You are on page 1of 10

Computers and Geotechnics 48 (2013) 117126

Contents lists available at SciVerse ScienceDirect

Computers and Geotechnics


journal homepage: www.elsevier.com/locate/compgeo

Finite element simulation of an embankment on soft clay Case study


Jinchun Chai a,, Yutaka Igaya b,1, Takenori Hino c,2, John Carter d,3
a
Department of Civil Engineering and Architecture, Graduate School of Science and Engineering, Saga University, Japan
b
Prefectural Planning Head Ofce, Saga Prefectural Government, Japan
c
Institute of Lowland and Marine Research, Saga University, Japan
d
Faculty of Engineering and Built Environment, The University of Newcastle, NSW 2308, Australia

a r t i c l e i n f o a b s t r a c t

Article history: Numerical simulations and eld measurements of an embankment constructed on a deposit of soft Ariake
Received 14 February 2012 clay in Saga, Japan are compared and discussed. The simulations were made both before (Class-A) and
Received in revised form 8 October 2012 after (Class-C) the eld data became known. It is shown that the Class-A prediction resulted in poor sim-
Accepted 8 October 2012
ulations of the measured settlementtime curves, mainly due to over-estimation of the magnitude of the
yield stresses of the subsoils (i.e., the sizes of the yielding loci) and under-estimation of the compressibil-
ity, hydraulic conductivity and the slope (M) of the critical state line. It is demonstrated that: (a) appro-
Keywords:
priate site investigation, soil testing and interpretation of the test results are essential for accurate
Soft ground
Finite element analysis
prediction of the behaviour of an earth structure constructed on soft clayey deposits; (b) when using a
Embankment soil model developed within the framework of Critical State Soil Mechanics to make such predictions,
Case history M value should be directly determined from tests with an appropriate effective stress path; and (c) yield
stresses of soft soil layers can be calibrated by comparing the predicted undrained shear strengths (Su)
with measured values, provided the effect of strain rate and/or strain softening on the value of Su is prop-
erly considered. The results of this analysis indicate that Bjerrums strain rate correction factor can be
adopted as a rst approximation of the correction factor applied to eld or laboratory measured values
of Su.
2012 Elsevier Ltd. All rights reserved.

1. Introduction cause of its simplicity and its ability to predict yielding, strain soft-
en as well as failure in soft clayey soils. However, MCC is an
Comparing the predicted and eld-measured behaviour of isotropic yielding model and it does not consider viscous behaviour
embankments constructed on soft clayey ground often provides a such as creep of clayey soils. Elasto-viscoplastic (EVP) models (e.g.,
good check on the suitability of the constitutive model adopted [31]) and anisotropic yielding elastoplastic models (e.g., [11]) have
for the clay soil, as well as the capacities of the numerical proce- been developed to account for these complicating effects. How-
dures used to make predictions of the embankment behaviour, ever, there are still differing opinions as to which model provides
providing of course that appropriate values have been adopted the best prediction of the eld response of clayey soils under
for the model parameters. The latter is a function of the quality embankment loading (e.g. [18,20]). In principle, a more sophisti-
of sampling, sample preparation, testing and overall characterisa- cated soil model should be able to represent better the mechanical
tion of the soils at the site. There is a relatively rich literature in behaviour of natural soft clayey soils, but the drawback in adopting
this particular eld of geotechnical engineering (e.g., them is that more sophisticated models require specication of
[30,22,4,6,9,12,15,20,16,21,18]). more soil parameters, and in many cases in engineering practice
The Modied Cam Clay (MCC) constitutive model [23] is one of there are insufcient test data to reliably dene those parameters.
the most widely used elastoplastic models for soft clayey soils be- Further, for some sophisticated soil models, some of the soil
parameters can only be calibrated by tting the model predictions
to the test results, rather than being determined directly from
those test results. On the other hand, the parameters of relatively
Corresponding author. Tel.: +81 952 28 8580; fax: +81 952 28 8190. simple soil models, such as the MCC model, which is acknowledged
E-mail addresses: chai@cc.saga-u.ac.jp (J. Chai), igaya-yutaka@pref.saga.lg.jp (Y.
for being capable of capturing the most important mechanical fea-
Igaya), hino@ilt.saga-u.ac.jp (T. Hino), John.Carter@newcastle.edu.au (J. Carter).
1
Tel.: +81 952 66 0912; fax: +81 952 66 0956.
tures of soft clayey soil, can be easily and reliably dened. It is gen-
2
Tel./fax: +81 952 28 8612. erally acknowledged that the use of some simple models can result
3
Tel.: +61 2 4921 6025. in acceptable predictions of soil behaviour, at least from a practical

0266-352X/$ - see front matter 2012 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.compgeo.2012.10.006
118 J. Chai et al. / Computers and Geotechnics 48 (2013) 117126

Fig. 2. Borehole locations in and around Test Site.

Fig. 1. Location of Ariake Sea Coastal Road and test embankment.


Grain size t
composition wp wn wL
(%) (%) (kN/m3 ) e0
perspective. Whichever the case, obtaining accurate Class-A pre- Soil 0 50 0 100 10 15 0 1 2 3 4
0 Surface
dictions [17] of the behaviour of embankments on soft clayey
layer
deposits still remains a difcult task. C M

As shown in Fig. 1, in Saga, Japan, a highway around the Ariake


BH-6
Sea has been planned and was under construction at the time of
writing. For its entire length this highway is located over deposits Soft
of soft Ariake clay. In order to verify the correctness of the assumed 5 silty
clay
Depth (m)

design strength and deformation parameters of the soft deposit, as


estimated from laboratory tests, a test embankment was built on
the natural deposit and its performance was monitored for more Silty
clay
than 3 years in terms of settlements, lateral displacements and ex-
cess pore water pressures. For this test embankment an internal 10
Organic
Class-A prediction was made and documented before construction. clay
S G
After the eld-measured data became known, these Class-A predic- Clayey
sand
tions were compared with the measurements and there were con- C: clay BH-6
M: silt BH-1, 3
siderable discrepancies. The same case was then re-analyzed S: sand
G: gravel &5
(Class-C prediction) using additional site investigation results and 15
after applying a correction to the measurements of the undrained
shear strength (Su) of the subsoils. For all the analyses reported Fig. 3. Soil prole and some physical and mechanical properties at the Test Site.
here, the soft Ariake clay was modelled by the MCC model.
In this paper the site conditions, history of the embankment
construction and the measured data are reported and compared to- the Class-A predictions were made. The soil prole and some phys-
gether with the results of the Class-A and Class-C predictions. The ical properties obtained from BH-1, 3, 5 and 6 are summarized in
insights gained into predicting the behaviour of an embankment Fig. 3. In this gure, Wp, WL and Wn are plastic limit, liquid limit
on soft ground are discussed. and natural water contents respectively, ct is the unit weight,
and e0 is the initial void ratio. Values of Wp and WL are only for
the samples from BH-6.
2. Soil prole and embankment construction It is noted that at this site there exists a surface layer about
1.5 m thick underlain by a thick soft silty clay layer (the Ariake
In total, three (3) test embankments were constructed at the clay) which is about 8.0 m thick. Below it is an organic clayey soil
location indicated in Fig. 1, one on natural soft ground and two layer about 0.3 m thick, underlain by alternating clayey sand and
on the same type of soft ground after it had been improved by sandy clay layers. The natural water content of the soft silty clay
the installation of soilcement columns formed by deep mixing was generally more than 100% and larger than the corresponding
[13]. The test embankment considered in this study is the one con- liquid limit. The groundwater level was about 1.0 m below the
structed on natural ground. As shown in Fig. 2, in and around the ground surface.
test site, six (6) boreholes (BH) were drilled in order to investigate For the undisturbed samples from BH-6, consolidated un-
the soil properties required for design of the road embankment. At drained triaxial compression tests with excess pore water pressure
the locations of BH-1, -3, -5 and -6, undisturbed soil samples were measurement were also conducted. The effective stress paths in a
taken using a Japanese thin-wall sampler and laboratory index p0 q plot (p0 is effective mean stress and q is deviator stress) of
tests and consolidation and unconned compression tests were the triaxial test are given in Fig. 4. In the gure, r01 and r03 are effec-
conducted on these samples. tive stresses in the vertical and horizontal directions respectively.
BH-1 to BH-5 were drilled and the corresponding laboratory The e- logr0v ) curves (e is void ratio and r0v is vertical consolidation
tests were conducted before the test embankment was con- stress) from odometer test results for the samples from BH-6 are
structed, and the resulting data were available at the time the given in Appendix A.
Class-A prediction was made. BH-6 was in the test site and was For the test embankment constructed on natural ground the
bored just before the commencement of embankment construc- critical height was estimated to be about 3.0 m, and so it was
tion. The test data from this borehole were not available when decided that an embankment should be constructed with an initial
J. Chai et al. / Computers and Geotechnics 48 (2013) 117126 119

Fig. 4. Effective stress paths.

ll thickness of 2.5 m. Once this was achieved, and depending on 3. Predictions and comparison with eld measurements
the results of the ground monitoring, a decision was then to be
made whether to increase the ll thickness to 3.0 m. In practice 3.1. Finite element modelling
the embankment was only constructed to a total ll thickness of
2.5 m. After the ll reached this thickness the monitored results Predictions were made using plane strain nite element analy-
indicated that the rate of lateral displacement was increasing ses (FEA). The nite element mesh and the boundary conditions
quickly and after stopping the placement of ll the lateral move- adopted are illustrated in Fig. 6. Due to symmetry, only half the
ment continued with the rate for about a week. The supervisor in embankment was modelled, and the modelled area had an overall
charge of this project decided to cease further lling altogether, be- horizontal width of 60.0 m and a vertical thickness of 22.5 m. At
cause building the embankment to failure was not an option. The the left and the right boundaries the horizontal displacement
base dimensions (length  width) of the embankment were was xed but vertical displacement was allowed. At the bottom
46.8 m  21.8 m and its side slopes were 1:1.8 (V:H), which re- boundary both the horizontal and vertical displacements were
sulted in plan dimensions of the top of the embankment of xed. Both the ground surface and the bottom boundaries (sand
37.8 m  13.8 m. Decomposed granite was used as ll material layer) were considered completely permeable, i.e., they were
and the average lling rate was about 0.05 m/day. The average to- drainage boundaries, and both the left and right boundaries were
tal unit weight of the embankment ll as placed was about considered to be impermeable. Eight-noded quadrilateral elements
19.0 kN/m3. A cross-section of the embankment and some of the with excess pore water pressure degrees of freedom at only the
key instrumentation points for measuring settlements, lateral dis- four (4) vertex nodes were used to represent the foundation soil.
placements and pore water pressures are shown in Fig. 5. The eld- Eight-noded quadrilateral elements without the excess pore water
measured data presented in the following sections were all sourced pressure degrees of freedom were used to represent the embank-
from the [1]. ment. The adequacy of the adopted mesh was checked by also
using a much ner mesh, by almost quadrupling the number of
13.8 m elements. By comparison of solutions it was found that the mesh
originally adopted is capable of providing accurate and converged
2.5 m S0
predictions of the nodal deformations.
0.0 m In the numerical analyses, the soft clayey layers were repre-
Surface layer P1 (1.4 m)
1.5 sented by the Modied Cam Clay (MCC) stressstrain model [23],
S1 (2.8 m)
Soft silty clay P2 (5.0 m) and the sand layers and the embankment ll material were simu-
S2 (7.1 m) Inclino-
P3 (8.3 m) meter lated by an elastoplastic stressstrain model which obeys the
9.5 Organic clayey soil S3 (9.5 m)
Mohr-Coulomb failure criterion.
9.8
P4 (10.0 m) S4 (12.0 m) The predictions were conducted using a fully coupled nite
Clayey sand
P5 (13.0m) Settlement plate element consolidation analysis and the program used for the
14.5
16.0 Stiff sandy clay Pore pressure gauge numerical calculations was CRISP-AIT [7], which is based on the
Clayey sand original CRISP program [5]. Large deformations were considered
20.5
22.4 Volcanic ash layer
approximately by updating the nodal coordinates at the end of
each incremental step. Further, to ensure that the true stress
S5 (24.0 m) To 24 m strain law is followed closely in the numerical model, the New-
tonRaphson method with an explicit sub-stepping technique
Fig. 5. Cross-section of the embankment and key instrumentation points.
120 J. Chai et al. / Computers and Geotechnics 48 (2013) 117126

Fig. 6. Mesh and boundary conditions.

that includes error control [26] has been incorporated into the - and Ck is a constant. Tavenas et al. [28] suggested that generally
nite element program. Ck = (0.40.5)e0 and in this study Ck = 0.4e0 was assumed.
The overconsolidation ratio (OCR) of the soft soil is a key param-
3.2. Class-A predictions and comparisons with measured data eter controlling the amount of deformation of the deposit under
the embankment loading. It is linked with the size of yield locus
3.2.1. Model parameters (p0y ) and therefore the undrained shear strength (Su), as predicted
The model parameters adopted for the Class-A prediction were by the MCC model. According to this model and for undrained tri-
estimated from the laboratory test results using the undisturbed axial compression stress paths, Su value predicted by MCC can be
samples obtained from BH-1, -3, and -5. The location of these bore- expressed by the following equation:
holes is referred to in the following as the Nearby Area. The param- !K
eter values deduced from the laboratory testing are listed in Table 1. p0 M 2 g2
In this table the values of Poissons ratio, m, were assumed to be 0.3.
Su 1K
M OCRK 2
2 M2
Values of j were assumed as 0.1k. At the time of making the Class-A
prediction, there were no test results that allowed an independent where K = 1  j/k, and g = q/p0 . Determining the value of the pre-
measure of the friction angle (/0 ), and so the slope of the critical consolidation stress (pc) and therefore the value of OCR from the
state line in p0 q space, M, was calculated by assuming a /0 value incremental loading laboratory consolidation test results may de-
of 30 for triaxial compression conditions (based on local experi- pend on the judgment of the person interpreting the test results.
ence). The values of Youngs modulus (E) of the sandy layers were To avoid completely subjective judgment, the approach adopted
estimated from standard penetration test N-values as was to adjust the value of pc by comparing the measured value of
E = 2500N (kPa) [14]. The values of kv were estimated as twice the Su with the value predicted by Eq. (2). The measured value of Su
values deduced from the laboratory incremental loading consolida- was assumed to be Su = qu/2, where qu is the measured unconned
tion tests, and the values of horizontal hydraulic conductivity, kh, compression strength of the undisturbed soil sample. In order to
were set as 1.5 times the corresponding value of kv, based on previ- predict the value of Su from the MCC model, Mayne and Kulhawys
ous experience with this soil [8]. The values of kv and kh listed in Ta- [19] equation was used to calculate the coefcient of earth pressure
ble 1 are initial values and during consolidation they were allowed at-rest (K0) and therefore the initial effective stress in the ground in
to vary with void ratio according to the following equation [29]: the horizontal direction. This value of K0 was computed by assum-
k k0  10e0 e=Ck 1 ing an internal friction angle of the subsoil of 30.
Measured data from BH-1, -3, and -5 (open circles) and the pre-
where k0 is the initial hydraulic conductivity, e0, the initial void ra- dicted values (dashed lines) are shown in Figs. 7a and 8a for Su (la-
tio, k, the current hydraulic conductivity, e, the current void ratio, belled Su-A&C1) and OCR (labelled OCR-A), respectively. The

Table 1
Model parameters.

Depth (m) Soil strata SPT N E (kPa) m j k M e0 ct (kN/m3) kv kh


(104 m/day)
0.01.5 Surface soil 0.30 0.025 0.25 1.2 1.50 16.0 6.0 9.1
1.54.0 Soft silty clay 0.30 0.065 0.65 1.2 3.14 13.7 5.1 7.7
4.06.0 0.30 0.059 0.59 1.2 2.89 13.9 5.4 8.1
6.08.0 0.30 0.060 0.60 1.2 2.67 14.1 5.4 8.1
8.010.0 0.30 0.071 0.71 1.2 2.55 14.3 4.6 6.9
10.012.0 Sandy clay 0.30 0.008 0.08 1.2 1.10 18.0 17.5 26.3
Depth (m) Soil strata SPT N E (kPa) m / () C (kPa) M e0 ct (kN/m3) kv kh
12.015.0 Clayey sand 8 20,000 0.25 35 20 0.80 18.0 2500 2500
15.020.0 Clayey sand 15 37,500 0.25 35 20 0.70 19.0 2500 2500
Embankment 2 5000 0.30 35 20 19.0

Note: E = Youngs modulus; m = Poissons ratio; k = slope of consolidation line in e-ln p0 plot (e is voids ratio and p0 is effective mean stress); j = slope of rebound line in e-ln p0
plot; M = strength parameter for Cam-clay model, stress ratio at failure, qf/p0 (q is deviator stress); e0 = initial void ratio; ct = unit weight; kh and kv = horizontal and vertical
hydraulic conductivity, c = cohesion, and /0 = friction angle of soil.
J. Chai et al. / Computers and Geotechnics 48 (2013) 117126 121

Su & Su' (kPa) Su & Su' (kPa)


0 10 20 30 40 0 10 20 30 40
0 0
Nearby Area Test Site

2 2

S u-A&C1
4 4

Depth, D (m)

Depth, D (m)
Su-A&C1

6 6

8 8 Su-C2
Su-C2

10 10
Measured (Su) Measured (S u)
Corrected (Su') Corrected (Su')
12 12
(a) Nearby area (b) Test site
Fig. 7. Variation of Su.

OCR OCR
0 2 4 6 8 0 2 4 6 8
0 0

Nearby Area 2
Test Site
2

4 4
Depth, D (m)
Depth, D (m)

6 6

8 8

Measured Measured
10 OCR-A 10 OCR-A
OCR-C1 OCR-C1
OCR-C2 OCR-C2
12 12
(a) Nearby area (b) Test site
Fig. 8. Variation of OCR.

predicted values of Su are slightly lower than the average measured son is probably related to the likelihood that the plastic strain was
values, but the predicted values of OCR form almost an upper concentrated largely in the very soft layer, and squeezing the soil
bound on the measured data. Initially these discrepancies were sideways meant that there might be slight stress decrease deeper
judged to be due to unavoidable sample disturbance, i.e., the mea- down. It is worth mentioning that from the settlement vs. log time
sured OCR values may have been less than the actual eld values. plot it is assumed that primary consolidation nished at about
The values of Su-A&C1 and OCR-A shown in Figs. 7a and 8a 3 years after the beginning of the construction.
were adopted in the Class-A prediction of the embankment The lateral displacement proles at the end of the embankment
response. construction and 2 years from the beginning of the construction
are compared in Fig. 10a and b, respectively. Although there are
3.2.2. Comparison of predictions and eld measurements discrepancies, compared with the settlement predictions it could
A comparison of the settlementtime curves is given in Fig. 9ac be concluded that the Class-A prediction has provided reasonable
for settlement gauges S0, S1 and S3, respectively (see Fig. 5 for the estimates of the lateral displacements.
locations). There were some problems at settlement gauge S2 and Comparisons of the measured and predicted excess pore water
the data were considered unreliable and there were only very small pressures (u) at the locations P1 to P4 (see Fig. 5 for the locations)
settlements measured at the location of S4 (about 18 mm), so that are shown in Fig. 11ad, respectively. Very small values of pre-
comparisons for these two locations have been omitted. It can be dicted and measured excess pore water were relevant at location
seen that as for the settlement at the ground surface (S0), the P5 and so a comparison is not presented. It is clear that the
Class-A prediction is at most about 50% of the measured data, i.e., Class-A prediction method yielded good estimates of excess pore
a poor Class-A prediction has been obtained for these settlements. water pressure (u) at locations P1 and P2, but under and over-pre-
The simulated settlement at a depth of 9.5 m (Fig. 9c) reduced dicted values of u at locations P3 and P4, respectively. Generally, the
slightly during the consolidation process. Although it is not very Class-A prediction method resulted in acceptable simulations of
obvious, the measured data also show the same tendency. The rea- these excess pore water pressures.
122 J. Chai et al. / Computers and Geotechnics 48 (2013) 117126

0 Based on the results of BH-6, values of the model parameters, k,


Measured j, e0, ct, kh and kv were redened for the soil layers from 1.5 m to
-0.2 Class-A
Class-C1
12.0 m, as listed in Table 2. Other modications are as follows:
Settlement, S (m)

-0.4 Class-C2
(1) Soil model: Based on the site investigation results of the
-0.6
Nearby Area, the soil layer from 10.0 m to 12.0 m depth
-0.8 was classied as sandy clay, but the results from the Test
Site indicate it is a clayey sand layer with a depth range of
-1
9.812.0 m. For this layer, the constitutive model was chan-
-1.2 ged from MCC to an elastoplastic stressstrain model that
S0 (Surface, center) obeys the Mohr-Coulomb failure criterion and the depths
-1.4
0 200 400 600 800 1000 1200 were changed accordingly.
Elapsed time, t (day) (2) M values: From the triaxial compression test results obtained
(a) Surface for four different depths at the Test Site (Fig. 4), the slope of a
straight line (sin(/0 )), drawn from the origin to the peak
0 point of each individual effective stress path, reduces as
-0.2 S1 (-2,8 m, center) the initial consolidation stress increases. Because MCC is a
no-cohesion model, an envelope of best t passing through
Settlement, S (m)

-0.4 the origin was determined by considering the representative


-0.6 stress levels in the deposit under the embankment loading.
The redened values of M (corresponding to a /0 value of
-0.8 about 39.2 under triaxial compression) are listed in Table 2.
-1 Measured
Class-A The sizes of the yield loci were subsequently redened in order
-1.2 Class-C1
Class-C2 to predict the target values of Su, as determined from the uncon-
-1.4 ned compression tests. However, the values of K0 used to calcu-
0 200 400 600 800 1000 1200
late the initial horizontal effective stresses in the deposit were
Elapsed time, t (day)
not changed, even though Mayne and Kulhawys [19] equation
(b) 2.8 m below the surface (S1) would suggest that a higher internal friction angle (/0 ) should re-
sult in a slightly smaller value of K0. Furthermore, it is noted that
Measured the results of constant rate of strain consolidation tests conducted
0.02 Class-A in the laboratory using undisturbed Ariake clay samples, cut verti-
Class-C1
Class-C2 cally and horizontally with respect to the in situ condition, indicate
Settlement, S (m)

0 that the yield stress in the horizontal direction is about 0.51.0


(average of about 0.7) times the value in the vertical direction
-0.02 [10]. Thus, for simplicity, it was assumed that values of K0 used
to dene the initial horizontal effective stress should be left at
-0.04 approximately 0.50.6 in the Class-C prediction.

S3 (-9.5 m) (3) Poissons ratio: Although the Class-A prediction resulted in a


-0.06
0 200 400 600 800 1000 1200 good prediction of the lateral displacement prole, it was
Elapsed time, t (day) considered that the lateral displacements might now be
over-predicted if the larger values of the compression
(c) 9.5 m below the surface (S3)
parameters, as listed in Table 2, were adopted in the revised
Fig. 9. Comparison of settlementtime curves.
analysis. In the Class-C prediction, a value of Poissons ratio
of 0.15 was adopted for all soil layers (except the embank-
ment ll material).
(4) Size of the initial yield loci: Changing the value of M will obvi-
3.3. Class-C predictions and comparisons with measured data ously change the shape of the yield function. As illustrated in
Fig. 13, in order to predict the same target value of Su corre-
3.3.1. Analysis with soil parameters from BH-6 sponding to a given initial stress state, the size of the yield
After the results of tests on soil samples recovered from bore- locus (p0y ) for M = 1.6 is smaller than that corresponding to
hole BH-6 (whose location will be referred to as the Test Site) be- M = 1.2. Also, with the assumed initial stress state and for
came known, the correctness and appropriateness of the values undrained triaxial compression, the effective stress path
assumed for the model input parameters were checked. Compari- for the case where M = 1.2 approaches the critical state line
sons of the adopted and measured values of Su and OCR are given (CSL) from the dry side, while for M = 1.6 it approaches CSL
in Figs. 7b and 8b, respectively. Although the data are scattered, from the wet side. Keeping the values labelled Su-A&C1
the adopted values could be considered to be reasonable. However, in Fig. 7 unchanged, the predicted OCR values were changed
for the values of k there are considerable differences, as shown in to those labelled OCR-C1 in Fig. 8.
Fig. 12. For soil layers from the ground surface to about 9 m depth,
the values of k from BH-6 are generally much larger than those ob- An analysis using the parameters in Table 2 was subsequently
tained from samples of the Nearby Area. The corresponding initial conducted. The results of this analysis are given in Figs. 911,
voids ratio, unit weight and hydraulic conductivity are also differ- where they are labelled as Class-C1 predictions. It can be seen that
ent. It is notable that this site was tidal land about 300 years ago there is considerable improvement in the settlement predictions,
[25]. Therefore, the very soft, more compressible spots may reect but generally these predictions are still smaller than the measured
the locations of the channels of old creeks or rivers. data (Fig. 9). Fig. 11a and b reveal an interesting point about the
J. Chai et al. / Computers and Geotechnics 48 (2013) 117126 123

Lateral displacement, (m) Lateral displacement, (m)


0 0.05 0.1 0.15 0 0.05 0.1 0.15
0 0

5 5

Depth, D (m)

Depth, D (m)
10 10

t = 50 days
(end of construction) t = 730 days
15 15 Measured
Measured
Class-A Class-A
Class-C1 Class-C1
Class-C2 Class-C2
20 20
(a) At the end of construction (b) At 2 years elapsed time
Fig. 10. Comparison of lateral displacement proles.

50 50
P1 (-1.4 m) Excess pore pressure, u (kPa)
Excess pore pressure, u (kPa)

P2 (-5.0 m)
40
Measured Measured
40
Class-A Class-A
Class-C1 Class-C1
30 Class-C2 30 Class-C2

20 20

10 10

0 0
0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200
Elapsed time, t (day) Elapsed time, t (day)
(a) At 1.4 m below the surface (P1) (b) At 5.0 m below the surface (P2)

50 50
P3 (-8.3 m)
Excess pore pressure, u (kPa)
Excess pore pressure, u (kPa)

P4 (-10.0 m)
40 Measured 40
Class-A Measured
Class-C1 Class-A
30 Class-C2 30 Class-C1
Class-C2
20 20

10 10

0 0
0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200
Elapsed time, t (kPa) Elapsed time, t (day)
(c) At 8.3 m below the surface (P3) (d) At 10.0 m below the surface (P4)

Fig. 11. Comparison of excess pore water pressuretime curves.

variation of u at location P1 (1.4 m from the ground surface) and P2 3.3.2. Analysis with modied values of Su and OCR (Class-C2)
(5.0 m from the ground surface). The Class-A prediction showed a It is well known that for clayey soils there is an effect of strain
slower dissipation rate, but in contrast the Class-C1 prediction rate on the undrained shear strength, Su (e.g., [2,3]). In addition, the
indicated much faster dissipation. The reasons for this difference soil at the site was micro-structured and has exhibited some
are considered to be: (1) the initial values of the hydraulic conduc- strain-softening behaviour, as indicated by the effective stress
tivities for the layers at depths between 1.5 m and 12.0 m shown in paths in Fig. 4. In the Class-A and Class-C1 analyses, the unconned
Table 2 are larger than the corresponding values listed in Table 1; compression strengths, qu, obtained from the undisturbed soil
and (2) the value of M was increased from 1.2 to 1.6. Due to these samples loaded at an axial strain rate of 1%/min, were used directly
changes, the predicted effective stress paths of the soils under the to calibrate the yield stress. Therefore, a possibility exists that the
embankment were altered. Fig. 14 shows an example comparison deduced values of Su, and hence the corresponding values of OCR,
of the effective stress paths for a soil element near point P2. might not be fully representative of eld conditions and it is possi-
124 J. Chai et al. / Computers and Geotechnics 48 (2013) 117126

40
0 0.5 1 1.5 M = 1.6
0
M =1.2

Deviator stress, q (kPa)


30
Target q f
2

4
Depth, D (m)

20
Effective
6 stress
path
10 Initial
8 point
py py
(M = 1.6) (M = 1.2)
10 0
Test Site 0 10 20 30 40 50 60
Nearby Area
12
Effective mean stress, p' (kPa)

Fig. 13. Illustration of the effect of M on the size of the yield locus.
Fig. 12. Comparison of k values.

ble that they have been over-estimated. For this reason further
analyses with modied values of Su and OCR were conducted. This
50
further modication was made by multiplying the values of Su (Su-
A&C1 in Fig. 7) by a factor a, which was assigned values of 0.75, Stay here for
more than 100
0.8 and 0.85. The corresponding values of OCR were also re-esti- 40 days M = 1.2

Deviator stress, q (kPa)


mated. By comparing the various predictions with the eld mea-
sured values, it was found that a value of a = 0.85 results in the
best predictions, and this particular analysis is designated here as 30
M = 1.6
Class-C2. The values of Su and OCR for the Class-C2 analysis are
plotted in Figs. 7 and 8, where they are labelled Su-C2 and 20
OCR-C2, respectively. The factor a = 0.85 was applied to the mea-
sured values of Su and the results are designated as Corrected (S0u )
in Fig. 7. 10 Class-A
Class-C1
The results of the Class-C2 analysis are compared with the mea-
Class-C2
sured and other simulated results in Figs. 911 for settlements, lat-
0
eral displacements and excess pore water pressures, respectively. 0 10 20 30 40 50
From Fig. 9, it can be seen that the Class-C2 analysis resulted in a Effective mean stress, p' (kPa)
good simulation of the settlementtime curves, although it still
Fig. 14. Effective stress paths for a point near P2.
slightly under-estimated the settlement magnitudes. The results
in Fig. 10 indicate that the Class-C2 prediction slightly over-esti-
mated the lateral displacements, but overall the predictions are
As for the strain rate effect, Bjerrum [2] proposed a factor (l) to
very good. As for the excess pore water pressures, generally the re-
correct the eld vane shear strength (Su) used in slope stability
sults from the Class-C2 predictions are excellent, except for the
analysis. He correlated this factor with the plasticity index (PI) of
values at location P1 where the simulated dissipation rate was fas-
the soil. Tanaka [27] reported a comparison of eld vane shear
ter than the measured rate (Fig. 11a).
strength (Su) with values determined from laboratory unconned
compression test (qu/2) for seven different clayey soils in Japan
and indicated that for values of PI of about 4080, the average ratio
3.4. Signicance of the factor a Su/(qu/2) is about 1.0. For the soft Ariake clay samples from BH-6,
the PI values were 5276 (in the Nearby Area the PI values were
The main reasons for operative eld values of Su being less than 3270). With a PI of about 50, the corresponding Bjerrum correc-
the laboratory measured values are: (a) strain rate effects, and (b) tion factor (l) will be about 0.8, which is slightly smaller but com-
de-structuring or strain softening of the micro-structured (or sen- parable with the back-estimated value of a = 0.85. Using a value of
sitive) soil. Therefore a can be regarded as a correction factor for a of 0.8, the predictions are good, but not quite as good as those
the effects of strain rate and/or strain-softening. corresponding to a = 0.85.

Table 2
Redened model parameters based on results obtained for samples from BH-6.

Depth (m) Soil strata SPT N E (kPa) m j k M e0 ct (kN/m3) kv kh


(104 m/day)
0.01.5 Surface soil 0.15 0.025 0.25 1.6 1.50 16.0 6.0 9.1
1.54.0 Soft silty clay 0.15 0.107 1.07 1.6 3.71 13.1 10.4 15.6
4.06.0 0.15 0.119 1.19 1.6 2.88 13.9 17.3 25.9
6.08.0 0.15 0.084 0.84 1.6 2.72 14.1 16.5 24.7
8.09.8 0.15 0.066 0.66 1.6 1.91 15.7 7.0 10.6
Depth (m) Soil strata SPT N E (kPa) m / () c (kPa) M e0 ct (kN/m3) kv kh
9.812.0 12.015.0 Clayey sand 3 7500 0.15 35 20 0.80 18.0 2500 2500
12.015.0 Clayey sand 8 20,000 0.15 35 20 0.80 18.0 2500 2500
15.020.0 Clayey sand 15 37,500 0.15 35 20 0.70 19.0 2500 2500
J. Chai et al. / Computers and Geotechnics 48 (2013) 117126 125

When Bjerrums correction factor, l, was rst proposed, the ef- the suitability of a particular model and the values selected
fect of de-structuring or strain-softening of the soils considered for the model parameters. In this process, the effect of strain
was not explicitly mentioned. However, since the values of l were rate and/or strain-softening on the values of Su has to be
obtained by comparing the eld vane shear strengths with the properly considered. The logic behind this approach is that
back-estimated eld mobilised strengths, and because it is gener- provided parameters like the compression index and the
ally recognised that all natural clayey soils are micro-structured coefcient of consolidation are chosen correctly, the magni-
(e.g., [24]), it is highly likely that both the effects of strain rate tudes of the predicted soil deformations are strongly inu-
and strain-softening are included implicitly in the values of l pro- enced by the yield stress (i.e., the size of the yield locus),
posed by Bjerrum. Although further research is needed to establish and for most constitutive models for clay, the predicted
a more rational way to determine the strength reduction factor, a, value of Su is closely related to the adopted value of the ini-
at present it is considered that Bjerrums strain rate correction fac- tial yield stress.
tor can be used as a reasonable rst approximation of the correc-
tion factor for the values of Su. It is proposed that a strength correction factor (a) should be ap-
The use of the Bjerrum correction has meant that the OCR val- plied to laboratory and eld measures of Su. Although further re-
ues adopted for the Class-C2 analyses are lower than the values search is needed to determine a values in a fundamental way,
determined from laboratory consolidation test results. It is noted the results of this study show that Bjerrums [2] empirical strain
that consolidation test results only provide a single point on the rate correction factor (l) can be used as a rst approximation of
yield surface, and the initial yield function (or yield surface) has the value of a.
to be extrapolated from this point by applying the appropriate Although the MCC model adopted in this study does not con-
MCC theory. Hence there is a possibility that the use of the MCC sider the anisotropic and time dependent behaviour possessed of
model together with a value of OCR determined from oedometer most natural clayey deposits, it has still resulted in quite good sim-
testing may result in over-estimation of the eld value of Su. It is ulation (Class-C2) of the eld measured response. It is considered
emphasised again that calibrating the model, specically the pre- that the corrected Su value most likely represents to sufcient
dicted values of Su, using the measured values of Su corrected for accuracy the average eld-mobilised value of Su under an embank-
the strain rate effect (and possibly any softening arising from mi- ment load, and using this value of Su with an isotropic soil model
cro-structure in the clay), is an important step in making successful captures the most important features of the mechanical behaviour
predictions of the effects of embankment loading. of soft clayey soil, and generally results in acceptable predictions of
that behaviour. However, if the available site investigation data are
4. Discussion sufcient to reliably dene the necessary parameters for more
sophisticated soil models, such as those capturing anisotropy, in
The case study presented above has revealed at least three principle use of these more sophisticated models should result in
important issues regarding prediction of the performance of earth improved predictions of soil behaviour.
structures on soft soils.
5. Conclusions
(1) Adequate soil investigation: Of course detailed and appropri-
ate site investigation, soil testing and interpretation of the Field measurements and numerical predictions of the behaviour
test results are important in all geotechnical designs. This of a test embankment constructed on a deposit of soft Ariake clay
case study has further emphasised this point. For any natural in Saga, Japan, have been presented. The numerical predictions
deposit there may be localised variation of the soil proper- were conducted by nite element analysis (FEA) in which the
ties, and there is additional risk if the design parameters mechanical behaviour of soft clayey soil layers was represented
are estimated using only information obtained from nearby by the Modied Cam Clay model. These involved two types of pre-
areas rather than the specic site in question. diction: Class-A, conducted before; and Class-C, conducted after
(2) Strength parameters of clayey soils: For most practical cases, the embankment was constructed. Comparisons were made be-
the effective stress strength parameters, e.g., the cohesion tween the various predictions and the eld measurements in terms
(c0 ) and internal friction angle (/0 ) of a clayey soil, are usually of settlements, lateral displacements and excess pore water pres-
interpreted based on the Mohr-Coulomb failure criterion, sures in the subsoil.
and normally nite values will be obtained for both c0 and The results of these comparisons indicate that the Class-A pre-
/0 . In cases where a no-cohesion soil model, such as MCC, diction resulted in a poor simulation of the eld performance,
is used to predict the soil response, there is a possibility that mainly due to over-estimation of the yield stresses (i.e., the sizes
the strength parameter M may be under-estimated if the of the initial yield loci) of the subsoils and under-estimation of
value of /0 interpreted from the Mohr-Coulomb criterion is compressibility, hydraulic conductivity and the slope (M) of the
adopted directly. This case study has demonstrated the critical state line. The following observations are suggested by
importance of determining the value of M from laboratory the results of this study.
tests following the appropriate effective stress path.
(3) Performance of the adopted constitutive model: To predict the (a) Detailed on-site soil investigation, correct testing and appro-
mechanical behaviour of a clayey deposit under embank- priate interpretation of the test results are essential issues
ment loading using the nite element approach, it is essen- for predicting the behaviour of an earth structure on a soft
tial to check whether the constitutive model, as well as the clayey deposit.
adopted values of the model parameters, are able represent (b) When using a soil model developed in the framework of
well the strength and deformation characteristics of the sub- Critical State Soil Mechanics, the value of parameter M
soil. However, there is no well-established procedure or should be determined directly from test result with an
method to conduct this kind of check. The results of this appropriate effective stress path.
study indicate that comparing the simulated prole of (c) Calibrating the yield stress by comparing the simulated pro-
undrained shear strength (Su) (under triaxial compression) le of undrained shear strength (Su) under triaxial compres-
with measured values of Su may be a useful way to check sion with the measured data provides an efcient check on
126 J. Chai et al. / Computers and Geotechnics 48 (2013) 117126

4 [9] Chai J-C, Miura N, Shen S-L. Performance of embankments with and without
reinforcement on soft subsoil. Can Geotech J 2002;39(8):83848.
[10] Chai J-C, Jia R, Hino T. Anisotropic consolidation behavior of Ariake clay from
three different CRS tests. Geotech Test J, ASTM 2012;35(6):19. http://
3 dx.doi.org/10.1520/GTJ103848.
[11] Grammatikopoulou A, Zdravkovic L, Potts DM. General formulation of two
Void ratio, e

kinematic hardening constitutive models with a smooth elastoplastic


transition. Int J Geomech, ASCE 2006;6(5):291302.
2 [12] Grammatikopoulou A, Zdravkovic L, Potts DM. The effect of the yield and
plastic potential deviatoric surfaces on the failure height of an embankment.
Depth (m) Gotechnique 2007;57(10):795806.
1 1.5-2.3 m [13] Igaya Y, Hino T, Chai J-C. Behavior of trial embankments on soft Ariake clay
4.6-5.4 m deposits with and without column improvement. In: Proceedings
7.9-8.7 m international symposium on geotechnical and geosymthetics engineering:
9.0-9.8 m challenges and opportunities on climate change, Bangkok, Thailand; 2010. p.
0 35462.
1 10 100 1000 [14] Japanese Society of Civil Engineer (JSCE). Manual for structural design of
Vertical consolidation pressure 'v (kPa) Japanese Railway, Tokyo; 1986.
[15] Karim MR, Gnanendran CT, Lo S-CR, Mak J. Predicting the long-term
performance of a wide embankment on soft soil using an elasticviscoplastic
Fig. A1. e- logr0 v ) curves. model. Can Geotech J 2010;47(2):24457.
[16] Karstunen M, Yin Z-Y. Modelling time-dependent behaviour of Murro test
embankment. Gotechnique 2010;60(10):73549. http://dx.doi.org/10.1680/
the suitability of the constitutive model, as well as the geot.8.P.027-735.
adopted values of the model parameters, provided that a [17] Lambe TW. Predictions in soil engineering. Gotechnique 1973;23:149202.
correction for the effect of strain rate or strain-softening [18] Manivannan G, Karim MR, Gnanendran CT, Lo S-CR. Calculated and observed
long term performance of Leneghans embankment. Geomech Geoeng
on Su value is properly considered. The results also indicate
2011;6(3):195207.
that Bjerrums strain rate correction factor can be adopted [19] Mayne PE, Kulhawy FH. K0-OCR relationships in soils. J Geotech Eng, ASCE
as a rst approximation of the correction factor applied to 1982;108(GT6):85172.
[20] Oliveira PJV, Lemos LJL, Coelho PALF. Behavior of an atypical embankment on
eld or laboratory measured values of Su.
soft soil: eld observations and numerical simulation. J Geotech Geoenviron
Eng 2010;136(1):3547.
[21] Oliveira PJV, Lemos LJL. Numerical predictions of the behaviour of soft clay
with two anisotropic elastoplastic models. Comput Geotech
Appendix A 2010;38(5):598611.
[22] Poulos HG, Lee CY, Small JC. Prediction of embankment performance on
Oedometer test results of undisturbed samples from BH-6 are Malaysian marine clays. In: Hudson RR, Toh CT, Chan SF, editors. Proceedings
of the international symposium on trial embankments on Malaysian marine
presented in Fig. A1. clays, Kuala Lumpur, Malaysia, vol. 2. Malaysia: The Malaysian Highway
Authority, Kuala Lumpur; 1989. p. 4/14/10.
References [23] Roscoe KH, Burland JB. On the generalized stressstrain behavior of wet clay.
In: Heyman J, Leckie FA, editors. Engineering plasticity. Cambridge University
[1] Ariake Sea Coastal Road Development Ofce (ASCRDO), Saga Prefecture. Report Press; 1986. p. 535609.
on eld measurements and analyses: improvement project for national road [24] Schmertmann JH. The mechanical aging of soils. J Geotech Eng, ASCE
no. 444, Saga, Japan; 2011 [in Japanese]. 1991;117(9):1288330.
[2] Bjerrum L. Embankment on soft ground: SOA report. In: Proc specialty conf on [25] Shimoyama S, Matsuura H, Hino T. Topography, geology of the saga district.
performance of earth and earth-supported structures, ASCE, vol. 2; 1972. p. 1 Quadrangle series, 1:50,000, Geological Survey of Japan, AIST; 2010. p. 17
54. [chapter 1, in Japanese].
[3] Bjerrum L. Embankment on soft ground: SOA report. In: Proc 8th conf soil [26] Sloan SW. Substepping schemes for numerical integration of elato-plastic
mech and found eng, vol. 3, Moscow, USSR; 1973. p. 11159. stressstrain relations. Int J Numer Methods Eng 1987;24:893911.
[4] Brand EW. Predicted and observed performance of an embankment built to [27] Tanaka H. Vane shear strength of a Japanese marine clay and applicability of
failure on soft clay. Geotech Eng, Southeastern Asian Geotech Soc Bjerrum correction factor. Soils Found 1994;34(3):3948.
1991;22(1):2342. [28] Tavenas F, Tremblay M, Larouche G, Lerouei lS. In situ measurement of
[5] Britto AM, Gunn MJ. Critical state soil mechanics via nite elements. Ellis permeability in soft clays. In: Proceedings ASCE special conference on use of
Horwood Limited; 1987. p. 486. in-situ tests in geotechnical engineering, Blacksburg; 1986. p. 103448.
[6] Chai JC, Miura N, Bergado DT, Long PV. Finite element analysis of embankment [29] Taylor DW. Fundamentals of soil mechanics. New York: John Wiley & Sons,
failure on soft subsoil. Geotech Eng, Southeast Asian Geotech Soc Inc.; 1948.
1997;28(2):24976. [30] Wroth CP. The predicted performance of soft clay under a trial embankment
[7] Chai J-C. Interaction between grid reinforcement and cohesive-frictional soil loading based on the Cam-clay model. In: Gudehus G, editor. Finite elements in
and performance of reinforced wall/embankment on soft ground. PhD geomechanics. Wiley; 1977. p. 191208.
dissertation, Asian Institute of Technology, Bangkok, Thailand; 1992. [31] Yin J-H, Zhu J-G, Graham J. A new elastic viscoplastic model for time
[8] Chai J-C, Miura N. Investigation on some factors affecting vertical drain dependent behaviour of normally and over consolidated clays: theory and
behavior. J Geotech Geoenviron Eng, ASCE 1999;125(3):21626. verication. Can Geotech J 2002;39(1):15773.

You might also like