SWITCHYARD BATTERY SIZING CALCULATION

0-1ST MINUTE LOAD 2nd (min) -10th (hr) LOAD


SL. NO. DESCRIPTION LOAD (WATTS) AMPS TOTAL NO. REMARKS
QTY. AMPS QTY. AMPS
Time Duration in Minutes 1 MIN 599 MIN

400kV Control Panel 5

Quantity for annunciators, auxiliary relays, etc only 50% considered


1 Semaphore 0.4 0.002 13 65 0.13 65 0.13
for DC load, since all are not continuously in operation.

2 Annunciator 12 0.05 1 3 0.16 3 0.16

3 Multifunction meter 4 0.02 19 95 1.73 95 1.73

4 Auxiliary relay 3 0.01 2 5 0.07 5 0.07

5 Indicating lamps 2.5 0.01 32 80 0.91 80 0.91


RD

6 Transducers 0.25 0.00 19 48 0.05 48 0.05


Discrepancy control switch with built in LED lamp &
7 2.5 0.01 14 35 0.40 0 0.00
flasher relay

Synchronising Trolley (400KV & 220KV) 2

1 Multifunction meter 4 0.02 2 4 0.07 0 0.00

2 Synchroscope 4 0.02 1 1 0.02 0 0.00

3 Indicating lamps 2.5 0.01 5 5 0.06 0 0.00

4 Check synchronising relay 3 0.01 1 2 0.03 0 0.00

5 Auxiliary relay - synchronising schemes 3 0.01 1 2 0.03 0 0.00

400kV Line Relay Panel 6

a Relays

1 Auxiliary relay contact multiplication 3 0.01 2 6 0.08 6 0.08

2 Trip coil supervision relay 19.5 0.09 6 36 3.19 36 3.19

RD
3 Numerical distance protection relay 26 0.12 2 12 1.42 12 1.42

4 Auxiliary relay 3 0.01 5 12 0.16 12 0.16

5 DC supply supvn relay 3 0.01 2 12 0.16 12 0.16

6 high speed inter trip relay 150 0.68 3 0 0.00 0 0.00 Busbar tripping relays are considered for worst condition.

7 High/Low burden tripping relay 150 0.68 6 0 0.00 0 0.00

8 Auxiliary relay - carrier healthy 3 0.01 2 12 0.16 12 0.16

9 Contact multiplication relay 20 0.09 4 6 0.55 6 0.55

10 Auxiliary relay - Direct trip received 3 0.01 2 6 0.08 0 0.00

11 AC supply supvn relay 3 0.01 3 18 0.25 18 0.25

12 Numerical interconnection protection relay 18 0.08 1 6 0.49 6 0.49

13 Bay Control unit 40 0.18 1 6 1.09 6 1.09


SWITCHYARD BATTERY SIZING CALCULATION

0-1ST MINUTE LOAD 2nd (min) -10th (hr) LOAD


SL. NO. DESCRIPTION LOAD (WATTS) AMPS TOTAL NO. REMARKS
QTY. AMPS QTY. AMPS

400kV ICT Relay Panel 1

a Relays

1 Trip coil supervision relay 19.5 0.09 6 6 0.53 6 0.53

2 Auxiliary relay 3 0.01 10 5 0.07 5 0.07

3 Numerical feeder management relay 14 0.06 3 3 0.19 0 0.00

4 DC supply supvn relay 3 0.01 2 2 0.03 2 0.00

5 High speed tripping relay 150 0.68 4 4 0.00 0 0.00 Busbar tripping relays are considered for worst condition.

6 Numerical diff protection relay type 41 0.19 2 2 0.37 2 0.37

7 Contact multiplication relay 20 0.09 4 1 0.09 1 0.09

8 Bay Control unit 40 0.18 1 1 0.18 1 0.18

9 Auxiliary rely - CB manual trip 3 0.01 1 1 0.01 1 0.01

3 DC change over relay 3 0.01 2 1 0.01 0 0.00

ICT RTCC PANEL - 5.50 1 1 5.50 1 5.50

C 400kV GT Relay Panel 2

a Relays

1 Trip coil supervision relay 19.5 0.09 6 12 1.06 12 1.06

2 Auxiliary relay 3 0.01 9 9 0.12 9 0.12

3 DC change over relay 3 0.01 2 1 0.01 0 0.00

4 DC supply supvn relay 3 0.01 2 4 0.05 4 0.05

5 High speed tripping relay 150 0.68 2 4 0.00 0 0.00 Busbar tripping relays are considered for worst condition.

6 Numerical over hang protection relay type 41 0.19 1 2 0.37 2 0.37

7 Contact multiplication relay 20 0.09 7 3 0.27 3 0.27

8 Trip relay contact multiplication 20 0.09 2 2 0.18 0 0.00

9 Bay Control unit 40 0.18 1 2 0.36 2 0.36

400kV Reactor Relay Panel 2

a Relays

1 Trip coil supervision relay 19.5 0.09 6 12 1.06 12 1.06

2 Auxiliary relay 3 0.01 6 6 0.08 6 0.08

3 Auxiliary relay - CB manual close/trip 3 0.01 1 2 0.03 2 0.03


SWITCHYARD BATTERY SIZING CALCULATION

0-1ST MINUTE LOAD 2nd (min) -10th (hr) LOAD


SL. NO. DESCRIPTION LOAD (WATTS) AMPS TOTAL NO. REMARKS
QTY. AMPS QTY. AMPS

4 Breaker failure relay 3 0.01 1 2 0.03 0 0.00

5 DC supply supvn relay 3 0.01 2 4 0.05 4 0.05

6 High speed tripping relay 150 0.68 2 4 0.00 0 0.00 Busbar tripping relays are considered for worst condition.

7 Numerical diff protection relay type 41 0.19 1 2 0.37 2 0.37

8 Numerical feeder management relay 14 0.06 1 1 0.06 1 0.06

9 Contact multiplication relay 20 0.09 3 1 0.09 1 0.09

10 Bay Control unit 40 0.18 1 2 0.36 2 0.36

11 DC change over relay 3 0.01 2 1 0.01 0 0.00

400kV Bus Bar Relay Panel 1

a Relays

1 High speed trip relay 150 0.68 15 15 10.23 0 0.00

2 Auxiliary relay 3 0.01 10 5 0.07 5 0.07

3 DC supply supervision relay 3 0.01 2 2 0.03 4 0.05

4 Numerical integrated busbar protection relay 43 0.20 4 4 0.78 4 0.78

3 DC change over relay 3 0.01 2 1 0.01 0 0.00

400kV Tie Relay Panel 5

a Relays

1 High speed tripping relay 150 0.68 1 5 0.00 0 0.00 Busbar tripping relays are considered for worst condition.

2 Trip coil supervision relay 19.5 0.09 6 30 2.66 30 2.66

3 Breaker failure relay 3 0.01 1 3 0.04 0 0.00

4 Contact multiplication relay 20 0.09 3 4 0.36 4 0.36


RD
5 Auxiliary relay 3 0.01 3 8 0.11 6 0.08

6 Auxiliary relay - CB manual close/trip 3 0.01 2 5 0.07 4 0.05

7 DC supply supvn relay 3 0.01 2 10 0.14 8 0.11

8 Bay Control unit 40 0.18 1 5 0.91 5 0.91

9 DC change over relay 3 0.01 2 3 0.04 0 0.00

10 Numerical distance protection relay 26 0.12 1 5 0.59 5 0.59

Metering Panel 1

1 Multifunction meter 4 0.02 13 13 0.24 13 0.24

2 DC supply supvn relay 3 0.01 2 2 0.03 2 0.03

3 DC change over relay 3 0.01 2 1 0.01 0 0.00


SWITCHYARD BATTERY SIZING CALCULATION

0-1ST MINUTE LOAD 2nd (min) -10th (hr) LOAD


SL. NO. DESCRIPTION LOAD (WATTS) AMPS TOTAL NO. REMARKS
QTY. AMPS QTY. AMPS

Station Auxiliary Panel 1

1 Bay Control unit 40 0.18 1 1 0.18 1 0.18

400KV CB TRIPPING COIL 1 & 2 FOR ALL PHASE


2 300 1.3636 3 42 57.27 0 0.00
DUE TO BUSBAR PROTECTION

220kV Line Control Panel 2

1 Semaphore 0.4 0.002 3 6 0.01 3 0.01

2 Annunciator 12 0.05 3 3 0.16 3 0.16

3 Multifunction meter 4 0.02 6 12 0.22 12 0.22

4 Indicating lamps 2.5 0.01 8 8 0.09 8 0.09

6 Transducers 0.25 0.00 9 18 0.02 18 0.02


Discrepancy control switch with built in LED lamp &
7 2.5 0.01 5 10 0.11 0 0.00
flasher relay

220kV Line Relay Panel 2

a Relays

1 Auxiliary relay contact multiplication 3 0.01 5 5 0.07 3 0.04

2 Trip coil supervision relay 19.5 0.09 6 12 1.06 6 0.53

3 Numerical distance protection relay 26 0.12 2 4 0.47 2 0.24

4 Auxiliary relay 3 0.01 3 3 0.04 1 0.01

5 DC supply supvn relay 3 0.01 1 2 0.03 1 0.01

6 high speed inter trip relay 150 0.68 3 0 0.00 0 0.00 Busbar tripping relays are considered for worst condition.

7 High/Low burden tripping relay 150 0.68 6 0 0.00 0 0.00 Busbar tripping relay is considered for worst condition.

8 Auxiliary relay - carrier healthy 3 0.01 2 4 0.05 2 0.03

9 Contact multiplication relay 20 0.09 6 3 0.27 1 0.09

10 Auxiliary relay - Direct trip received 3 0.01 2 2 0.03 1 0.01

11 Trip coil supervision relay 19.5 0.09 3 6 0.53 3 0.27

12 Contact multiplication relay 20 0.09 1 1 0.09 1 0.09

13 DC supply supvn relay 3 0.01 1 2 0.03 2 0.03

14 Numerical interconnection protection relay 18 0.08 1 2 0.16 2 0.16

15 Bay Control unit 40 0.18 1 2 0.36 2 0.36

16 DC change over relay 3 0.01 2 1 0.01 0 0.00

220kV ICT Control Panel 1

1 Semaphore 0.4 0.002 3 3 0.01 2 0.00

2 Annunciator 12 0.05 3 2 0.11 1 0.05


SWITCHYARD BATTERY SIZING CALCULATION

0-1ST MINUTE LOAD 2nd (min) -10th (hr) LOAD


SL. NO. DESCRIPTION LOAD (WATTS) AMPS TOTAL NO. REMARKS
QTY. AMPS QTY. AMPS

3 Multifunction meter 4 0.02 6 6 0.11 6 0.11

4 Indicating lamps 2.5 0.01 8 4 0.05 2 0.02

5 Transducers 0.25 0.00 6 12 0.01 9 0.01


Discrepancy control switch with built in LED lamp &
6 2.5 0.01 5 10 0.11 0 0.00
flasher relay

220kV ICT Relay Panel 1

a Relays

1 Trip coil supervision relay 19.5 0.09 6 6 0.53 3 0.27

2 Contact multiplication relay 20 0.09 7 3 0.27 3 0.27

3 Auxiliary relay 3 0.01 3 1 0.01 1 0.01

4 DC supply supvn relay 3 0.01 2 2 0.03 2 0.03

5 Bay Control unit 40 0.18 1 1 0.18 1 0.18

6 DC change over relay 3 0.01 2 1 0.01 0 0.00

220kV Bus Coupler Control Panel 1

1 Semaphore 0.4 0.002 3 3 0.01 2 0.00

2 Annunciator 12 0.05 3 2 0.11 2 0.11

3 Multifunction meter 4 0.02 9 9 0.16 6 0.11

4 Indicating lamps 2.5 0.01 8 4 0.05 4 0.05

6 Transducers 0.25 0.00 7 7 0.01 7 0.01


Discrepancy control switch with built in LED lamp &
7 2.5 0.01 3 3 0.03 0 0.00
flasher relay

220kV Bus Coupler Relay Panel 1

a Relays

1 Trip coil supervision relay 19.5 0.09 6 6 0.53 3 0.27

2 Numerical feeder management relay 14 0.06 1 1 0.06 1 0.06

3 Contact multiplication relay 20 0.09 3 2 0.18 2 0.18

4 Auxiliary relay 3 0.01 3 2 0.03 2 0.03

5 DC supply supvn relay 3 0.01 2 2 0.03 2 0.03

6 High speed tripping relay 150 0.68 1 1 0.00 0 0.00 Busbar tripping relays are considered for worst condition.

7 Bay Control unit 40 0.18 1 1 0.18 1 0.18

8 DC change over relay 3 0.01 1 1 0.01 0 0.00

220kV Bus Transfer Relay Panel 1


SWITCHYARD BATTERY SIZING CALCULATION

0-1ST MINUTE LOAD 2nd (min) -10th (hr) LOAD


SL. NO. DESCRIPTION LOAD (WATTS) AMPS TOTAL NO. REMARKS
QTY. AMPS QTY. AMPS

a Relays

1 High speed tripping relay 150 0.68 1 1 0.00 0 0.00 Busbar tripping relays are considered for worst condition.

2 Trip coil supervision relay 19.5 0.09 6 6 0.53 4 0.35

3 Auxiliary relay contact multiplication 3 0.01 2 1 0.01 1 0.01

4 Contact multiplication relay 20 0.09 4 2 0.18 1 0.09

5 Auxiliary relay 3 0.01 3 1 0.01 1 0.01

6 AC supply supvn relay 3 0.01 2 2 0.03 1 0.01

7 Bay Control unit 40 0.18 1 1 0.18 1 0.18

3 DC change over relay 3 0.01 2 1 0.01 0 0.00

220kV Bus Transfer Control Panel 1

1 Semaphore 0.4 0.002 3 3 0.01 2 0.00

2 Annunciator 12 0.05 3 2 0.11 1 0.05

3 Indicating lamps 2.5 0.01 8 4 0.05 3 0.03


Discrepancy control switch with built in LED lamp &
4 2.5 0.01 4 4 0.05 0 0.00
flasher relay

220kV Bus Bar Relay Panel 1

a Relays

1 Integrated busbar protection - peripheral unit 37 0.17 6 6 1.01 6 1.01

2 DC supply supvn relay 3 0.01 2 2 0.03 2 0.03

3 Numerical Integrated busbar protection - central unit 43 0.20 2 2 0.39 2 0.39

3 DC change over relay 3 0.01 2 1 0.01 0 0.00

1 High speed tripping relay 150 0.68 10 0 0.00 0 0.00

Metering Panel 1

1 Multifunction meter 4 0.02 13 13 0.24 7 0.13

2 DC supply supvn relay 3 0.01 2 2 0.03 1 0.01

3 DC change over relay 3 0.01 2 1 0.01 0 0.00

220KV CB TRIPPING COIL 1 & 2 FOR ALL PHASE


2 300 1.3636 3 0 0.00 0 0.00
DUE TO BUSBAR PROTECTION

EMERGENCY DC LIGHTING 4500 20.4545 1 1 20.45 1 20.45


SWITCHYARD BATTERY SIZING CALCULATION

0-1ST MINUTE LOAD 2nd (min) -10th (hr) LOAD


SL. NO. DESCRIPTION LOAD (WATTS) AMPS TOTAL NO. REMARKS
QTY. AMPS QTY. AMPS

DC Supply for 415V SWYD PMCC

1 Tripping coil 150 0.68 3 3 2.05 0 0.00

2 Tripping relay 15 0.07 3 3 0.20 0 0.00

3 Indicating lamps 2.5 0.01 21 9 0.10 9 0.10

4 Auxiliary relay 5 0.02 6 3 0.07 3 0.07

5 Spring charging motor 350 1.59 3 1 1.59 0 0.00

7 Numerical Protection relay 10 0.05 3 3 0.14 3 0.14

8 Annunciator 10 0.05 1 1 0.05 0 0.00

9 Transducers 6 0.03 9 9 0.25 9 0.25

C DCDB

1 Indicating lamps 2.5 0.01 7 2 0.02 3 0.03

2 Transducers 5 0.02 3 3 0.07 3 0.07

3 Multifunction meter 5 0.02 1 1 0.02 1 0.02

4 Under voltage relay 5 0.02 1 1 0.02 1 0.02

131.24 55.69