Professional Documents
Culture Documents
Module 2.1
Identify the GOSP Air and Nitrogen Systems
Module 2.1
Identify the GOSP Air and Nitrogen Systems
TRAINEE HANDBOOK
Information Sheets................................................................1
Exercise A........................................................................27
Exercise B.........................................................................39
Plant Visit
Exercise C.........................................................................40
Glossary.................................................................................43
September 2012
INFORMATION SHEET
Enabling Objectives
Terminal Objective
2.1.1
Unaided, the trainee
Unaided, the trainee will correctly state the will correctly identify the
function of a GOSP air system and identify the GOSP air and nitrogen
major equipment and controls. systems.
2.1.2
Unaided, the trainee will correctly state the
function of a GOSP nitrogen system and identify
the major equipment and controls.
INTRODUCTION
In part I of this module, you will learn the GOSP
air system. In part II, you will learn about the GOSP
nitrogen system.
INTRODUCTION
Air systems play important roles in GOSPs. In this
part of the module, you will learn about the:
o system controls
UTILITY AIR
INTAKE
FILTER INSTRUMENT AIR
COMPRESSOR RECEIVER PREFILTER DRYER AFTERFILTER
DISTRIBUTOR
HEADER
Figure 1
Overview of an Air System
o instrument air
Utility Air
GOSPs use utility air for certain process equipment
operations. Utility air coming from the receiver is
sent directly into the utility air header (see figure
1), which then supplies the GOSP utility stations.
Instrument Air
GOSPs use instrument air to operate instruments
and the emergency shutdown (ESD) valves that Loss of instrument air, will
close during emergencies. Instrument air must not cause a complete shutdown
of the GOSP.
have water or other impurities that might damage
valves and instruments. Water and other impurities
can corrode tanks and air lines. All these can cause
process problems in the GOSP.
o air receiver
o prefilters
o air dryers
o afterfilters
Air Compressor
The function of the air compressor is to supply
compressed air. The compressor takes air from the
atmosphere through filters that are made of
disposable paper and compresses the air to
approximately 110 psig. The filters remove dust
and sand in the air.
Figure 2
Reciprocating Compressors
Figure 2
Northern Area GOSP Outside Operator
Module 2.1
Figure 3
Centrifugal
Figure 3 Compressor
Northern Area GOSP Outside Operator
Figure 4 shows the air flow from a two-stage
Module 2.1
compressor, through a cooler, to the air receiver.
TO AIR
COOLER RECEIVER
INLET
FILTERS
INTEGRAL
OIL PUMP MOTOR
COMPRESSOR COMPRESSOR
FIRST STAGE SECOND STAGE
Figure 4
Air Flow5Through a Compressor
Figure
Northern Area GOSP Outside Operator
Module 2.1
Air Receiver
The air receiver (see figure 5) is normally a
vertically mounted drum. It receives compressed air
from the compressor. The air receiver stores
compressed air during normal operations until it is
needed. The air receiver also acts as a surge vessel
to reduce the effects of sudden load changes on
the compressor
PZVs
AUXILIARY TO PLANT
AIR INLET UTILITY
AIR SYSTEM
Figure 5
Air Receiver
Figure 5
TO Northern Area GOSP Outside Operator
PREFILTER Module 2.1
AIR
RECEIVER
FROM
COMPRESSOR
A
FROM
COMPRESSOR
B
AUTO
DRAIN
GS
Figure 6
Flow
FigureThrough
6 an Air Receiver
Northern Area GOSP Outside Operator
Module 2.1
Moisture Separator
Some GOSP air systems also have moisture
separators. (This equipment is not shown in figure
1.) The moisture separator removes water droplets
from the air that is discharged from the compressor.
Figure 7 shows an air system with a moisture
separator between the aftercooler and the prefilters.
PRE-FILTER
C/W MOISTURE
SEPARATOR
AFTER
COOLER
AUTO PRE-FILTER
DRAIN
Figure 7
Air System with Moisture Separator
Figure 7
Northern Area GOSP Outside Operator In many separators, compressed air flows into the
Module 2.1 DEFLECTOR
PLATE
moisture separator from the compressor after-
cooler and goes over a deflector plate in the
AIR DEMISTER
INLET PAD separator inlet. The deflector plate is a flat metal
section that redirects and slows down the flow of
the air and helps to remove drops of water. Figure
8 shows the deflector plate at the air inlet, air
outlet with demister pad, and the water outlet
LG
with automatic drain pot, which drains to the
gravity sewer.
WATER
OUTLET
AUTOMATIC
DRAIN POT
TO
GRAVITY Figure 8
SEWER Moisture Separator
Prefilters
The two prefilters are vertically mounted drums
that contain coalescing-type filter elements. The
function of the filters is to remove any water
remaining in the air before the air flows to the
Figure 9
dryer. One is online, and the other is on standby. Cyclone 9Moister Separator
Figure
An alarm will sound to indicate that the filter is Northern Area GOSP Outside Operator
blocking and the filter element needs to be Module 2.1
FILTER
replaced. Figure 10 points out the filter element, ELEMENT
the air inlet and outlet, the water outlet, the AIR
INLET
automatic drain, and the piping to the sewer.
PDI
AIR
OUTLET
WATER
OUTLET
AUTOMATIC
DRAIN
TO
GRAVITY
SEWER
Figure 10
Prefilter
Figure 10
Module 2.1
Northern Area GOSP Outside Operator
September 2012 9
Module 2.1
INFORMATION SHEET
MECHANICAL
PRE-FILTER LINKAGE
THREE-WAY THREE-WAY
VALVE VALVE
PRE-FILTER
Figure 11
Air Flow Through Prefilters
Figure 11
Northern
Also note Area GOSP
the OutsideofOperator
position the bypass valve in figure
Module 2.1
11. You can bypass the prefilters by using a line
that is controlled by a manually operated bypass
valve, which normally is closed. If both filters are
out of service, you open the bypass valve so air
continues to flow to the instrument air system.
After it passes through the prefilters, the air flows
to the instrument air dry dryer(s).
Air Dryers
The air coming from the pre filter is still warm,
and it contains moisture. The air cools and loses
pressure as it passes through the instrument air
lines and instruments. If permitted to go forward
untreated, the compressed air would reach its dew
point. To prevent this, the air passes through a
special drying tower. Figure 12 shows the air dryers
in operation in a plant and points to the prefilter
at lower right side of the picture.
AIR-DRYERS
PRE-FILTER
Figure 12
Figure 12 and Prefilter
Air Dryers
Northern Area GOSP Outside Operator
Module 2.1 are two vertical vessels (desiccant towers)
Air dryers
that are packed with desiccant (an activated
alumina) that remove remaining moisture in the
compressed air. The dryers dry the air to a low
dew point of about -40F. Drying the air keeps
moisture from forming in the instrument lines and
instruments.
AIR INLET
/ OUTLET One dryer is online while the other reactivates.
The dryers are switched over periodically every five
Figure 13 minutes. A computerized changeover system
Figure 13 Interior View
Air Dryers
Northern Area GOSP Outside Operator controls the timing sequence. Figure 14 shows
Module 2.1
details of the air dryer
TO INSTRUMENT changeover system. You can
1 AIR SYSTEM A - ON-LINE
B - REACTIVATING see the air coming from the
prefilters, the invent and vent
valves, the two dryers (one
10% AIR FLOW
online and one offline), the
PZV PZV PZVs and the air flow to the
instrument air system.
PI PI
A B
TO
ATMOSPHERE
INLET INLET
VENT VALVE VALVE VALVE VENT VALVE
C D E F
AIR FROM
AIR DRYER
CHANGEOVER PRE-FILTERS
SYSTEM
Figure 14
Air Dryer Changeover
12 14
Figure September 2012 Northern Area GOSP Outside Operator
Northern Area GOSP Outside Operator
Module 2.1
INFORMATION SHEET
Afterfilters
The prefilters and afterfilters are almost identical
in their operation. Afterfilters are small, vertically-
mounted drums that contain particulate filters.
Afterfilters remove desiccant and any fine particles
carried over from the dryer. Each afterfilter
contains a replaceable filter element. Normally, one
is online, and the other is on standby.
PZVs
AIR OUTLET
AIR
INLET
Psid
AFTER FILTERS
Figure 16
Figure 16
Afterfilters
Figure 15 Northern Area GOSP Outside Operator
Afterfilters in Plant Module 2.1
Figure 15
Northern Area GOSP Outside Operator
Module 2.1
SYSTEM CONTROLS
The air system controls ensure a constant supply of
compressed air is supplied at the correct pressure.
System controls also protect the compressors from
damage from heat or insufficient lubrication. The
variables controlled in the air system are:
o air pressure
o dryer changeover
Air Pressure
The air pressure is the primary requirement in the
instrument/utility air system. Air pressure is
controlled by the load/unload control loop. In
addition, pressure relief valves (PZVs) protect the
system from damage from high pressures. Pressure
sensors monitor the instrument air distribution
header for low pressure. You will now learn about:
o high-pressure relief
o low-pressure protection
AIR
RECEIVER
COOLING
WATER
AIR
INLET PS
AFTERCOOLER
ZV UNLOADING
VALVE
COMPRESSOR
Figure 17
Figure 17 Compressor Air Pressure Control
Reciprocating
Northern Area GOSP Outside Operator
Module 2.1
On reciprocating compressors, unloading is
controlled by a spring-loaded, pneumatically
operated unloading device. When the pressure in
the air receiver reaches unload (or high) pressure
setting, a pressure switch at the air receiver signals
the unloading valve to hold the compressor inlet
(suction) valve open. No air is compressed as long
as this valve is open.
PRESSURE- DIAPHRAGM
REGULATING
SCREW
LOCK
NUT
VALVE
AIR FROM
RECEIVER
INLET
VALVE
Figure 18
Cutaway View of the Unloader Device
Figure 18
16 September 2012 Northern Area GOSP Outside Operator
Northern Area GOSP Outside Operator
Module 2.1
INFORMATION SHEET
On the left side of figure 18, you see the air from
the receiver and the valve, the lock nut under the
pressure-regulating screw, and the hand-operated
unload screw. On the right side of figure 18, you
see the inlet valve and its movable fork for
opening inlet valve, and the diaphragm.
SURGE
flow to the atmosphere. A check valve keeps the CONTROL
instrument air from flowing back from the receiver UNLOADING
PCV
when the unloading valve is open. AIR
IN
High-Pressure Relief
The air system normally operates automatically.
However, pressure relief valves (PZVs) protect the
air system from excessive pressures, if any part of
the automatic control system fails. PZVs are located
on each compressor and on the air receiver, dryers,
and air surge drums.
PI 0 - 160 PSIG
FROM
INTER-COOLER
TO
INTER-COOLER
SET AT TO
55 PSIG AFTER-COOLER
SET AT
PZV PZV
PZV
ATM. 140 PSIG
ATM.
L.O. L.O.
INLET
FILTERS
Figure 20
Centrifugal Air Compressor Load/Unload
Figure 20
Northern Area GOSP Outside Operator
Module 2.1
Low-Pressure Protection
GOSPs must control for low pressure for reasons of
safety and operations. The minimum air pressure
required to operate the ESD valves and process
instrumentation is 65 psig. If the air pressure in
the air system drops below 65 psig, the ESD system
will be activated and the whole GOSP will be shut
down. Figure 21 shows the flow of air from the air
compressor skid to the instrument air distribution
header, with all pressure sensors (PS) connected to
the ESD set at 65 psig.
COMPRESSED TO INSTRUMENT
AIR AIR DISTRIBUTION
HEADER
SET AT SET AT
65 PSIG PS PS PS 65 PSIG
SET
AT 65
PSIG
ESD
SYSTEM
Figure 21
Figure 21 Protection
Low-Pressure
Northern Area GOSP Outside Operator
Module
The 2.1 low-pressure sensors (set at 65 psig)
three
monitor the pressure in the instrument-air
distribution header. Two of the sensors must be
activated before the ESD system will operate. This
prevents one faulty sensor from shutting down the
GOSP.
UTILITY
AIR
PCV
PT
- AIR
PRE-FILTER INSTRUMENT
- DRYERS AIR
- AFTERFILTER
Figure 22
Utility Air Limiting
Figure 22
Northern Area GOSP Outside Operator
Module
20 2.1September 2012 Northern Area GOSP Outside Operator
INFORMATION SHEET
COMPRESSOR
CHANGEOVER AND
SHUTDOWN SYSTEM
Figure 23
Compressor Changeover and Shutdown System
Figure 23
Northern
Module 2.1 Area GOSP Outside Operator September 2012 21
Module 2.1
INFORMATION SHEET
Dryer Changeover
The dryer changeover involves changing the
direction of air flow from the operating dryer to
the standby dryer.
The dried air flows out from the top of the dryer
through a check valve to the afterfilters. Some of
the air passes through a restricted orifice (RO) and
flows downward through the offline dryer. This
downward air flow dries the desiccant in the off-
line dryer. This is called reactivating. The purged
air leaves the bottom of the dryer through a
control valve and passes through a silencer. The air
is then vented to the atmosphere.
TO INSTRUMENT
1 AIR SYSTEM A - ON-LINE
B - REACTIVATING
PZV PZV
PI PI
A B
TO
ATMOSPHERE
INLET INLET
VENT VALVE VALVE VALVE VENT VALVE
C D E F
AIR FROM
AIR DRYER
CHANGEOVER PRE-FILTERS
SYSTEM
Figure 24
Air Dryer Controls (#1)
Figure 24
Northern
Look at Area GOSP
figure 24.Outside
Dryer Operator
A is online, while dryer B
Module 2.1 When monitoring the dryer
is reactivating. Air flows into dryer A through the purge sequence, it is important
inlet valve D. The dry air leaves the top of dryer A. to not have high back
pressure on the tower that is
Most of it passes the instrument air system. But a being reactivated. Otherwise,
small amount (typically less than 10%) flows into complete reactivation will not
take place.
the top of dryer B, and down through dryer Bs
desiccant bed. It reactivates the alumina in the
desiccant bed. The reactivation air from dryer B is
vented to the atmosphere vent valve F.
PZV PZV
PI PI
A B
TO
ATMOSPHERE
INLET INLET
VENT VALVE VALVE VALVE VENT VALVE
C D E F
AIR FROM
AIR DRYER
CHANGEOVER PRE-FILTERS
SYSTEM Figure 25
Air Dryer Controls (#2)
to atmosphere, the
reactivation flow will start
through dryer A. TO
ATMOSPHERE
INLET INLET
VENT VALVE VALVE VALVE VENT VALVE
C D E F
AIR FROM
AIR DRYER
CHANGEOVER PRE-FILTERS
Figure 26 SYSTEM
Air Dryer Controls (#3)
Figure 26
INFORMATION SHEET
TO INSTRUMENT
4 AIR SYSTEM A - PRESSURIZING
B - ON-LINE
PZV PZV
PI PI
A B
TO
ATMOSPHERE
INLET INLET
VENT VALVE VALVE VALVE VENT VALVE
C D E F
AIR FROM
AIR DRYER
CHANGEOVER PRE-FILTERS
SYSTEM
Figure 27
Air Dryer Controls (#4)
Figure 27
Northern Area GOSP Outside Operator
Module 2.1
SUMMARY
As an outside operator, you will be directly
involved in the instrument and utility air systems.
You will monitor the compressor to make sure it is
operating correctly. You will make sure the air
dryers are recycling correctly and they provide
clean, dry air. Regular checks of the whole system
will be part of your duties on every shift.
EXERCISE A
B
Directions: Use figures 28 through 31 to complete this
exercise. C
A
D
1. Name the components of the moisture
separator that are labeled A through G in
figure 28. Write the names in the spaces next
to their letters.
a.
F
b.
E
c.
G
d.
e.
Figure
Figure2828
f.
Northern Area GOSP Outside Operator
Module 2.1
g.
b.
c. D
d. C
e.
Figure 29
Figure 29
Module 2.1 Northern Area September 27
2012 Operator
GOSP Outside
Module 2.1
INFORMATION SHEET
B
b.
c.
C
d.
e.
D
COMPRESSED TO INSTRUMENT
AIR AIR DISTRIBUTION
HEADER
SET AT SET AT
65 PSIG PS PS PS 65 PSIG
SET
AT 65
PSIG
ESD
SYSTEM
Figure 31
Figure 31
Northern Area GOSP Outside Operator
Module 2.1
INTRODUCTION
This part of the module teaches you about the:
o heater
o membrane separators
o oxygen analyzer
o outlet filters
o distribution header
FEED
AIR
FILTER MEMBRANE
SEPARATOR OXYGEN
HEATER ANALYZER OUTLET FILTER
110 F D-317A
STANDBY
INSTRUMENT DISTRIBUTION
AIR N2 HEADER
RECEIVER
ONLINE
110 F D-317B
HEATER OXYGEN OUTLET FILTER
MEMBRANE ANALYZER
FEED SEPARATOR
AIR
FILTER
Figure 32
Figure
Nitrogen32
Generation Equipment
Northern Area GOSP Outside Operator
Module 2.1
Heater
The filtered air then passes through an electric
heater. The heater maintains the feed air
temperature at the optimum temperature for the
maximum production of nitrogen. The efficiency of
the membrane separator depends on both the
pressure and temperature of the feed air. Feed
pressure is preset. The feed air temperature is read
at a temperature indicator.
Membrane Separator
The atmosphere is 78% nitrogen, 21% oxygen, and O2
N2 N2
1% trace gases. In nitrogen generation, the
membrane modules separate nitrogen from the
compressed instrument air coming from the filter.
This feed air is compressed, dried, heated, and
filtered. The separation equipment must have pure
air to produce good quality nitrogen.
OXYGEN
Oxygen Analyzer
Oxygen content in the nitrogen affects its purity.
The oxygen analyzer monitors a sample from the
nitrogen membrane outlet. If the oxygen content
in the sample stream goes above 5%, the analyzer
activates an alarm. The analyzer also activates a
relay. The relay opens a valve at the membrane
outlet. The valve vents the nitrogen product to the
atmosphere.
Outlet Filters
Outlet filters are on the line between the nitrogen
drum and the nitrogen distribution header. One
filter is in service and the other is on standby. A
pressure differential switch measures the
differential across the filters. When the online filter
reaches the high differential pressure setpoint, it
means the filter is dirty and blocking up. You
switch filters when this happens.
Distribution Header
The nitrogen flows from the outlet filter to the
distribution header. The distribution header is
controlled by PCVs. You will find the distribution
headers are different on each GOSP.
NITROGEN NITROGEN
STORAGE STORAGE
TANK TANK
VACUUM
PUMPS FILL LINE FILL LINE
N2 N2
VAPORIZER NITROGEN VAPORIZER
SUPPLY
VAPORIZER
BOIL OFF
HEATER
TO GOSP DISTRIBUTION
Figure 34
Nitrogen Storage
Figure 34
Northern Area GOSP Outside Operator
The nitrogen
Module 2.1 storage system holds liquid nitrogen
in bulk. The liquid nitrogen storage system also
vaporizes the liquid nitrogen. The vaporized
nitrogen is distributed through the nitrogen header
to equipment that uses nitrogen gas. The
equipment used in nitrogen storage system are:
o pressure-building system
o boil-off heater
Figure 35
Figure
Nitrogen35Storage Tank
o vacuum insulation Northern Area GOSP Outside Operator
Module 2.1
Pressure-Building System
Both nitrogen storage tanks have a pressure-
building system. Each system has a PCV and a
vaporizer. If the tank pressure falls too lower than
the set pressure, a controller opens. The controller
admits liquid nitrogen to the vaporizer. The
vaporizer changes the liquid into gas. The nitrogen
gas has a higher pressure than the liquid. The gas
returns to the tank. The gas increases the tank
pressure to the normal pressure.
Boil-Off Heater
The boil-off heater keeps the storage tanks from
over-pressurizing. If the storage tank pressure goes
too high, a pressure regulator valve opens.
Nitrogen vapor flows to the header for distribution
Vacuum Insulation
Vacuum insulation in the storage tanks keeps the
liquid nitrogen in the tanks cold. As you have
learned, if nitrogen is not kept cold, it boils off
and vaporizes. When the liquid nitrogen boils off,
the pressure in the tank increases and nitrogen
vapor will be lost to the relief system that goes to
the atmosphere. A space between the inner
nitrogen storage tank and the tank shell is a
vacuum. The vacuum space is filled with granular
insulating material called perlite that helps insulate
the nitrogen. Vacuum pumps maintain the vacuum
insulation.
Controls
The pressure control in the nitrogen header makes
sure enough pressure is in the header to supply
nitrogen users. A PCV maintains the nitrogen
header pressure at 125 psig. This regulates the
nitrogen flow through the nitrogen supply
vaporizer. A temperature switch located before the
nitrogen supply header PCV senses any low
temperature and closes the PCV. This protects the
header pipe metal from the extreme cold
temperature for which it is not designed.
SUMMARY
You now know about a GOSP air system and GOSP
nitrogen system. In part I, you learned the function
of major equipment and components of the air
system and how the system provides utility and
instrument air. You also learned the components
and controls in the instrument air system. You will
use this knowledge to help you operate the air
system safely and efficiently when you work in the
plant as an outside operator.
EXERCISE B
Directions: Identify the numbered components in figure 37
by writing the component number in the diagram next to
the name of each component in the list below.
7 7
3 3
Figure 37
Figure 37
Northern Area GOSP Outside Operator
1.
Module 2.1
nitrogen supply vaporizer 5. distribution header
4. pressure-building system
PLANT VISIT
QUESTIONS
Part 1
PLANT VISIT
Part 2
Activate Drop/Droplet
To start up or make active. Small unit of a liquid that is still heavy
enough to fall as a sphere, like a
Alumina raindrop. A droplet is a very small drop.
Any of several forms of aluminum
oxide, consisting of two parts of Inert
aluminum and three of oxygen. Without chemical reaction. Forms few
or no chemical compounds.
Bulk
A very large size, mass, quantity, or Lead/Lag
volume. For example, you can buy food In front of or ahead of. Lag means to
by single item, such as 5 kilo of rice, or follow or be behind the lead. The one
in bulk (many kilos). in a group who goes first leads the way.
Followers lag behind. For example,
Cyclone moister separator a lead compressor is the one that is
A circular vessel that uses centrifugal operating. To lead means to go first or
force to push the water droplets out show the way to accomplish a goal. (Do
of the air. The droplets coalesce on the not confuse this meaning of lead with
side of the separator and run down to name of the metal of the same spelling
the bottom of the vessel to a drain. and pronunciation. A type of heavy
metal is the element lead.)
Deflector plate
A flat metal section mounted over a Load/Unload
vessel inlet. Redirects and slows down To do work. For example, a compressor
the flow of gas and liquid into a vessel. load when it is compressing air.
Unloading a compressor stops it
Desiccant working.
A drying agent. A substance that
attracts and absorbs moisture. Membrane
A thin, soft sheet or layer.
Dew point
Air temperature and pressure at which Nitrogen blanket
a gas condenses to a liquid. A nitrogen layer in the upper part of
a vessel. The blanket keeps a positive
pressure on the tank.
Perlite
Granular insulating material that helps
insulate the nitrogen.
Permeable
Having pores or openings that liquids or
gases can pass through.
Pneumatic
Air operated, as in air-operated
instruments.
Reactivate (Regenerate)
Reactivate is to make active again.
Regenerate is to restore or return
something to a previous condition.
For example, you reactive a piece of
equipment by turning it on when it is
turned off. You regenerate a desiccant
by removing the water from the
desiccant so it can absorb more water.
Standby
One that is held in reserve, ready
for use. Also: a system where a fixed
quantity of liquid or gas circulates
continuously.
Surge (to)
To rise and fall continuously.
Tube/tubes
A pipe, usually of small diameter, and
normally made of plastic or light metal.
2-1A-151-203
PP-15154
COMPRESSED
011 AIR FROM AIR
COMPRESSOR 8-10 1-1A-150-201
PP-18164
PI SET@ PI SET@ TO PLANT AIR
2-1A-152-203 PI PCV SET@ 015
PP-15154 PSIG PSIG DISTRIBUTION
2104 2904 PSIG 2104
COMPRESSED 2904
012 AIR FROM AIR ST LSTE ST LSTE
NOTE 1 CONTRACTOR
COMPRESSOR 8-10 CONTRACTOR NOTE 1
AUXILIARY
VENDOR 803-U-7A 2 VENDOR
803-U-7B
UV FT
AIR INLET
2 2-1A-154-203 0114 2701 MOISTURE
UV 1 UV
LOCATE 0708 0708
A GRADE
2-1A-155-203
ZV 1/2 FT ZV 1/2 FT
0114 1714 2704 1714
SET@
2-1A-157-203
SET@
2-1A-161-203
PI PSIG FT AIR SET@
PSIG AOV AOV PI PSIG
1704 1714 100 PI 1704 1714 8927
PI LL SET@
FROM AIR RECEIVER 0113 2429 PSIG
HIGH HIGH PRESSURE 1 1-1A-150-201
PP-138164 SET@ PP-18164
TO ATM @ TO ATM @ TO ATM @ SET@ TO LOADER/
011 ALARM TO COMPRESSOR TO ATM @
SAFE LOCATION PSIG SAFE LOCATION SAFE LOCATION PSIG
LO 012
C-1A CONTROL PANEL SAFE LOCATION PS UNLOADER SV
PS
HH PI PS 2429 PI PS PI PIT
PI 0112
FROM AIR RECEIVER 0112 0113 0112 8928 8927 1 1-1A-151-201
2905 0113 100
HIGH HIGH PRESSURE SET@ SET@ SET@ SET@ PP-18164
PP-138164 TEST LO TO LOADER/
PSIG PSIG PSIG PSIG
ALARM TO COMPRESSOR PI PI PI PI ORIFICE UNLOADER SV 011
012 C-1A CONTROL PANEL LO LO 0111 2429 LO LO
HH 0111 PZV PZV PZV PZV 0111 2
FROM AIR RECEIVER PS 0113 0114 2429 0114 1-1A-151-201
LOW PRESSURE ALARM SET @ 2905 + PP-18164
PP-138164
& AUTO START SYSTEM
PSIG
-
2 803-K-7A 803-K-8A 2 2
803-K-1B 803-K-3B 2 TO INSTRUMENT
015
AIR DISTRIBUTION
011 TO COMPRESSOR X-1A
AUTO START 2 PS PS PS SET@
150-RF A B C PSIG
FROM AIR RECEIVER 8929 8929 8929
LOW PRESSURE ALARM LL LL LL
& AUTO START SYSTEM PS
PP-138164 TIMER TIMER
SET @ 2905
012 TO COMPRESSOR IT LL
X-1A AUTO START PSIG C
2905
PI LL
FROM AIR RECEIVER 2905 B
HIGH LIQUID LEVEL ALARM 2 2 2 2 LL XI
PP-138164 PURGE TO PURGE TO DISCREPANCY
TO COMPRESSOR A
011 X-1A CONTROL PANEL ATM & ATM &
SAFE SAFE LL
ZV ZV ZV ZV ZV ZV SEA
LOCATION LOCATION
FROM AIR RECEIVER 0101 0102 0103 0101 0102 0103 TO CENTRAL
HIGH LIQUID LEVEL ALARM S S S S S S S S
GOSP
PP-138164 2 OUT OF
TO COMPRESSOR LCV MOV LCV LL SHUTDOWN
012 X-1A CONTROL PANEL MOV 1 VOTING
2 0101 0103 0101 0103
102 102 P P P P PI
SET @ SET @
0340 LL
150 PSIG 150 PSIG
2-1A-155-203
2 158 - RF
2 2
LO 803-0-42A LC
803-0-42B
LC
1 2 2 2
803-D-34 PI
Pd3
2
Pd3
LO 1901
EXTERNALLY 100 PRE-FILTERS PI PRE-FILTERS
PI P4 P4 2
COATED RF V 2 2 2 PI
1901 1901 1901
1 1901 0340
Pd3 Pd3
NOTE 2 NOTE 2
LO PC PC
0340 0340
803-0-43A 803-0-43B
FG 2 FC FG 2 2
LC LS FC
1901 1901 1901 1901 1901
1901
AFTER
AFTER
FILTERS
24 LA FILTERS
1/2 2 1/2 1/2 2 2
1
2 1901
LO
AUTO AUTO 803-0-44A E3-0-45A AUTO AUTO
803-0-44B 803-0-45B
DRAIN DRAIN DRAIN DRAIN
NOTE 1 NOTE 1
NOTE 1 NOTE 1
2-5R-544-101 MINIMUM 1X2 3
LO 1A10
203 NPT
AUTO
DRAIN 2-5R-545-203
NPT
NOTE 1 PI
0340
1A10 GS
GS
203 190 AF
GS
Handout 2.1-1
Northern
NorthernArea GOSPGOSP
Area OutsideOutside
Operator Operator September 2012 Handout 2.1-1
Module 2.1
HANDOUT
BY VENDOR
SET AT PZV PZV
1834kP00 726 1 1 727
(150 PSIG) LO LO SET AT PRE- 2 2
1834kP00 PRE-
(150 PSIG) FILTER FILTER
2 8
HANDHOLE 2
G77-D-024 1/2 1/2 1/2 1/2 2
TRM 1A-37-IAIA
0-1600kPog LC VL
PI (0-250 PSIG) 3/4 1 x 3/4
2 251
LO 732
8
2 HAND 2 2
UNLOAD HOLE G77-0-118/119
LEAD H
PS PS LOAD LAG
COMPR. 728 730 LL-SET
SET AT PS 0-680kPog
792kPog 729 (180 PSIG) 1/2 1/2
(115 PSIG) LOAD L-SET 1/2
0-120kPog
LEAD (105 PSIG)
3/4 COMPR.
PI
733
0-1600kPog
(0-230 PSIG)
INSTRUMENT AIR
PACKAGE
CONTROL PANEL
G77-K-001
1-SR-212-IAIL
0-200 oC H
(0-400 o F) TI TI H TI H TI H TE H TI H
o 0-200 oC o
295 296 297 298 0-200 oC 293 294 0-200 oC
(0-400 F) (0-400 o F) (0-400 F)
0-200 oC 0-200 oC BOTH ALARMS
TO OPEN DRAIN o o
HEADER (0-400 F) (0-400 F) SET @ 165 o C (329 oF)
DWG. XA-J62992.SH.2 BOTH ALARMS SET @ 165 o C (329 o F)
DP
LEVEL TEST
COCK
PCV
September 2012
PZE PZV
PCV
STEAM INJECTION
WATER
TO R.O. OVERFLOW
ATMOSPHERE PCV
AMBIENT
AIR
VAPORIZER STEAM
TCV
Handout 2.1-3
Handout 2.1-3
Northern Area GOSP Outside Operator
Module 2.1