Raw Data Diagnosis Analytics

Sl # of Data Need Advance Sl # of Data Need Advance


Parameter Name Parameter Name
No. Points Analysis ? No. Points Analysis ?
1 Ambient Temperature 1 No 23 Inlet Temperatures 2 No
2 Oil Tempertaure 2 No 24 Outlet Temperatures 2 No
3 Winding Temperature 6 No 25 Fan Bank Motor Current 4 No
4 Direct Winding Hot Spot 16 No 26 Fan Motor Status 16 No
5 Main Tank Oil Level 1 No 27 Pump Motor Current 2 No
6 Oil Tank Pressure 1 No 28 Pump Status 2 No
7 Load Current 6 No 29 Flow Indicator 2 No
8 Load Voltage 6 No
30 Cooling Control Voltage 1 No
9 Dissolved Gases (PPM) 9 Yes
31 Cooling Supply Voltage 1 No
10 Dissolved Gases (RoC) 9 Yes
32 OLTC Tap Position 1 No
11 Moisture 1 Yes
33 OLTC Temperature 1 No
12 Main Tank Vibration 6 Yes
34 OLTC Oil Level 1 No
13 Buchholz Relay 1 No
35 OLTC Oil Pressure 1 No
14 Bladder Rupture Realy 1 No
15 Core ground current 1 No 36 OLTC Motor Current 1 No
16 GIC 1 Yes 37 OLTC Motor Voltage 1 No
17 Partial Discharge (Amplitude) 6 Yes 38 OLTC Motor Power Consumption 1 Yes
18 Partial Discharge (Discharge Rate) 6 Yes 39 OLTC Motor Torque 1 Yes
19 Bushing Tan Delta (PF) 6 Yes 40 OLTC Swithing time 1 Yes
20 Bushing Capacitance 6 Yes 41 PRD Status 2 No
21 Bushing Temperature 6 Yes 42 Smart Breather Data 2 No
22 Bushing Leakage Currennt 6 Yes 43 Nitrogen Pressure 1 No


Periodic
Monitoring

Offline Testing
Higher Frequency

Offline Testing


PERFOR COST
MANCE


RISK

Monitored Parameters
Major Fault

Gas accumulation relay

Total percent dissolved


Conditions

Ambient temperature

Multi-gas Gas analysis

Oil temp at moisture


Core hotspot (Fiber)

Pressure at Hot Spot


Core ground current

Top oil temperature


Critical for Fault Detection

Top and bottom oil


Excitation current

Winding hot spot


Moisture in oil

Tank vibration
temperatures
temperature

temperature
Load current
Moniotring increases Fault

Hydrogen

gas-in-oil
\location
UHF PD
Detection Probability

Overheating of laminations and/or core joints


Mag. Circuit

Loss of core ground

Unintentional core ground

Unintentional shield ground

Winding insulation general overheating

Winding insulation local overheating

Winding insulation excessive moisture


Winding

Winding insulation bubble generation

Winding insulation overloading of transformer

Winding insulation partial discharge

Winding loose
Monitored Parameters

Winding hot spot temperature


Oil temp at moisture \location

Motor (fan, pump) currents


Inlet and outlet radiator

Oil level in main tank or


Cooling control voltage
Major Fault

Cooling supply voltage


Bearing wear detector
Critical for Fault Detection

Ambient temperature

Multi-gas Gas analysis


Bladder rupture relay
Conditions

Core hotspot (Fiber)

Top oil temperature


Top and bottom oil
Nitrogen pressure
Moisture in oil
Moniotring increases Fault

temperatures

temperatures
temperature

Load current

conservator

Pump flow
Hydrogen
Detection Probability

UHF PD
Liquid insulation moisture contamination
Liquid

Liquid insulation arcing


Liquid insulation partial discharge

Pumps and fans electrical failures

Pumps and fans mechanical failure


Cooling

Cooling control inaccuracy of temperature sensors

Cooling controls failure


Pumps and fans running in reverse
Internal or external blocking of radiators (
dependent on all cooling rules pass )
Oil level drops, exposing the windings
Main Tank

Moisture contamination
Conservator tank bladder rupture
Loose connection
Monitored Parameters

Tan Delta (Power Factor)

Capacitance Absolute

LTC Operational Model


Ambient Temperature
Major Fault

Vibro-Acoustic Model
Absolute Value and

Bushing temperature
Conditions

Dissolved Gases (Oil


Critical for Fault Detection

LTC Motor Current

LTC Motor Torque


LTC Motor Power

LTC Temperature
Oil Pressure (OIP

Partial Discharge

Moisture Model
Bushings & LTC)

Bushings & LTC)

Switching Time
Consumption

Differential
Moniotring increases Fault

and RoC
Detection Probability

RoC
Overheating and Insulation Failure

Insulation Decay / Normal Aging


Bushings

Moisture in bushings

Bad Contact

Partial Discharge

Short Circuit in Capacitive Layers

OLTC contact Coking

OLTC Motor Drive Issues


OLTC

OLTC excessive Arcing

OLTC weak Insulation

OLTC multiple Tap Movement


OLTC Aging






Minimum Monitoring Comprehensive Minimum Monitoring Comprehensive
Monitoring Monitoring

Multi Gas DGA + Moisture Single Gas DGA + Moisture


Single Gas DGA (H2) + Moisture
Single Gas DGA (H2) + Moisture Thermal Models Thermal Models

Tank wall & OLTC Vibrations Thermal Models UHF PD Monitoring


Thermal Models Tank wall & OLTC Vibrations
Bushing Monitor (Ref. Method)
UHF PD Monitoring Bushing Monitoring (Ref. Method)
OLTC Operation Model
Tank wall & OLTC Vibrations
Gas Accumulation Rate
Gas Accumulation Rate Tank wall & OLTC Vibrations
Load Currents and Voltages
Bushing Monitoring (Reference
Method) Load Currents and Voltages Bushing Monitoring (Reference
Core Ground Current
Method)
Core Ground Current Inrush and Fault Currents
OLTC Operation Model OLTC Operation Model
Inrush and Fault Currents OLTC Operation Model




Mag Circuit
90
80
70
LTC 60 Winding
50
40
30
20

10
0

Bushing Main Tank


Liquid Cooling

Failure Risk



Enterprise Asset Condition
Monitoring System for monitoring Continuous Online Condition Monitoring
Systems (IEDs) DASHBOARDS
multiple assets in utility network Top 10 Critical Assets (Risk Index)
Top 10 Critical Substations

Central data collections for all assets Web based DB


for Offline tetsing
Asset Management System
Presentation Layer

Utility databases and systems e.g.


CASCADE, MAXIMO, SharePoint etc. User
Interface
Remote
Access
Email/
SMS
SCADA

Offline Testing Data e.g. TOA, DTA, Analytics & Reporting


Smart
Reporting
SmartPDM

SmartITM

Power DB etc. Customer


Specific SmartGDM SmartDGA

INTEGRATION INTERFACE Analysis SmartBM SmartLTC

Data historian and SCADA system


Models SmartCSM

Qualirols Health
Index Models
Continuous Online Monitoring Devices Data Layer

at assets; Qualitrol or Third-Party Database


Database
Database

Devices (IEDs) Nameplate

Advanced analytical models Offline Test


Results
Inspection
Records Spreadsheets
CASCADE Historian SCADA
AUTOMATED
Asset Health Index list

Asset Specific Analysis, AHI, CI, RI










Core Analytics (AHI, PoF)

at Central Location

Data flow

Transformer Monitor Asset Specific Analytics at


(Data Aggregator / Gateway)
the Monitor (Edge)



Bushing Other Basic
PD Sensors FO Sensors DGA
Sensors Sensors