You are on page 1of 28

0 ISSUE FOR CONSTRUCTION 08/25/2017 RLLC RLLC RAY

REV. DESCRIPTION DATE PROY. EXEC. CONT. PASSED

FORTIGEN
GENEVA - NEBRASKA
STORAGE & TRUCK LOADING
CALCULATION
OPERATIONAL PLATFORM FOR E-1500
REPORT
FOUNDATION

GORH-2023-C-MC-17 REV. 0
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 2 of 28

INDEX

INDEX ......................................................................................................................................................2
OVERVIEW ...............................................................................................................................................3
DESCRIPTION ..........................................................................................................................................4
CODES......................................................................................................................................................4
MATERIALS ..............................................................................................................................................5
SOIL ........................................................................................................................................ 5
CONCRETE ............................................................................................................................... 5
STEEL REINFORCEMENT ........................................................................................................... 5
LOADS ......................................................................................................................................................5
WIND ...................................................................................................................................... 5
EARTHQUAKE ........................................................................................................................... 6
PLATFORM REACTIONS............................................................................................................. 7
LOAD COMBINATIONS.............................................................................................................................10
ASCE 7-10 ASD ...................................................................................................................... 10
ASCE 7-10 LRFD .................................................................................................................... 11
PLATFORM FOUNDATION ....................................................................................................................12
SOIL PRESSURE........................................................................................................................ 12
REINFORCING MAT BS-20 - A .................................................................................................. 13
REINFORCING MAT BS-20 - B .................................................................................................. 16
REINFORCING MAT BS-20 - C .................................................................................................. 19
REINFORCING MAT BS-20 - D ................................................................................................. 22
COLUMN DESIGN 17 x 17 in FLEXO-COMPRESSION ................................................................. 25
COLUMN DESIGN 17 x 17 in SHEAR ........................................................................................ 27
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 3 of 28

OVERVIEW

In this report we are designing and checking the Foundation for operational platform of equipment E-1500.
It is composed of concrete footings.

This report must be complemented with drawings GORH-2023-C-DE-69_H01 and GORH-2023-C-DE-71.

Fig.: 1 Foundation for operational platform of equipment E-1500 Plan View

Fig.: 2 Foundation for operational platform of equipment E-1500 Elevation view


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 4 of 28

DESCRIPTION

The foundation is composed of reinforced concrete bases and pedestals.


Concrete fc = 4 ksi, and reinforcing steel fy = 60 ksi.

Fig.: 3 Foundation BS-20 - Plan View

Fig.: 4 Foundation BS-20 Section A-A

CODES

ASCE 7-10 (LOADS)


ACI 318 (CONCRETE)
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 5 of 28

MATERIALS

SOIL
a = 1500 lb/ft2
K = 96.5 kip/ft3

CONCRETE
fc = 4000psi

STEEL REINFORCEMENT
ASTM 615 Grade 60

LOADS

Specific weights
Steel: 491 pcf
Concrete: 150 pcf

WIND
ASCE 7-10

Basic Wind Speed (Geneva, Nebraska) 120 mph


Exposure Category C
Exposure Coeficient Kz = 0.85
Topographic Factor Kzt = 1.00
Wind direccionality Factor Kd = 0.85

Velocity Pressure
qz = 0.00256 Kz Kzt Kd V2 qz = 26.63 Lb/ft2
ASCE7-10:
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 6 of 28

EARTHQUAKE
ASCE 7-10
IMPORTANCE FACTOR AND RISK CATEGORY
Risk Category III Table 1.5-1
Importance Factor, Table 1.5-2

Fig.: 5 Table 1.5-2


Ie = 1.25
SITE CLASS: D
SDS < 0.25g
Fa =1.6 Table 11.4-1
Fv=2.4 Table 11.4-2

Fig.: 6 Table 11.4-1 / 11.4-2


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 7 of 28

Site Class D
Ss = 0.112
S1 = 0.045

Fa = 1.60
Fv = 2.40

SMS = Fa Ss = 0.1792
SM1 = Fv S1 = 0.1080

SDS = 2/3 SMS = 0.1195


SD1 = 2/3 SM1 = 0.0720

SEISMIC RESPONSE COEFFICIENT

Cs = SDS / (R/ Ie)

SDS = 0.1195
R = response modification factor
R = 3.0
Ie = 1.25
Cs = 0.050

PLATFORM REACTIONS

Fig.: 7 Platform Reaction


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 8 of 28

Joint OutputCase F1 F2 F3 M1 M2 M3
Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
1 D -0.86 -207.08 -1754.05 154.15 -2.18 -0.11
1 L -4.07 17.75 -1255.94 24.64 -10.30 -0.57
1 WX+ 66.84 -0.84 60.61 -6.08 40.54 0.00
1 WX- -66.84 0.84 -60.61 6.08 -40.54 0.00
1 WY+ 0.43 209.24 183.33 -231.78 1.09 0.02
1 WY- -0.43 -209.24 -183.33 231.78 -1.09 -0.02
1 EX+ 0.89 -1.16 8.94 0.31 2.25 0.00
1 EX- -0.82 1.52 -8.61 -0.70 -2.09 0.00
1 EY+ 0.08 56.82 42.46 -75.32 0.20 0.01
1 EY- -0.08 -56.82 -42.46 75.32 -0.20 -0.01
1 S -1.04 4.52 -320.27 6.28 -2.63 -0.14
3 D 0.09 199.54 -1070.86 -164.67 0.22 0.02
3 L 0.30 61.37 -738.61 -31.11 0.71 0.08
3 WX+ 50.88 5.37 3.02 -9.32 28.30 0.10
3 WX- -50.88 -5.37 -3.02 9.32 -28.30 -0.10
3 WY+ -0.24 188.56 -184.87 -225.17 -0.61 -0.03
3 WY- 0.24 -188.56 184.87 225.17 0.61 0.03
3 EX+ 0.91 0.68 -0.89 -0.93 2.30 0.00
3 EX- -0.26 -0.45 0.55 0.61 -0.67 -0.01
3 EY+ -0.02 51.41 -50.46 -74.01 -0.06 0.00
3 EY- 0.02 -51.41 50.46 74.01 0.06 0.00
3 S 0.08 15.65 -188.35 -7.93 0.18 0.02
9 D -0.61 -232.03 -1585.57 187.80 -1.54 -0.04
9 L -2.88 -215.56 -1650.15 167.49 -7.29 -0.19
9 WX+ 51.50 -9.94 -21.68 13.03 29.88 -0.09
9 WX- -51.50 9.94 21.68 -13.03 -29.88 0.09
9 WY+ 0.35 386.71 385.23 -517.08 0.88 0.01
9 WY- -0.35 -386.71 -385.23 517.08 -0.88 -0.01
9 EX+ 0.83 0.04 0.09 -0.06 2.10 0.00
9 EX- -0.77 -0.28 -0.42 0.40 -1.94 0.00
9 EY+ 0.06 110.87 97.05 -162.00 0.15 0.00
9 EY- -0.06 -110.87 -97.05 162.00 -0.15 0.00
9 S -0.73 -54.97 -420.78 42.71 -1.86 -0.05
11 D 0.08 207.41 -1185.68 -168.60 0.20 0.02
11 L 0.26 218.00 -1626.84 -184.16 0.64 0.08
11 WX+ 50.79 -6.11 0.92 9.93 28.07 0.11
11 WX- -50.79 6.11 -0.92 -9.93 -28.07 -0.11
11 WY+ -0.22 381.35 -324.40 -512.54 -0.54 -0.03
11 WY- 0.22 -381.35 324.40 512.54 0.54 0.03
11 EX+ 0.82 0.04 -0.07 -0.06 2.09 0.00
11 EX- -0.34 -0.29 0.41 0.41 -0.88 0.00
11 EY+ -0.02 110.72 -97.06 -161.85 -0.05 0.00
11 EY- 0.02 -110.72 97.06 161.85 0.05 0.00
11 S 0.07 55.59 -414.84 -46.96 0.16 0.02
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 9 of 28

13 D -184.85 -111.72 -1208.47 87.44 3.26 -0.04


13 L -588.36 -217.07 -2386.37 169.89 -3.95 -0.17
13 WX+ 507.66 -14.41 582.35 17.28 18.20 -0.11
13 WX- -507.66 14.41 -582.35 -17.28 -18.20 0.11
13 WY+ 70.22 545.49 517.69 -650.05 -1.22 -0.16
13 WY- -70.22 -545.49 -517.69 650.05 1.22 0.16
13 EX+ 196.46 0.00 294.28 0.00 5.65 0.00
13 EX- -178.06 0.00 -266.73 0.01 -5.10 0.00
13 EY+ 10.46 104.48 108.09 -152.64 -0.42 -0.05
13 EY- -10.46 -104.48 -108.09 152.64 0.42 0.05
13 S -150.02 -55.35 -608.51 43.32 -1.01 -0.04
15 D -60.86 109.47 -870.54 -91.92 5.75 0.02
15 L -72.38 217.10 -1531.40 -182.19 11.61 0.08
15 WX+ 372.11 -4.10 411.14 8.87 13.97 0.13
15 WX- -372.11 4.10 -411.14 -8.87 -13.97 -0.13
15 WY+ -48.84 546.58 -470.62 -650.83 1.75 -0.21
15 WY- 48.84 -546.58 470.62 650.83 -1.75 0.21
15 EX+ 188.36 0.00 282.16 0.00 5.42 0.00
15 EX- -96.98 0.00 -145.31 0.01 -2.73 0.00
15 EY+ -4.41 104.48 -99.05 -152.64 0.60 -0.06
15 EY- 4.41 -104.48 99.05 152.64 -0.60 0.06
15 S -18.46 55.36 -390.51 -46.46 2.96 0.02
17 D -28.96 -73.23 -617.52 52.49 -6.96 -0.03
17 L -404.76 -108.60 -73.82 84.94 -16.58 -0.14
17 WX+ 507.26 -4.33 -637.07 5.32 16.66 -0.12
17 WX- -507.26 4.33 637.07 -5.32 -16.66 0.12
17 WY+ 69.26 396.16 154.50 -432.71 3.81 0.06
17 WY- -69.26 -396.16 -154.50 432.71 -3.81 -0.06
17 EX+ 196.19 0.00 -294.28 0.00 5.00 -0.01
17 EX- -177.82 0.00 266.73 -0.01 -4.54 0.01
17 EY+ 10.26 52.32 30.69 -76.43 0.62 0.01
17 EY- -10.26 -52.32 -30.69 76.43 -0.62 -0.01
17 S -103.21 -27.69 -18.83 21.66 -4.23 -0.04
19 D 96.55 86.72 -719.54 -77.18 -3.20 0.03
19 L 206.53 108.58 -913.69 -91.09 -1.64 0.09
19 WX+ 371.91 -1.65 -424.36 3.18 13.37 0.13
19 WX- -371.91 1.65 424.36 -3.18 -13.37 -0.13
19 WY+ -47.97 396.73 -179.06 -433.12 -3.24 0.02
19 WY- 47.97 -396.73 179.06 433.12 3.24 -0.02
19 EX+ 188.10 0.00 -282.16 0.00 4.79 0.01
19 EX- -96.89 0.00 145.31 -0.01 -2.52 -0.01
19 EY+ -4.24 52.32 -39.74 -76.43 -0.48 0.00
19 EY- 4.24 -52.32 39.74 76.43 0.48 0.00
19 S 52.66 27.69 -232.99 -23.23 -0.42 0.02
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 10 of 28

LOAD COMBINATIONS

ASCE 7-10 ASD

SC1 = 1.0 D
SC2 = 1.0 D + 1.0 L
SC3 = 1.0 D + 1.0 S
SC4 = 1.0 D + 0.75 L + 0.75 S
SC5A = 1.0 D + 0.6 WX+
SC5B = 1.0 D + 0.6 WX-
SC5C = 1.0 D + 0.6 WY+
SC5C = 1.0 D + 0.6 WY-
SC6A = 1.0 D + 0.7 EX+
SC6B = 1.0 D + 0.7 EX-
SC6C = 1.0 D + 0.7 EY+
SC6D = 1.0 D + 0.7 EY-
SC7A = 1.0 D +0.75 L + 0.75 S + 0.45 WX+
SC7B = 1.0 D +0.75 L + 0.75 S + 0.45 WX-
SC7C = 1.0 D +0.75 L + 0.75 S + 0.45 WY+
SC7D = 1.0 D +0.75 L + 0.75 S + 0.45 WY-
SC8A = 1.0 D +0.75 L + 0.75 S + 0.525 EX+
SC8B = 1.0 D +0.75 L + 0.75 S + 0.525 EX-
SC8C = 1.0 D +0.75 L + 0.75 S + 0.525 EY+
SC8D = 1.0 D +0.75 L + 0.75 S + 0.525 EY-
SC9A = 0.6 D + 0.6 WX+
SC9B = 0.6 D + 0.6 WX-
SC9C = 0.6 D + 0.6 WY+
SC9D = 0.6 D + 0.6 WY-
SC10A = 0.6 D + 0.7 EX+
SC10B = 0.6 D + 0.7 EX-
SC10C = 0.6 D + 0.7 EY+
SC10D = 0.6 D + 0.7 EY-

Where:
D: Foundation weight, Equipment weight, Platform weight
L: Platform overload
S: Snow load
WX+: Wind Force in direction X+
WX-: Wind Force in direction X-
WY+: Wind Force in direction Y+
WY+: Wind Force in direction Y+
EX+: Seismic force in direction X+
EX-: Seismic force in direction X-
EY+: Seismic force in direction Y+
EY-: Seismic force in direction Y-
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 11 of 28

ASCE 7-10 LRFD

DES1 = 1.4 D
DES2 = 1.2 D + 0.5 S + 1.6 L
DES3 = 1.2 D + 1.6 S + 1.0 L
DES4A = 1.2 D + 1.6 S + 0.5 WX+
DES4B = 1.2 D + 1.6 S + 0.5 WX-
DES4C = 1.2 D + 1.6 S + 0.5 WY+
DES4D = 1.2 D + 1.6 S + 0.5 WY-
DES5A = 1.2 D + 0.5 S + 1.0 L + 1.0 WX+
DES5B = 1.2 D + 0.5 S + 1.0 L + 1.0 WX-
DES5C = 1.2 D + 0.5 S + 1.0 L + 1.0 WY+
DES5D = 1.2 D + 0.5 S + 1.0 L + 1.0 WY-
DES6A = 1.2 D + 0.2 S + 1.0 L + 1.0 EX+
DES6B = 1.2 D + 0.2 S + 1.0 L + 1.0 EX-
DES6C = 1.2 D + 0.2 S + 1.0 L + 1.0 EY+
DES6D = 1.2 D + 0.2 S + 1.0 L + 1.0 EY-
DES7A = 0.9 D + 1.0 WX+
DES7B = 0.9 D + 1.0 WX-
DES7C = 0.9 D + 1.0 WY+
DES7D = 0.9 D + 1.0 WY-
DES8A = 0.9 D + 1.0 EX+
DES8B = 0.9 D + 1.0 EX-
DES8C = 0.9 D + 1.0 EY+
DES8D = 0.9 D + 1.0 EY-

Where:
D: Foundation weight, Equipment weight, Platform weight
L: Platform overload
S: Snow load
WX+: Wind Force in direction X+
WX-: Wind Force in direction X-
WY+: Wind Force in direction Y+
WY+: Wind Force in direction Y+
EX+: Seismic force in direction X+
EX-: Seismic force in direction X-
EY+: Seismic force in direction Y+
EY-: Seismic force in direction Y-
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 12 of 28

PLATFORM FOUNDATION

Fig.: 8 Foundation Layout

SOIL PRESSURE
Foundation Combination Reaction Influence Area Tension on ground Admissible tension Check
Lb ft2 Lb/ft2 Lb/ft2
BS-20 A SC7D 20.40 0.0256 796.88 1500.00 OK
BS-20 B SC7D 21.05 0.0256 822.30 1500.00 OK
BS-20 C SC7B 28.35 0.0256 1107.42 1500.00 OK
BS-20 D SC7B 18.94 0.0256 739.80 1500.00 OK
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 13 of 28

REINFORCING MAT BS-20 - A

Fig.: 9 M11+ (DES2) / M11-(DES5D) Lb-in/in


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 14 of 28

Fig.: 10 M22+ (DES5D) / M22- (DES2) Lb-in/in

M11+ = 1362.81 Lb-in/in DES2


M11- = 26.43 Lb-in/in DES5D
M22+ = 893.41 Lb-in/in DES5D
M22- = 2530.62 Lb-in/in DES2
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 15 of 28

Mu = 2530.62 Lb-in/in 36 in = 91102.32 Lb-in

DATE a (in) As(in2)


Mu (Lb-in) 91102.32 2.61 0.14
f'c (Lb/in) 4000.00 0.07 0.13
fy (Lb/in) 60
60000.00 0.06 0.13
B (in) 36.00 0.06 0.13
H (in) 16.00 0.06 0.13
d (in) 13.06 0.06 0.13

As = Mu
fy ( d - a/2 )

a= As fy
0.85 f'c B

a = d/5 First iteration

ASMIN = 0.0018 B H/2 = 0.518 in2

Av = 0.307 in2 (#5)

S = 36 Av / As =36 0.307 / 0.518 = 21.33 in

It will be used reinforcement #5 @ 6


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 16 of 28

REINFORCING MAT BS-20 - B

Fig.: 11 M11+ (DES5D) / M11-(DES2) Lb-in/in


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 17 of 28

Fig.: 12 M22+ (DES5D) / M22- (DES2) Lb-in/in

M11+ = 1770.81 Lb-in/in DES2


M11- = 41.73 Lb-in/in DES5D
M22+ = 1212.39 Lb-in/in DES5D
M22- = 3695.04 Lb-in/in DES2
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 18 of 28

Mu = 3695.04 Lb-in/in 36 in = 133021.44 Lb-in

DATE a (in) As(in2)


Mu (Lb-in) 133021.44 2.61 0.21
f'c (Lb/in) 4000.00 0.10 0.19
fy (Lb/in) 60
60000.00 0.09 0.19
B (in) 36.00 0.09 0.19
H (in) 16.00 0.09 0.19
d (in) 13.06 0.09 0.19

As = Mu
fy ( d - a/2 )

a= As fy
0.85 f'c B

a = d/5 First iteration

ASMIN = 0.0018 B H/2 = 0.518 in2

Av = 0.307 in2 (#5)

S = 36 Av / As =36 0.307 / 0.518 = 21.33 in

It will be used reinforcement #5 @ 6


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 19 of 28

REINFORCING MAT BS-20 - C

Fig.: 13 M11+ (DES2) / M11-(DES5B) Lb-in/in


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 20 of 28

Fig.: 14 M22+ (DES2) / M22- (DES2) Lb-in/in

M11+ = 2913.54 Lb-in/in DES2


M11- = 741.67 Lb-in/in DES5B
M22+ = 1632.00 Lb-in/in DES2
M22- = 3799.06 Lb-in/in DES2
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 21 of 28

Mu = 3799.06 Lb-in/in 36 in = 136766.16 Lb-in

DATE a (in) As(in2)


Mu (Lb-in) 136766.16 2.61 0.22
f'c (Lb/in) 4000.00 0.11 0.20
fy (Lb/in) 60
60000.00 0.10 0.20
B (in) 36.00 0.10 0.20
H (in) 16.00 0.10 0.20
d (in) 13.06 0.10 0.20

As = Mu
fy ( d - a/2 )

a= As fy
0.85 f'c B

a = d/5 First iteration

ASMIN = 0.0018 B H/2 = 0.518 in2

Av = 0.307 in2 (#5)

S = 36 Av / As =36 0.307 / 0.518 = 21.33 in

It will be used reinforcement #5 @ 6


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 22 of 28

REINFORCING MAT BS-20 - D

Fig.: 15 M11+ (DES5A) / M11-(DES5B) Lb-in/in


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 23 of 28

Fig.: 16 M22+ (DES5A) / M22- (DES5A) Lb-in/in

M11+ = 1524.06 Lb-in/in DES5A


M11- = 1056.86 Lb-in/in DES5B
M22+ = 845.10 Lb-in/in DES5A
M22- = 1828.51 Lb-in/in DES5A
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 24 of 28

Mu = 1828.51 Lb-in/in 36 in = 65826.36 Lb-in

DATE a (in) As(in2)


Mu (Lb-in) 65826.36 2.61 0.10
f'c (Lb/in) 4000.00 0.05 0.09
60
60000.00 0.05 0.09
B (in) 36.00 0.05 0.09
H (in) 16.00 0.05 0.09
d (in) 13.06 0.05 0.09

As = Mu
fy ( d - a/2 )

a= As fy
0.85 f'c B

a = d/5 First iteration

ASMIN = 0.0018 B H/2 = 0.518 in2

Av = 0.307 in2 (#5)

S = 36 Av / As =36 0.307 / 0.518 = 21.33 in

It will be used reinforcement #5 @ 6


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 25 of 28

COLUMN DESIGN 17 x 17 in FLEXO-COMPRESSION

SUMMARY OF FORCE

Pu MU2 MU3 VU2 VU3


Foundation Combination
Kip Kip-ft Kip-ft Kip Kip
BS-20 A DES5C -6.52 7.70 0.01 0.00 1.10
BS-20 B DES5C -9.34 14.40 0.01 0.00 1.93
BS-20 C DES5C -11.72 -15.00 -8.42 -2.11 -2.04
BS-20 D DES5C -3.60 -9.63 -5.16 -1.24 -1.34

Assuming a minimum amount of 1%

Asmin = 1.0% 17 17 = 2.89 in2

As (4 #6 + 4 #5) = 2.99 in2

In Fig. 17 shows the section of the shaft with dimensions and distribution of the reinforcement.

In Fig. 18 shows the interaction diagram axial load - Moment of the column of 17 in x 17 in with reinforcement
of 4 # 6 + 4 #5.

In Fig. 19 shows the Moment-Moment interaction diagram for axial load of 11.72 Kip.

As you can see the values of forces are within the diagrams mentioned by what checks the column with the
amount of reinforcement indicated.

Fig.: 17 Column 17 x 17 in with reinforcement 4 #6 + 4#5


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 26 of 28

Fig.: 18 Interaction diagram Pn Mn

Fig.: 19 Interaction diagram Mnx Mny - Pu = 11.72 Kip


REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 27 of 28

COLUMN DESIGN 17 x 17 in SHEAR

VU2 VU3
Foundation Combination
Kip Kip
DES5B 0.16 -
BS-20 A
DES5C - 1.10
DES5B 0.12 -
BS-20 B
DES5D - 2.00
DES5B 3.07 -
BS-20 C
DES5D - 2.04
DES5B 2.20 -
BS-20 - D
DES5C - 1.37

Ultimate Shear, VU = 3.07 Kip


Nominal Shear, VN = VU2/ = 4.09 Kip
Column dimension, B = 17.00 in
Column dimension, D = 17.00 in
Stirrup diameter, E = 3/8 in
Principal reinforcement diameter, P = 3/4 in
Covering, R = 2.00 in
Spacing between stirrups, S = 6.00 in
d = D (R + E + P/2) = 14.25 in
Resistance to concrete Shear, VC = 2.00 (f'c) B d = 30642.47 Lb = 30.64 Kip
VC > VN VC = 30.64 Kip > VN = 4.09 Kip Minimum reinforcement
Minimal reinforcement area, AVMIN = 49.80 B S / fy = 0.0847 in2
Area of the section of stirrups, A = 0.11 in2
Reinforcement area, A = 2 A = 0.22 in2 > 0.0847 in2 OK
REV: 0

DATE: 08/25/2017

FORTIGEN
DOC: GORH-2023-C-MC-17
GENEVA-NEBRASKA
CALCULATION REPORT PAGE: 28 of 28

Fig.: 20 Reinforcement - Elevation

Fig.: 21 Reinforcement - Column

You might also like