Professional Documents
Culture Documents
Description Features
Instantaneous, maximum and minimum Nominal voltage 300 Vac (ph-n) / 520 Vac (ph-ph)
parameter display Frequency 45..0.65 Hz
Digital output with optoinsulated transistor Nominal current In .../ 5 A
ITF Technology: Galvanic insulation pro- Current consumption of the circuit 0.75 VA
tection inputs inputs, depending on the type Overload (permanent) 1.1 In
Maximeter function (A / A III / kW III / kVA
Class/Accuracy
III)
Voltage 0.5 % 2 digits
Default page selection
Current 0.5 % 2 digits
Universal power AC and DC optional
Power rating 1 % 2 digits
Active energy Class 1 - EN 62053-21 (*)
Reactive energy Class 2 - EN 62053-23 (*)
Ambient conditions
1
CVM NRG 96
Three-phase power analyzer (balanced and unbalanced) for panel mounting
References
Internal
Max. A Ranges Class 0,5 Power Measurement Type Code
diameter
Connections
CVM NRG96, 3 or 4 wires (low voltage) CVM NRG96, 3 wires (2 Voltage transformers CVM NRG96, 3 wires (2 Voltage transformers
and 3 Current transformers) and 2 Current transformers)
3
4
6
7
8
Single-phase power analyzer, DIN rail
CVM-1D
Description
Power analyzer for single-phase circuits, up to 32 A. Features an LCD display with a
rotating screen system, showing a total of 24 instantaneous, maximum and minimum
electrical variables. It has been designed in an enclosure with only 1 DIN module (18 mm).
The compact size of the analyzer allows it to be installed on any electric panel. The unit
has the Modbus/RTU (RS-485) protocol and is compatible with the PowerStudio energy
management software.
Applications
Control application in switchboards and low- and medium-voltage connection
points, where an analyzer must be installed on a DIN rail due to space restrictions.
Alarm control; the variable to be controlled, the maximum and
minimum values, and the delay are fully programmable.
Control of active or reactive energy using the impulse output.
Capture of instantaneous, maximum and minimum data
of the electrical parameters measured.
Technical features
Power Single-phase power supply 230 Vac 20%
circuit Power supply frequency 50 / 60 Hz
Power supply use 1.5 VA
Measurement circuit Rated voltage (P-N) 184...276 Vac
Frequency 50 / 60 Hz
Nominal current 5A
Minimum current 20 mA
Maximum current 32 A
Accuracy class Voltage 0.5% 1 digits
Current 0.5% 1 digits
Power 1% 1 digits
Active energy (optional) Class B (EN 50470) MID
Reactive energy Class 2 (IEC 62053-23) MID
Output transistors Type: Isolated transistor Open NPN collector
Maximum operating voltage 35 Vdc
Maximum operating current 50 mA
Maximum frequency 5 impulses / s
Impulse duration 100 ms (congurable)
Insulation 3.7 kV RMS / 1 min
Environmental Operating temperature -10 C...+50 C
conditions Relative humidity (without 5%...95%
condensation)
Altitude 2,000 m
Communications Type RS-485
Protocol Modbus / RTU
Build Type of box V0 self-extinguishing plastic
features Protection degree IP 31
Dimensions 17.5 x 90 x 71.6 mm (1 module)
Safety EN 61010 Double-insulated electric shock protection, class II
Standards IEC 664, VDE 0110, UL94-V0, EC 801, IEC 348, IEC 571-1,
Class B EN 50470-3 Active Energy,
Class 2 EN 62053-23 Reactive Energy, EN 50470-1, EN 61010,
EN 61000-4-3, EN 61000-4-4, EN 61000-6-4, EN 55022
9
Single-phase power analyzer, DIN rail
CVM-1D
References
Type Code Communications Protocol
CVM-1D-C M55510 - -
Dimensions
71.6
44
90
64
45
17.5
Connections
RS-485 communication connection via RS-232 / RS-485 intelligent converter
(only model with RS-485 communications)
10
Three-phase power analyzer,
CVM MINI assembly on DIN rail
Description
Three-phase power analyzer (balanced and unbalanced), assembly on DIN rail,
very compact size (3 modules) and 4-quadrant measurement.
Dimensions
Applications
Control application in switchboards and low- and medium-voltage connection
points, where an analyzer must be installed on a DIN rail due to space restrictions.
Alarm control; the variable to be controlled, the maximum and
minimum values and the delay are fully programmable.
Control of active or reactive energy using the impulse output.
Capture of instantaneous, maximum and minimum data
of the electrical parameters measured.
Technical features
Power standard: 230 Vac (-15%...+10%)
circuit optional: 85...265 Vac / 95...300 Vdc / 20...120 Vdc
Consumption 3 VA
Frequency 45...65 Hz
Measurement circuit Rated voltage 300 Vac (P-N) / 520 Vac (P-P)
Frequency 40...65 Hz
Voltage circuit consumption 0.7 VA
Current circuit consumption ITF 0.9 / Shunt 0.75 VA
Transformers .../5 A or .../1 A / 250 mA
Minimum direct current 110 mA
Maximum direct current 6A
Maximum current with transformer In /5 1.2 In
Output transistors Type: Isolated transistor Open NPN collector
Maximum operating voltage 24 Vdc
Maximum operating current 50 mA
Maximum frequency 5 imp/s
Impulse duration 100 ms
Accuracy class Voltage 0.5% 1 digits
Current 0.5% 1 digits
Power 1% 1 digits
Communications Port RS-485
Protocol Modbus/RTU, LonWorks, BACnet
Environmental Operating temperature -10 C...+50 C
conditions Relative humidity (without 5%...95%
condensation)
Altitude 2,000 m
Build Type of box V0 self-extinguishing plastic
features Protection degree Embedded unit: IP 41
Terminals: IP 20
Dimensions 52.5 x 85 x 67.9 mm (3 modules)
Weight 210 g
Safety Designed for CAT III 300/520 Vac installations, in accordance with EN 61010 .
Double-insulated electric shock protection, class II
Standards IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3 ,
EN 61000-6-1 , EN 61010-1
11
Three-phase power analyzer,
CVM MINI assembly on DIN rail
References
Quadrants Class (U, I) Communications Protocol Digital output Harmonics Type Code
LonTalk
4 0.5 ISO/IEC14908 LonWorks 2 - CVM-MINI-ITFLonWorks-C2 M52091
ANSI/EIA 7091
Max. A Ranges Class 0.5 Power Measurement Internal diameter Type Code
Coding table
Code Internal Code
M 5 X X X X 0 0 X
20...120 Vdc 5
Connections
CVM MINI , 3 or 4 wires (low voltage) CVM MINI , 3 wires (2 voltage transformers CVM MINI , 3 wires (2 voltage transformers
and 3 current transformers) and 3 current transformers)
12
Three-phase power analyzer,
CVM NET assembly on DIN rail - without display
Description
Power analyzer for the measurement of balanced and unbalanced three-phase networks;
specically designed for measuring up to 230 electrical parameters and for transmitting
this data through the RS-485 communication bus with Modbus/RTU protocol to the
supervision SCADA.
Applications
Control application in switchboards and low- and medium-voltage connection
points, where an analyzer must be installed on a DIN rail due to space restrictions
Alarm control; the variable to be controlled, the maximum and
minimum values and the delay are fully programmable
Control of active or reactive energy using the impulse output
Capture of instantaneous, maximum and minimum data
of the electrical parameters measured
Technical features
Power Rated voltage 230 Vac
circuit Power supply frequency 50 - 60 Hz
Maximum power consumption 3.0 VA
Measurement circuit Rated voltage 300 Vac (P-N) / 520 Vac (P-P)
Frequency 40...65 Hz
Nominal current In / 5 A or / 250 mA
Communications Port RS-485
Protocol Modbus / RTU
Output transistors Type: Isolated transistor Open NPN collector
Maximum operating voltage 24 Vdc
Maximum operating current 50 mA
Maximum frequency 5 imp/s
Impulse duration 100 ms
Accuracy class Voltage 0.5% 1 digits
Current 0.5% 1 digits
Power 1% 1 digits
Build Measurement module Assembly on DIN 46277 rail
features (EN 50022)
Number of modules 3
Type of box V0 self-extinguishing plastic
Protection degree Embedded unit: IP 41
Terminals: IP 20
Dimensions 52.5 x 85 x 67.9 mm (3 modules)
Environmental Operating temperature -10 C...+50 C
conditions Humidity (without condensation) 5%...95% (without condensation)
Maximum altitude 2,000 m
Safety EN 61010 Double-insulated electric shock protection, class II
Standards IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-
6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2,
EN 61000-4-3, EN 61000-4-4, EN-61000-4-5, EN 55011, CE
13
Three-phase power analyzer,
CVM NET assembly on DIN rail - without display
References
Type Code Communications Transformer type
Dimensions
67,9
52,5 43,5
85
Connections 45
a b a b a b a b
A B A B A B A B
14
Analyzer for 4 three-phase electrical networks,
CVM-NET-4 assembly on DIN rail - without display
Description
Power analyzer for measuring balanced and unbalanced three-phase networks;
specically designed to take measurements from 4 different points of the installation,
with a single three-phase voltage input but with 4 three-phase channels for current
signal inputs, received from the MC efcient current transformers . The data acquired by
the analyzer is transmitted via the RS-485 communications bus with the Modbus/RTU
protocol to the supervision SCADA.
Applications
Can take measurements from 4 points of the installation at the same time. Ideal
for assembling on electric panels (compact dimensions: 6 DIN rail modules)
Control of active and reactive energy via impulses
Ideal EDS accessory. This unit measures the main
parameters and the records and manages them.
Technical features
Power Rated voltage 85...365 Vac / 95...300 Vdc
circuit Power supply frequency 50-60 Hz (AC mode)
Maximum power consumption 6.0 VA
Measurement circuit Rated voltage 300 Vac (P-N) / 520 Vac (P-P)
Frequency 40...65 Hz
Voltage circuit consumption 0.7 VA
Current circuit consumption ITF 0.9 / Shunt 0.75 VA
Transformers .../250 mA
Minimum direct current 110 mA
Maximum direct current 6A
Maximum current with transformer In /5 1.2 I n
Accuracy class Voltage 0.5% 1 digits
Current 0.5% 1 digits
Power 1% 1 digits
Communications Port RS-485
Protocol Modbus / RTU
Output transistors Type: Isolated transistor Open NPN collector
Maximum operating voltage 24 Vdc
Maximum operating current 50 mA
Maximum frequency 5 imp/s
Impulse duration 100 ms
Build Measurement module Assembly on DIN 46277 rail
features (EN 50022)
Number of modules 6
Type of box V0 self-extinguishing plastic
Protection degree Embedded unit: IP 41
Terminals: IP 20
Dimensions 140 x 110 x 70 mm (6 modules)
Environmental Operating temperature -10 C...+50 C
conditions Humidity (without condensation) 5%...95% (without condensation)
Maximum altitude 2,000 m
Safety EN 61010 Double-insulated electric shock protection, class II
Standards IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-
6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2,
EN 61000-4-3, EN 61000-4-4, EN-61000-4-5, EN 55011, CE
15
Analyzer for 4 three-phase electrical networks,
CVM-NET-4 assembly on DIN rail - without display
References
Type Code Communications Measurement Transformer
4 three-phase
CVM-NET4-MC-RS-485-C4 M M55732 RS-485 Modbus/RTU .../250 mA (type MC )
channels
Dimensions
140 70
01 02 03 04 C B(-) S A(+)
Power V1 V2 V3 N COM
Supply DIGITAL OUTPUTS RS-485
110
45
1 2 3 4 2S13S1CS2
1S1 1S12S13S1CS2 1S12S13S1CS2 1S12S13S1CS2
Connections
Connection of 4 three-phase channels
L1 L2 L3 N
01 02 03 04 C B(-) S A(+)
Power V1 V2 V3 N COM
Supply DIGITAL OUTPUTS RS-485
1 2 3 4 2S13S1CS2
1S1 1S12S13S1CS2 1S12S13S1CS2 1S12S13S1CS2
L1
L2
L3
L3 L2 L1 L3 L2 L1 L3 L2 L1
L1 L2 L3
16
Three-phase power analyzer,
CVMk2 assembly on panel or DIN rail
Description
Three-phase power analyzer (balanced and unbalanced networks), assembly on panels or
DIN rails, with a graphical display, with 4-quadrant measurement.
Technical features
Power circuit Rated voltage 85...265 Vac /90...300 Vdc
AC power supply frequency 50...60 Hz
AC power supply consumption 30 VA
DC power supply consumption < 25 W
Measurement circuit Rated voltage 300/500 VP-N / VP-P
500 / 866 VP-N / VP-P
Frequency 45...65 Hz
Measurement margin 5%...120% of the U n for Un = 300 Vac (P-N)
5%...120% of the U n for Un = 500 Vac (P-N)
Maximum measurement voltage 360 Vac
Admissible overvoltage 750 Vac
Maximum power consumption < 0.6 VA
(limited current)
Current measurement Nominal current .../5 A or .../1 A
circuit Measurement margin 1%...120% of I n for In = 5 A
Primary current measured Programmable < 30,000 A
Admissible overload 6 A permanent, 100 A t < 1 s
Consumption < 0.45 VA
Accuracy class Power and energy 0.2 or 0.5
Maximum meter value 100 GWh
Build Measurement module DIN 46277 rail (EN 50022)
features Screen or screen + Assembly on panels (96x96, 144x144mm)
measurement module or holes with a diameter of 103 mm
Dimensions 144 x 144 x 116 mm
Environmental Operating temperature -10 C...+50 C
conditions Humidity (without condensation) 5%...95% (without condensation)
Maximum altitude 2,000 m
Safety Designed for CAT III 300 / 520 Vac installations, in accordance with EN 61010 .
Double-insulated electric shock protection, class II
Standards IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-11, IEC 61000-4-4, IEC 61000-4-5
17
Three-phase power analyzer,
CVMk2 assembly on panel or DIN rail
References
Compact units (measurement module + display)
Dimensions
Connections
Connection of 4 current transformers (5 wires) Connection of 4 current transformers Connection of 3 current transformers (3 wires)
and 2 voltage transformers
18
CVM
Renewable energies
Power Analyzers
www.circutor.es