Company SufHam
Consultant Sufi
Table of contents
1.Main supply
1.1. Main Transformer .................................................................................................................. 1
2.Board load schedule
2.1. Main Distribution Board ......................................................................................................... 2
3.Board brief calculations
3.1. Main Distribution Board ......................................................................................................... 3
4.Board voltage drop calculations
4.1. Main Distribution Board ......................................................................................................... 4
5.Analytical calculations per board circuit
5.1. Main Distribution Board ......................................................................................................... 5
6.Bill of quantities report
6.1. Bill of quantities report ........................................................................................................... 10
7.Installation schematic diagrams
7.1. Main ....................................................................................................................................... 12
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
Supply Report
Description Main Transformer
Supply method User defined transformer @65kVA
Phase/Voltage Threephase 400/230V 50Hz
Earthing system TN
Voltage drop limit Public supply: Ligting 3%, other uses 5%
Premises type Individual house hold
Load calculations
Phase L1 L2 L3
Connected load (A) 28.26 34.63 28.26
Diversified load (A) 26.18 19.1 26.18
Diversified + Spare load (A) 28.8 21.01 28.8 8.76
4x1Cx25mm + 1x16mm E
Main conductor
Pvc70/S/Cu,Flexible Length: 30m
1
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
Board schedule: Main Distribution Board Power factor Connected load (A)
Diversity factor Diversified load (A)
Spare load: 10%
3rd Harmonics % Diversified+Spare load (A)
Way Phase Description Conductor Protective devices L1 L2 L3 L1 L2 L3
4x1Cx2.5mm + 1x6mm E 0.9 0.9 0.9 7 7 7
1 L1,L2,L3 Motors Xlpe90/S/Cu,Flexible MCCB 3P Ir=16A/16kA 0.9 0.9 0.9
Length: 12m 1 1 1
2x1Cx6mm + 1x6mm E 0.9 21.26
2 L1 Lighting Loads Pvc70/S/Cu,Flexible MCCB 1P Ir=25A/16kA 1
Length: 25m 1
2x2x1Cx10mm + 2x10mm E 0.94 27.66
MCCB 2P Ir=32A/50kA
2 L2 Socket Outlets Xlpe90/S/Cu,Flexible 0.5
RCD 25A 30mA Instant
Length: 35m 1
2x1Cx6mm + 1x6mm E 0.9 21.26
2 L3 Lighting Loads Pvc70/S/Cu,Flexible MCCB 1P Ir=25A/16kA 1
Length: 25m 1
4x1Cx25mm + 1x16mm E 0.9 0.93 0.9 28.26 34.63 28.26
MCB B 3P 40A/10kA
L1,L2,L3 Main Distribution Board Pvc70/S/Cu,Flexible
RCD 25A 30mA Instant
0.95 0.95 0.95 26.18 19.1 26.18
Length: 30m 1 1 1 28.8 21.01 28.8
2
Sarepul Electrical Project
Status
Circuit Current inequalities check
check check check earth fault disconnection time
Way Phase Description Ib In/Ir (A) minIz It (A) Isc Icu (kA) It ks (x10) s (It)/k (mm) Zs maxZs () disc max (s)
1 L1,L2,L3 Motors 7 16 12.13 21.85 1.47 16 2.03 127.81 6 4.15 0.49 7283.33 0.01 0.4 OK
2 L1 Lighting Loads 21.26 25 34.51 38.95 1.28 16 2.41 476.1 6 5.16 0.51 7283.33 0.01 0.4 OK
2 L2 Socket Outlets 27.66 32 34.65 71.25 1.28 50 4.91 2044.9 10 4.15 0.37 7283.33 0.01 0.4 OK
2 L3 Lighting Loads 21.26 25 34.51 38.95 1.28 16 2.41 476.1 6 5.16 0.51 7283.33 0.01 0.4 OK
L1,L2,L3 Main Distribution Board 28.8 40 68.35 86.33 1.71 10 6.58 8265.63 16 0.62 0.32 7283.33 0.01 5 OK
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
1 L1,L2,L3 Motors 12m, 4x1Cx2.5mm + 1x6mm E Xlpe90/S/Cu,Flexib 0.12 0.9 0.94 0.41 0.31 0.72 5
2 L1 Lighting Loads 25m, 2x1Cx6mm + 1x6mm E Pvc70/S/Cu,Flexible 0.1 0.9 0.97 0.41 1.22 1.63 3
2 L2 Socket Outlets 35m, 2x2x1Cx10mm + 2x10mm E Xlpe90/S/Cu,Fle 0.02 0.94 0.95 0.16 0.49 0.64 5
2 L3 Lighting Loads 25m, 2x1Cx6mm + 1x6mm E Pvc70/S/Cu,Flexible 0.1 0.9 0.97 0.34 1.22 1.56 3
L1,L2,L3 Main Distribution Board 30m, 4x1Cx25mm + 1x16mm E Pvc70/S/Cu,Flexib 0.03 0.9 0.97 0 0.41 0.41 5
4
Sarepul Electrical Project
Analytical calculations
Description Main Distribution Board Voltage / Phase Three phase+N (400V and 230V) / L1,L2,L3
Supply from Main Transformer Circuit type Din Rail
Conductor type 30m, Single-core 70C thermoplastic insulated non-armoured, 4x1Cx25mm + 1x16mm E
Element Copper (Cu) Armour No Working temp. (C) 70 Table in BS7671 4D1
Circuit calculations
Currents inequalities (A) Impetances ()
Design current-Ib Device rating-In Min conductor capacity-Iz Actual conductor rating-It Phase conductor-Z1 CPC-Z2 Earth external Phase external
28.8 40 68.35 86.33 0.0281 0.0281 0.2536 0.2026
Earth fault Earth fault current(k) Zs() Max Zs() Min Disconection time (s) Device Disconection time (s) Min CPC (mm)
Calculations 0.6821 0.3203 7283.3333 5 0.01 0.62
Phase fault Max at starting point(kA) Max at end point(kA) Min at end point(kA) Disconnection time of MCB (s) Conductors withstand duration (s)
Calculations 1.71 1.471 0.8111 0.01 12.56
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
Analytical calculations
Description Motors Voltage / Phase Three phase+N (400V and 230V) / L1,L2,L3
Supply from Main Distribution Board (Way 1) Circuit type Electric motor 3Ph and N Type Soft Start Efficiency = 0.92
Conductor type 12m, Single-core 90C thermosetting insulated non-armoured, 4x1Cx2.5mm + 1x6mm E
Element Copper (Cu) Armour No Working temp. (C) 90 Table in BS7671 4E1
Circuit calculations
Currents inequalities (A) Impetances ()
Design current-Ib Device rating-In Min conductor capacity-Iz Actual conductor rating-It Phase conductor-Z1 CPC-Z2 Earth external Phase external
7 16 12.13 21.85 0.1219 0.1219 0.3247 0.2611
Earth fault Earth fault current(k) Zs() Max Zs() Min Disconection time (s) Device Disconection time (s) Min CPC (mm)
Calculations 0.4487 0.487 7283.3333 0.4 0.01 4.15
Phase fault Max at starting point(kA) Max at end point(kA) Min at end point(kA) Disconnection time of MCB (s) Conductors withstand duration (s)
Calculations 1.471 0.9509 0.4501 0.01 0.63
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
Analytical calculations
Conductor type 25m, Single-core 70C thermoplastic insulated non-armoured, 2x1Cx6mm + 1x6mm E
Element Copper (Cu) Armour No Working temp. (C) 70 Table in BS7671 4D1
Circuit calculations
Currents inequalities (A) Impetances ()
Design current-Ib Device rating-In Min conductor capacity-Iz Actual conductor rating-It Phase conductor-Z1 CPC-Z2 Earth external Phase external
21.26 25 34.51 38.95 0.1004 0.1004 0.3213 0.2597
Earth fault Earth fault current(k) Zs() Max Zs() Min Disconection time (s) Device Disconection time (s) Min CPC (mm)
Calculations 0.4294 0.5089 7283.3333 0.4 0.01 5.16
Phase fault Max at starting point(kA) Max at end point(kA) Min at end point(kA) Disconnection time of MCB (s) Conductors withstand duration (s)
Calculations 1.2766 0.6854 0.491 0.01 1.98
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
Analytical calculations
Conductor type 35m, Single-core 90C thermosetting insulated non-armoured, 2x2x1Cx10mm + 2x10mm E
Element Copper (Cu) Armour No Working temp. (C) 90 Table in BS7671 4E1
Circuit calculations
Currents inequalities (A) Impetances ()
Design current-Ib Device rating-In Min conductor capacity-Iz Actual conductor rating-It Phase conductor-Z1 CPC-Z2 Earth external Phase external
27.66 32 34.65 71.25 0.0226 0.0226 0.3258 0.2632
Earth fault Earth fault current(k) Zs() Max Zs() Min Disconection time (s) Device Disconection time (s) Min CPC (mm)
Calculations 0.5955 0.3669 7283.3333 0.4 0.01 4.15
Phase fault Max at starting point(kA) Max at end point(kA) Min at end point(kA) Disconnection time of MCB (s) Conductors withstand duration (s)
Calculations 1.2766 1.0875 0.7009 0.01 4.16
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
Analytical calculations
Conductor type 25m, Single-core 70C thermoplastic insulated non-armoured, 2x1Cx6mm + 1x6mm E
Element Copper (Cu) Armour No Working temp. (C) 70 Table in BS7671 4D1
Circuit calculations
Currents inequalities (A) Impetances ()
Design current-Ib Device rating-In Min conductor capacity-Iz Actual conductor rating-It Phase conductor-Z1 CPC-Z2 Earth external Phase external
21.26 25 34.51 38.95 0.1004 0.1004 0.3213 0.2597
Earth fault Earth fault current(k) Zs() Max Zs() Min Disconection time (s) Device Disconection time (s) Min CPC (mm)
Calculations 0.4294 0.5089 7283.3333 0.4 0.01 5.16
Phase fault Max at starting point(kA) Max at end point(kA) Min at end point(kA) Disconnection time of MCB (s) Conductors withstand duration (s)
Calculations 1.2766 0.6854 0.491 0.01 1.98
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
Bill of quantities
Final circuits
36
Boards
Cables
465
Protective devices
10
C:\Users\SufHam\Desktop\Sarepul Prison.eom
Sarepul Electrical Project
127
637
11