Professional Documents
Culture Documents
ABSTRACT
An alternative approach to calculation of the channel-base lightning parameters
using a well-known Heidler function without discontinuity of its first derivative at
t=0 of the lightning current is presented in the article. Based on a graph-analytical
method, the lightning parameters of the Heidler current can be derived from
statistical characteristics of the registered lightning activity such as the current
peak, the current rise-time and decay-time to half of the peak value. The effect of
the lightning current wave-shape on the estimated over-voltages has been studied
during lightning strikes to a 500 kV overhead power line in a vicinity of a
transformer-generator block of a power station using the Heidler and double
exponential functions. It appears that the calculated over-voltages in power systems
depend on the adopted channel-base lightning current. This becomes very critical
for fast transient processes of less than 2s current rise-time with reactive electrical
plants in the circuit.
Index Terms - Lightning current, lightning parameters, insulation, over-voltage
protection.
DOI 10.1109/TDEI.2014.004419
816 A. A. Reykherdt and K. P. Kadomskaya: An Engineering Approach to Calculation of Channel-base Lightning Current Parameters
The channel-base current which was earlier proposed by statistically evaluated parameters: the current peak ( I 0 ) and its
Bruce and Golde was a double exponential (DEXP) form due to steepness ( di0 dt ), the current rise-time ( t f ) and the current
easy differentiation and calculation of the lightning parameters
in early engineering applications [14, 15]: decay-time ( t d ) to half of the peak value. Quite often the rise-
time is described in more detail using the rise-time of 0.1 or 0.3 ,
I0 t t
i0 (t ) exp exp (1) which are the rise-time for the lightning current between 10% to
1 2 90% and 30% to 90%, respectively (Figure 1). The front duration
( t f ) is also determined as approximately 1.25 times of 0.1 or
where I 0 is the current peak; is a correction coefficient for 1.67 times of 0.3 according to [17, 18, 24, 25].
the current peak; 1 and 2 are time constants, which can be
derived from the current rise-time and the current decay-time.
However this function (1) has a discontinuity of the first
derivative at the initial time of t = 0 and is not suitable for the
lightning electromagnetic pulse calculations (LEMP).
More functions have been proposed to overcome this
td
discontinuity problem, but they are still based on double
exponential form [16], e.g.:
1
I t 1 t 1
i0 (t ) 0 exp exp (2) tf
2 2
Apparently, the DEXP lightning current models have physically Figure 1. Definitions of lightning waveshape.
non-realistic wave-shape with very steep current in the rising part
In addition to the above lightning parameters, the authors
that makes it difficult to use in LEMP applications and over-
consider in this article that it is worth describing an overall front
voltage assessment.
rise-time ( t f ), which is the front time from nearly zero current to
In order to better reflect the physics of the channel-base
lightning current and overcome the discontinuity problem where its peak. This rise-time ( t f ) determines the time duration to the
the function derivative is equal to zero at t = 0, Heidler proposed highest peak of the lightning current, when even small
the following functional form of the current [7,8]: oscillations of the current exist around its peak. It also helps to
i0 (t )
I0 t 1 n exp t I x(t ) y(t ) (3)
perform better modeling of the lightning current and integration
of the total current.
1 t 1 n 0
2 A charge transfer parameter (Q0 ) is another indirect quantity of
n the lightning current, which has been used for estimation of the
t
t current decay-time parameter ( 2 ) in the current decay-
where x(t ) 1 n and y (t ) exp are function of y (t ) in (3). However, the Q0 is more problematic
2
1 t to estimate for engineers as well as to recognize in engineering
1 applications in relation to the lightning parameters.
lightning current rise- and decay-functions, respectively, and n
Authors have made an attempt to calculate the lightning
is a current steepness factor of rise-time.
channel-base current parameters in equation (3) using a different
Equation (3) has also been used for the lightning current in the approach based on those parameters, which are already known
International standard IEC 62305 [17]. In some cases, researchers or earlier estimated by researchers such as the current peak,
use a sum of two Heidler functions with different lightning the rise-time ( 0.1 ) and the decay-time ( t d ) of the lightning
parameters for better correlation of the calculated current
waveform with the observed ones by Oscillograph measurements current. The effect of the lightning current wave-shape is also
of the lightning current on elevated objects e.g. transmission shown in comparison with the DEXP current based on
towers [18-21] or by recording the electric and magnetic fields of calculated over-voltages in a generator-transformer block
the triggered lightning [22, 23]. presented at the end of this article.
It is worth pointing to another function for representing the
lightning current proposed by Nucci et al [12] as a sum of the
2 CALCULATION OF CHANNEL-BASE LIGHTNING
DEXP (1) and Heidler functions (3). However despite its PARAMETERS FOR HEIDLER FUNCTION OF
flexibility for approximation of the channel-base lightning EQUATION (3)
current, the lightning parameters cannot be easily related to the The channel-base lightning current based on Heidler
observed shape in engineering applications. function allows researchers to represent the lightning wave-
The lightning current parameters, which represent the above shape without discontinuity of its first derivative at the base of
wave-shapes in equations (1) to (3), are based on the following the current at t=0 [7, 8]. As one can see, the lightning current
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 22, No. 2; April 2015 817
assumed to have two components: initial or breakdown If one assumes that t I max is approximately half of the rise-
current, which flows during the development of downward
and upward leaders near a breakdown point following by time ( 0.1 ), then the rise-time constant is:
corona leakage current. The second part of this process 0.1
contains most of the lightning energy which can be integrated 1 1/ n
(9)
to obtain a charge transfer parameter at the striking point. n 1
2
However, in general the statistical distribution law of the Q0 n 1
is unknown and a graphical solution was presented in [8] to To determine the decay-time constant ( 2 ), one can take
overcome this issue.
the rise-time component x(t ) in equation (3) equivalent to 1.0
In this paper a new solution for calculation of the channel-
base lightning parameters in equation (3) is analyzed. and the decay function y (t ) is 0.5, then the 2 is
Figures 3 demonstrates the lightning current parameters, Figure 5 shows the approximation of the lightning current
and n , versus the ratio t d / 0.1 in the range of 6 to 100, and for 0.1 =1 s obtained using the DEXP function (1) and the
Figure 4 in the range of 6 to 20 for more detailed proposed method of calculation of the lightning parameters in
equation (3) providing a zero derivative of the current at t = 0.
representation of these parameters. A probability of the ratio
of t d / 0.1 < 6 is less likely to appear in nature as it will be
shown in a statistical distribution of the lightning parameters
in the next paragraph.
Figure 5. Lightning current according to DEXP (1) and Heidler function (3)
Figure 3. Current ccorrection coefficient and steepness factor n in (3) using parameters in Table 1.
using the expression: In a likely event of the lightning stroke to one of the phases of the
zx
OHTL link, a flashover of external line insulation may occur
creating a chopped lightning wave travelling towards the
P( Z z ) FZ ( z ) f X ( x)dx f Y ( y )dy
500/15.75kV generator transformer. The calculated over-voltages
0 0
will depend on both a voltage-time (V-t) characteristic of insulator
strings of the OHTL and on the adopted lightning current.
f X ( x) FY ( zx)dx (15)
0
Figure 7 illustrates a different chopping time of the lightning
current of equations (1) and (3) for a V-t characteristic of
Table 2. Statistical characteristic of lightning parameters using log-normal external line insulation. Apparently, the estimated breakdown
distribution law.
voltage of the insulator string caused by the lightning current
is expected to be less when using the lightning current (3).
LIGHTNING M [x] [x] m
ln x ln x FX ( x)
PARAMETERS
0.05 0.50 0.95
I 0 (KA) 28.0 23.8 3.061 0.737 6.3 21.3 71.9
0.1 ( S) 4.5 2.8 1.338 0.576 1.5 3.8 9.8
1
1 ln x mln X 2
FZ ( z )
2 ln X 0 x 2 ln2 X
exp
2 ln Y
and (3) using V-t characteristic of external line insulation.
Table 3 shows the calculated distribution function FZ (z ) as The generator block during the lightning stroke in one of the
phases can be represented by a single phase diagram shown in
a ratio of the lightning current decay-time to its rise-time
Figure 8. For high frequency processes such as a rise-time of
( t d / 01 ) using equation (16). the lightning current, the generator transformer can be
As one can see from Table 3, a probability of this ratio simplified by equivalent capacitances, which are calculated
( t d / 01 ) 5 appears to be relatively low. from the measured transformer capacitances of HV and LV
windings [26, 31]:
Table 3. Statistical distribution of Z function.
C1 C C
Z t d / 0.1 C1E , C2 E C2 12 , C12 E 12 , (17)
2 2 2
1 2 3 5 10 20 50 70 100
where C1 and C 2 are the capacitances of HV and LV
0.0003 0.0046 0.0176 0.070 0.265 0.589 0.911 0.961 0.986
windings to the transformer tank, respectively; C12 is the
capacitance between windings. In some cases for longer rise-
4 THE EFFECT OF LIGHTNING CURRENT WAVE-
time of the lightning current, one can use an inductance ( LT )
SHAPE ON ESTIMATED OVER-VOLTAGES IN A
of the transformer circuit to account for magnetic coupling
500/15.75 KV GENERATOR-TRANSFORMER BLOCK between windings.
OF A POWER STATION
In Figure 8 the following circuit parameters are specified for
In this example, the effect of the lightning current wave- calculation of over-voltages in the 500/15.75 kV generator-
shape on estimated over-voltages has been studied during a
lightning stroke to a 500 kV overhead transmission line
(OHTL) adjacent to a 500/15.75 kV generator-transformer
block (Figure 6).
Figure 6. Lightning stroke to a 500 kV OHTL link adjacent to a generator Figure 8. Single phase diagram for calculation of lightning over-voltages in
transformer the 500/15.75 kV generator block
820 A. A. Reykherdt and K. P. Kadomskaya: An Engineering Approach to Calculation of Channel-base Lightning Current Parameters
Table 4. Calculated over-voltages on generator stator winding and LV surge arrester current. CONCLUSION
Case
I0 0.1 Lightning Lightning LV side without LV side with LV surge
A new engineering approach to
study chopping current surge arresters surge arresters arrester current
(KA) ( S) time (S) equation U (kV) U (kV) calculation of the channel-base
I (kA)
1 71.9 1.5 0.3 (1) 102.0 33.4 2.75 lightning parameters has been
provided for the Heidler lightning
0.8 (3) 73.2 32.2 1.66
current wave-shape (3). The proposed
2 28.0 4.5 1.5 (1) 82.4 33.2 2.57
graph-analytical method allows
3.4 (3) 92.4 33.7 3.03 engineers to determine the current
3 71.9 9.8 1.0 (1) 88.3 33.3 2.61 parameters ( 1 , 2 , and n ) more
4.1 (3) 90.5 33.6 2.99 easily without need to know a charge
transfer value (Q) at the striking point.
transformer block: The method can be used for a ratio of the lightning decay-time
Z OHTL = 315 is the surge (wave) impedance including constant ( 2 ) to the rise-time constant ( 1 ) above 5 utilizing
corona effect of the OHTL link between the transformer and the statistical distribution of the lighting current peak ( I 0 ), its
station switchyard; rise- ( 0.1 ) and decay time ( t d ).
R 10 is the ground resistance of OHTL towers to the The estimated over-voltages in the power network depend
lightning current during flashover across insulator strings; on the adopted lightning current. For a study of transient
Z G = 30 is the surge impedance of the stator generator processes in power systems this becomes very critical with a
rise-time of the lightning current of less than 2 s, where over-
winding; voltages appear on power equipment with winding insulation
AL and AG are surge arresters on the 500 kV transformer side such as power and measurement transformers, rotating
and LV generator side; machines and generators.
LT = 0.15 mH; C1E = 12.8 nF; C2 E = 15 nF; C12 E = 6.4 nF. REFERENCES
Transient over-voltages will appear on the stator winding [1] V.A. Rakov, R. Thottappillil and M.A. Uman, On the empirical
formula of Willett et al. relating lightning return-stroke peak current and
mainly through electrostatic coupling between transformer peak electric field, J. of Geophy. Res., Vol.97, No. D11, pp.11527
windings (C12 + C2)/C12 = 3.3, which is approx. 6 times 11533, 1992.
higher in comparison with the HV to LV transformer ratio [2] F. Rachidi and R. Thottappillil, Determination of lightning currents
from far electromagnetic fields, J. of Geophy. Res., Vol.89, No. D10,
of 500/3/15.75 kV = 18.3. pp.18315-18321, 1993.
These over-voltages on the 15.75 kV stator winding were [3] M.A. Uman and D.K. Mclain, Magnetic field of lightning return
evaluated with- and without surge arresters for both DEXP stroke, J. Geophysical Research, Vol.74, No. 28, pp. 6899-6910, 1969.
[4] V.A. Rakov, and A.A. Dulzon, A modified transmission line model for
lightning current (1) and Heidler function (3) using a new lightning return stroke field calculations, 9th Intl. Sympos.
approach to calculation of the lightning parameters. Three Electromagn. Compat., Zurich, Switzerland, pp. 229-235, 1991.
case studies are presented in Table 4 for the rise- and decay [5] V.A. Rakov and M.A. Uman, Review and evaluation of lightning return
time of the lightning current according to Table 2. stroke models including some aspects of their application, IEEE Trans.
Electromagnetic Compatibility, Vol. 40, No. 4, pp. 403-426, 1998.
As one can see from Table 4, an insulation breakdown [6] C.A. Nucci, C. Mazzetti, F. Rachidi, and M. Ianoz, On lightning return
time of the 500 kV insulator string strongly depends on the stroke models for LEMP calculations, 19th Intl. Conf. Lighting
adopted lightning current, which is apparently earlier for Protection, Craz, Austria, pp.463-470, 1988.
[7] F. Heidler, Travelling current source model for LEMP calculations. 6th
the DEXP current. The calculated over-voltages on the Intl. Zurich Sympos. EMC, Zurich, Switzerland, pp.157-162, 1985.
generator stator windings appear to be of less magnitude [8] F. Heidler, J.M. Cvetic and B.V. Stanic, Calculation of Lightning
when using Heidler expression (3) in comparison with the Current Parameters, IEEE Trans. Power Delivery, Vol.14, No. 2, 1999,
DEXP current of equation (1). However, this is only valid pp.399-404.
[9] R. Thottappillil and M.A. Uman, Comparison of lightning return-stroke
for a steep rise-time of the lightning current of less than 2 models, J. of Geophysical Research, Vol. 98, No.D12, pp. 22903-
s (Case No.1). The current of more than 2s rise-time 22914, 1993.
shows nearly the same level of over-voltages as the [10] J. Schoene, M.A. Uman, V.A. Rakov, K.J. Rambo, J. Jerauld, and G.H.
transient processes become of lower frequency as well as Schnetzer, Test of the transmission line model and the travelling
current source model with triggered lightning return strokes at very close
magnetic coupling between transformer windings becomes range, J. Geophysical Research, Vol. 108, No.D23, pp. 4737-4746,
more significant. 2003.
[11] V. Cooray, R. Montano, and V. Rakov, A model to represent negative
Although typical breakdown voltage to earth of 15.75 kV and positive lighting first strokes with connecting leaders, J.
generator stator winding is around 38 kV, the insulation Electrostatistics, Vol. 60, pp. 97109, 2004.
level can be exceeded by relatively low stroke current if [12] C.A. Nucci, G, Diendorfer, M.A. Uman, F. Rachidi, M. Ianoz, and C.
there are no surge arresters for lightning protection in the Mazzetti, Lightning return stroke current models with specified
channel-base current: A review and comparison, J. Geophysical
circuit. The calculated surge arrester current on LV side of Research, Vol. 95, No. D12, pp.20395-20408, 1990.
the transformer is relatively small due to the chopped [13] G. Diendorfer and M.A. Uman, An Improved Return Stroke Model
lightning current and existing protection on the primary with Specified Channel-Base Current, J. Geophys. Res., Vol. 95,
side of the transformer. pp.13621-13644, 1990.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 22, No. 2; April 2015 821
[14] C.E.R. Bruce, and R.H. Golde, The lightning discharge, J. Inst. Electr. [30] J. Takami and S. Okabe, Observational Results of Lightning Current on
Eng., Pt.2, Vol. 88, pp. 487-520, 1941. Transmission Towers, IEEE Trans. Power Delivery, Vol. 22, No.1, pp.
[15] R.H. Golde, Lightning, Vols. 1 and 2, London, Academic Press Inc, 547-556, 2007.
1977. [31] K.P. Kadomskaya, U.A. Lavrov and A.A. Reykherdt, Over-Voltages in
[16] R.L. Gardner, L. Baker, C.E. Baum and D.J. Andersh, Comparison of Power Networks and Protection, Novosibirsk, ISBN 5-7782-0460-4,
Lightning with Public Domain HEMP Waveforms on the Surface of an 2004 (in Russian).
Aircraft, 6th EMC Symposium, Zurich, pp.175-180, 1985.
[17] IEC 62305-1 Ed.1.0 (2006). Protection against lightning. Part 1: General Andrey A. Reykherdt (M10) received the M.Sc.
principles, Internation Standard, IEC: 2006. and Ph.D. degrees in High-Voltage Power
[18] T. Narita, T. Yamada, A. Mochizuki, E. Zaima and M. Ishii Engineering from Novosibirsk State Technical
Observation of Current Waveshapes of Lightning Strokes on University, Russia, in 1998 and 2000, respectively.
Transmission Towers, IEEE Trans. Power Delivery, Vol. 15, No.1, pp. Currently he is a Condition Monitoring Engineer
429-435, 2000. with Select Solutions of AusNet Services power
[19] H. Motoyama, K. Shinjo, Y. Matsumoto and N. Itamoto, Observation company, Australia. Before joining AusNet Services
and Analysis of Multiphase Back Flashover on the Okushishiku Test in 2007, he was a Resercher in the Centre for Power
Transmission Line caused by Winter Lightning, IEEE Trans. Power Transformer Monitoring, Diagnostics and Life
Delivery, Vol.13, No.4, pp. 1391-1398, 1998. Management with the Department of Electrical and
[20] A.J. Eriksson, Lightning and Tall Structures, Trans. South African Computer Systems Engineering, Monash University,
IEE, Vol. 69, No.8, pp. 238-252, 1978. Australia, since 2001. He was an Electrical Engineer in the Diagnostic and
[21] O. Beierl, Front Shape Parameters of Negative Subsequent Strokes Test Department of Electroservice of Federal Grid Company in Russia since
Measured at the Peissenberg Tower, 21st Intl. Conf. Lightning 1998. His research interests include high-voltage engineering, condition
Protection, Berlin, pp. 19-24, 1992. assessment, monitoring and diagnosis of high voltage power equipment;
[22] J. Schoene, M.A. Uman, V.A. Rakov, V. Kodali, K.J. Kambo and G.H. optimization, coordination and protection of external line insulation.
Schnetzer, Statistical Characteristics of the Electric and Magnetic
Fields and their Time Derivatives 15m and 30m from Triggered
Lightning, J. Geophysical Research, Vol. 108, No. D6, 4192, doi: Kira P. Kadomskaya (SM96) received the Ph.D.
10.1029/2002 JD002698, 2003. and the post Doctoral degrees in high voltage
[23] M.A. Uman, J. Schoene, V.A. Rakov, K.J. Rambo and G.H. Schnetzer, engineering from Saint Petersburg State
Correlated Time Derivatives of Current, Electric Field Intensity, and Polytechnical University, Russia, in 1957 and 1972,
Magnetic Flux Density for Triggered Lightning at 15m, J. Geophysical respectively. Currently, she is a Professor in the
Research, Vol.107, No.D13, 10.1029/2000JD 000249, 2002. Departemnt of High Voltage Technique and
[24] R.B Anderson and A.J Eriksson, Lightning parameters for engineering Electrophysics, Faculty of Power Engineering,
application, Electra, No.69, pp.65-102, 1980. Novosibirsk State Technical University, Russia,
[25] IEC 60060-1 Ed.3.0 (2010-09). High-voltage test techniques Part 1: holding this position since 1971. She was head of
General definitions and test requirements, Internation Standard, IEC: the same Department since 1971 until 1989. She is
2010. an author of more than 400 scientific publications in electrical power
[26] Guide for Lightning and System Overvoltage Protection of 6 1150 kV engineering, including 15 books and 29 textbooks and lecturers synopsis. She
Overhead Lines, RD 153-34.3-35.125-99. 2nd Edition, St-Petersburg, is also holding 6 authors patents. Dr. Kadomskaya is an Honorary Member of
Mintopenergo, 1999, 353 pages. the Academy of Electrotechnical Science in Russia, a member of Internetional
[27] K. Berger, R.B. Anderson and H. Kroeninger,Parameters of Lightning Electrotechnical commision (IEC), and also a member of Sibierian Division of
Flashes, Electra, No.41, 1975, pp.23-27. Higher Education Academy of Sciences, Russia.
[28] R.B. Anderson and A.J. Eriksson, Lightning Parameters for Her research interests include electromagnetic processes and over-voltages in
Engineering Applications, Electra, No.69, 1980, p.65-102. power networks; lightning strokes in overhead power lines and lightning
[29] Jun Takami and Shigemitsu Okabe, Characteristics of Direct Lightning protection; physicomathematical applications in power engineering; and
Strokes to Phase Conductors of UHV Transmission Lines, IEEE Trans. optimisation of design parameters for underground and underwater HV/EHV
Power Delivery, Vol. 22, No.1, pp.537-546, 2007. cables to increase their performance and ecological compatibility.