You are on page 1of 4

Bulletin 003

Model DH80
Model DH80 Recessed

Bulletin 003
Model DH80 Concealed
Quick Response,
Extended Coverage Sprinkler
For coverages up to 28 feet wide and
14 feet long. * 250 psi (17,2 bar) Rated.

Features:
1. Coverage for long and narrow spaces such
as hallways, corridors, decks and rooms
up to 28 feet wide and 14 feet long.*
2. Deflector to ceiling dimensions are:
4 (100mm) min. to 12 (305mm) max. DH80 DH80 FP Recessed
3. Minimum spacing between sprinklers
12 feet (3,6m).
4. UL Listed for light hazard applications.
5. 8.0 K Factor.
6. Sprinkler is approved for
250 psi (17,2 bar) applications.
7. Quick response performance.
8. (13mm) adjustment of escutcheon
and cover. DH80 Concealed DH80 F2 Recessed
9. Rugged, damage resistant assembly. with SWC cover plate
No exposed thermal element with the
concealed version.
10. Push-on/thread-off sturdy convenient
escutcheon for recessed and cover for with the FP or F2 Escutcheon to make a recessed sprinkler.
The SWC cover plate, FP and F2 recessed escutcheons have
concealed. adjustment. The SWC cover plate is attached with
11. Factory assembled sprinkler & cup, 135-degree solder. In the event of a fire the rising ambient
shipped complete with protective cap for temperature melts the solder and the cover plate is ejected
concealed version. away by springs exposing the 3mm frangible glass bulb. The
use of a 3mm bulb allows quick response which enables the
12. Sprinkler & cup assembly and escutcheon sprinkler to apply water to a fire sooner than standard
or cover are separately packaged. response sprinkles of the same temperature rating.
13. Cover finishes available in standard white Application
paint, special bronze, black paint or flat The Model DH80 is a horizontal sidewall sprinkler intended
white paint. for installation in light hazard occupancies in accordance with
14. Patent Pending NFPA 13. These sprinklers are designed to provide fire
protection in long and narrow spaces such as hallways,
* See Figure 3 corridors, decks and rooms up to 28 feet (8,5m) wide and 14
feet (4,3m) long. They are rated for 250 psi (17,2 bar) and can
Approval Organizations be mounted between 4 and 12 inches (102 and 305mm)
Listed by Underwriters Laboratories Inc. and down from the ceiling.
UL certified for Canada (cULus) Installation
DH80 Recessed, FP Escutcheon
Products Description To install the DH80 with the FP Escutcheon as a recessed
The Model DH80 family of sprinklers are quick response sprinkler cut a 2 5 8 diameter hole in the wall as shown in
extended coverage sidewall sprinklers for use in light hazard Fig.5. Thread the DH80 into the cup hand tight, then use the
applications. The Model DH80 with SWC cover plate is a GFR1 wrench to tighten the sprinkler until secured. NOTE:
concealed sprinkler that uses Reliables push on/thread off The GFR1 wrench has a notch in it to accommodate the
sidewall cover. This sprinkler has the cup factory mounted and deflector top. This wrench can only be inserted one way.
is shipped with a protective cap that protects the 3mm Care must be taken not to damage the deflector during
frangible glass bulb during shipping and post installation tightening. Apply a Teflon* based sealant to the sprinkler
finishing operations. The DH80 can be combined in the field threads before installing in the fitting. When inserting or
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
removing the wrench from the sprinkler cup, care must be
taken to prevent damage to the sprinkler. Wrench only on Coverage Area
the square boss. DO NOT WRENCH ON ANY OTHER Flow Rate Pressure
Maximum Coverage Area
Width x Length
PART OF THE SPRINKLER. It is recommended that the gpm (L/min) psi (bar) ft x ft (m xm)
sprinkler be protected during plastering and painting 40 (151,4) 25 (1,7) 28 x 14 (8,5 x 4,3)
operations by using the protective cap P/N 6802710003.
These must be ordered separately. Installation is completed
by removing the protective cap and inserting the push-on
Escutcheon. Turn to adjust the Escutcheon. Approval Type:
DH80 Recessed, F2 Escutcheon Quick Response, Extended Coverage.
To install the DH80 with the F2 Escutcheon as a recessed Approved for installation in accordance with NFPA 13
sprinkler cut a 2 diameter hole in the wall as shown in for Light hazard occupancies.
Figure 2. Thread the DH80 into the collar hand tight. Apply a
Teflon* based sealant to the sprinkler threads and install in
the fitting. Wrench only on the square boss. NOTE: The
GFR1 wrench has a notch in it to accommodate the deflector Maintenance
top. This wrench can only be inserted one way. When Model DH80 should be inspected quarterly and the
inserting or removing the wrench from the sprinkler cup care sprinkler maintained in accordance with NFPA 25. Do not
must be taken to prevent damage to the sprinkler. DO NOT clean sprinklers with soap and water, ammonia or any
WRENCH ON ANY OTHER PART OF THE SPRINKLER. It is other cleaning fluids. Remove dust by using a soft brush or
recommended that the sprinkler be protected during gentle vacuuming. Remove any sprinkler/cover assembly,
plastering and painting operations by using the protective which has been painted (other than factory applied) or
cap P/N 6999991009. These must be ordered separately. damaged in any way. A stock of spare sprinklers should
Installation is completed by removing the protective cap and be maintained to allow quick replacement of damaged or
inserting the F2 Escutcheon over the collar. operated sprinklers. Prior to installation, sprinklers should
DH80 with SWC Cover Plate Concealed be maintained in their original cartons and packaging until
To install the sprinkler, cut a 2 5 8 diameter hole into the wall used to minimize the potential for damage to sprinklers that
as shown in Fig.1. A Teflon* based thread sealant should be would cause improper operation or non-operation.
applied to the sprinkler threads only. Remove the protective
cap (P/N 6802710003) and then position the GFR1 wrench
into the sprinkler/cup assembly until the wrench engages the
flats of the square boss. Then tighten the sprinkler into the UL Listing Category Ordering Information
pipe fitting. When inserting or removing the wrench from the Sprinklers, Automatic Specify:
sprinkler/cup assembly, care should be taken to prevent and Open.
Quick Response Sprinklers. DH80
damage to the sprinkler. DO NOT WRENCH ON ANY - Sprinkler Finish
OTHER PART OF THE SPRINKLER. The protective caps Installation Wrench
Model GFR1 Sprinkler Wrench DH80 Recessed
should be reinstalled for protection during plastering and -Sprinkler Finish
painting. Remove caps only when covers are being Installation Aid FP or F2 Escutcheon
installed.The cover assembly is then pushed onto the cup. For concealed, a protective plastic -Escutcheon Finish
Cover assemblies provide (13mm) of adjustment. Final cap is included for use during
adjustment is made by turning the cover clockwise until the installation. SWC Concealed
skirt flange makes full contact with the wall surface. Cover -Cover-Plate Finish
Escutcheon Data:
removal requires turning in the counter- clockwise direction. FP cup/escutcheon Protective cap for
Concealed cover/cup assemblies are listed only for use assembly - 1 2 (13mm) adjustment use with F2 or FP
with specific sprinklers. The use of any other concealed F2 - 1 2 (13mm) adjustment escutcheons
cover/cup assembly with the Model DH80 Horizontal Sidewall
Sprinkler or the use of the concealed cover assembly on any
sprinkler with which it is not specifically listed will void all
guarantees, warranties, listings and approvals.
Finishes (1)

Standard Finishes(1)
Technical Data*:
Sprinkler FP Escutcheon F2 Escutcheon Cover Plate
K Factor Temperature Rating Sprinkler
Maximum Identification White/ Chrome / White / Chrome /
Thread SWC Ambient Number White / Chrome White
Raw Bronze Bright Brass
US Metric Size Sprinkler Cover Temperature (SIN) (1)
Other colors and finishes are available. Consult factory for details.
155F
3 (68C) 135F 100F
8.0 115,3 RA0362
4
135F (57C) (38C) Note: Paint or any other coatings applied over the factory finish
(57C) will void all approvals and warranties.
*Minimum spacing of 12 feet (3,7m).

*
DuPont Registered Trademark

2.
Figure 1.

Figure 2.

Figure 3.
3.
Reliable...For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.

Automatic sprinklers Deluge valves


Flush automatic sprinklers Detector check valves
Recessed automatic sprinklers Check valves
Concealed automatic sprinklers Supertrol electrical system
Adjustable automatic sprinklers Sprinkler emergency cabinets
Dry automatic sprinklers Sprinkler wrenches
Intermediate level sprinklers Sprinkler escutcheons and guards
Open sprinklers Inspectors test connections
Spray nozzles Sight drains
Alarm valves Ball drips and drum drips
Retarding chambers Control valve seals
Dry pipe valves Air maintenance devices
Accelerators for dry pipe valves Air compressors
Mechanical sprinkler alarms Pressure gauges
Electrical sprinkler alarm switches Identification signs
Water flow detectors Fire department connection

The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

Manufactured by
The Reliable Automatic Sprinkler Co., Inc. Recycled
Paper
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 668-3470 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address E.G. Printed in U.S.A. 3/03 P/N 9999970246