MV switchgear / SM6
Reduce wear & tear, maximize Safety & Availability of your Electrical equipment
Your equipment needs regular check-ups in order to maintain its original level of
performance. Moreover, to ensure the maintenance is conducted in the optimal
way, it needs to be executed by skilled professionals.
PM103193
SM6 - MV switchgear
Visual inspection
Switchgear compartment
Busbars compartment
Connection / switchgear compartment
Operating mechanism cabinet
LV Control cabinet
Disassembly
Remove covers (LV Control cabinet, Operating mechanism cabinet, connection / switchgear)
Remove operating mechanism (if any)
Remove MV fuses
Contactor disconnection
Clean / Grease
Busbar compartment
Clean compartment / enclosure / busbars
Check presence of tension
Connection / switchgear compartment
Clean compartment / enclosure / clusters / earth disconnector splitters
Grease earth disconnector clusters / links / contacts
Operating mechanism
Clean mechanical links (do NOT grease)
Inspection
Inspection of auxiliaries (weldings, triggers, motors, )
Inspection of lockings
Inspection of latching system
Inspection of earthing interlock disconnector operating mechanism
Inspection of operating mechanism electrical connections (tightening, fixing), microcontacts
Busbar compartment
Inspection of enclosure (chalking, cracking, signs of heating)
Inspection of busbars (signs of heating, thightening)
Inspection of isolators (chalking, signs of heating)
Inspection of earth disconnector (cluster strength / tightening, mechanical operation)
Connection / switchgear compartment
Inspection of enclosure (chalking, cracking, signs of heating)
inspection of cables (chalking, heating signs) & connections (tightening, fixing)
Inspection of isolators (chalking, signs of heating)
Inspection of clusters contact pressure
Clean / inspection of Volt Trans (chalking, cracking, signs of heating)
Clean / inspection of Current transformers / toroids (chalking, signs of heating)
Inspection of MV fuses
Inspection of fuses fixing
Inspection of fuse caliber, general status (chalking, color, cracking, corrosion)
Inspection of clusters contact pressure
Tests
Check mechanical / electrical operation of operating mechanism
Check electrical opening/closing of disconnector / contactor / circuit-breaker
Check fuse disconnection system
Reassembly
Fix covers (LV Control cabinet, Operating mechanism cabinet)
Fusibles
Secure good fuse hublots location
Schneider Electric proprietary Predictive tools
ProDiag
ProCorona
ProFusion
IR Thermography (non proprietary tool)
(1) For normal operating conditions To be increased in severe atmospheres (corrosive, naval, offshore) according to Manufacturers after-sales services
(2) except CIT
Medium Voltage distribution maintenance service offer 03
Cubicles
Automatic Transfer
Frequency (1) / Performance Level
Fuses Contactor
Circuit Breaker
De-energized
Fuse Switch
Combination
Fuse Switch
Contactor
Metering
Y10
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Switch
system
L2 L2 L2 L2 L2 L2 L2 L2 L2 L2
L2 L2 L2 L2 L2 L2 L2 L2 L2 L2
L2 L2 L2 L2 L2 L2 L2 L2 L2 L2
L2 L2 L2 L2 L2 L2 L2 L2 L2 L2
L2 L2 L2 L2 L2 L2 L2 L2 L2 L2
L3 L3 L3
L3 L3 L3
L3 L3 L3
L3 L3 L3
L3 L3 L3
L3 L3 L3
L3 L3 L3
L3 L3 L3
L4 L4 L4
L4 L4 L4
L4 L4 L4
(2) L4 L4 L4
L4 L4 L4
L3 L3 L3
L3 L3 L3
L3 L3 L3
L3 L3 L3
L4 L4 L4
L3 L3 L3
L3 L3 L3
L3 L3 L3
L4 L4 L4
L3 L3 L3
L3 L3 L3
L3 L3 L3
L3 L3 L3
L4 L4 L4
L3 L3 L3
L3 L3 L3
L4 L4 L4
L3 L3 L3
L3 L3 L3
L3 L3 L3
L4 L4 L4
L4 L4 L4
L4 L4 L4
L3 L3 L3
Medium Voltage distribution maintenance service offer 04
Level of maintenance
Level 1 = Schneider Electric after-sales services or customer employee according to the manufacturer maintenance instruction
Level 2 = Schneider Electric after-sales services or certified customer employee according to the manufacturer maintenance
Level 3 = Schneider Electric after-sales services or qualified customer technician using the tools and measurement /
setting devices specified in the manufacturer maintenance instructions
Level 4 = Schneider Electric after-sales services only.