LOAD CALCULATIONS

Job No. : Rev. No. : R0


Project : Date : 31/10/2017
Clint : Designed by : SANDEEP
Description : LOADS APPLIED ON THE MAIN FRAME-1 Checked by :
Building Type =
Length (o/o) = 82.00 m
Width (o/o) = 40.50 m
Width module =
Bay spacing = 7.00 m
Clear eave height = 7.00 m
Max. eave height = 8.00 m
Roof slope () = 5.71
DEAD LOAD (DL)
Wt. of sheet & purline = 15.00 Kg/m
Dead Load (DL) = 1.05 KN/m

COLLATERAL LOAD
Collateral Load on Rafter = 0.00 Kg/m Other Collateral Load = 0.00 Kg/m
= 0.00 KN/m = 0.00 KN/m

LIVE LOAD (LL)


Live load/unit area, roof = 75.00 Kg/m
Live Load (LL) = 5.25 KN/m

WIND LOAD (WL)


Basic wind speed (Vb) = 39 m/s
Design wind speed (Vz) = Vbxk1xk2xk3
where,
k1 = probability factor (risk coefficient)
= 1 Terrain Category Class
k2 = terrain, height and structure size factor 2 B
= 0.93
k3 = topography factor
= 1
Vz = 36.27 m/s

Design wind pressure (pz) = 0.6xVz


pz = 0.789 KN/m

PRESURE COEFFICIENTS:~
Encloser condition of the building = Enclosed
Internal pressure coeff.(Cpi) = 0.20

h/w = 0.20
= h/w<=1/2
l/w = 2.02
= 3/2<=l/w<4
External pressure coeff.(Cpe) : Table 4 Table 5
Wind Angle Coeff. For Wall Coeff. For Roof
()
Left Right Left Right
0 degree 0.70 -0.25 -0.9350 -0.40
90 degree -0.50 -0.50 -0.80 -0.80

WIND LOAD DIAGRAMS:~

Wind Across the Ridge (With -Ve Cpi) Wind Across the Ridge (With +Ve Cpi)
KN/m
-0.74 -4.06 KN/m -0.20 -1.11 KN/m -1.14 -6.271 KN/m -0.60 -3.32

KN/m KN/m KN/m KN/m


4.97 -0.28 2.76 -2.49
0.90 -0.05 0.50 -0.45

Wind Parallel to Ridge(With +Ve Cpi)


-1.00 -5.53 KN/m -1.00 -5.53 KN/m

KN/m KN/m
-3.87 -3.87
-0.70 -0.70

Wind Parallel to Ridge(With -Ve Cpi)


-0.60 -3.32 KN/m -0.60 -3.32 KN/m

KN/m KN/m
-1.66 0.00
-0.30 -0.30
Note:
1) Values within the circles are the UDL
2) -Ve value means, load applied
away from structure.