06 Reliability of High Voltage Equipment


Intermediate Results CIRCUIT BREAKERS

CIGRE WG A3.06
Reliability
of
High Voltage Equipment

Intermediate Results
Circuit Breakers

1
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Po
da pu
Old Survey 1988-
1988-91 ta l a
tio
n
70.708 CB years

New Survey
22 countries 55.088 CB / 2004
46.470 CB / 2005
6.329 CB / 2006
14.763 CB / 2007

122.650 CB years

21 countries

2
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Po
Age Distribution da pu
Total 122650 CB years ta l a
tio
n

before 1979 1979-1983 1984-1988 1989-1993 1994-1998 1999-2003 2004-2007

Age Distribution 3
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Po
Voltage distribution da pu
Old survey ta l a
tio
500 V < n
300 V < 700 700 V
500 3% 0% Voltage distribution
14% New survey
63 V < 500<= ... <700
200 V < 100 kV >= 700 kV
300<= ... <500 0,1%
300 35% 2,7%
kV
15%
10,2%
60<= ... <100
kV
100 V < 36,7%
200
33% 200<= ... <300
kV
14,5%

100<= ... <200


kV
35,7%

Voltage distribution 4
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Po
da pu
Type of enclosure ta l a
Old survey tio
n
Non metal
enclosed
Type of enclosure
57% New survey
Non metal
Dead tank
enclosed
29%
38%

Metal
enclosed
43%

GIS - GIS -
3 phase 1 phase
15% 18%

Type of enclosure 5
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Po
Location da pu
Old survey ta l a
tio
n
Indoors
Outdoors
Location
15% New survey
85%
Indoor
Outdoor
16%
84%

Location 6
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Po
da pu
Kind of service ta l a
tio
n
Capacitor Bus-coupler
3% 10%
Shunt reactor
Other
1%
1%

Cable
6%
Overhead
line
Transformer 54%
25%

Kind of service 7
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Po
Type of operating mechanism da pu
Old survey ta l a
tio
Spring
n
18%
Type of operating mechanism
New survey
Spring Other
49% 1%

Hydraulic
Pneumati Hydraulic
c 52% 27%
30%

Pneumatic
23%

Type of operating mechanism 8


CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Po
Maintenance philosophy da pu
New survey ta l a
tio
n
Other
Combination 0,2%
37,9%

Time
Run to failure based
0,0% Condition
based
57,2%
4,7%

Maintenance philosophy 9
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Failure Distribution

10
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Old Survey New Survey


1988-91
re
ilu Minor: 3358 up to 2007:
a
Fa at
d Major: 475 2342 reports

Failure classification Failure classification


old survey new survey

m ajor
m ajor
12%

minor m inor
88%

Failure classification 11
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

re Contribution environment "major"


ilu New survey
a
Fa at Contribution environment "major"
d Old survey
contribution
7%
Snow , ice or
Corrosive Fog or high
hoarfrost
Sudden variation atmosphere humidity Pollution
1%
in tem perature 0% 1% including dust
2% 0%
Rain
0% Lightning
3%
Others
Strong w ind
1%
1%

No
contribution
93%
No
contribution
91%

Contribution of environment 12
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Service conditions / New survey

re
ilu
a
Fa at Service conditions
d Old survey
minor
3000 major

2500

2000

major 1 2 3 4 5 6
1500
minor

1000 1 de-energized - Available for service


500 2 Normal service - no operation command

0
3 Normal service operation demanded
In service or During Other cases
available for maintenance
4 Fault clearing operation
service
5 Operation occurred without command
6 During or directly after testing / maintenance

Service conditions 13
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

re
ilu Major failor mode Major failor mode
Fa ata Old survey New survey
d

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

Main failure modes:


1+2 Does not close / open on command
20 Locking in open or closed position by the control system
21 Loss of mechanical integrity

Major failure modes 14


CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Components responsible for major failures

r e
ilu
Fa ata
d

New survey%
Old survey%

Component at Electrical control Operating Kinematic chain


service voltage and auxiliary circuits mechanism

Components responcible 15
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Components responsible for MF


dependence on age
r e
ilu
Fa ata Electrical control
d and auxiliary
circuits

Operating
mechanism

Component at
service voltage

Kinematic chain
before 1984 1984 - 1993 1994 - 2003

Components responsible 16
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

Major failure rate / age


r e
ilu
Fa ata
d

before 1984 1984 - 1993 1994 - 2003

Major failure rate 17


CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS
The majority of the CBs is used at Po
service voltages between 60 and 200 kV da pu
ta l a
r e tio
lu The majority of the CBs is installed outdoors n
i
Fa ata
d 54% of the CBs are used for overhead line
switching

The mainly used type of operating mechanism has


changed from hydraulic to spring design

Most of the failures seem to happen during normal


service

Leakage of SF6 or oil seems still to be a problem

Operating mechanisms are still the most reported


components responsible for mayor failures But getting
better!
Main Conclusions 18
CIGRE WG A3.06 Reliability of High Voltage Equipment
Intermediate Results CIRCUIT BREAKERS

CIGRE WG A3.06
Intermediate Results
Circuit Breakers
Task Force Circuit Breakers:
WG A3-06 Tutorial
October 2008 Dirk Makareinis, Carl E. Slver,
Seoul Antoni Hyrczak, Kresimir Mestrovic,
Manuel Lopez Cormenzana,
Antonio Carvalho, Bob Sweeney