 10A. (1 nos.) ITEM (Carried to next page)

1.3 Bus bars 400 volts, 200Amp., 4 pole with accessories. (1 nos.)

1.4 Ammeter complete with CTS etc., as required. Scale 0-200Amp., AC


50Hz square or rectangular. (3 nos.)
1.5 Voltmeter scaled 0-500 volts, AC 50Hz complete with fuses etc.,
square or rectangular. (1 nos.)

To Collection

ELECTRICAL INSTALLATION (Cont'd)

MAIN DISTRIBUTION BOARD (Cont'd)

A. Gen. Panel (Emergency) (Cont'd)

1.6 Feeder MCCB, 3 pole, 40Amp., to equal frame size with breaking
capacity of not less than 10KA at 400 V fitted with thermal over-load
trips rated 75 to 100% of 40A magnetic short circuit protection. (1 Nr
connect direct to the generator side of C.O.S. for emergency lights of
houses). (7 nos.)

1.7 Feeder MCCB, 3 pole (TP) 63Amp., to equal frame size with breaking
capacity of not less than 10KA at 400 V fitted with thermal over-load
trips rated 75 to 100% of 63A magnetic short circuit protection. (1 nr
connect direct to the generator side of C.O.S. for emergency lights of
houses). (3 nos.) Item 455,357.00

1.8 Feeder MCCB, 3 pole (TP) 125Amp., to equal frame size with breaking
capacity of not less than 10KA at 400 V fitted with thermal over-load
trips rated 75 to 100% of 125A magnetic short circuit protection. (1 nr
connect direct to the generator side of C.O.S. for emergency lights of
houses). (1 nos.)

1.9 Phase neon indicators for R,Y,B (transformer type). (3 nos.)

1.10 Voltmeter selector switch. (1 nos.)

To Collection
ELECTRICAL INSTALLATION (Cont'd)

A. Overhead Cable Tray

Supply and install following GI Trays made with 14 SWG sheet as


shown in the electrical drawings and specifications. Including
suspending GI rods, (thread bars and nuts ) GI brackets and all
accessories required to make complete installation.

i 600 x 100mm 16 m 3,911.00

ii 450 x 100mm (Two Compartment) 30 m 3,171.00

iii 300 x 100mm 10 m 2,464.00

B. Cable Ladders

Supply and install G.I cable ladder ( as required size ) in electrical Item 225,000.00
duct according to the specified details which shall be approved by
the engineer. Including fixing charges with all materials required to
make complete installation.

To Collection

ELECTRICAL INSTALLATION (Cont'd)

A. FEEDER CABLES

1 Cu /PVC/PVC Cables

Supply all materials and install ,terminate following CU/PVC/PVC


feeder cables, drawn through and protect by rigid conduits/cable
trays/cable ladders as required to make complete installation
according to the specifications & electrical drawings.

1.1 6mm2 cable 2 wire and earth 6mm2 215 m 257.00


1.2 6mm2 cable 3 wire and earth 6mm2 600 m 316.00
1.3 6mm2 cable 4 wire and earth 6mm2 110 m 423.00
1.4 6mm2 cable 4 wire 2740 m 316.00
1.5 10mm2 cable 4 wire and earth 10mm2 250 m 611.00
1.6 16mm2 cable 4 wire and earth 16mm2 120 m 857.00
1.7 35mm2 cable 4 wire and earth 16mm2 40 m 1,811.00
1.8 6mm2 cable 2 wire 490 m 188.00
1.9 1 x 6mm2 earth cable 640 m 27.00

2 Cu/XLPE/SWA/PVC Cable

Supply, install, terminate and glanding following


CU/XLPE/SWA/PVC cables with all accessories on cable tray/ trench
as required to make complete installation according to the
specifications and electrical drawings. (the glanding and the earth
bar of the panel to be interconnected).

2.1 1x4C , 95 mm2 Cu/XLPE/SWA/PVC Cable 80 m 5,357.00


[From CEB Bulk supply unit to Gen. panel (Emergency Panel )]

To Collection

ELECTRICAL INSTALLATION (Cont'd)

FEEDER CABLES (Cont'd)

A. Main Earth Cable/Riser

Supply all materials and install terminate following CU/PVC/earth


cables/riser drawn through and protect by rigid conduits/cable
trays/cable ladders as required to make complete installation
according to the specifications & electrical drawings. Cu earth riser
shall be fixed on cable ladder (in duct) by standard insulating
clamps/brackets and provide required holes or tap off points to
connect earth cable at every floor levels.

1 1 x 35mm2 CU/PVC cables (ECC) 40 m 557.00


(from Gen. panel to feeder point of earth riser)

2 25x4 mm Cu bar Riser ( from 1st floor to 8th floor) 24 m 1,125.00

B. WARNING LAMP

Supply and installation surface mounting type (aircraft) warning


lamp and other materials required to make complete installation as
per the specifications. Including photo electric switch and rough
surface bulb 01 Nr 17,679.00

C. Testing and commissioning of Elctrical Installation Item 26,786.00

D. Preliminaries Item 107,143.00

To Collection

COLLECTION

FROM PAGE - 64
FROM PAGE - 65
FROM PAGE - 66
FROM PAGE - 67
FROM PAGE - 68
FROM PAGE - 69
FROM PAGE - 70
FROM PAGE - 71
FROM PAGE - 72
FROM PAGE - 73
FROM PAGE - 74
FROM PAGE - 75
FROM PAGE - 76
FROM PAGE - 77
FROM PAGE - 78
FROM PAGE - 79
FROM PAGE - 80
FROM PAGE - 81
FROM PAGE - 82
FROM PAGE - 83

TOTAL CARRIED TO SUMMARY


Y FREE PRICE DUTY PAID PRICE
AMOUNT RATE AMOUNT

89,652.00

93,990.00

647,808.00

21,690.00

853,140.00 Rs. -
7,230.00

127,248.00

951,468.00

40,488.00

108,000.00

1,234,434.00 Rs.

21,690.00
44,826.00
323,904.00

5,784.00
5,784.00

187,716.00

589,704.00 Rs. -

2,892.00

11,568.00

80,976.00

2,892.00
2,892.00

4,338.00

30,366.00

2,892.00

138,816.00 Rs. -

51,000.00

459,000.00

3,339,000.00

12,000.00

4,661.00

27,966.00
195,762.00

4,661.00

4,094,050.00 Rs. -

112,999.00

510,531.00

87,618.00
350,574.00

1,061,722.00 Rs.
17,676.00

83,244.00

30,002.00

194,236.00

325,158.00 Rs. -
58,980.00

258,195.00

65,043.00

405,867.00

788,085.00 Rs. -
95,144.00

95,144.00

83,251.00

83,251.00

95,144.00

11,893.00

11,893.00

475,720.00 Rs. -

115,712.00

115,712.00

101,248.00

101,248.00

115,712.00
14,464.00

14,464.00

578,560.00 Rs. -

80,568.00

14,518.00
95,086.00 Rs. -

12,000.00

14,304.00

26,304.00 Rs. -
32,464.00

64,284.00

96,748.00 Rs. -

13,286.00
11,732.00

25,018.00 Rs. -

15,214.00

17,572.00
32,786.00 Rs. -

o next page)
Rs.

455,357.00

455,357.00 Rs. -
62,576.00

95,130.00

24,640.00

225,000.00

407,346.00 Rs. -
55,255.00
189,600.00
46,530.00
865,840.00
152,750.00
102,840.00
72,440.00
92,120.00
17,280.00

428,560.00

2,023,215.00 Rs.

22,280.00
27,000.00

17,679.00

26,786.00

107,143.00

200,888.00 Rs. -

853,140.00
1,234,434.00
589,704.00
138,816.00
4,094,050.00
1,061,722.00
325,158.00
788,085.00
475,720.00
578,560.00
95,086.00
26,304.00
96,748.00
25,018.00
32,786.00

455,357.00
407,346.00
2,023,215.00
200,888.00

13,502,137.00