GHR

Dehumidiers for radiant cooling systems with


heat recovery
GHR

The units have been designed to dehumidify both in neutrum VERSIONS


air, that is at the same temperature at which its taken, and
with cooled air, managing very small air ows and avoiding Version suitable for swimming pool installation:
so the annoying typical air currents of the traditional air Supplied with painted frame and heat exchangers
suitable for swimming pool
conditioning systems.
WZ version: Units supplied with double condenser
The dehumidiers with heat recovery, series GHR, are the (the rst is an air condenser, the second is a water
best ones for residential building or for small factories. The one) and of a logic which allows the dehumidication
units can adapt to any kind of ambient since they are very with neutrum air or with cooled air.
silent and versatile.

ACCESSORIES

Remote mechanical hygrostat


Remote mechanical hygrostat + thermostat (WZ
versions only)

18
GHR
Mod. GHR25 GHR25WZ GHR50 GHR50WZ
Moisture removed (1) l/24h 20,1 20,1 48,5 48,5

GHR
(1)
Cooling capacity W --- 1250 --- 3500
Nominal input power (1) W 340 340 700 700
(2)
Maximum input power W 450 450 800 800
Nominal input current (1) A 2,5 2,5 4,6 4,6
(2)
Maximum input current A 2,8 2,8 4,9 4,9
l/h 150 --- 500 ---
Cold water coils
kPa 8 --- 17 ---
l/h --- 150 --- 500
Condenser waterow
kPa --- 7,8 --- 22
Air ow m3/h 250 250 600 600
Available static pressure (max. speed) Pa 35 35 60 60
Refrigerant R134a R134a R407C R407C
Sound pressure (3) dB(A) 39 39 44 44
Temperature operating range C 15-35 15-35 15-35 15-35
Campo di lavoro umidit % 40-99 40-99 40-99 40-99
Weight Kg 35 37 52 55
Power supply V/Ph/Hz 230/1~/50

Mod. GHR100 GHR100WZ GHR100 GHR100WZ


Moisture removed (1) l/24h 87,2 87,2 164 164
(1)
Cooling capacity W --- 6000 --- 11300
Nominal input power (1) W 1450 1450 2450 2450
(2)
Maximum input power W 1600 1600 2950 2950
Nominal input current (1) A 7 7 13,5 13,5
Maximum input current (2) A 8,8 8,8 15 15
l/h 600 --- 900 ---
Cold water coils
kPa 32 --- 48 ---
l/h --- 600 --- 900
Condenser waterow
kPa --- 39,5 --- 64
Air ow m3/h 1000 1000 1850 1850
Available static pressure (max. speed) Pa 75 75 120 120
Refrigerant R407C R407C R407C R407C
Sound pressure (3) dB(A) 51 51 58 58
Temperature operating range C 15-35 15-35 15-35 15-35
Campo di lavoro umidit % 40-99 40-99 40-99 40-99
Weight Kg 87 90 115 120
Power supply V/Ph/Hz 230/1~/50

1)
Performances refer to the following conditions: Room temperature 26C; relative humidity 65% with cold water coil water inlet temp. 15C.
2)
Performances refer to the following conditions: room temperature 35C; relative humidity 80%.
3)
Sound pressure level measured at 1 mt from the unit in free eld conditions according to ISO 3746, minimum fan speed.

www.hidros.it
19
GHR
FRAME PRE AND POST WATER COOLING ELECTRIC BOX
All units GHR series are made from hot- COILS The electric switch board is made accor-
galvanised thick sheet metal, to ensure the The pre and post cold water coils are made ding to electromagnetic compatibility norms
best resistance against the corrosions. The of copper pipes and aluminium ns. The CEE 73/23 and 89/336. The accessibility to
GHR

frame is self-supporting with removable pa- diameter of the copper pipes is 3/8 and the the board is possible after removing the
nels. The drip tray is present standard in thickness of the aluminium ns is 0,1 mm. front panel of the unit. Ready for the con-
all units and is made of plastic material for The tubes are mechanically expanded into nection to the power and to the consensus
model 25 and in metal material for models the aluminium ns to improve the heat ex- control, The terminal board is also supplied
50-100-200. change factor. The pre-cooling coil is used with voltage free contacts for remote ON-
to increase the dehumidication capacity of OFF. The terminal block is also built with
REFRIGERANT CIRCUIT the unit, while the post-cooling coil is used a clean contact to allow the operation of
The refrigerant circuit is made by using in- to keep the outlet air temperature at the single-mode ventilation, while the second
ternational primary brands components and same inlet value. In WZ version only the for the cooling version (WZ). By closing the
according to ISO 97/23 concerning welding pre cooled water coil is present. rst contact, only the fan is abled to work,
procedures. The refrigerant gas used in while the dehumidication is disabled.
these units is R134a for the model 25 and SUPPLY FAN
R407C for the models 50-100-200.The re- The supply fan is centrifugal type, double
frigerant circuit includes: lter drier, capilla- inlet with forwards blades, dynamically and
ry expansion device, Schrader valves for statically balanced and directly connected
maintenance and control, pressure safety to a 3 speed fan motor.
device (according to PED regulation).
RECOVERY
COMPRESSOR Aluminium crossed ow plate recovery, with
The compressor (for model 25) is alterna- efciency > of 60%, supplied with stainless
tive or rotative type (for models 50-100- steel condensate drip tray.
200), equipped with crankcase heater and
thermal overload protection by a klixon em- RECOVERY FAN
bedded in the motor winding. Its mounted The recovery fan is centrifugal type, double
on rubber vibration dampers to reduce the inlet with forwards blades, dynamically and
noise. statically balanced and directly connected
to a 3 speed fan motor.
CONDENSER AND EVAPORATOR
The condensers and evaporators are made AIR FILTER
of copper pipes and aluminium ns. The For the model GHR 25-50 its supplied
diameter of the copper pipes is 3/8 and standard with the unit and its built in nylon.
the thickness of the aluminium ns is 0,1 It can be removed for differential disposal,
mm. The tubes are mechanically expan- class G2, according to EN 779:2002.
ded into the aluminium ns to improve Regarding the model GHR 100-GHR 200
the heat exchange factor. The geometry instead, its made of ltering material in
of these condensers guarantees a low air synthetic bre without electrostatic charge.
side pressure drop and then the use of low It can be removed for differential disposal,
rotation (and low noise emission) fans. All class G3, according to EN 779:2002
the units have a stainless steel drip tray.
Besides this, each evaporator is supplied MICROPROCESSOR
of a temperature probe used as automatic All units GHR are supplied standard with
antifreeze probe. In all units WZ besides microprocessor controls. The microproces-
these exchangers, there is a third stainless sor controls the following functions: com-
steel INOX AISI 316 plate exchanger used pressor timing, automatic defrost cycles
us condenser in cooling modality. and alarms. An appropriate LCD display
shows the operation mode of the unit, set
point and alarms.

20
GHR
REFRIGERANT CIRCUIT STANDARD ter than the air in inlet. so that to avoid to send air in the ambient in
VERSION neutrum thermic conditions.
REFRIGERANT CIRCUIT WZ VERSION
The functioning of the dehumidier model Dehumidication with cooling mode.

GHR
GHR is as follows: the fan takes the air from The operation of the dehumidier model GH The unit condensates the 100% in water
the ambient (7) and its made go through the is as follows: the fan takes the air from the through the heat exchanger (10). The air,
lter (1) and the pre-cooling water coil (2) ambient (7) and its made go through the then, go through the condenser (5) (disa-
where its cooled and brought to a condition lter (1) and the pre-cooling water coil (2) bled) where does not change its characteri-
closed to saturation. Now it passes through where its cooled and brought to a condition stics (temperature and humidity).
the evaporating coil (3) where its fatherly closed to saturation. Now it passes through
cooled and dehumidied. The air passes the evaporating coil (3) where its fatherly
now through the condensing coil (5) where cooled and dehumidied.
its post heated (with a constant humidity) At this point there are two possible moda-
and in the post-cooling coil (6) where its lities:
reported to the required conditions.
All the dehumidiers model GHR can work Dehumidication mode.
without the help of the pre and post cooling The air passes now through the conden-
coils. This function is very useful in case sing coil (5) which allows to condensate the
there is the request of dehumidication in 50% of the total gas, (the unit condensate
middle-season or when the chiller is off. the 50% on air with the heat exchanger
Obviously, if the unit works without the help (5) and the 50% in water with the heat ex-
of the cold water, the air in outlet will be hot- changer (10)) then there is the post-heating

Main Components
Refrigerant circuit
GHR

3 5 6
7

1 2 9 8

4
Return air for
recirculation
Supply air outlet

Exhaust air Refrigerant circuit


GHRWZ

Fresh air inlet Exhaust air 3 5


7

1 2
9 8

10

1 Air lter 6 Post-cooling coil 4

2 Pre-cooling coil 7 Fan


3 Evaporator 8 Dry lter
4 Compressor 9 Expansion device
5 Condenser 10 Water condenser

www.hidros.it
21
GHR
RECIRCULATION MODE
GHR

Setting this function, the unit will make the midied and post-heated in the post- coil Winter operation
ambient air re-circle only through the dehu- supplied with hot water). Dehumidication with double condensation
midier part. Only air heating (by closing the fan contact (a part in the air and part in the water throu-
This setting allows the following functions: and supplying the hot water coils, the unit gh the plate condenser, dehumidied and
will make the re-circle and the heating of neutrum air).
GHR VERSION the air through the coils supplied with hot Dehumidication + with only air heating (by
water). closing the fan contact and supplying the
Summer function hot water coils, the unit will make the re-
Dehumidication without water on the pre- circle and the heating of the air through the
post treatment coils (air dehumidied and GHR/WZ VERSION coils supplied with hot water). Integration in
heated by the condensing heat). heating.
Dehumidication with water on the pre-post Summer function
treatment coils (dehumidied and neutrum Dehumidication with double condensation
air). (a part in the air and part in the water throu-
gh the plate condenser, dehumidied and
Winter operation neutrum air.
Dehumidication without water on the pre- Dehumidication with 100% of the conden-
post treatment coils (air dehumidied and sation in water.
heated by the condensing heat).
Dehumidication + integration in heating
with hot water on the post-coil (air dehu-

Fresh air inlet


Exhaust air

Exhaust air
Supply air
outlet

Return air for


recirculation

FRESH AIR MODE

By setting this function, the unit will renew Winter operation GHR/WZ VERSION
the room air with the ambient air through Renew - Dehumidication without water on
the heat recovery. the pre-post treatment coils (air dehumidi- Summer function
The possible functions are: ed and heated by the condensing heat) Dehumidication with double condensation
Renew-Dehumidication+integration in he- (a part in the air and part in the water throu-
GHR VERSION ating with hot water on the post-coil (air de- gh the plate condenser, dehumidied and
humidied and post-heated in the post- coil neutrum air.
Summer function supplied with hot water). Renew + Dehumidication with 100% of
Renew+ Dehumidication without water on Dehumidication + with only air heating (by the condensation in water (dehumidied
the pre-post treatment coils (air dehumidi- closing the fan contact and supplying the and cooled air).
ed and heated by the condensing heat). hot water coils, the unit will make the re-
Renew + Dehumidication with water on circle and the heating of the air through the
the pre-post treatment coils (dehumidied coils supplied with hot water).
and neutrum air).

22
GHR
Winter operation hot water coils, the unit will make the re-
Renew + Dehumidication with double con- circle and the heating of the air through the
densation (a part in the air and part in the coils supplied with hot water). Integration in
water through the plate condenser, dehu- heating.

GHR
midied and neutrum air.
Dehumidication + with only air heating (by
closing the fan contact and supplying the
Fresh air inlet
Exhaust air

Exhaust air
Supply air
outlet

Return air for


recirculation

Mod. GHR25 GHR25WZ GHR50 GHR50WZ


Fresh air + recirculation dampers, supplied with on-off
servomotor
Remote mechanical hygrostat + thermostat

Mod. GHR100 GHR100WZ GHR200 GHR200WZ


Fresh air + recirculation dampers, supplied with on-off
servomotor
Remote mechanical hygrostat + thermostat

Standard, Optional, Not Available.

Mod. A (mm) B (mm) C (mm)


25 253 1546 698
50 353 1821 700
100 394 1991 847
200 469 2444 1094
25WZ 253 1546 698
50WZ 353 1821 700
100WZ 394 1991 847
200WZ 469 2444 1094