Update to the S7-1200 Functional Safety Manual, edition
07/2015
Product Information
WARNING
The "SIMATIC, Industrial Software, SIMATIC Safety - Configuring and Programming, Programming and Operating Manual"
in the current version is the authoritative source for Functional Safety-related information concerning configuring and
programming.
Siemens identifies the "SIMATIC, Industrial Software, SIMATIC Safety - Configuring and Programming, Programming and
Operating Manual" (http://support.automation.siemens.com/WW/view/en/54110126) as the authoritative and/or original
source in the case of discrepancies between the manuals.
All warnings in the "SIMATIC, Industrial Software, SIMATIC Safety - Configuring and Programming, Programming and
Operating Manual" have to be observed.
Security information
Siemens provides products and solutions with industrial security functions that support the secure operation of plants,
solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept.
With this in mind, Siemens products and solutions undergo continuous development. Siemens recommends strongly that
you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell
protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party
products that may be in use should also be considered. You can find more information about industrial security on the
Internet (http://www.siemens.com/industrialsecurity).
To stay informed about product updates as they occur, sign up for a product-specific newsletter. You can find more
information on the Internet (http://support.automation.siemens.com).
You should include the expected discrepancy time between your sensor inputs in your external sensor
delay. Your configured TDIS contributes to TOFDT as the time delay for the F-DI to passivate the channel
due to fault case extension of the discrepancy time.
This parameter can be listed separately in the RT_calculator. Do not include TDIS in the value of TOFDT
that you enter into the RT_calculator if you enter TDIS as a separate item.
Tsct Time delay for short-circuit test duration:
"0" if no short-circuit test configured
"0" for 1oo2 channels changing from "1" to "0" and "Supply value 0" option configured for discrepancy
behavior
"Duration of short-circuit test" + "Input filters" time if short-circuit test is configured
(Confirmation: "Input filters" can occur twice in equation for TWCDT_i if short-circuit test is configured.)
Tscf Time delay for short-circuit fault detection:
Configured "Interval for short-circuit test", when operating in high demand or continuous mode and
depending on the short-circuit test to achieve your required level of safety integrity
"0" when not depending on the short-circuit test to achieve your required level of safety integrity
Tcycle_i Internal cycle time of F-DI
8 ms
The term "2 x Tcycle_i" allows for other input delays to complete just after the beginning of a cycle. The F-DI processes and
reports the changed input data on the next cycle.
The S7-1200 Automation System satisfies requirements and safety related objectives according to the EC directives listed
below, and conforms to the harmonized European standards (EN) for the programmable controllers listed in the Official
Journals of the European Union.
EC Directive 2004/108/EC (EMC Directive) "Electromagnetic Compatibility"
Emission standard
EN 61000-6-4:2007/A1:2011: Industrial Environment
Immunity standard
EN 61000-6-2:2005/AC:2005: Industrial Environment
EC Directive 2006/42/EC (Machine Directive) "Machinery and Amending Directive 95/16/EC"
Safety of Machinery
EN ISO 13849-1:2008/AC:2009 and EN ISO 13849-2:2012: Safety Related Parts of Control Systems
EN 62061:2005/A1:2013: Functional Safety of Safety Related Electrical, Electronic, and Programmable Electronic
Control Systems
EC Directive 2006/95/EC (Low Voltage Directive) "Electrical Equipment Designed for Use within Certain Voltage Limits"
EN 61131-2:2007: Programmable Controllers - Equipment requirements and Tests
EC Directive 94/9/EC (ATEX) "Equipment and Protective Systems Intended for Use in Potentially Explosive Atmosphere"
EN 60079-0:2012/A11:2013
EN 60079-15:2010: Type of Protection 'n'
Note
Not all S7-1200 products are suitable for potentially explosive atmosphere locations. Only S7-1200 products that are marked
with the ATEX symbol are suitable for ATEX classified hazardous locations as marked.
Note
Ferrules or end sleeves on stranded conductors reduce the risk of stray strands causing short circuits. Ferrules longer than
the recommended strip length should include an insulating collar to prevent shorts due to side movement of conductors.
Cross-sectional area limits for bare conductors also apply to ferrules.