You are on page 1of 76

D800025X082

March 2014

Installing Your DeltaV SIS Process Safety


System Hardware
Printed in the Republic of Singapore.

Emerson Process Management 1996 - 2014. All rights reserved. For Emerson Process Management trademarks and service marks,
go to Emerson Process Management Trademarks and Service Marks. All other marks are property of their respective owners. The
contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their
accuracy, they are not to be construed as warranties or guarantees, expressed or implied, regarding the products or services
described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We
reserve the right to modify or improve the design or specification of such products at any time without notice.

See the CE statement in Chapter 2 in this manual.

Emerson Process Management Distribution Ltd. Process Systems and Solutions


Meridian East
Meridian Business Park
Leicester, LE19 1uX, UK

Emerson a.s.
European System and Assembly
Pietansk 1202/44
Nov Mesto nad Vhom 91528
Slovakia

Fisher-Rosemount Systems, Inc. an Emerson Process Management company


1100 W. Louis Henna Blvd.
Round Rock, TX 78681
Contents

Contents
Preface ............................................................................................................................ iii
Chapter 1 Overview to the DeltaV SIS System ....................................................................................1
DeltaV SIS hardware ................................................................................................................................... 1
Communication in the DeltaV SIS system ................................................................................................... 3
Chapter 2 Installing the system .........................................................................................................5
Agency approvals ....................................................................................................................................... 5
CE statement .............................................................................................................................................. 5
Tools required for installation ..................................................................................................................... 5
Wiring guidelines ........................................................................................................................................6
Install the carriers ....................................................................................................................................... 6
Install the terminal blocks ........................................................................................................................... 7
Install the Logic Solver ................................................................................................................................ 8
Connecting the field wiring .........................................................................................................................8
Install the SISNet Repeater ..........................................................................................................................9
Installing extender cables ........................................................................................................................... 9
Install carrier extender cables ........................................................................................................10
Install local peer bus extender cables ............................................................................................ 10
Terminate the local peer bus .....................................................................................................................11
Providing power ....................................................................................................................................... 12
Provide power to the Logic Solvers ................................................................................................12
Provide power to SISNet Repeaters ............................................................................................... 13
Provide power to SISNet Distance Extenders ................................................................................. 14
Setting up the remote peer ring ................................................................................................................15
Connect a remote peer ring with multimode fiber .........................................................................16
Extending the remote peer ring .................................................................................................... 17
Chapter 3 Checking out and troubleshooting your DeltaV SIS hardware .......................................... 23
Logic Solver LEDs ...................................................................................................................................... 23
SISNet Repeater LEDs ................................................................................................................................24
SISNet Distance Extender LEDs ................................................................................................................. 26
Chapter 4 Environmental and heat dissipation specifications .......................................................... 29
Chapter 5 Logic Solver and channel specifications ........................................................................... 31
Logic Solver specifications ........................................................................................................................ 31
Simplex Logic Solver termination block .........................................................................................32
Redundant Logic Solver termination block .................................................................................... 33
Analog input channel specifications ..........................................................................................................33
HART two-state output channel specifications ..........................................................................................34
Discrete input channel specifications ........................................................................................................35
Discrete output channel specifications ..................................................................................................... 38
Chapter 6 SISNet Repeater and SISNet Distance Extender specifications .......................................... 41
SISNet Repeater specifications ..................................................................................................................41
SISNet Distance Extender specifications ....................................................................................................42
Calculating the fiber-optic link loss ........................................................................................................... 44
Chapter 7 Extending an operational system .................................................................................... 47
Add carriers to an operational system ....................................................................................................... 47

i
Contents

Add SISNet Repeaters to an operational system ........................................................................................48


Using DeltaV intrinsically safe cards with DeltaV SIS hardware .................................................................. 50
Install intrinsically safe cards in a DeltaV SIS system ...................................................................... 50
Chapter 8 Using auxiliary equipment with DeltaV SIS hardware ...................................................... 53
Relay Modules for fire and gas applications ............................................................................................... 53
Auxiliary Relay DTA-Inverting module specifications .................................................................................54
Auxiliary Relay Diode module ....................................................................................................................57
Relay Module for other applications ..........................................................................................................58
Auxiliary Relay ETA-Direct module specifications ...................................................................................... 59
SIS Relay Module .......................................................................................................................................60
SIS Relay module specifications .....................................................................................................60
Proof testing the SIS Relay Module ................................................................................................ 62
Voltage Monitor specifications ......................................................................................................63
SIS Current Limiter specifications .................................................................................................. 66

Index ................................................................................................................................................. 69

ii
Welcome

Preface

Welcome
This manual is designed to help you install your DeltaV SIS hardware and get it started up
quickly. It shows factory tested and supported wiring connections. If your system requires
a different configuration, contact your Emerson Process Management representative or
sales office for help with design or review. It is assumed that all installation and
maintenance procedures described in this document are performed by qualified personnel
and that the equipment is used only for the purposes described.

Related documentation

The DeltaV S-series and CHARMs Hardware Reference manual contains installation
notes, specifications, wiring diagrams, dimensions, and other reference information
for Deltav S-series and CHARMs hardware components.
The Installing Your DeltaV Digital Automation System manual contains installation
information specifications, wiring diagrams, dimensions, and other reference
information for DeltaV M-series hardware.
The Quick Start Guide for DeltaV Power, Grounding, and Surge Suppression manual
contains instructions for properly preparing your site for electrical power and
grounding.

Assumptions

It is assumed that you have read the Quick Start Guide for DeltaV Power, Grounding, and
Surge Suppression and have followed the instructions for properly preparing your site for
electrical power and grounding before installing your DeltaV system. The Quick Start Guide
for DeltaV Power, Grounding, and Surge Suppression is available from your Emerson Process
Management representative or sales office. It is also assumed that you have read the
Installing Your DeltaV Digital Automation System manual and have followed the instructions
for properly installing your DeltaV system hardware.

WARNING!
The DeltaV SIS Process Safety System Safety Manual contains user requirements for installing,
operating, and maintaining a DeltaV Safety Instrumented System. Refer to the DeltaV SIS
Process Safety System Safety Manual for all user requirements.

Conventions used in this manual

Notes are used to help you to understand important information.

Warnings are used to describe a critical procedure that must be followed to prevent a
safety risk or equipment damage.

Cautions describes a procedure that must be followed to prevent equipment malfunction.

iii
Welcome

iv
Overview to the DeltaV SIS System

1 Overview to the DeltaV SIS System


Topics covered in this chapter:
DeltaV SIS hardware
Communication in the DeltaV SIS system

DeltaV SIS hardware


A DeltaV automation system consists of carriers, one or more I/O subsystems, controllers,
power supplies, workstations, and a control network.

DeltaV SIS hardware consists of:

Logic Solvers (SLS 1508) and termination blocks


SISNet Repeaters
SISNet Distance Extenders
Carrier extender cables
Local peer bus extender cables
Right one-wide carrier with termination

Note
DeltaV SIS systems require an MD Series 2 or later model controller.

Logic Solvers (SLS) contain the logic solving capability and provide an interface to 16 I/O
channels that can be configured as Discrete Input, Discrete Output, Analog Input (HART)
and HART Two-state output channels. Logic Solvers and termination blocks install on the
8-wide carrier. DeltaV SIS systems supports simplex and redundant Logic Solvers. Logic
Solvers communicate with each other through the carriers over a two-channel, local peer
bus and remote peer ring. Local Logic Solvers are hosted by the same DeltaV controller and
remote Logic Solvers are hosted by a different DeltaV controller. Logic Solvers are powered
by a 24VDC power supply that is separate from the power supply that drives the DeltaV
controller and I/O. Logic Solvers install in odd numbered slots (1,3,5,7) on the 8-wide
carrier. Simplex Logic Solvers use two slots and redundant Logic Solvers use four slots.

SISNet Repeaters extend communication beyond the local Logic Solvers connected to one
DeltaV controller and broadcast global messages to remote Logic Solvers through a fiber-
optic ring. Global messages refer to messages that are intended for all Logic Solvers. The
SISNet Repeater installs on a 2-wide carrier. There is a primary and secondary SISNet
Repeater on each carrier.

SISNet Distance Extenders convert multimode fiber-optic signals to single mode fiber-
optic signals to allow SISNet Repeaters to communicate over greater distances.
Depending upon the installation, the remote peer ring can be extended by an additional
20 km when single mode fiber-optic cable is used.

1
Overview to the DeltaV SIS System

Carrier extender cables extend LocalBus power and signals between 8-wide carriers.
Local peer bus extender cables extend the local peer bus between Logic Solvers on
different carriers. One-wide carriers with terminators terminate the local peer bus at the
final carrier.

The figure shows carrier extender cables and local peer bus extender cables connecting a
DeltaV controller and 8-wide carrier with standard DeltaV I/O and DeltaV SIS components
to a second 8-wide carrier (hosted by the same controller) installed with Logic Solvers,
SISNet Repeaters, and a terminated one wide carrier. Logic Solver messages are
communicated to a remote DeltaV SIS system (hosted by a separate controller) through
multimode fiber-optic cables.

Note
SISNet Distance Extenders and single mode fiber-optic cable are not used in the example installation
depicted in the figure.

2
Overview to the DeltaV SIS System

Figure 1-1: DeltaV SIS system overview


Primary Secondary Workstation
control network control network
Primary hub Secondary hub
Primary control Secondary control
network cables network cables

Controller DeltaV System with SIS


Carrier extender
System cables
power supply Power
Error
Power
Error
Active
Standby
Power
Fault
Power
Fault
Power
Fault
Power
Fault
Power
Fault
Power
Fault
Pri CN Ch.1 Ch.1 Ch.1 Ch.1 Ch.1 Ch.1
Sec CN Ch. 2 Ch. 2 Ch. 2 Ch. 2 Ch. 2 Ch. 2
Ch. 3 Ch. 3 Ch. 3 Ch. 3 Ch. 3 Ch. 3
Ch. 4 Ch. 4 Ch. 4 Ch. 4 Ch. 4 Ch. 4
Ch. 5 Ch. 5 Ch. 5 Ch. 5 Ch. 5 Ch. 5
Controller Ch. 6 Ch. 6 Ch. 6 Ch. 6 Ch. 6 Ch. 6
System MD Ch. 7 Ch. 7 Ch. 7 Ch. 7 Ch. 7 Ch. 7
Passthrough
Power Supply Ch. 8 Ch. 8 Ch. 8 Ch. 8 Ch. 8 Ch. 8
(DC/DC) System System System System System System LOCK
Repeater Repeater Repeater Repeater Repeater Repeater

FISHER-ROSEMOUNT Local peer bus


D
extender cables

Logic Solvers
SISNet Repeaters

C D
SLS 1580 SLS 1580
A Power
Fault
Power
Fault
Terminated
one wide
Local Peer PX Local Peer PX
Local Peer RX Local Peer RX
Remote Peer PX Remote Peer PX
Remote Peer RX Remote Peer RX

LOCK
System
Repeater
System
Repeater
LOCK carrier
B B

+ +
D

Fiber optic

Remote DeltaV SIS System


Controller Logic Solvers
SISNet Repeaters

System SLS 1580 SLS 1580


power supply Power
Error
Power
Error
Active
Standby
Pri CN
Power
Fault
Local Peer PX
Power
Fault
Local Peer PX
Terminated
one wide
Sec CN Local Peer RX Local Peer RX
Remote Peer PX Remote Peer PX
Remote Peer RX Remote Peer RX

Controller
System MD

carrier
Passthrough
Power Supply System System
(DC/DC) Repeater Repeater

LOCK

FISHER-ROSEMOUNT

Fiber optic

Related information

Extend the remote peer ring with SISNet distance extenders

Communication in the DeltaV SIS system


In a DeltaV SIS system, communication occurs over a Control Network, LocalBus, local peer
bus, and remote peer bus

3
Overview to the DeltaV SIS System

Control The DeltaV Control Network provides communication between the nodes
Network in the DeltaV network. Refer to the DeltaV S-series and CHARMs Hardware
Reference manual for complete information on the Control Network.
LocalBus The LocalBus provides communication between DeltaV controllers and
Logic Solvers and between DeltaV controllers and SISNet Repeaters.
Local peer Logic Solvers communicate with other Logic Solvers and with local SISNet
bus Repeaters through the carriers over a 2 channel local peer bus. The same
message is broadcast over both channels. The local peer bus must be
terminated at both ends. The local peer bus is terminated at the left end
through the 2-wide power/controller carrier and at the right end through a
terminated one wide carrier.
Remote SISNet Repeaters hosted by one DeltaV controller communicate with
peer ring SISNet Repeaters hosted by a different DeltaV controller over a fiber-optic
remote peer ring. A local SISNet Repeater collects locally generated global
messages into a single message and sends it to the next SISNet Repeater in
the ring. Upon receipt of a message, the receiving SISNet Repeater
broadcasts it to its local peer bus and forwards the message to the next
SISNet Repeater in the ring. A global message is forwarded around the ring
once. The primary SISNet Repeaters form one fiber-optic ring and the
secondary form a separate, independent ring. SISNet Distance Extenders
that convert multimode fiber-optic signals to single mode fiber-optic
signals can be used to extend the remote peer ring

4
Installing the system

2 Installing the system


Topics covered in this chapter:
Agency approvals
CE statement
Tools required for installation
Wiring guidelines
Install the carriers
Install the terminal blocks
Install the Logic Solver
Connecting the field wiring
Install the SISNet Repeater
Installing extender cables
Terminate the local peer bus
Providing power
Setting up the remote peer ring

Agency approvals
The DeltaV SIS hardware is certified to:

European EMC compliance


Low Voltage Directive IEC 61010-1
NAMUR NE21 EMC requirements
Factory Mutual, Non-Arcing
ATEX 3 G EEx IIC- nA T4 EN60079-15
CSA 1010 or 61010

CE statement
This manual describes installation and maintenance procedures for products that have
been tested to be in compliance with appropriate CE directives. To maintain compliance,
these products must be installed and maintained according to the procedures described in
this document. Failure to follow the procedures may compromise compliance.

Tools required for installation

5
Installing the system

The following tools are needed to install DeltaV SIS hardware:

Standard electrical tools (voltmeter, wire cutter, wire stripper, pliers, screwdrivers)
Standard installation tools (screwdrivers, drill with standard bits)
Ethernet cable tools (crimper, cable tester)

Wiring guidelines
The power and grounding terminals and field termination points on the carriers' terminal
blocks are 2.8 mm by 2.5 mm (2.8 mm x 2.5 mm). The maximum recommended wire size
for the terminals is 14 AWG, stranded or solid gauge wire, or a 14 AWG ferrule. To select
wire, calculate the maximum current limit expected for each wire. Local electrical codes
define the wire size required for a specific current.

Shielded twisted pair wiring is recommended for low-level signal wiring to reduce
susceptibility to noise.

Install the carriers

Note
For vertically-mounted systems, DeltaV SIS hardware is supported on VerticalPLUS carriers only. It is
not supported on legacy vertical carriers. Refer to the Installing Your DeltaV Digital Automation System
manual for information on installing VerticalPLUS carriers.

1. Install the 2-wide power/controller carriers and the 8-wide I/O interface carriers on
the DIN rails. Install a DeltaV controller and power supply on the 2-wide power/
controller carrier. Refer to the Installing Your DeltaV Digital Automation System
manual for installation instructions.

Read the following Important information and be sure that you are using the correct
2-wide power/controller carrier

Important
Be sure that you are using the 2-wide power/controller carrier numbered KJ4001X1-BA3 or
higher. DeltaV SIS hardware requires this version. A small white rectangle is printed on the
front of this carrier to distinguish it from earlier versions. The topic on installing the terminal
blocks includes an image that will help you to determine if you are using the correct 2-wide
carrier.

2. Install the 2-wide SISNet Repeater carriers on the DIN rails if remote communication
is required. SISNet Repeater carriers can be installed anywhere between the 2-wide
power/controller carrier and the terminated one-wide carrier. The 2-wide SISNet
Repeater carrier installs exactly like a 2-wide power/controller carrier. The topic on
terminating the local peer bus provides information on the one-wide carrier.

6
Installing the system

3. Connect the carriers to any adjacent carriers by sliding together the 48 pin
connectors on the sides of the carriers.
4. If you are installing carriers on separate DIN rails, you will need to connect two (left
and right) one-wide carriers and then connect extender cables to extend the
LocalBus and local peer bus.

You can also add carriers to an existing operational system.

Related information

Install the terminal blocks


Install the SISNet Repeater
Terminate the local peer bus
Install carrier extender cables
Install local peer bus extender cables
Add carriers to an operational system

Install the terminal blocks


Logic Solver (SLS) terminal blocks are yellow to distinguish them from other terminal
blocks.

1. Locate an odd slot number on the I/O interface carrier. Simplex terminal blocks take
two slots and redundant terminal blocks take four slots.
2. Insert the tabs on the back of the terminal block through the slots on the carrier and
push the terminal block up to lock it into place.

The following image shows a redundant terminal block installed on an I/O interface
carrier.

Figure 2-1: Redundant terminal block installed on carrier


Terminated
White 2-Wide Power 2-Wide SISNet 8-Wide I/O right 1-Wide
rectangle Controller carrier Repeater carrier interface carrier carrier
+ + + +

SIS NET SIS NET


REPEATER REPEATER
A

Power

C
Fault
Local Peer PX
Local Peer RX
Remote Peer PX
Remote Peer RX

System
Repeater

LOCK
LOCK
LOCK

LOCK
LOCK
LOCK
LOCK 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 1
2
2 3 4 5 6 7 8 9
3
10 11 12 13 14 15 16
4 5 6 7 8 D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

DIN Redundant 48 Pin


Rail SLS Terminal connector
block

7
Installing the system

3. Connect the field wiring.

Note
The Logic Solver terminal blocks have tabs for quick release. Simplex Logic Solver terminal
blocks have one tab and redundant Logic Solver terminal blocks have two tabs.

Related information

Connecting the field wiring


Logic Solver specifications

Install the Logic Solver


Logic Solvers install on the terminal blocks in odd numbered slots (1,3,5,7) on the 8-wide
carrier. Simplex Logic Solvers take two slots and redundant Logic Solvers take four slots.

1. Locate the Logic Solver terminal block on the I/O interface carrier.
2. Align the connectors on the back of the Logic Solver with the connectors on the
front of the terminal block and push to attach.

Figure 2-2: Logic Solver installation


White 2-Wide Power 2-Wide SISNet 8-Wide I/O Terminated
rectangle Controller carrier Repeater carrier interface carrier right 1-Wide
+ + + +
carrier

SIS NET SIS NET


REPEATER REPEATER
A

SLS 1508

Power

C
Fault
Local Peer PX
Local Peer RX
Remote Peer PX
Remote Peer RX

System
Repeater

LOCK
LOCK
LOCK

LOCK
LOCK
LOCK
LOCK
B

1 2 1 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 1508
SLS 7 8 D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

DIN Simplex Logic Solver


Rail terminal block

Connecting the field wiring


The terminal blocks provide 16 channels of I/O. Each channel can be configured as Discrete
Input, Discrete Output, Analog Input (HART) and HART Two-state output.

8
Installing the system

Related information

Analog input channel specifications


HART two-state output channel specifications
Discrete input channel specifications
Discrete output channel specifications

Install the SISNet Repeater


The SISNet Repeater installs on the 2-wide SISNet Repeater carrier.

1. Align the connector on the back of the SISNet Repeater with the connector on the 2-
wide SISNet Repeater carrier and push to attach.
2. Tighten the mounting screw.

Figure 2-3: SISNet Repeater installation


White 2-Wide Power 2-Wide SISNet 8-Wide I/O
rectangle Controller carrier Repeater carrier interface carrier
+ + + +

SIS NET SIS NET


REPEATER REPEATER
A

Power
SLS 1508 SLS 1508 SLS 1508 SLS 1508
Fault
Local Peer PX
Local Peer RX
Power
Remote Peer PX
C
Fault
Local Peer PX
Local Peer RX
Remote Peer PX Remote Peer RX
Remote Peer RX

System
Repeater

LOCK
System LOCK
LOCK Repeater

Power
LOCK Fault
LOCK
Local Peer PX

LOCK Local Peer RX


LOCK
Remote Peer PX
B
Remote Peer RX

1 2 1
System
Repeater
2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

DIN SISNet Logic Solvers Terminated


Rail Repeater right 1-Wide
carrier

Related information

Setting up the remote peer ring

Installing extender cables


When carriers are installed on separate DIN rails, carrier extender cables and local peer bus
extender cables are used to extend the LocalBus and local peer bus. Extender cables
connect to one-wide carriers on the left and right sides of the 2-wide and 8-wide carriers.
Remove the dust covers from the D-shell and BNC connectors on the one-wide carriers.

9
Installing the system

Install carrier extender cables


A standard installation uses one carrier extender cable; however, dual carrier extender
cables can also be used. The following procedure is for a standard installation that uses one
carrier extender cable.

1. Install the right and left-side one-wide carriers by sliding together the 48 pin
connectors on the sides of the carriers.

Figure 2-4: One-wide carriers


White BNC Left one-wide carrier Right one-wide carrier
connector Black BNC Top D-Shell connector
connector (44 pin)

Top D-Shell
connector C D
(44 pins)
A
White BNC connector
A

C
D-Shell connector
(for dual LOCK LOCK D-Shell connector
cables only) (for dual cables only)
48 Pin
connectors
B B Black BNC connector

+ +
D

2. Connect the 44 pin D-shell (male) connector on the carrier extender cable to the top
D-shell connector labeled A on the right-side carrier and fasten the retainer screws.
3. Connect the 44 pin D-shell connector on the other end of the cable to the top D-
shell connector labeled A on the left-side carrier and fasten the retainer screws.

Install local peer bus extender cables


Notice that the local peer bus extender cable has black and white boots. The cables
connect black-to-black (D) and white-to-white (C).

1. Place the cable end onto the BNC connector on the one-wide carrier.

10
Installing the system

Figure 2-5: One-wide carriers


White BNC Left one-wide carrier Right one-wide carrier
connector Black BNC Top D-Shell connector
connector (44 pin)

Top D-Shell
connector C D
(44 pins)
A
White BNC connector
A

C
D-Shell connector
(for dual LOCK LOCK D-Shell connector
cables only) (for dual cables only)
48 Pin
connectors
B B Black BNC connector

+ +
D

2. Push and turn to lock the cable into place.

Terminate the local peer bus


The local peer bus is terminated by 120 ohm BNC terminators on the right one-wide carrier
connected to the last 8-wide carrier.

Important
Be sure to use BNC terminators numbered KJ4010X1-BN1.

1. Install a one-wide carrier onto the right side of the last carrier.
2. Place a 120 ohms BNC terminator onto each BNC connector on the carrier and push
and turn to lock the terminator into place. Terminate both connectors.

11
Installing the system

Figure 2-6: Local peer bus terminations on the one-wide carrier

A
BNC connector
with terminator installed

LOCK

48 Pin B
connector
BNC connector
with terminator installed

Providing power
Logic Solvers, SISNet Repeaters, and SISNet Distance Extenders are powered separately
from DeltaV controllers and I/O. This ensures that a loss of power to the DeltaV controller
does not affect the operation of Logic Solvers, SISNet Repeaters, and SISNet Distance
Extenders. In most installations, redundant 24 VDC power is used for both simplex and
redundant SIS applications. When redundant 24 VDC power is used, both power supplies
must be referenced to a common connection to ground.

CAUTION!
Although the screw terminal connector on the Logic Solver, SISNet Repeater, and SISNet
Distance Extender has two positive and two negative connectors, it is recommended that they
not be used to daisy-chain power. Daisy-chaining could result in a loss of power to
downstream Logic Solvers if power is removed or lost at an upstream Logic Solver.

Provide power to the Logic Solvers


Note
Read the Caution in the Providing power topic before proceeding.

12
Installing the system

Top View
Logic Solver

24 VDC return
24 VDC return
+ 24 VDC
+ 24 VDC

Front

24 VDC Power
distribution

SLS 1508

Logic Solver

1. Locate the removable 24 VDC screw terminal connectors on the top of the Logic
Solver.
2. Connect power supply positive (+) to the positive (+) connector on the Logic Solver
and power supply negative (-) to the negative connector on the Logic Solver.

Provide power to SISNet Repeaters


Note
Read the important Caution in the Providing power topic before proceeding.

13
Installing the system

Top view
SISNet Repeater

+ 24 VDC
+ 24 VDC
24 VDC return
24 VDC return

Front

24 VDC Power
distribution

Power
Fault
Local Peer PX
Local Peer RX
Remote Peer PX
Remote Peer RX

System
Repeater

SISNet Repeater

1. Locate the removable 24 VDC screw terminal connectors on the top of the SISNet
Repeater.
2. Connect power supply positive (+) to the positive (+) connector on the SISNet
Repeater and power supply negative (-) to the negative (-) connector on the SISNet
Repeater.

Provide power to SISNet Distance Extenders


Note
Read the Caution in the Providing power topic before proceeding.

14
Installing the system

Top view
SISNet Distance Extender

4 3 2 1
-24 VDC
return +24VDC

24 VDC Power
distribution

Rear

SISNet
Distance
Extender

Power DIN Rail


Single
Multi

SISNet Distance Extender

1. Locate the removable 24 VDC screw terminal connectors on the top of the SISNet
Distance Extender.
2. Connect power supply positive (+) to the positive (+) connector on the SISNet
Distance Extender and power supply negative (-) to the negative (-) connector on
the SISNet Distance Extender.

Setting up the remote peer ring


When link distances are a few kilometers (nominal) one way transmit to receive, SISNet
Repeaters can be connected with multimode fiber-optic cables to form the remote peer
ring. When link distances exceed a few kilometers one way, SISNet Distance Extenders can
be used to convert multimode fiber-optic signals to single mode fiber-optic signals to
extend the remote peer ring.

The SISNet Repeaters connect transmit to receive, transmit to receive to form a fiber-optic
ring. It is highly recommend that you connect SISNet Repeaters in a counter-rotation
topology in which two signal paths, one in each direction, exist in the ring. This topology
increases availability in the event of a failure in a single SISNet Repeater pair.

15
Installing the system

The following figure shows a multimode fiber-optic ring with a counter-rotation topology.
The primary SISNet Repeaters are connected 1-2-3-1 and the secondary are connected
3-2-1-3. If any single pair in this ring fails, the remaining two pairs continue to
communicate. No SISNet Distance Extenders are used in this remote peer ring.

Figure 2-7: SISNet Repeaters connected by multimode cable in a counter-rotation


fiber-optic ring topology
1
Pri Sec

Power Power
Fault Fault
Local Peer PX Local Peer PX
Local Peer RX Local Peer RX
Remote Peer PX Remote Peer PX
Remote Peer RX Remote Peer RX

System System
Repeater Repeater

RT R T

2
Pri Sec

Power Power
Fault Fault
Local Peer PX Local Peer PX
Local Peer RX Local Peer RX
Remote Peer PX Remote Peer PX
Remote Peer RX Remote Peer RX

System System
Repeater Repeater

RT R T

3
Pri Sec

Power Power
Fault Fault
Local Peer PX Local Peer PX
Local Peer RX Local Peer RX
Remote Peer PX Remote Peer PX
Remote Peer RX Remote Peer RX

System System
Repeater Repeater

R T R T

Related information

Extend the remote peer ring with SISNet distance extenders

Connect a remote peer ring with multimode fiber

16
Installing the system

Figure 2-8: Connectors on the SISNet Repeater (Bottom View)


Front

RxD

TxD

SISNet Bridge Port

1. Place one end of the fiber-optic cable connector on the input terminal (RxD) and
push and turn the cable connector into place.
2. Place the other end of the fiber-optic cable on the output terminal (TxD) of the
successor SISNet Repeater and push and turn the cable connector into place.
3. Connect straight-through or crossover cable (100 meter maximum) to the SISNet
Bridge Port.

Note
To prevent ground loops, build this cable assembly with a shielded, metal-enclosed RJ45
connector on one end and an isolated, plastic-enclosed RJ45 connector on the other end. The
metal connector end of the cable assembly must be connected to an Ethernet switch and the
plastic end must be connected to the SISNet Bridge Port.

4. Connect together all SISNet Repeaters in a counter-rotation topology.

Extending the remote peer ring


Use SISNet Distance Extenders to enable SISNet Repeaters to communicate over distances
greater than a few kilometers.

Note
The multimode fiber-optic cable on the SISNet Repeater connects to the SISNet Distance Extender
through a conversion cable. The SISNet Repeater end of the conversion cable has an ST male and the
SISNet Distance Extender end of the conversion cable has an SC male.

17
Installing the system

The following figure shows a remote peer ring with two local nodes (Nodes 1 and 3) and
one remote node (Node 2) where node refers to a SISNet Repeater pair and SISNet
Distance Extender pair. Link distances for a local node are less than or equal to 2 km
(nominal) one way. Link distances for a remote node are up to 20 km (nominal) one way.
This remote peer ring uses a counter-rotation topology in which the primary SISNet
Repeaters are connected clockwise and the secondary counterclockwise. Secure
parameters travel from Node 1 to Node 2 via Node 3 on the secondary ring. On the primary
ring, parameters travel from Node 2 to Node 1 via Node 3.

Figure 2-9: Remote peer ring with local and remote nodes

Node 1
TR TR

SIS Net SIS Net


Repeater Repeater

Power
Fault
Local Peer TX
Power
Fault
Local Peer TX
SISNet
Distance
SISNet
Distance
SISNet Distance
Local Peer RX Local Peer RX
Repeater Repeater
Remote Peer TX
Remote Peer RX
Remote Peer TX
Remote Peer RX Extenders
Power Power

SISNet Repeaters System


Repeater
System
Repeater
Single
Multi
Single
Multi REMOTE
TR TR

SIS NET SIS NET


REPEATER REPEATER

TR TR
RT RT Power
Fault
Local Peer TX
Local Peer RX
Power
Fault
Local Peer TX
Local Peer RX
SISNET
DISTANCE
SISNET
DISTANCE
Remote Peer TX Remote Peer TX REPEATER REPEATER
Remote Peer RX Remote Peer RX

Node 2 Power Power


Single Single
System System
Repeater Repeater Multi Multi

TR TR
TR TR
SIS NET
REPEATER
SIS NET
REPEATER
RT RT

Power Power
Fault Fault SISNET SISNET
Local Peer TX Local Peer TX
DISTANCE DISTANCE
Local Peer RX Local Peer RX
Remote Peer TX Remote Peer TX REPEATER REPEATER
Remote Peer RX Remote Peer RX

Node 3 System System


Power
Single
Multi
Power
Single
Multi
Repeater Repeater

RT RT TR TR

The following figure shows a remote peer ring in which all nodes are remote. Again, node
refers to a SISNet Repeater pair and SISNet Distance Extender pair. This remote peer ring
uses a counter-rotation topology in which the primary SISNet Repeaters are connected
clockwise and the secondary counterclockwise. Secure parameters travel from Node 1 to
Node 2 via Node 3 on the primary ring. On the secondary ring, parameters travel from
Node 2 to Node 1 via Node 3.

18
Installing the system

Figure 2-10: Remote peer ring with all remote nodes

Node 1
TR TR

SIS Net SIS Net


Repeater Repeater

SISNet
SISNet Distance
Repeaters Power
Fault
Power
Fault SISNet SISNet
Local Peer TX
Local Peer RX
Remote Peer TX
Local Peer TX
Local Peer RX
Remote Peer TX
Distance
Repeater
Distance
Repeater Extenders
Remote Peer RX Remote Peer RX

Power Power
Single Single
System System
Repeater Repeater Multi Multi

Node 2
TR TR

SIS NET SIS NET


REPEATER REPEATER

RT RT TR TR Power Power
Fault Fault SISNET SISNET
Local Peer TX Local Peer TX
DISTANCE DISTANCE
Local Peer RX Local Peer RX
Remote Peer TX Remote Peer TX REPEATER REPEATER
Remote Peer RX Remote Peer RX

Power Power
Single Single
System System
Repeater Repeater Multi Multi

Node 3
TR TR TR TR
RT RT
SIS NET SIS NET
REPEATER REPEATER

Power Power
Fault Fault SISNET SISNET
Local Peer TX Local Peer TX
DISTANCE DISTANCE
Local Peer RX Local Peer RX
Remote Peer TX Remote Peer TX REPEATER REPEATER
Remote Peer RX Remote Peer RX

Power Power
Single Single
System System
Repeater Repeater Multi Multi

TR TR
RT RT

Extend the remote peer ring with SISNet distance extenders

Note
The multimode fiber-optic cable on the SISNet Repeater connects to the SISNet Distance Extender
through a conversion cable. The SISNet Repeater end of the conversion cable has an ST male and the
SISNet Distance Extender end of the conversion cable has an SC male.

19
Installing the system

Figure 2-11: Multimode fiber-optic connectors on the SISNet Distance Extender


(bottom view)

Multimode RxD

Multimode TxD

Rear

20
Installing the system

Figure 2-12: Single mode fiber-optic connectors on the SISNet Distance Extender
(top view)

Single Mode TxD

Single Mode RxD

4 3 2 1

-24 VDC Return +24VDC

Rear

1. Install the SISNet Distance Extender on the DIN rail.


2. Connect multimode fiber-optic cable TxD to RxD between the SISNet Repeaters and
SISNet Distance Extenders.
3. Place a single mode fiber-optic cable end onto the SISNet Distance Extender's RxD
terminal and push the cable into place.
4. Place the other end onto the TxD terminal of the predecessor SISNet Distance
Extender and push the cable into place.
5. Place a single mode fiber-optic cable end onto the SISNet Distance Extender's TxD
terminal and push the cable into place.
6. Place the other end onto the RxD terminal of the successor SISNet Distance
extender and push the cable into place.
7. Connect together all SISNet Distance Extenders.

21
Installing the system

22
Checking out and troubleshooting your DeltaV SIS hardware

3 Checking out and troubleshooting


your DeltaV SIS hardware
Topics covered in this chapter:
Logic Solver LEDs
SISNet Repeater LEDs
SISNet Distance Extender LEDs

After installing, it is recommended that you check out the hardware for a smooth startup.
Follow these steps to check out your system:

Verify all power and ground connections.


Verify all field connections.
Verify all LED indicators.

Logic Solver LEDs

Table 3-1: Logic Solver LEDs

LED Pattern State


All (Simplex, Active, Standby) Off No Power
Green - Power and Yellow Standby On flashing Power-up tests in progress.
alternating with On flashing
Red - Error and Yellow Active
Simplex On solid Not commissioned
Green - Power On flashing
Red -Error On flashing
Yellow-Active
Redundant pair (Active) On solid Not commissioned
Green - Power On flashing
Red - Error On flashing
Yellow - Active
Redundant pair (Standby) On solid Not commissioned
Green - Power On flashing
Red - Error On flashing
Yellow-Standby

23
Checking out and troubleshooting your DeltaV SIS hardware

Table 3-1: Logic Solver LEDs (continued)

LED Pattern State


Simplex On solid Commissioned, not configured
Green - Power On flashing
Yellow - Active
Redundant pair (Active) On solid Commissioned, not configured
Green - Power On flashing
Yellow - Active
Redundant pair (Standby) On solid Commissioned, not configured or configuration
Green - Power On flashing in progress
Yellow - Standby
Simplex On solid Configured
Green-Power and Yellow-Active
Redundant pair (Active) On solid Configured
Green-Power and Yellow-Active
Redundant pair (Standby) On solid Configured
Green-Power and Yellow-Standby
Green - Power(1) On solid Card is not fully operational. Contact technical
Red - Error On solid support.
Yellow - Active On flashing
Yellow - Standby On flashing
Green - Power a On solid Error detected during power-up tests. Contact
Red - Error On solid technical support.

SISNet Repeater LEDs

Table 3-2: SISNet Repeater LEDs

Correct operat-
LED ing condition Fault indications Probably cause Corrective action
Power (green) On Off Power is not sup- Check power and
plied to unit. connections.
Fault (red) Off On Internal fault Contact technical
support
Flashing Maintenance re- Contact technical
quired. support

(1) Same for Simplex, Active, or Standby

24
Checking out and troubleshooting your DeltaV SIS hardware

Table 3-2: SISNet Repeater LEDs (continued)

Correct operat-
LED ing condition Fault indications Probably cause Corrective action
Local Peer Tx (yel- On - normal oper- Flashing (Local The SISNet Re- Contact technical
low) ations. The SISNet peer Tx only) peater is not re- support
Repeater is re- ceiving its own
ceiving global da- transmissions
ta from other SIS- while still receiv-
Net Repeaters ing the transmis-
and transmitting sions of local Log-
it to the Local ic Solvers.
peer bus. Flashing (both Lo- Local peer bus ex- Check Local peer
Flashing - normal cal peer Tx and tender cables are bus cables and
operations. There Rx) disconnected, termination.
is no Logic Solver bus is not termi-
for the SISNet Re- nated or is termi-
peater to syn- nated with wrong
chronize with on resistance.
the Local peer
Off The SISNet Re- Contact technical
bus.
peater Local peer support
bus transmitter
Note hardware has de-
This normally oc- tected a problem.
curs during early
configuration
when Logic Solv-
ers are planned,
but not yet instal-
led.

Local Peer Rx (yel- On - normal oper- Flashing (both Lo- The Local peer Check Local peer
low) ations. The SISNet cal peer Rx and bus extender ca- bus cables and
Repeater is re- Tx) bles are discon- termination.
ceiving transmis- nected, bus is not
sions from local terminated or is
Logic Solvers. terminated with
Off - normal oper- wrong resistance.
ations. There is no More than 5% of Check Local peer
Logic Solver for received messag- bus termination.
the SISNet Re- es have errors. Contact technical
peater to syn- support
chronize with on
the Local peer
bus.

25
Checking out and troubleshooting your DeltaV SIS hardware

Table 3-2: SISNet Repeater LEDs (continued)

Correct operat-
LED ing condition Fault indications Probably cause Corrective action
Off The SISNet Re- Contact technical
peater Local peer support
Note
bus receiver hard-
This normally oc-
ware has detec-
curs during early
configuration ted an error.
when Logic Solv-
ers are planned,
but not yet instal-
led.

Remote Peer Tx On - normal oper- Flashing Break in fiber-op- Check that this
(yellow) ations. The SISNet tic ring. SISNet Repeater
Repeater is trans- is receiving re-
mitting local and mote global data
remote global and its own global
messages on the data is making it
fiber-optic ring. around the ring.
Off Hardware error. Contact technical
support.
Remote Peer Rx On - normal oper- Flashing Fiber-optic cable Check fiber-optic
(yellow) ation. This SISNet is disconnected, cable connec-
Repeater is re- broken, or tions. Connec-
ceiving global da- crossed. tions are: primary
ta. to primary, sec-
ondary to secon-
dary.
More than 5% of Check remote
received messag- peer predecessor
es have errors. for transmit error.
Contact technical
support.
Off Hardware error. Contact technical
support.

Note
If a single SISNet Repeater is used (for example for diagnostic testing), loop the SISNet Repeater to
itself input to output.

SISNet Distance Extender LEDs

26
Checking out and troubleshooting your DeltaV SIS hardware

Table 3-3: SISNet Distance Extender LEDs

Correct Oper-
ating Condi- Fault Indica-
LED tion tors Probable Cause Corrective Action
PWR On Off Power is not supplied to Provide power to unit.
unit.
SM On Off No single mode carrier Restore connection to prede-
detected. cessor SISNet Distance Extend-
er's single mode TxD.
MM On Off No multimode carrier Restore connection to prede-
detected. cessor SISNet Repeater's multi-
mode TxD.

27
Checking out and troubleshooting your DeltaV SIS hardware

28
Environmental and heat dissipation specifications

4 Environmental and heat dissipation


specifications

The environmental specifications for normal operation of DeltaV SIS devices are:

Operating temperature: -40C to 70C (-40F to 158F) (1)


Storage temperature: -40C to 85C (-40F to 185F)
Relative humidity: 5% to 95% non-condensing
Shock: 10 g half-sine wave for 11 ms
Vibration: 1 mm peak-to-peak from 5 to 16 Hz; 0.5g from 16 to 150 Hz
Airborne contaminants: Severity level G3
IP 20 rating
Electromagnetic compatibility: Per EN61326-1, Criteria A and Namur NE21

Table 4-1: SIS devices' heat dissipation specifications

Product Specification
Simplex Logic Solver 16.0 W
Redundant Logic Solver 24.0 W
SISNet Repeater 9.6 W (per Repeater)
Auxiliary Relay Modules, Energize to Actuate and De-Energize to Actuate, 4.65 W
24 VDC
Auxiliary Relay Diode Module 2.25 W

(1) Forced air is required for Logic Solvers installed on VerticalPLUS carriers operating in a temperature range of 60C to 70C (140F to 158F).

29
Environmental and heat dissipation specifications

30
Logic Solver and channel specifications

5 Logic Solver and channel


specifications
Topics covered in this chapter:
Logic Solver specifications
Analog input channel specifications
HART two-state output channel specifications
Discrete input channel specifications
Discrete output channel specifications

Logic Solver specifications


The Logic Solver provides 16 channels of flexible I/O, meaning that each channel can be
configured as an Analog Input (HART), HART Two-State Output, Discrete Input, or Discrete
Output channel. Logic Solvers install on termination blocks.

Table 5-1: Logic Solver specifications

Item Specification
Input power 24 VDC 20%, 1.0 A plus field power (5.0 A total)
Note It is recommended that the Logic Solver and DeltaV controller and I/O use
separate power supplies.
Field Power 4 A maximum (actual value depends upon channel type and field device type)
Isolation Each channel is optically isolated from the system and factory tested to 1500
VDC. No channel-to-channel isolation.
LocalBus current None
Mounting On Logic Solver (yellow) terminal blocks in odd numbered slots (1, 3, 5, 7) on
the 8-wide carrier. Simplex Logic Solvers take 2 slots and redundant Logic Solv-
ers take 4 slots.

31
Logic Solver and channel specifications

Figure 5-1: Logic Solver dimensions

Input + + EMERSONTM
SLS 1508 24 VDC
Input Power Rating 24 VDC, 1.0 A plus Field Power (5.0 A total)
Ain w/HART 24 VDC, 24mA
Field Aout w/HART 24 VDC, 24mA
SLS 1508 Circuit
Rating
Dout 24 VDC, 500mA/Ch, 4.0 A/Card
Din 12 VDC, 8mA/Ch,
Ambient Temperature -40 \70o C
Field Connection Details
Power

105.5 mm
CHANNEL TERMINAL BLOCK FRONT ORIENTATION

(4.1 in)
Error NUMBER 1 2 3 14 15 16
Active TYPE Ain Aout Din Dout
Standby A + + + +
B
C
See Manual for complete specifications.

FM

83.8 mm (3.3 in) 110.0 mm (4.3 in)

Front View Side View

Simplex Logic Solver termination block


Logic Solvers install on termination blocks that provide 16 channels of I/O. There are
simplex and redundant Logic Solver terminal blocks. Each channel can be configured as an
Analog Input (HART), HART Two-State Output, Discrete Input, or Discrete Output channel.

Figure 5-2: Simplex Logic Solver termination block


Quick release tab

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

11 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

16 Channels

32
Logic Solver and channel specifications

Redundant Logic Solver termination block


Logic Solvers install on termination blocks that provide 16 channels of I/O. There are
simplex and redundant Logic Solver terminal blocks. Each channel can be configured as an
Analog Input (HART), HART Two-State Output, Discrete Input, or Discrete Output channel.

Figure 5-3: Redundant Logic Solver termination block


Quick release tabs

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

16 Channels

Analog input channel specifications


Specifications

Table 5-2: Analog Input channel specifications (includes HART)

Item Specification
Number of channels 16
Isolation Each channel is optically isolated from the system and factory tes-
ted to 1500 VDC. No channel-to-channel isolation.
Nominal signal range (span) 4 to 20 mA
Full signal range 1 to 24mA
Field circuit power per channel 24 mA
2-wire transmitter power 15.0 V minimum terminal to terminal @ 20 mA; current limited to
24 mA max.
Input measurement accuracy 0.2 % of span

33
Logic Solver and channel specifications

Table 5-2: Analog Input channel specifications (includes HART) (continued)

Item Specification
Safety/diagnostic accuracy 2.0% of span
Resolution 16 bits
Filtering 2-pole filter, corner frequency 5.68 Hz
-3 db at 5.68 Hz
-20.0 db at 40 Hz (half the sample rate)

Wiring diagram

Figure 5-4: Wiring diagram and terminations for HART Analog Input channels

A+
24 VDC FET

2-Wire analog
Diagnostics T and/or HART field
transmitter
B
HART

Current
limit
250 sense
A1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A+
2-Wire analog
B1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B T and/or HART field
transmitter
C1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

HART two-state output channel specifications


Specifications

Table 5-3: HART two-state output channel specifications

Item Specification
Number of channels 16
Isolation Each channel is optically isolated from the system and factory tested
to 1500 VDC. No channel-to-channel isolation.
Nominal signal range (span) On state - 20 mA
Off state - 0 or 4 mA (configurable)
Full signal range 0 to 24 mA
Safety/diagnostic accuracy 5% of span
Resolution 12 bits
Compliance voltage 20 mA into 600 load

34
Logic Solver and channel specifications

Table 5-3: HART two-state output channel specifications (continued)

Item Specification
Open-loop detection < 1.0 mA - when the output drifts 15% out of the configured value

Wiring diagram

Figure 5-5: Wiring diagram and terminations for 2- wire HART two-state output
channels

A+
24 VDC FET

Diagnostics load Two-state valve


B
HART

DAC

Read
A1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A+
back B1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
load

C1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Discrete input channel specifications


Specifications

Table 5-4: Discrete Input channel specifications

Item Specification
Number of channels 16
Isolation Each channel is optically isolated from the sys-
tem and factory tested to 1500 VDC. No chan-
nel-to-channel isolation.
Detection level for ON 2 mA
Detection level for OFF < 1.65 mA
Input impedance 1790
Input compatibility Inputs compatible with:
NAMUR sensors (12 V)
Dry contact
Dry contact with end of line resistance

35
Logic Solver and channel specifications

Table 5-4: Discrete Input channel specifications (continued)

Item Specification
Line fault detection - short circuit (optional) <100 for guaranteed short circuit detec-
tion
>6 mA (simplex)
>11 mA (redundant)
Line fault detection - open circuit (optional) >40 k for guaranteed open loop detection
<0.35 mA

Line fault detection

The Discrete Input channels have line fault detection for detecting open or short circuits in
field wiring. To use this capability you must:

Enable line fault detection in your configuration. Enable line fault detection on a
channel-by-channel basis when you configure the channels.
Connect the dry contact to external resistors. Connect the dry contact to a 12 k
resistor in parallel (allows the open circuit detection) and a 2.4 k resistor in series
(allows short circuit detection).
Emerson's End of Line Resistance Module (KJ2231X1-EC1) provides this function.
This module connects to the Discrete Input channel and to a field contact.

Line fault detection in NAMUR sensors

Line fault detection is built into NAMUR sensors. Do not use external resistors with NAMUR
sensors; however, you must enable line fault detection in your configuration when using
NAMUR sensors.

36
Logic Solver and channel specifications

Wiring diagrams

Figure 5-6: Wiring diagram and terminations for Discrete Input channels showing
the line fault detection options

+- Namur
sensor

or
1.5K A+
12 VDC FET
2.4K
+
12K Field devices
Diagnostics

B -
or

Current EOL Resistance


limit Module
250 sense
+ + +
- - -

A1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A+
B1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Field device

C1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 B

It is assumed and recommended that applications use line fault detection; however, line
fault detection can be omitted. The following image shows a wiring diagram and
terminations for the Discrete Input channels without the line fault detection options.

37
Logic Solver and channel specifications

Figure 5-7: Wiring diagram and terminations for Discrete Input channels without
line fault detection options
1.5K A+
12 VDC FET

Field device
Diagnostics

Current
limit
250 sense

A1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A+
B1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Field device

C1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 B

Discrete output channel specifications


Installation notes

When driving inductive loads greater than or equal to 0.8 Henry in simplex or 0.3 Henry in
redundant, an RC compensator may be required. Size the RC compensator at 3.3 k and
0.47 f for simplex and 2.7 k and 0.22 f for redundant. Emerson's R-C Compensator
module (KJ2231X1-ED1) provides this function. This module can be used for simplex and
redundant applications.

Important
The R-C Compensator should not be used with LS DO CHARMs.

Pulse testing is recommended; however, it can be disabled for field devices such as solid
state relays or active electronics that cannot support it. With redundant Logic Solvers,
pulse testing requires partner synchronization and stops if the redundant partner becomes
unavailable.

Line fault detection is not compatible with significant capacitive loading (cable + load > 30
nF) and must be disabled under these conditions.

38
Logic Solver and channel specifications

Specifications

Table 5-5: Discrete Output Channel Specifications

Item Specification
Number of channels 16
Isolation Each channel is optically isolated from the system and factory tested to
1500 VDC. No channel-to-channel isolation.
Output voltage Field power minus 2 V
Field power 0.5 A continuous per channel; 4.0 A max. per card
Output loading 56 to 3500
Off-state leakage Open loop test off: 4.5 A typical; 10 A max.
Note Optional pulse test will apply 24 VDC pulse on line for 1.0 mS ev-
ery 50 mS. Refer to the Installation notes for more information on pulse
testing.
Short circuit protection Outputs current limited to 2.0 A typical
Line fault detection - < 5 for > 1 second with +24 VDC field power. Refer to the
short circuit Installation notes for information on pulse testing.
Line fault detection - >25 k for guaranteed open loop detection
open circuit (with +24 < 3.5 k for guaranteed no open loop detection
VDC field power) Refer to the Installation notes for information on pulse testing.

39
Logic Solver and channel specifications

Wiring Diagram

Figure 5-8: Wiring diagram and terminations for Discrete Output channels

A+
24 VDC FET

Diagnostics

B
R (3.3 K simplex and 2.7 K redundant)

load RC
Compensator
C (0.47 f simplex and 0.22 f redundant)

(return)

A1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A+
B1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

load
C1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

40
SISNet Repeater and SISNet Distance Extender specifications

6 SISNet Repeater and SISNet Distance


Extender specifications
Topics covered in this chapter:
SISNet Repeater specifications
SISNet Distance Extender specifications
Calculating the fiber-optic link loss

SISNet Repeater specifications

Table 6-1: SISNet Repeater specifications

Item Specification
Port type ST female
Cable type Multimode 62.5 /125 m ST type or Multimode 50 /125 m ST type
Output power < -12dBm
Link budget Multimode 62.5 /125 m - max attenuation 11 dB
Multimode 50 /125 m - max attenuation 8 dB
Wavelength 1300 nm
Link distance (nominal) 2 km one way TxD to RxD; actual length depends upon the quality of the
fiber-optic cable
Refer to Calculating the fiber-optic link loss for additional information.
Topology Physical ring: RxD connects to TxD of predecessor and TxD connects to
RxD of successor.
SISNet Bridge port Used to make an Ethernet connection between SISNet Repeaters in dif-
ferent SISNet rings.
Mounting 2-wide SISNet Repeater carrier; left carrier position is primary SISNet Re-
peater; right carrier position is secondary SISNet Repeater

Table 6-2: SISNet Repeater power specifications

Item Specification
Input power 24 VDC 300 mA (max)
Connector type 4-position screw terminal
Wire type Solid or Stranded
Wire gauge 12 AWG maximum

41
SISNet Repeater and SISNet Distance Extender specifications

Dimensions

Figure 6-1: SISNet Repeater dimensions

+ + Input
24 VDC

SIS NET
SIS Net Repeater
EMERSONTM
REPEATER
Input Power Rating 24 VDC, 300mA Max
Ambient Temperature -40 to 70o C
See manual for complete specifications.

Power
Fault
Local Peer TX
Local Peer RX
Remote Peer TX
Remote Peer RX

CL. I Div. 2
159.6 mm
II 3G
System
Repeater
FM GP .A,B,C,D
HAZ.LOC.
Ex nA IIC (6.3 in)
TEMP . Rating T4
Nemco 02ATEX431U LR87534
APPROVED

See dwg 12P1293 for installation information

05

Fisher-Rosemount Systems
Emerson Process Managemant, Ltd
Round Rock, TX USA

Bridge
RxD TxD

41.8 mm (1.6 in) 110.0 mm (4.3 in)

Front View Side View

Related information

Calculating the fiber-optic link loss

SISNet Distance Extender specifications

Table 6-3: SISNet Distance Extender specifications

Item Specification
Port types Multimode fiber port- Duplex SC
Single mode fiber port - Duplex LC
Cable types Multimode - 62.5 /125 m ST type or 50/125 m ST type
Single mode- 9/125 m, 8.8/125 m, 8.5/125 m, 8.2/125 m
Refer to the note about the conversion cable ends in
Extend the remote peer ring with SISNet distance extenders.

42
SISNet Repeater and SISNet Distance Extender specifications

Table 6-3: SISNet Distance Extender specifications (continued)

Item Specification
Output power Multimode - 14 dBm
Single mode - 0 dBm
Link budget Multimode
62.5 /125 m - max attenuation 11 dB
50/125 m - max attenuation 8 dB
Wavelength 1300 nm
Single mode
9/125 m - max attenuation 30.0 dB
8.8/125 m - max attenuation? 29.0 dB
8.5/125 m - max attenuation 28.5 dB
8.2/125 m - max attenuation 28.0 dB
Wavelength 1310 nm
Link distance Multimode - 2 km one way TxD to RxD
(nominal) Single mode - 60 km one way TxD to RxD
Note Actual lengths depend upon the quality of the fiber-optic cable and the
connections.
Topology Multimode (between SISNet Repeaters and SISNet Distance Extenders):SISNet
Repeater RxD to SISNet Distance Extender TxD and SISNet Repeater TxD to SIS-
Net Distance Extender RxD.
Single mode (between SISNet Distance Extenders): RxD of successor SISNet Dis-
tance Extender to TxD of predecessor SISNet Distance Extender.
Mounting DIN rail

Table 6-4: SISNet Distance Extender power specifications

Item Specification
Input power 19.2 VDC to 28.8 VDC @ 250 mA max
Connector type 4-position screw terminal
Wire type Solid or Stranded
Wire gauge 12 AWG maximum

43
SISNet Repeater and SISNet Distance Extender specifications

Dimensions

Figure 6-2: SISNet Distance Extender dimensions


RXD TXD
1. 24VDC

1 2 3 4
2. 24VDC
3. RETURN (GND)
4. RETURN (GND) SINGLE MODE FIBER

SISNET
DISTANCE
KJ2222 SISNet Distance Extender EMERSONTM
EXTENDER
Power Rating 24VDC, 250mA
Ambient Temp -40 TO 70o C
See Installation Manual for complete specifications.
Front Bezel LED Descriptor Legend
Power
ON=POWER PRESENT
Single PWR OFF=POWER ABSENT
Multi 73.6 mm 99.1 mm
ON=SINGLE MODE CARRIER DETECTED
(2.9 in) SM
OFF=NO SINGLE MODE CARRIER DETECTED (3.9 in)
ON=MULTI-MODE CARRIER DETECTED
MM OFF=NO MULTI-MODE CARRIER DETECTED

Class I Div. 2
II 3 G
EEx nA IIC T4
FM GP A,B,C,D
HAZ.LOC.
Nemko 02ATEX431U 1180 TEMP. Rating T4 Ta+70oC
APPROVED
LR87534 See dwg 12P1293 for installation information

WARNING: Do not separate when electrical connections are energized


unless the area is known to be non-hazardous.

SISNET REPEATER

TXD RXD

19.2 mm 113.5 mm (4.5 in)


(0.75 in)
Front View Side View

Related information

Extend the remote peer ring with SISNet distance extenders

Calculating the fiber-optic link loss


The fiber-optic link budget must account for all losses at fiber-optic cable splices and
connector insertion points. Keep an accurate account of losses at all connectors and
splices in the system. Refer to SISNet Repeater specifications and
SISNet Distance Extender specifications for the link budgets for single mode and multimode
fiber at various core diameters. The manufacturer of the components can provide the loss
specifications. Many types of cables and connectors with different loss (attenuation)
specifications are available.

Example fiber-optic link loss calculation for multimode fiber

The following example shows typical link losses in a multimode, point-to-point fiber-optic
link.

Link budget 11 dB
Fiber-optic cable (example 2 dB/km) x 2 km max = 4 dB

44
SISNet Repeater and SISNet Distance Extender specifications

TxD connector =.5 dB


RxD connector =.5 dB
Patch panel splices 2 x .5 dB = 1 dB
Fiber-optic cable loss due to aging over time = 3 dB
Total link losses = 4 + .5 + .5 + 1 + 3 = 9 dB

Margin = 11 dB -9 dB = 2 dB (the margin is greater than zero and falls within the link
budget).

Example fiber-optic link loss calculation for single mode fiber

The following example shows typical link losses in a single mode, point-to-point fiber-optic
link with a core diameter of 9/125 m. Refer to SISNet Repeater specifications and
SISNet Distance Extender specifications for the link budgets for other fiber-optic core
diameters.

Link budget 30 dB
Fiber-optic cable (example 0.38 dB/km) x 60 km max = 22.8 dB
TxD connector = 0.6 dB
RxD connector = 0.6 dB
Patch panel splices 2 x 0.1 dB = 0.2 dB
Cable splices 10 x 0.1 dB = 1 dB
Fiber-optic cable loss due to aging over time = 3 dB
Total link losses = 22.8 + 0.6 + 0.6 + 0.2 + 1.0 + 3.0 = 28.2 dB

Margin = 30 dB - 28.2 dB = 1.8 dB (the margin is greater than zero and falls within the link
budget).

Related information

SISNet Repeater specifications


SISNet Distance Extender specifications

45
SISNet Repeater and SISNet Distance Extender specifications

46
Extending an operational system

7 Extending an operational system


Topics covered in this chapter:
Add carriers to an operational system
Add SISNet Repeaters to an operational system
Using DeltaV intrinsically safe cards with DeltaV SIS hardware

Add carriers to an operational system


Additional carriers and components can be added to an operational DeltaV SIS system to
extend the system. However, care must be taken to add the carriers without disrupting
communication on the local peer bus. Follow these steps to add one or more 8-wide
carriers to an operational system.

WARNING!
Be sure to follow the manufacturer's installation procedure and all applicable plant procedures
when performing installation maintenance on an operational system. Failure to follow the
appropriate procedures could result in unexpected and undesired system operation.

1. Install a left and right one-wide carrier to the 8-wide carrier that you intend to add to
the existing system.
2. Connect the 44 pin D-Shell carrier extender cables between the existing carrier and
the new carrier.
3. Remove the 120 ohms BNC terminator from the secondary black connector on the
existing right one-wide carrier and install it on the black connector on the new right
one-wide carrier.
4. Connect the local peer bus cable from the open, secondary black BNC connector on
the existing carrier to the secondary black BNC connector on the new left one-wide
carrier.
5. Open DeltaV Diagnostics and verify that there are no MaintAlerts or AdviseAlerts
involving SISNet Error or SISNet High Error Rate for any Logic Solver. Also if using
SISNet Repeaters, verify that Repeater02 OInteg is Good.

WARNING!
Do not proceed until all alerts and statuses are Good in DeltaV Diagnostics.

6. Remove the 120 ohms BNC terminator from the primary white connector on the
existing one-wide carrier and install it on the white connector on the new right one-
wide carrier.

47
Extending an operational system

7. Connect the local peer bus cable from the primary white BNC connector on the
existing right one-wide to the primary white BNC connector on the new left one-
wide carrier.
8. In DeltaV Diagnostics verify that there are no MaintAlerts or AdviseAlerts involving
SISNet Error or SISNet High Error Rate for any Logic Solver. If using SISNet Repeaters,
verify that Repeater01 OInteg is Good.

Related information

Install carrier extender cables


Terminate the local peer bus

Add SISNet Repeaters to an operational system


Additional SISNet Repeaters can be added to an operational DeltaV SIS system to extend
the system. However, care must be taken to add the SISNet Repeaters without disrupting
communication on the remote peer ring.

Note
Refer to Setting up the remote peer ring and to the specifications in the SISNet Repeater specifications
section before adding SISNet Repeaters and SISNet Distance Extenders to an operational system.

Note
SISNet Distance Extenders are considered to be part of a SISNet Repeater node (primary or
secondary). Add SISNet Distance Extenders along with SISNet Repeaters one node at a time to
ensure that communication on the remote peer ring is not disrupted.

The following example shows how to add a third SISNet Repeater pair to an operational
system.

1. Install the carriers, Logic Solvers, cards, terminators, and the new SISNet Repeater
pair.

In this example, the new SISNet Repeater pair is referred to as Pri. (Primary) and Sec.
(Secondary) SISNet Repeater 3.

48
Extending an operational system

Figure 7-1: A Third SISNet Repeater added to an operational system


Two SISNet Repeater nodes in A third SISNet Repeater node
an operational DeltaV SIS added to the same DeltaV SIS
1 1
Pri Sec Pri Sec

Power Power Power Power


Fault Fault Fault Fault
Local Peer PX Local Peer PX Local Peer PX Local Peer PX
Local Peer RX Local Peer RX Local Peer RX Local Peer RX
Remote Peer PX Remote Peer PX Remote Peer PX Remote Peer PX
Remote Peer RX Remote Peer RX Remote Peer RX Remote Peer RX

System System System System


Repeater Repeater Repeater Repeater

RT R T RT R T

2 2
Pri Sec Pri Sec

a Power
Fault
Local Peer PX
Local Peer RX
Remote Peer PX
Remote Peer RX
Power
Fault
Local Peer PX
Local Peer RX
Remote Peer PX
Remote Peer RX
b Power
Fault
Local Peer PX
Local Peer RX
Remote Peer PX
Remote Peer RX
Power
Fault
Local Peer PX
Local Peer RX
Remote Peer PX
Remote Peer RX

System System System System


Repeater Repeater Repeater Repeater

RT R T a RT R T b

3
Pri Sec

Power Power
Fault Fault
Local Peer PX Local Peer PX
Local Peer RX Local Peer RX
Remote Peer PX Remote Peer PX
Remote Peer RX Remote Peer RX

New SISNet Repeater node 3 System


Repeater
System
Repeater

R T R T

2. Remove the cable labeled a in the preceding image from the existing two Pri.
SISNet Repeater nodes and replace it with a new fiber-optic cable that connects R
(RxD) on Pri. SISNet Repeater 1 to T (TxD) on the new Pri. SISNet Repeater 3.
3. Install a fiber-optic cable that connects R (RxD) on the new Pri. SISNet Repeater 3 to
T (TxD) on Pri. SISNet Repeater 2.
4. Open DeltaV Diagnostics and be sure that OInteg is GOOD for each primary SISNet
Repeater (REPEATER01). (The path to SISNet Repeaters is SISNetwork/Repeaters/
Controller/SISNet Repeaters/REPEATER01/02.)
5. Remove the cable labeled b in the preceding image from the existing two Sec.
SISNet Repeater nodes and replace it with a new fiber-optic cable that connects T
(TxD) on Sec. SISNet Repeater 1 to R (RxD) on the new Sec. SISNet Repeater 3.
6. Install a fiber-optic cable that connects T (TxD) on the new Sec. SISNet Repeater 3 to
R (RxD) on Sec. SISNet Repeater 2.
7. In DeltaV Diagnostics, be sure that OInteg is GOOD for each secondary SISNet
Repeater (REPEATER02). (The path to SISNet Repeaters is SISNetwork/Repeaters/
Controller/SISNet Repeaters/REPEATER01/02.)

49
Extending an operational system

Related information

Setting up the remote peer ring


SISNet Repeater specifications
Agency approvals

Using DeltaV intrinsically safe cards with


DeltaV SIS hardware
A single DeltaV controller can host both DeltaV SIS hardware and DeltaV Intrinsically Safe
(I.S.) cards making it possible to use DeltaV I.S. cards in a DeltaV Safety Instrumented
System. One-wide carriers and extender cable, with the right one-wide carrier terminated,
are used to connect DeltaV SIS to a second 8-wide carrier installed with DeltaV I.S. cards. A
LocalBus Isolator and I.S. Power Supply must be installed on the second carrier. The
LocalBus Isolator separates DeltaV I.S. cards from standard I/O cards to protect the I.S.
cards from damaging voltages.

Install intrinsically safe cards in a DeltaV SIS system

50
Extending an operational system

Figure 7-2: DeltaV I.S. cards used with DeltaV SIS hardware

Controller
System Standard DeltaV
power supply cards (optional)
SISNet Repeaters

SLS 1580 SLS 1580 A


Power Power
Error Error
Power Power
Active
Fault Fault
Standby
Local Peer PX Local Peer PX
Pri CN
Sec CN Local Peer RX Local Peer RX
Remote Peer PX Remote Peer PX
Remote Peer RX Remote Peer RX

Controller
System
Passthrough
MD C
Power Supply System System
(DC/DC)
Repeater Repeater

LOCK

B
FISHER-ROSEMOUNT

Logic Solvers
Terminated right
one-wide carrier

LocalBus IS
Isolator Power supply DeltaV IS cards

C D

Left one-wide A
carrier

LOCK

+ +

1. Install a right one-wide carrier onto the 8-wide carrier installed with DeltaV SIS
components by sliding together the 48 pin connectors on the carriers.
2. Install a left one-wide carrier onto the 8-wide carrier to be installed with DeltaV I.S.
cards by sliding together the 48 pin connectors on the carriers.
3. Terminate the right one-wide carrier.
4. Connect the 44 pin D-shell (male) connector on the one-wide carrier extender cable
to the top D-shell (female) connector on the terminated, right one-wide carrier and
fasten the retainer screws.
5. Connect the 44 pin D-shell connector on the other end of the cable to the top D-
shell connector on the left one-wide carrier and fasten the retainer screws.
6. Install a LocalBus Isolator and I.S. Power Supply on the 8-wide carrier holding the
DeltaV I.S. cards to separate standard DeltaV cards from DeltaV I.S. cards. Refer to
the Installing Your DeltaV Digital Automation System manual for information on
installing DeltaV I.S. components.

Related information

Terminate the local peer bus

51
Extending an operational system

52
Using auxiliary equipment with DeltaV SIS hardware

8 Using auxiliary equipment with


DeltaV SIS hardware
Topics covered in this chapter:
Relay Modules for fire and gas applications
Auxiliary Relay DTA-Inverting module specifications
Auxiliary Relay Diode module
Relay Module for other applications
Auxiliary Relay ETA-Direct module specifications
SIS Relay Module

Relay Modules for fire and gas applications


DeltaV SIS hardware can be used with auxiliary equipment to support energize to actuate
applications such as fire and gas applications.

Two modules are available for fire and gas and other energize to actuate applications:

Auxiliary Relay De-Energize to Actuate (DTA-Inverting) module


Auxiliary Relay Diode module

The Auxiliary Relay DTA-Inverting module has a connection to a redundant Logic Solver's
discrete input and discrete output channels and connections to redundant 24 VDC power
supplies. Field terminals are used to connect to the Relay Diode module that is located
next to the field actuator as shown in the following figure.

Figure 8-1: Block diagram for fire and gas application


Redundant
Redundant 24VDC
Logic Solvers Power Supply
DIN
DOUT

Input power

Relay Relay Field


Status Diode Actuator
output
Module

Auxiliary
Relay
Coil DTA-Inverting
Module

53
Using auxiliary equipment with DeltaV SIS hardware

Auxiliary Relay DTA-Inverting module


specifications
The Auxiliary Relay DTA-Inverting module energizes the field when Discrete Out is turned
Off.

The Auxiliary Relay DTA-Inverting module is paired with the Auxiliary Relay Diode module
to perform the required function such as monitoring field wiring when not actuated. A
switch on the Auxiliary Relay Diode module is used to change between Energize to Actuate
and De-Energize to Actuate. The Auxiliary Relay DTA-Inverting module's LED shows if
power is correctly installed and the state of the relay coil.

The Auxiliary Relay DTA-Inverting module has the following connections:

Two pin connections for primary power


Two pin connections for secondary power
Two pin connections for field output to the Auxiliary Relay Diode module
Two pin connections for coil input
Two pin connections for status output
Two pin connections for auxiliary output contact closure (not used in the application
depicted in the following figure).

54
Using auxiliary equipment with DeltaV SIS hardware

Figure 8-2: Auxiliary Relay DTA-Inverting module top view and dimensions
22.5 mm
(0.9 in)
DIN Rail End

+ To field
diode module
8
7
6
4
5 3
2
1
Secondary 24 +
VDC power
100.0 mm Primary 24 VDC power
+
(4.0 in)

RY
I LIA
X
AULAY
REA TING
DtVER R
IN OWE
P

Y
LA
RE

114.0 mm
(4.5 in)

55
Using auxiliary equipment with DeltaV SIS hardware

Figure 8-3: Bottom view of the Auxiliary Relay DTA-Inverting module

AU
RE XIL
Dt LAYIARY
IN A
VE
DIN Rail End RT
IN
G
PO
W
ER

RE
LA
Y

Auxiliary contact
(normally open) +

Status to Logic
Solver Discrete In +
9
10
11
1 2
13
14 +
15 Coil input from
16
Logic Solver Discrete Out

Table 8-1: Auxiliary Relay DTA-Inverting module specifications

Item Specification
Input field power 24 VDC 20% 5A maximum (actual current depends upon actuator used)
Contains integrated OR-ing diodes for redundant 24 V inputs.
Relay current rating 5 A @ 24 VDC nominal
Isolation None
Power input and Logic Solvers must be connected to a common ground.
Coil input voltage 17-28.8 VDC to energize
Coil input impedance 430
Mounting horizontal DIN rail

Note
The line fault detection values in the following table only apply when line fault detection is enabled.
When line fault detection is not enabled, the On states detect opens only and the Off states detect
shorts only.

56
Using auxiliary equipment with DeltaV SIS hardware

Table 8-2: Auxiliary Relay DTA-Inverting module functions

DI Chan-
nel
Process DO Relay Relay Relay (Relay
State Channel State LED Output Status) Line Fault Detection

Relay Out-
DO DI put
Normal On (1) On On Off On (1) Open/ Open/ Open/
(Alarm Off) Short Short Short
Tripped Off (0) Off Off On Off (0) Open/ Open/ N/A
(Alarm On) Short Short

Related information

Auxiliary Relay Diode module

Auxiliary Relay Diode module

Table 8-3: Auxiliary Relay Diode module specifications

Item Specification
Mode selection Switch selectable between ETA and DTA operation. Incorrect switch position will
cause bad status on SLS Discrete Input.
Diode rating 24 VDC 20% 5 A maximum (actual current depends upon actuator used)
Mounting Per DIN 43729

57
Using auxiliary equipment with DeltaV SIS hardware

Figure 8-4: Auxiliary Relay Diode Module connections, switch positions, and
dimensions
Input from Output to field actuator
Aux Relay
Module

Mounting
screws

+ +

DTA

ETA
(as shown)

30.0 mm
(1.2 in)

57.0 mm (2.2 in)

Relay Module for other applications


DeltaV SIS can be used with auxiliary equipment to support other applications. Two
modules are available for other applications:

Auxiliary Relay Energize to Actuate (ETA-Direct) module


Auxiliary Relay Diode module

The Auxiliary Relay ETA-Direct module energizes the field when Discrete Out is turned On.

The Auxiliary Relay ETA-Direct module has a connection to a Logic Solver's discrete input
and discrete output channels and a connection to a dual 24 VDC power supply. Two field
terminals are used to connect to the Auxiliary Relay Diode module that is located next to
the field actuator as shown in the following figure.

58
Using auxiliary equipment with DeltaV SIS hardware

Figure 8-5: Block Diagram for other application


Redundant
Redundant 24VDC
Logic Solvers Power Supply

DIN
DOUT

Input power

Relay Relay Field


Status Diode Actuator
output
Module

Auxiliary
Relay
Coil DTA-Inverting
Module

Auxiliary Relay ETA-Direct module


specifications
The Auxiliary Relay ETA-Direct module energizes the field when Discrete Out is turned On.
This module is not intended for SIL-certified applications but may be useful in lock-out or
deluge applications where an unintended trip caused by a Logic Solver fault or operator
error could be hazardous to personnel and equipment.

The Auxiliary Relay ETA-Direct module is paired with the Auxiliary Relay Diode module to
perform the required function. A switch on the Auxiliary Relay Diode module is used to
change between Energize to Actuate and De-Energize to Actuate. The Auxiliary Relay ETA-
Direct module's LED shows if power is correctly installed and the state of the relay coil.

Table 8-4: Auxiliary Relay ETA-Direct module specifications

Item Specification
Input field power 24 VDC 20% 5A maximum l (actual current depends upon actuator used)
Contains integrated OR-ing diodes for redundant 24 V inputs.
Relay current rating 5 A @ 24 VDC nominal
Isolation None
Power input and Logic Solvers must be connected to a common ground.
Coil input voltage 17-28.8 VDC to energize
Coil input impedance 430
Mounting horizontal DIN rail

The connections on the Auxiliary Relay ETA-Direct module are the same as those on the
Auxiliary Relay DTA-Inverting module.

59
Using auxiliary equipment with DeltaV SIS hardware

Note
The line fault detection states in the following table apply only when line fault detection is enabled.
When line fault detection is not enabled, the On states detect opens only and the Off states detect
shorts only.

Table 8-5: Auxiliary Relay ETA-Direct module functions

DI Chan-
nel
Process DO Relay Relay Relay (Relay
State Channel State LED Output Status) Line Fault Detection

Relay
DO DI Output
Normal Off (0) Off Off Off On (1) Open/ Open/ Open/
(Alarm Off) Short Short Short
Tripped On (1) On On On Off (0) Open/ Open/ N/A
(Alarm On) Short Short

Related information

Auxiliary Relay Diode module


Auxiliary Relay DTA-Inverting module specifications

SIS Relay Module


The SIS Relay module can be used with DeltaV SIS hardware to switch up to 2.5A at 250
VAC for safety applications. It opens contacts for field power when de-energized.

The SIS Relay module contains three relays from different manufacturers. A relay coil is
energized for all three relays in normal operation. If a demand occurs, the SLS removes the
power from the coil for all three relays at the same time. Each relay can be proof tested in
the field. The SIS Relay module's LED shows if power is correctly installed and the state of
the relay coil. The dimensions for the SIS Relay are the same as the Voltage Monitor.

Related information

Proof testing the SIS Relay Module


Voltage Monitor specifications

SIS Relay module specifications

60
Using auxiliary equipment with DeltaV SIS hardware

Table 8-6: SIS Relay module specifications

Item Specification
Input power rating 70 mA @24 VDC 20%
Relay current rating 2.5 A @ 250 VAC
2.5 A @ 30 VDC
Mounting Horizontal DIN rail

The SIS Relay module has the following AC field wiring connections:

Two pin connections for input from an SLS Discrete Output channel
Two pin connections for input from an AC power source
Two pin connections for output to an AC field device

Figure 8-6: SIS Relay module for AC field wiring

43
2
1
87
6

SI
RE
To SLS discrete S
LA
5

output channel + Y
PW
R
Power LED
TE
ST
1
TE
ST
2
Toggle switches for
TE
ST
proof testing the
3 circuits

To - AC field devices

9
10
11
1 2 From AC
16 Power Source
15
14
13

The SIS Relay module has the following DC field wiring connections:

61
Using auxiliary equipment with DeltaV SIS hardware

Two pin connections for input from an SLS Discrete Output channel
Four pin connections for input from two DC power sources
Four pin connections for output to two DC field devices

Figure 8-7: SIS Relay module for DC field wiring

43
To DC Power source 2
+

2
1
To DC Power source 1
+

87
6
SI
RE
To SLS Discrete S
LA

5
Output channel + Y
PW
R
Power LED
TE
ST
1
TE
ST
2
Toggle switches for
TE
ST
proof testing the
3 circuits

+
To - DC field device 1

+
To - DC field device 2

9
10
11
1 2

16
15
14
13

Proof testing the SIS Relay Module


It is important that you proof test all three relays individually. A circuit that does not open
when the switch is toggled indicates a stuck contact. If this occurs, replace the module. It is
the user's responsibility to by-pass the field circuit during proof testing if required.

Proof test the SIS Relay module for AC wiring


1. Measure the voltage at the AC field device's + and - connections (screw terminals 9
and 11). The voltage at these points should match the input voltage.

62
Using auxiliary equipment with DeltaV SIS hardware

2. Slide the switch labeled Test 1 down to toggle it and then measure the voltage at
the AC field device's + and - connections (screw terminals 9 and 11). The voltage at
these points should be 0 when toggled. Release the toggle and re-measure the
voltage.
3. Slide the switch labeled Test 2 down to toggle it and then measure the voltage at
the AC field device's + and - connections (screw terminals 9 and 11). The voltage at
these points should be 0 when toggled. Release the toggle and re-measure the
voltage.
4. Slide the switch labeled Test 3 down to toggle it and then measure the voltage at
the AC field device's + and - connections (screw terminals 9 and 11). The voltage at
these points should be 0 when toggled. Release the toggle and re-measure the
voltage.

Proof test the SIS Relay module for DC wiring


1. Measure the voltage at the first DC field device's + and - connections (screw
terminals 9 and 10). The voltage at these points should match the input voltage.
2. Slide the switch labeled Test 1 down to toggle it and then measure the voltage at
the DC field device's + and - connections (screw terminals 9 and 10). The voltage at
these points should be 0 when toggled. Release the toggle and re-measure the
voltage.
3. Slide the switch labeled Test 2 down to toggle it and then measure the voltage at
the DC field device's + and - connections (screw terminals 9 and 10). The voltage at
these points should be 0 when toggled. Release the toggle and re-measure the
voltage.
4. Slide the switch labeled Test 3 down to toggle it and then measure the voltage at
the DC field device's + and - connections (screw terminals 9 and 10). The voltage at
these points should be 0 when toggled. Release the toggle and re-measure the
voltage.

If you have a second DC field device, perform steps 1-4 by measuring the voltage at pins 11
and 12.

Voltage Monitor specifications


The Voltage Monitor can be used with DeltaV SIS hardware to drive a Logic Solver's
Discrete Input channel or a Series 2 DI Dry Contact channel based on the output of the SIS
Relay module. As shown in the image, the Voltage Monitor has the following connections:

Four pin connections for connecting input to DC or AC power sources


Four pin connections for connecting outputs to two SLS DI channels
Four pin connections for connecting outputs to two DI, Dry Contact channels

63
Using auxiliary equipment with DeltaV SIS hardware

Table 8-7: Voltage Monitor specifications

Item Specification
Input power rating per channel 6 mA @ 24 VDC 20%
15 mA @ 120/230 VAC
Mounting horizontal DIN rail

Figure 8-8: Voltage Monitor top view and dimensions


22.5 mm
(0.9 in)
DIN Rail End

8
7 Input 1
+
6 24 VDC, 120 VAC
5
or 230 VAC
4
Input 2 3
24 VDC, + 2
120 VAC 1
or 230 VAC

100.0 mm
(4.0 in)
GE
L TAOR
VO NIT
MO
A
st
Te
B
1 st Toggle switches
AN Te A
CH st for proof testing
Te
2 est B
AN T
CH

114.0 mm
(4.5 in)

64
Using auxiliary equipment with DeltaV SIS hardware

Figure 8-9: Voltage Monitor bottom view

VO
MOLTA
NI GE
TO
R

Te
CH st
AN A
1
Te
st
B
Te
CH st
AN A
2
Te
s tB

+
To SLS Discrete Input channel
9
10
11
1 2

13 + To Auxiliary 1
14
15
16

+ To Auxiliary 2

+ To SLS Discrete Input channel

Proof test the Voltage Monitor


The output to the SLS Discrete Input channels can be proof tested. A circuit that does not
open when the switch is toggled indicates a stuck contact. If this occurs, replace the
Voltage Monitor.

1. Measure the voltage at SLS Discrete Input channel one (screw terminals 9 and 10).
The voltage should be about 7 VDC.
2. Slide the switch labeled CHAN 1 to the Test A position and then measure the voltage
at SLS Discrete Input channel one (screw terminals 9 and 10). The voltage should
increase to about 11 VDC.
3. Release the switch to its original position.
4. Slide the switch labeled CHAN 1 to the Test B position and then measure the voltage
at SLS Discrete Input channel one (screw terminals 9 and 10). The voltage should
increase to about 11 VDC.
5. Measure the voltage at SLS Discrete Input channel two (screw terminals 13 and 14).
The voltage should be about 7 VDC.

65
Using auxiliary equipment with DeltaV SIS hardware

6. Slide the switch labeled CHAN 2 to the Test A position and then measure the voltage
at SLS Discrete Input channel one (screw terminals 13 and 14). The voltage should
should increase to about 11 VDC.
7. Release the switch to its original position.
8. Slide the switch labeled CHAN 2 to the Test B position and then measure the voltage
at SLS Discrete Input channel one (screw terminals 13 and 14). The voltage should
should increase to about 11 VDC.

SIS Current Limiter specifications


The SIS Current Limiter limits the current from the SLS Discrete Output channels to levels
below the ignition curves for Class 1 Div 2 and Zone 2 installations. Field wiring from the
Current Limiter output to the field can be removed and reconnected under power.

Table 8-8: SIS Current Limiter specifications

Item Specification
Input power (from SLS DO channels) 17 to 29 VDC; 22 VDC nominal
Output power 28.8 VDC (max)
Output current range 0-100 mA (max)
Output current limit threshold 100 mA (min); 120 mA (max)
Mounting Horizontal DIN rail

The SIS Current Limiter has the following connections as shown in the image:

Four pin connections for input from the SLS DO channels


Four pin connections for output to energy-limited loads

66
Using auxiliary equipment with DeltaV SIS hardware

Figure 8-10: SIS Current Limiter top view and dimensions


22.5 mm
(0.9 in)
DIN Rail End

From DOUT + (Input 3)


From DOUT - (Input 3)
From DOUT + (Input 4)
From DOUT - (Input 4)

8
7
6
4
5 3
2
1 From DOUT - (Input 2)
From DOUT + (Input 2)
From DOUT - (Input 1)
100.0 mm
From DOUT + (Input 1)
(4.0 in)

T
S EN
SI RR R
C ITE
U
LIM

114.0 mm
(4.5 in)

67
Using auxiliary equipment with DeltaV SIS hardware

Figure 8-11: Bottom view of the SIS Current Limiter

SI
S
CU
LIMRR
ITEENT
R
DIN Rail End

Current-limited output 4-
Current-limited output 4+
Current-limited output 3-
Current-limited output 3+ 9
10
11
1 2
13
14
15 Current-limited output 2-
16
Current-limited output 2+
Current-limited output 1-
Current-limited output 1+

68
Index

Index
A F
adding carriers to an operational system 47 fiber-optic link loss 44, 45
adding SISNet Repeaters 48 field wiring 8
agency approvals 5 fire and gas applications
Analog input channel specifications 33, 34 modules for 53
Auxiliary Relay Diode module specifications 57
Auxiliary Relay DTA-Inverting module specifications 54 H
Auxiliary Relay ETA-Direct module specifications 59
hardware used in a DeltaV SIS system 1
Auxiliary Relay Module
HART two-state output channel specifications 34, 35
environmental specifications 29
heat dissipation 29
heat dissipation 29

I
C
installation
carrier extender cables
carriers 6
description of 1
extender cables 9
carriers
intrinsically safe cards 50
adding to an operational system 47
Logic Solver 8
installing 6
SISNet Repeater 9
certifications 5
terminal blocks 7
communication in a DeltaV SIS system 3
intrinsically safe cards
control network
installing in a DeltaV SIS system 50
description of 3
counter-rotation fiber-optic ring 15
L
D LEDs
Logic Solver 23
De-Energize to Actuate Module
SISNet Distance Extender 26
environmental specifications 29
SISNet Repeater 24
heat dissipation 29
local peer bus
specifications and functions 54
description of 3
DeltaV SIS hardware 1
terminating 11
Discrete input channel specifications 3537
local peer bus extender cables
Discrete output channel specifications 3840
description of 1
LocalBus
E description of 3
Energize to Actuate Module Logic Solver LEDs 23
environmental specifications 29 Logic Solvers
heat dissipation 29 description of 1
specifications and functions 59 environmental specifications 29
environmental specifications 29 heat dissipation 29
extender cables installing 8
installing 9 powering 12
extending a system 47 SISNet Repeaters
extending the remote peer ring 19 environmental specifications 29
heat dissipation 29
specifications 31

69
Index

P specifications
powering Logic Solvers 12 Analog input channel 33, 34
powering SIS hardware 12 Auxiliary Relay Diode module 57
powering SISNet Distance Extenders 14 Auxiliary Relay DTA-Inverting module 54
powering SISNet Repeaters 13 Auxiliary Relay ETA-Direct module 59
proof testing the SIS Relay module 62, 63 HART Analog input channel 33, 34
HART Analog input channel specifications 33, 34
HART two-state output channel 34, 35
R Logic Solver 31
remote peer ring SIS Current Limiter 66
description of 3 SIS Relay module 60
extending 19 SISNet Distance Extender 42, 44
setting up 15 SISNet Repeater 41, 42
Voltage monitor 63
S Specifications
SIS Current Limiter specifications 66 Discrete output channel 3540
SIS Net Repeater
installing 9 T
SIS Relay module terminal blocks
proof testing for AC wiring 62 instaling 7
proof testing for DC wiring 63 termination
SIS Relay module specifications 60 local peer bus 11
SISNet Distance Extender LEDs 26
SISNet Distance Extender specifications 42, 44
V
SISNet Distance Extenders
description of 1 Voltage Monitor
powering 14 proof testing 65
SISNet Repeater LEDs 24 proof testing the Voltage Monitor 65
SISNet Repeater specifications 41, 42 Voltage monitor specifications 63
SISNet Repeaters
adding to an operational system 48 W
description of 1 wiring guidelines 6
powering 13
Smart Logic Solvers, See Logic Solvers

70