Setting of ICC500+ FCB

Laptop IP: 192.168.0.167


Subnet Mask: 255.255.255.0
Gateway: 192.168.0.1
Browse https//:192.168.0.10 in Internet Explorer (Browser)
LOGIN:
Username: admin
Password: Changeme
1. Change Battery type only when New Battery Bank is installed.
Default Value: DCB-A
Note: During changing Battery type ECC500 will restart/reset.

2. Change DG Configuration Mode Default Value: Single DG (If


site is DG site)
Setting Value: No DG (if
non DG site)

3. Change DC Under Voltage Threshold Default Value: 46V


Setting Value: 47V
4. Change Load LVD Voltage Default Value: 44V
Setting Value: 46V
5. Change BLVD Voltage (V) Default Value: 43.2V
Setting Value: 44V
6. Change Current Limit Threshold (C10) Default Value: 0.10C10
Setting Value: 0.20C10

Note: Consult with power team (NCELL/HW) if MCCB rating is 3 phase 20A or below.
7. Change Battery Capacity Default Value: 490AH
Setting Value: as per installed battery
(340 AH (=2x170AH) if only 2 battery bank and 680AH (4x170AH)
if 4 battery bank)
Note: Total Capacity of Battery e.g. If there is 4 banks of 140AH North Star Blue battery,
Setting will 560AH (140 * 4).
8. Relate Bus Bar Under Voltage in 6 number Port Relay.
[Alarm configuration Site Summary Bas Bar undervoltage
from N/A to 6]
9. Relate HEX Fault in 1 number Port Relay.
[Alarm configuration HEX HEX Fault from 6 to 1]
10. Alarm Information of ICC500(FCB)
Port
Port
CARD ICC310 Alarm Description Voltage Sevarity
BTS *
End

BTS/SMPS/PIU alarms

EMUB S1+ DO_1 NO


Temperature control unit Temperature control unit
EMUB S1- DO_1 COM fault/hex fault fault Low Major

EMUB S2+ DO_2 NO

EMUB S2_ DO_2 COM Door Door High Critical

EMUB S3+ DO_3 NO

EMUB S3- DO_3 COM PSU Fault(Rectifier) PSU Fault(Rectifier) Low Minor

EMUB S4+ DO_4 NO

EMUB S4- DO_4 COM Fuse Fault Fuse Fault Low Critical

EMUB S5+ DO_5 NO


Battery or Battery
EMUB S5- DO_5 COM Temperature Cabinet Temperature Low Major

EMUB S6+ DO_6 NO DC undervoltage(Battery DC undervoltage(Battery

EMUB S6- DO_6 COM Discharge) Discharge) Low Major

EMUB S7+ DO_7 NO


No Main Power supply at
EMUB S7- DO_7 COM Mains Power Failure Power Plant Low Critical

EMUB S8+ DO_8 NO

EMUB S8- DO_8 COM SPD Fault SPD Fault Low Major

Port BTS will depend of BTS vendor type. If Huawei port will be as
per above and if ZTE as per below
Color
Old name New name
code
Main power
white-
supply has a Mains Failure
blue
fault alarm
Rectifier white-
Rectifier Failure
module alarm orange
white-
Flood alarm Temperature Alarm
green
white-
Battery alarm Battery alarm
brown
white-
Smog alarm Load on DG
grey
Door alarm Red-blue
Over-voltage
red-
alarm of main Over Voltage Alarm
orange
power input
Battery low- red-
Battery Discharge Alarm
voltage alarm green

11. Change Site name /Date/ Time and Set Actual Time, Date and
Site [Site Config System Date Time and Site Information]
For any kind of doubt during installation and commissioning Please
contact with Power team of HW Subash C Adhikari 9851156083,
Firoj Khan 9802055452,Ncell Krishna Manandhar-
9802100232,Ncell Dipendra Shah- 9802100171

Tighten all Power connection and Set


Battery Switch in AUTO Mode