JUNE-2011
PROJECT: MIOT INTERNATIONAL
Issue Location Instruction Given Date Status
Description
Improper 1st Basement, Remove the cut -piece 01.07.2011 Pending
insulation of Zone-3 AHU insulation & re-execute
Ducts room covering all the areas.
Cut-piece should not be
used for insulation
Issue Location Instruction Given date Status
Description
Improper Ground Floor Remove the insulation & 01.07.2011 Pending
insulation of Zone-3 re-execute covering all
Ducts the areas
Issue Location Instruction Given date Status
Description
1.Improper Ground 1.Ducts to be aligned 01.07.2011 Pending
alignment & Floor Zone- horizontally & proper
support of 2 supports to be given.
HVAC ducts.
2.Duct resting 2. Minimum 100 mm gap to
on soil line be retained between
individual services line.
Issue Description Location Instruction Given date Status
Poor quality of Ground floor Avoid repeated & 28.06.11 Pending
welding in CHW Zone-2 & 1st uneven layers of
line. floor Zone -3 welding .
Painting is done Welding joints must
before grinding of be uniform, free of
welded joints slag, grinded ,cleaned
welding is getting & painted. Applicable
rusted for all welded joints in
site
Issue Description Location Instruction date Status
Given
Poor quality of Service Avoid repeated & 30.06.2011 Pending
welding in CHW line. building uneven layers of
welding is getting terrace welding .
rusted floor Welding joints
1st Floor must be uniform,
Zone-3 free of slag, grinded
,cleaned & painted.
Issue Description Location Instruction Given date Status
Defects found over Service Defected area of the 01.07.2011 Pending
CHW pipe surface building pipe must be cut and
terrace replaced by fresh
floor piece of pipe.
1st Floor Insulation is put on
Zone-3 hold till the
completion of this
job
Issue Description Location Instruction Given date Status
Defects & crack in EPS Ground Defected & cracked 01.07.2011 Pending
insulation for CHW Floor insulation to be
pipeline due to poor Zone-2 rectified or replaced
workmanship with fresh insulation.
CHW pipeline Minimum gap to be
touching the soil line. maintained between
Uneven insulation individual services
thickness, no aesthetics line
Issue Description Location Instruction Given date Status
CI pipes other than the Ground The subject pipes must 17.06.11 Pending
make approved by the Floor- be immediately
PMC are being erected Zone-3 removed.
at site. For any new
procurement
submission of
Specification , MIR
with DC & TC is
compulsory before
erection at site
Issue Description Location Instruction Given date Status