(Received January 7, 2016, Accepted September 9, 2016, Published online October 14, 2016)
Abstract: In this experimental study, six post-tensioned light weight concrete (LWC) continuous one-way slabs were tested in the
following manner: the exural behaviors of the members were compared with the calculations from the existing standards. The test
also examined the effect of prestressing in tendons and proper prestress conditions to reduce the deection and crack width, and to
enhance the exural capacity and ductility of LWC members. Flexural capacity and stress increments in unbonded tendons of the
specimens were compared with those of the simply supported normal and the lightweight concrete members. The suggested safety
limit from the American Concrete Institute (ACI) regulation on the maximum capacity and the stress incremental in unbonded
tendons were also compared with the test results under simple and continuous supporting conditions.
Keywords: post-tensioned, continuous one-way slab, lightweight concrete, exural capacity.
425
One of the most important factors in the design of post- were also compared to the test results under simple and
tensioned exural members is to evaluate the stress incre- continuous supporting conditions.
mental in unbonded tendons to which the sectional strain
compatibility condition is not applicable. The stress increase 1.1 Signicance of Research
in unbonded tendons is suggested by the member compati- This research provides meaningful test results on the
bility condition based upon the test results using simply behaviors of the post-tensioned continuous lightweight
supported NWC beams (ACI Committee 318 2011; Yang slabs. Here, the applicability of the stress incremental
et al. 2013). However, when it comes to the LWC, insuf- equations for unbonded tendons suggested by design stan-
cient data have been provided to assure the safety of the dards was evaluated. The stress increments in unbonded
existing models and current design standards. For safe tendons were also reviewed under simple and continuous
design of post-tensioned LWC beams, the effects of vari- support conditions. Authors believe the results can provide
ables on the stress incremental in unbonded tendons must be basic data for development of a future design manual of
studied under both simple and continuous support condi- post-tensioned continuous lightweight concrete slabs.
tions. Therefore, the bond reduction coefcients of plastic
hinge length proposed to evaluate stress increase in unbon-
ded tendon need to be adjusted in LWC members because 2. Experimental Program
the proposed equations are empirically derived using limited
test data from the NWC members. However, available test 2.1 Specimens
results and information are very rare for LWC exural Six LWC one-way continuous slab specimens post-ten-
members. sioned with unbonded tendons were prepared for exural
In this experimental study, six post-tensioned LWC con- tests, as shown in Table 1. The nomenclature for each
tinuous one-way slabs were tested. For each test parameter, specimen is shown in Fig. 1. Each specimen had three
the crack developments, failure modes, loaddisplacement supports with two spans. Two critical parameters affecting
relation, and load-tendon stress relationship were measured. the stress increase in unbonded tendons were considered in
The ultimate stress and stress incremental of the tendons experiments: span-to-effective tendon depth ratio (L/dp) in
were compared to the calculation results using the existing Group 1; and steel ratio in member section (qs) in Group 2.
standards; ACI 318-11, AASHTO (1998) and CAN3-A23- As known well from the study by Mojtahedi and Gamble
M94. The stress increments of the tendons were also com- (1978), L/dp of the concrete member can affect the stress in
pared to the previous NWC test data generated by Lim et al. tendons. ACI 318 equation (18-4) overestimates Dfps in
(1999). The exural behaviors of the members were com- NWC members when L/dp is greater than 35. In this study, L/
pared using calculations derived from the existing standards dp varies from 25, 35, and 45 to evaluate the stress changes
(ACI, AASHTO, and CAN3). The tests also examined the in tendons. It was Warwaruk et al. (1962) who conducted an
effect of prestressing in tendons and proper prestress pro-
cedures to reduce the deection and crack width, and to
enhance the exural capacity and ductility of LWC mem-
bers. Flexural capacity and stress increment in unbonded
tendons of the specimens were compared to those of the
simply supported normal and the LWC members. The sug-
gested safety limit from the ACI regulation on the maximum
capacity and the stress incremental in unbonded tendons Fig. 1 Specimen nomenclature.
426 | International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016)
experiment about the loading pattern for the rst time. 25, 35 and 45. The ACI 318-11 requires at least 0.4 %
Harajli and Kanj (1990) found the length of the plastic reinforcement of the cross section between the exural ten-
hinges of beams, as well as the stress in tendons, can be sion face and center of gravity of gross section (Act). Three
changed according to the loading patterns. When it comes to slabs in Group 2 receiving uniformly distributed load have
continuous slabs, a uniform loading method has been sug- three different qss with the same span and the L/dp; half of
gested for ideal member behaviors (Burns et al. 1978), so the the ACI requirement (S-PPR-0.5), same with the require-
use of uniformly distributed loading was applied in this test. ment (S-PPR-1.0), and 50 % more than the requirement
Group 1 consists of three continuous one-way slabs (SPPR-1.5). In all specimens, identical three-strand tendons
receiving uniformly distributed load whose L/dp ranges from with 2050 MPa tensile strength were used. D10 and D6
(a) (b)
300kN Oil-Jack
Load Cell
P/8 P/8 P/8 P/8 P/8 P/8 P/8 P/8 Loading beam
Hinge and loading plate
(c)
Fig. 2 Test setup a actuator and specimen b loading points and support c load cell and LVDT.
(a)
(b)
(c)
Fig. 3 Loading points and supports of a specimen S-L/dp-25, b specimen S-L/dp-35, c specimen S-L/dp-45 and specimen S-PPR.
International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016) | 427
rebars were used as reinforcing steel. The effective prestress the mixed LWC was approximately 1770 kg/m3. The
of tendon (fpe) was 60 % of its ultimate stress (fpu). The mechanical properties of the steel reinforcing bars are listed
concrete compressive strength was 35 MPa. See Figs. 2 and in Table 5. The tensile strength and equivalent yield strength
3 for their congurations. (fpy) of the low relaxation three-wire mono-strand were 2050
The mixtures of LWC for the test are listed in Table 2, and and 1852 MPa, respectively. The equivalent yield strength of
the material properties of lightweight aggregates are listed in the strand was calculated using measured nonlinear stress
Table 3. Test results of lightweight concrete mixture are strain curves according to ASTM A 416 (American Society
shown in Table 4. The designed compressive strength of the for Testing and Materials 1996). The yield strengths of the
ready-mixed concrete using lightweight aggregates was mild reinforcing bars with diameters of 10 and 6 mm were
35 MPa for all specimens. Articially expanded clay gran- 446 and 475 MPa, respectively.
ules with maximum sizes of 20 and 5 mm were used for
lightweight coarse and lightweight ne aggregates, respec- 2.2 Test Procedure and Measurement
tively. The lightweight ne aggregates were replaced with Each continuous one-way slab specimen was supported on
local natural sand by as much as 30 % by volume in order to hinges at both ends and on a roller at the center. The uniform
control the continuous grading. The average dry density of load was applied by universal testing machine (UTM) at a
1 220 4.9 15.1 30.4 36.7 38.7 39.3 3.19 0.53 2.81 0.46 11,614
2 230 4.7 13.5 24.1 29.2 30.5 31.9 2.62 0.49 3.15 0.58 13,442
3 242 5.2 16.7 29.4 35.2 38.5 39.3 2.53 0.47 2.91 0.49 11,280
428 | International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016)
(a) Group 1
(b) Group 2
Fig. 4 Section details and arrangement of reinforcing bars in specimens.
80 76 60 24 35
67 70 7680 70 68 68 70 47 47 45
S-L/d p=35 55 6064 75 71 68 45 79
47 67 60 68 60 49 60 75 64 75
73 73 55 43 80 47 60 60 70 70 71 76
(a) Group 1
25
S-PPR-0.5 36 36 35 38 35 30 34 34 34 34 35 35 28 35
37
34 31 30 29 29 29 29 28
30 30
58 64 585453615750 52 61 65 55 64 31 50 26 38
S-PPR-1.0 50 54 53 42 53 53 50 50 5959 5259 61 40
64 37 38 34 34 38 40 40 53 52 55 56 52 52 5559 50
64 64 50 56 4850 48 48 48 3459 3461 56 56
25 40 15
44 44 48 50 51 48 48 40 48 48 49 40 48 48 4855 55 55 48 20 15
S-PPR-1.5 43 40 40 31 4046 36 36 47 47 55 48 48 30 49 3540
44 44 43 43 43 40 48 47 47 40 48 36 48
(b) Group 2
Fig. 5 Crack development of each group.
International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016) | 429
Pcr cracking load, Py yielding load, Pn ultimate load, Vn force at failed span, Dcr, Dy, Dn deection at the rst exural crack, at yielding of mild longitudinal tensile reinforcement, and at the ultimate state, respectively, fps, D fps stress of prestressing strands and its
rate of 2.5 mm per minute. Linear variable differential
Mn-EXP/
Mn-ACI
1.35
1.32
1.22
0.97
1.22
1.32
transducers (LVDTs) were installed beneath the specimens at
the loading points to measure the vertical deection (Fig. 2).
0.0732
0.0713
0.0588
0.0398
0.0588
0.0728
The 200 kN capacity load cells were installed on both ends
gn
of specimens to trace the stress incremental in unbonded
tendons. The loading points and supports of each specimen
(kN m)
26.98
26.29
21.68
14.68
21.68
26.82
Mn
are described in Fig. 3 and the section details are shown in
Fig. 4. The crack width was measured from where the rst
0.123
0.095
0.130
0.114
0.116
0.116
cracks appeared until the reinforcing steels yielded. Electri-
x
cal resistance strain gages were attached to the surface of the
.
A fps As fy
concrete and the steel to check how the strain changes,
0.0401
0.0398
0.0332
0.0332
0.0365
0.0311
0
ef c
gcr
increase, Pn-ACI ultimate load predicted by ACI, Pn(ExP) ultimate load by experiment, gcr cracking moment capcity (=Mcr/f0 cbwh2), gn ultimate moment capcity (=Mn/f0 cbwh2), x reinforcing index p bd
especially when concrete reached its ultimate strain (0.003).
Concrete strain gages were installed on both compressive
(kN m)
14.77
14.68
12.25
12.25
13.43
11.46
and tensile area of the center and the edges of specimens.
Mcr
Wire strain gages were installed on rebars at intervals of d/2.
All data from the UTM, load cells, and gages were collected
Pn-EXP/
Pn-ACI
1.19
1.00
0.92
0.78
0.92
0.99
into a data logger and saved in a computer. Through the
process, the following information was obtained: crack
214.5
155.9
120.7
120.7
131.8
97.5
development pattern and failure mode; loaddisplacement
relationship; load-reaction relationship; load-tendon stress;
exural capacity; exural ductility; and curvature-prestress
1.40
1.97
3.25
2.16
3.25
3.03
loss.
256
256
132
132
132
132
3. Test Results
(MPa)
D fps
358
505
430
285
430
400
Table 6 Test results.
1613
1788
1669
1540
1669
1655
Group 1
Group 2
diagonal crack was found; that means in this test, that ex-
ural behavior was dominant. The maximum moment
48.8
85.3
95.8
113.6
165.8
165.8
occurred at the center supports of the slabs; therefore, cracks
were initiated at the upper parts of the center supports
(negative moment region) and then developed at the lower
13.0
31.1
36.8
14.0
36.8
57.5
parts of mid-spans (positive moment region). Due to the
reinforcing steels, the cracks maintained the same intervals
5.6
11.8
11.6
11.6
29.1
16.7
to each other, propagating towards the middle of the spans.
Upon reaching maximum loading, cracks also achieved their
maximum width at the center of the spans, while cracks at
Edge
50.1
29.4
22.3
14.1
22.3
24.0
48.3
33.2
23.9
33.2
40.9
Mid
155.5
111.1
111.1
129.9
gated until the peak loading was reached and then com-
pressive fractures were triggered. With the higher L/dp, the
Edge
89.8
64.2
43.3
24.4
43.3
55.0
37.8
46.6
25.7
46.6
34.1
Mid
65.7
46.1
30.4
28.4
30.4
33.3
23.5
14.7
14.7
14.7
25.5
Mid
S-PPR-1.0
S-PPR-1.5
S-L/dp-25
S-L/dp-35
S-L/dp-45
Specimen
430 | International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016)
Fig. 6 Load-deection relationship for each group.
Table 7 Comparison of experiments and standards for ultimate stress increment of unbonded tendons.
Specimen Experimental .
Dfps exp Dfps pre
fps (MPa) Dfps (MPa) ACI AASHTO CAN3
S-L/dp = 25 1613 358 1.38 1.14 0.66
S-L/dp = 35 1760 505 3.79 2.28 1.32
S-L/dp = 45 1669 430 3.22 2.45 1.42
S-PPR-0.5 1540 285 2.14 1.58 0.92
S-PPR-1.0 1669 430 3.22 2.45 1.42
S-PPR-1.5 1655 400 2.99 2.34 1.34
shown in Fig. 6a, as L/dp increased, the maximum exural 3.3 Stress of Unbonded Prestressing Tendons
strength of the slabs decreased and the ductility increased. In The relationship of the load and the unbonded prestressing
Group 2, as shown in Fig. 6b, specimen S-PPR-1.0 showed tendon stress was almost identical to that of the loadde-
excellent ductility while specimen S-PPR-0.5 reinforced with ection. Even after reaching the ultimate loading, the tendon
the least number of reinforcement among Group 2 specimens stresses increased continuously to bear the tension stress
showed compressive fracture after the reinforcement yielding. until the member failure. Figure 7a shows the effect of the L/
Specimen S-PPR-1.5 which is reinforced with 50 % more dp on the load-tendon stress relationship. As the L/dp
steel than required was less ductile than S-PPR-1.0 with 17 % increased, the ultimate stress in tendons decreased. Fig-
higher ultimate load. ure 7b shows the effects of the qs on the load-tendon stress
International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016) | 431
Fig. 8 Comparisons of measured and ACI318-11 predicted ultimate moment capacities.
relationship. All specimens in Group 2 showed similar stress AASHTO 1998 were in better agreement with the test results
increments until the initial crack happened. The maximum than ACI 318-11, showing that the mean, standard deviation,
stress of S-PPR-1.0 was higher than S-PPR-0.5, even higher and coefcient of variation of the ratios between measured
than S-PPR-1.5. The measured stress increase in unbonded and predicted stress increases (Dfps) are 1.70, 0.53, and 0.31,
tendons was higher than that from ACI and AASHTO respectively. The predictions obtained from CAN 3 were the
(Table 7). least conservative among three standards showing that the
mean, standard deviation, and coefcient of variation of the
3.4 Cracking and Ultimate Moment Capacities ratios between measured and predicted stress increases (Dfps)
The normalized cracking capacities, gcr =Mcr/(f0 cbwh2) are 1.10, 0.23, and 0.21, respectively. The ratios of measured
and the ultimate moment capacities, gn =Mn/(f0 cbwh2) of the to predicted incremental stresses are plotted against x
specimens are listed in Table 6. The gcr decreased as the L/dp accompanying with the NWC test results by Lim et al.
ratio increased in Group 1, and a higher gn was developed (1999) in Fig. 9. .
with an L/dp ratio of 25 than those with an L/dp ratio of 35 or In all cases, Dfps exp
Df ps .pre for LWC is less than that
45. In Group 2, gn increased in proportion to the qs. for NWC. Note that Dfps exp Dfps pre of specimen S-L/
In Fig. 7, the ultimate moment of the specimens, (Mn)Exp dp = 25, S-L/dp = 45, and S-PPR-0.5 in CAN 3 are less
is compared with the corresponding value predicted by the than one, while all NWC data are more than one.
ACI 318-11 design procedure, (Mn)Pre. The safety of the
ACI 318-11 provision is signicantly dependent on the
reinforcing index (x) and the loading type, but it is inde- 5. Conclusions
pendent of the L/dp ratio. However, a moment capacity
reduction was observed in the S-L/dp-45 of Group 1 To evaluate the exural capacity and the ductility of post-
(Fig. 8a). When qs is half of the requirement, the (Mn)Exp/ tensioned LWC continuous slabs, six specimens were tested
(Mn)Pre is less than unit (Fig. 8b). and compared with the design standards. Through the test
the followings have been found: (1) The initial crack hap-
pened at the center of negative moment and then developed
4. Comparison with Standards at the positive moment areas on both sides simultaneously;
(2) As the steel ratio in member section (qs) increased, the
In Table 7, the stress in prestressing steel (fps) and its width of the crack decreased while the number of micro
increment (Dfps) of each specimen are listed. Also, the cracks increased. Also the maximum capacity increased
experimental results were compared to the standards. while the ductility decreased; (3) As the span-to-effective
The mean and standard deviation of the ratios of the tendon depth ratio (L/dp) increased, the maximum strength
measured and predicted moment capacities of the post-ten- (Pu) decreased. The initial crack load (Pcr) and the yielding
sioned NWC beams are 1.05 and 0.22, respectively (Yang capacity (Py) also decreased while the deection increased
et al. 2013). Hence, the ACI 318-11 procedure for predicting with L/dp growth; (4) As the quantity of minimum required
the Mn value of post-tensioned exural members can be rebars increased, the initial crack load, yielding capacity, and
considered conservative for LWC. In other words, the ACI maximum strength increased; (5) Even after reaching the
318 design equations generally underestimated Dfps. The ultimate stress of exural members, the stress in the tendons
Dfps predictions from ACI 318 are as conservative as in continuously increased sharing the tensile stresses. The
NWC. In addition the predictions obtained from the stress increases stopped when the exural member nally
432 | International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016)
differences were not negligible quantity so it may cause
overdesign.
Open Access
References
International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016) | 433
Harajli, M. H. & Kanj, M. (1990). Experimental and analytical Oh, B. H., & Choi, Y. C. (2004). State-of-the-arts of prestressed
study of the behavior of concrete beams prestressed with concrete structures. Magazine of the Korea Concrete
unbonded tendons, Report No. CE/FSEL 90-02, University Institute, 16(1), 1221.
of Oklahoma, Norman, OK. Ozkul, O., Nassif, H., Tanchan, P., & Haraili, M. (2008).
Kayali, O. (2008). Fly ash lightweight aggregates in high per- Actional approach for predicting stress in beams with
formance concrete. Construction and Building Materials, unbonded tendons. ACI Structural Journal, 105(3),
22(12), 23932399. 338347.
Lim, J. H., Moon, J. H., & Lee, L. H. (1999). Experimental Tang, W. C., Lo, T. Y., & Chan, W. K. (2008). Fracture prop-
examination of inuential variables on unbonded tendon erties of normal and lightweight high-strength concrete.
stresses. Journal of Korea Concrete Instititute, 11(1), Magazine of Concrete Research, 60(4), 237244.
209219. Warwaruk, J., Sozen, M. A., & Siess, C. P. (1962). Investigation
Lou, T. J., & Xiang, Y. Q. (2007). Effects of ordinary tension of prestressed reinforced concrete for highway bridges,
reinforcement on the response of beams with unbonded part III: Strength and behavior in exure of prestressed
tendons. Advances in Structural Engineering, 10(1), concrete beams, Bulletin No. 464, Engineering Experiment
95109. Station, University of Illinois, Urbana, IL.
Manisekar, R., & Senthil, R. (2006). Stress at ultimate in Yang, K. H. (2010). Tests on lightweight concrete deep beams.
unbonded post tensioning tendons for simply supported ACI Structural Journal, 107(6), 663670.
beams: A state-of-the-art review. Advances in Structural Yang, K. H., & Mun, J. H. (2013). Flexural capacity and stress
Engineering, 9(3), 321335. in unbonded tendons of post-tensioned lightweight concrete
Mojtahedi, S., & Gamble, W. (1978). Ultimate steel stress in beams. Advances in Structural Engineering, 16(7),
unbonded prestressed concrete. Journal of Structural 12971310.
Division, ASCE, 104(ST7), 11591165. Yang, K. H., Mun, J. H., & Kim, G. H. (2013). Flexural behavior
Naaman, A. E., & Alkhairi, F. M. (1991). Stress at ultimate of post-tensioned normal-strength lightweight concrete one-
unbonded post-tensioned tendons. ACI Structural Journal, way slabs. Engineering Structures, 56, 12951307.
88(6), 683692.
434 | International Journal of Concrete Structures and Materials (Vol.10, No.4, December 2016)