System
Indoor Unit R410A
SERVICE MANUAL R410A
MODEL : ARNU Series
URNU Series
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions............................................................................................................................3
Part 1 General Information .............................................................................................................10
Model Names .............................................................................................................................11
External Appearance .................................................................................................................12
Nomenclature .............................................................................................................................15
3. Nomenclature .............................................6
1. Model Names
Capacity(Btu/h(kW))
Category Chassis
Name 7k 9k 12k 15k 18k 24k 28k 36k 42k 48k 76k 96k
(2.2) (2.8) (3.6) (4.5) (5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28)
SE ARNU07 ARNU09 ARNU12 ARNU15
Wall Mounted GSE*2 GSE*2 GSE*2 GSE*2
(General) ARNU18G ARNU24G
S5
S5*2 S5*2
ARNU07 ARNU09 ARNU12 ARNU15
SE
GSE*2 GSE*2 GSE*2 GSE*2
Mirror
ART COOL ARNU18 ARNU24
S3 GS3*2 GS3*2
ART Cool ARNU07 ARNU09 ARNU12
SF
Gallery GSF*2 GSF*2 GSF*2
1 Way TJ ARNU07 ARNU09 ARNU12
GTJ*2 GTJ*2 GTJ*2
ARNU18 ARNU24
2 Way TL GTL*2 GTL*2
ARNU07 ARNU09 ARNU12 ARNU15 ARNU18
Ceiling TE GTE*2 GTE*2 GTE*2 GTE*2 GTE*2
Cassette ARNU24G ARNU28G
TP
4 Way TP*2 TP*2
ARNU36
TN
GTN*2
ARNU42G ARNU48G
TM TM*2 TM*2
BH ARNU07 ARNU09 ARNU12 ARNU15 ARNU18 ARNU24
GBHA2 GBHA2 GBHA2 GBHA2 GBHA2 GBHA2
ARNU28 ARNU36 ARNU42
BG
High GBGA2 GBGA2 GBGA2
Static ARNU48
BR GBRA2
URNU76 URNU96
Ceiling B8
GB8A2 GB8A2
Concealed
ARNU07 ARNU09 ARNU12 ARNU15
Duct B1
GB1G2 GB1G2 GB1G2 GB1G2
Low Static
ARNU18 ARNU24
B2
GB2G2 GB2G2
B3 ARNU07 ARNU09 ARNU12 ARNU15
GB3G2 GB3G2 GB3G2 GB3G2
Built In
B4 ARNU18 ARNU24
GB4G2 GB4G2
ARNU09G ARNU12G
Ceiling & Floor VE VEA2 VEA2
ARNU18 ARNU24
Ceiling Suspended VJ GVJA2 GVJA2
ARNU07 ARNU09 ARNU12 ARNU15
CE
GCEA2 GCEA2 GCEA2 GCEA2
With Case
ARNU18 ARNU24
CF
Floor GCFA2 GCFA2
Standing ARNU07 ARNU09 ARNU12 ARNU15
CE GCEU2 GCEU2 GCEU2 GCEU2
Without
Case ARNU18 ARNU24
CF
GCFU2 GCFU2
*ART COOL- B: Blue, M:Metal, D:Wood, R:Mirror, W:White Wood, V:Silver, E:Red, G:Gold, 1: Kiss (Photo changeable)
*Wall Mounted- A: Basic, L:Plasma
*Ceiling Cassette- A: Basic, C:Plasma
2. External Appearance
Ceiling Cassette- 1Way Ceiling Cassette -2Way
ARNU07GTJ*2 ARNU18GTL*2
ARNU09GTJ*2 ARNU24GTL*2
ARNU12GTJ*2
* A:Basic, L:Plasma
3. Nomenclature
ARN U 07 G TJ A 2
Serial Number
Combinations of functions
A:Basic function
L:Neo Plasma(Wall Mounted)
C:Plasma(Ceiling Cassette)
G: Low Static
ART COOL Type Panel Color
B:Blue D:Wood M:Metal R:Mirror W:White Wood
V: Silver E:Red G:Gold 1: Kiss (Photo changeable)
Chassis Name
Electrical Ratings
1:1, 115V, 60Hz 2: 1, 220V, 60Hz
6:1, 220 ~ 240V, 50Hz 7: 1, 100V, 50/60Hz
G:1, 220 ~ 240V, 50Hz / 220V 60Hz
Total Cooling Capacity in Btu/h
EX) 5,000 Btu/h'05' 18,000 Btu/h'18'
Combination of Inverter Type and
Cooling Only or Heat Pump
N: AC Inverter and H/P V: AC Inverter and C/O
U: DC Inverter and H/P and C/O
System with
Indoor Unit using R410A
LGETA:U Ex) URN
Ceiling Cassette
1 Way .................................................................................8
2 Way ...............................................................................13
4 Way(1)...........................................................................20
4 Way(2)...........................................................................23
Art Cool Series
ART COOL Miror .............................................................30
ART COOL Gallery ..........................................................41
Ceiling Concealed Duct
Low Static ........................................................................51
Built In ..............................................................................57
High Static........................................................................63
Wall Mounted(General)
Wall Mounted ...................................................................72
Ceiling & Floor
Ceiling & Floor
Ceiling Suspended...........................................................83
Floor Standing
Floor Standing..................................................................90
1. Functions ......................................................................................9
2. Operation Details........................................................................10
3. Dimensions .................................................................................12
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Airflow Direction Control The louver can be set at swing up and down automatically.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
2. Operation Detail
(1) The function of main control
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. ON
(SET TEMPERATURE +0.5C)
Thermo. OFF
(SET TEMPERATURE -0.5C) More than More than
3 minutes 3 minutes
Indoor pipe
Temperature
36(42)C
33(39)C
25C
22(20)C
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C.
The operation diagram is as following.
Pipe
temperature
35 C
30 C
27 C
25 C
22 C
LO
LOW
ARNU07GTJ*2
ARNU09GTJ*2
ARNU12GTJ*2
961.2
19.1 16.5 860
410
2 Gas pipe connection 12.7 flare
344.4
3 Air suction grill
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
198.8 131 .
16.4
2 2. Unit shall be grounded in accordance with the local regulations or
- 12 -
applicable national codes.
110
1
242.5
173
151
100
56
83 30
36
138 50
1070
83
939
480
3
1. Functions ....................................................................................14
2. Operation Details........................................................................15
3. Dimensions .................................................................................17
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Airflow Direction Control The louver can be set at swing up and down automatically.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
2. Operation Detail
(1) The function of main control
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. ON
(SET TEMPERATURE +0.5C)
Thermo. OFF
(SET TEMPERATURE -0.5C) More than More than
3 minutes 3 minutes
Indoor pipe
Temperature
36(42)C
33(39)C
25C
22(20)C
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C.
The operation diagram is as following.
Pipe
temperature
35 C
30 C
27 C
25 C
22 C
LO
LOW
ARNU18GTL*2
ARNU24GTL*2
A
830 B
47.9
(unit : mm)
275
1 Liquid pipe connection (18k) 6.35, (24k)9.52
2
3. Dimensions
550
3 Air suction grill
69.5
Note
1. Unit should be installed in compliance with the installation manual
889.2 in the product box.
TL 2. Unit shall be grounded in accordance with the local regulations or
- 17 -
A 225 applicable national codes.
B 126.5
1050
28.5
640
4
1. Functions ....................................................................................19
2. Operation Details........................................................................20
3. Dimensions .................................................................................22
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Airflow Direction Control The louver can be set at swing up and down automatically.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
2. Operation Detail
(1) The function of main control
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. ON
(SET TEMPERATURE +0.5C)
Thermo. OFF
(SET TEMPERATURE -0.5C) More than More than
3 minutes 3 minutes
Vane 1 Vane 3
Vane 4
Indoor pipe
Temperature
36(42)C
33(39)C
25C
22(20)C
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C.
The operation diagram is as following.
Pipe
temperature
35 C
30 C
27 C
25 C
22 C
LO
LOW
ARNU09GTE*2
ARNU12GTE*2
269
ARNU15GTE*2
670 ARNU18GTE*2
670
(unit : mm)
5
Note
1. Unit should be installed in compliance with the installation manual
- 22 -
570
521
in the product box.
670
6 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
40
4
1 2
30
110 110
269
90
90
30
120.4
3
1. Functions ....................................................................................24
2. Operation Details........................................................................25
3. Dimensions .................................................................................27
1. Functions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Airflow Direction Control The louver can be set at swing up and down automatically.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator pip-
ing temperature will be reached at 25C.
High-Ceiling corresponding Function According to the height of ceiling, the RPM of indoor fan
motor is selected to increase air reaching distance.
2. Operation Detail
(1) The function of main control
Auto Swing Control
This function is to swing the louver up and down automatically.
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
Thermo. ON
(SET TEMPERATURE +0.5C)
Thermo. OFF
(SET TEMPERATURE -0.5C) More than More than
3 minutes 3 minutes
Vane 1 Vane 3
Vane 4
Indoor pipe
Temperature
36(42)C
33(39)C
25C
22(20)C
Room
Temperature
Thermal Off
Thermal On
Minimum
3min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting Setting
Indoor fan Stop Low Low fan Low fan Low Stop Stop Low fan
speed speed speed
4 Way ON
Hot-start Control
The indoor fan does no rotate until the evaporator piping temperature will be reached to 25C.
The operation diagram is as following.
Pipe
temperature
35 C
30 C
27 C
25 C
22 C
LO
LOW
154
204
R35
126
62
A direction View
618
0
292 787
R2
4-
A
618
671
684
840
950
4 Power supply connection
- 27 -
500(Air outlet hole) 787
54 734 Note
950 840
6 1. Unit should be installed in compliance with the installation manual
5 in the product box.
4
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
204
25
82
99
60
65 40
108 60 80
2 840 3
1
195
Dimensions
ARNU36GTN*2
246
R35
126
62
A
A direction View
- 28 -
5 Air discharge grill
6 Air suction grill
6
5 4
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
2 3
1
ARNU42GTM*2
ARNU48GTM*2
840
R35
126
237
288
109
A direction View
(unit : mm)
Number Name Descripition
- 29 -
6 Air suction grill
Note
1. Unit should be installed in compliance with the installation manual
4 in the product box.
6
5 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
3
2
1. Functions ....................................................................................31
2. Operation Details........................................................................32
3. Dimensions .................................................................................39
1. Functions
Indoor Unit
Airflow Direction Control The indoor fan does not rotate until the
evaporator pipe temperature will be reached
The louver can be set at the desired position or swing at 28C.
up and down automatically.
2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
On while in appliance operation, off while in appliance pause
Timer Indicator
On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
On while auto restart mode, off while auto restart mode is canceled.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
Operation starts, when this button is pressed and stops when you press the button again.
Cooling Mode Operation
When the intake air temperature reaches 0.5C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5C
Compressor OFF Temp => Setting Temp-0.5C
While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.
Defrost Control
While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.
On-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
Off-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
165
1
3. Dimensions
ARNU07GSE*2
169 ARNU09GSE*2 915 282 169
ARNU12GSE*2
(unit : mm)
Number Name Descripition
282
282
1 Air discharge grill
- 39 -
53
2 Air suction grill
915 51
567
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
265
ARNU24GS3*2
173
1
(unit : mm)
1170 Model W H D
315
(unit : mm)
Number Name Descripition
- 40 -
1 Air discharge grill
2 Air suction grill
Note
1. Functions ....................................................................................42
2. Operation Details........................................................................43
3. Dimensions .................................................................................50
1. Functions
Indoor Unit
Airflow Direction Control The indoor fan does not rotate until the
evaporator pipe temperature will be reached
The louver can be set at the desired position or swing at 28C.
up and down automatically.
2. Operation Details
Function of Controls
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
On while in appliance operation, off while in appliance pause
Timer Indicator
On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
On while auto restart mode, off while auto restart mode is canceled.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
Operation starts, when this button is pressed and stops when you press the button again.
Cooling Mode Operation
When the intake air temperature reaches 0.5C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5C
Compressor OFF Temp => Setting Temp-0.5C
While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.
Defrost Control
While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost of the outdoor unit.
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to
the intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.
On-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
Off-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
ARNU07GSF*2
ARNU09GSF*2
ARNU12GSF*2
H (unit : mm)
Model W H D
(unit : mm)
- 50 -
500
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
525
Fix Hole
1. Funtions ......................................................................................52
2. Operation Details........................................................................53
3. Dimensions .................................................................................56
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25C.
High head height Drain pump A standard drain-head height of up to 700mm is possible.
2. Operation Details
(1) The function of main control
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C, fan operates
at low speed, when it becomes lower than 40C fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
Initial Hotstart On state
Power Off On
Operation Off On
Cooling operation Heating operation
Defrost operation
ARNU07GB1G2
ARNU09GB1G2
ARNU12GB1G2
ARNU15GB1G2
ARNU18GB2G2
D 5 13 ARNU24GB2G2
161
A B C D
3. Dimensions
ARNU07GB1G2
190
14
ARNU09GB1G2
65 60 820 728 856 794
216
1100 1008 1131 1072
2 ARNU24GB2G2
277
24
(unit : mm)
575
383
- 56 -
Number Name Descripition
Unit size(7k,9k,12k,18k):6.35
3 1 Liquid pipe connection Unit size(24k):9.52
Unit size(7k,9k,12k,18k):12.7
2 Gas pipe connection Unit size(24k):15.88
C
3 Drain pipe connection
4 4 Power supply connection
18
6
5 Air discharge
6 Air suction
190
154
Note
18 B
1. Unit should be installed in compliance with the installation manual
A in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
1. Funtions ......................................................................................58
2. Operation Details........................................................................59
3. Dimensions .................................................................................62
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 25C.
High head height Drain pump A standard drain-head height of up to 700mm is possible.
2. Operation Details
(1) The function of main control
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C, fan operates
at low speed, when it becomes lower than 40C fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
Initial Hotstart On state
Power Off On
Operation Off On
Cooling operation Heating operation
Defrost operation
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
With Suction Grille ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
With Suction Grille & Suction Canvas
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
216
277
2
24
3
5
A
With Suction Grille 4
B
- 62 -
Btu/h A
7,9,12k 820
190
18,24k 1100 (unit : mm)
250
A
Number Name Descripition
C Unit size(7k,9k,12k,18k):6.35
With Suction Grille & Suction Canvas 1 Liquid pipe connection Unit size(24k):9.52
A B C
Unit size(7k,9k,12k,18k):12.7
2 Gas pipe connection Unit size(24k):15.88
PBSGB30 910 359 56
190
PBSGB40 1188 359 56 3 Drain pipe connection
4 Power supply connection
A B C
500(Max)
PBSC30 821 274 42~250 5 Air discharge
PBSC40 1100 274 42~250 6 Air suction
C
Note
A B 1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
1. Funtions ......................................................................................64
2. Operation Details........................................................................65
3. Dimensions .................................................................................68
1. Funtions
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
The indoor fan does not rotate until the evaporator piping
Hot-start Control (Heating)
temperature reaches 30C.
High head height Drain pump A standard drain-head height of up to 700mm is possible.
2. Operation Details
(1) The function of main control
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C, fan operates
at low speed, when it becomes lower than 40C fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 22C.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
20
Dimensions
ARNU07GBHA2
175
ARNU09GBHA2
ARNU12GBHA2
ARNU15GBHA2
6 ARNU18GBHA2
49 101
ARNU24GBHA2
224
R3
3. Dimensions
7.
5
100 Number Name Descripition
355
60
450
355
450
Unit size(7k,9k,12k,18k):6.35
133
Unit size(7k,9k,12k,18k):12.7
47 47 2
2 Gas pipe connection Unit size(24k):15.88
21 3 3 Drain pipe connection
87 30 260
4 Power supply connection
750
5 5 Air discharge
882 108
- 68 -
6 Air suction
65
75
158
Note
260
1. Unit should be installed in compliance with the installation manual
in the product box.
64 243 212 243 119 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
450
882
20
ARNU36GBGA2
ARNU42GBGA2
220
(unit : mm)
6
224
0 0
3 Drain pipe connection
100
450
60
355
4 Power supply connection
- 69 -
1,182 108
Note
158
186
298
1. Unit should be installed in compliance with the installation manual
in the product box.
113
2. Unit shall be grounded in accordance with the local regulations or
232 243 232 243 232 applicable national codes.
450
1,182
25
ARNU48GBRA2
Dimensions
303
(unit : mm)
6 101
1,284 Number Name Descripition
83
1,230 115 26 1 Liquid pipe connection Unit size(48k):9.52
123
221
198
3 Drain pipe connection
312
R6
0
90
60 4 Power supply connection
477
590
5 Air discharge
122
144
1
56
50 3
32
118 114 135
1,004 190
260
5 Note
1. Unit should be installed in compliance with the installation manual
in the product box.
- 70 -
168
140
2. Unit shall be grounded in accordance with the local regulations or
380
applicable national codes.
185
215 279 241 279 215
590
1,230
20
URNU96GB8A2
440
2
70
6
58 1
18
(unit : mm)
122 60 70 64
Number Name Descripition
688
560
68 1 Liquid pipe connection Unit size(76k,96k):9.52
358
Unit size(76k):19.05
2 Gas pipe connection Unit size(96k):22.2
64
3 Drain pipe connection
30
1,220
4 Power supply connection
- 71 -
5 5 Air discharge
6 Air suction
290
318
Note
460
1. Unit should be installed in compliance with the installation manual
161
in the product box.
293 329 320 329 2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
688
1,562
1. Functions ....................................................................................73
2. Operation Details........................................................................74
3. Dimensions .................................................................................81
1. Functions
Indoor Unit
Airflow Direction Control The indoor fan does not rotate until the
evaporator pipe temperature will be reached
The louver can be set at the desired position or swing
at 28C.
up and down automatically.
2. Operation Details
Function of Controls
DISPLAY
(1) High quality LCD remote controller supplied
Operation Indicator
On while in appliance operation, off while in appliance pause
Timer(on/off) and Sleep timer Indicator
On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
On while in plasma mode, off while plasma mode is canceled.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
Operation starts, when this button is pressed and stops when you press the button again.
Cooling Mode Operation
When the intake air temperature reaches 0.5C below the setting temp, the compressor and the outdoor fan
stop.
When it reaches 0.5C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5C
Compressor OFF Temp => Setting Temp-0.5C
While in compressor running, operating with the airflow speed set by the remote controller. While in com-
pressor not running, operating with the low airflow speed regardless of the setting.
Defrost Control
While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to
defrost the outdoor unit.
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26C Intake Air Temp => 25C
24C Intake Air Temp<26C => Intake Air Temp+1C
22C Intake Air Temp<24C => Intake Air Temp+0.5C
18C Intake Air Temp<22C => Intake Air Temp
Intake Air Temp < 18C => 18C
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed
selection key on the remote controller.
On-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
Off-Timer Operation
When the set time is reached after the time is input by the remote controller, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
If the appliance is on pause at the time set by the timer, the pause continues.
Forced Operation
Operation procedures when the remote control can't be used.
The operation will be started if the power button is pressed.
If you want to stop operation, re-press the button.
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem-
perature and resets in 181 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets.
If you want to use this operation, Press and hold ON/OFF button 3~5 seconds, then the buzzer sound 1 "beep".
If you want to stop the operation, re-press the button.
165
ARNU15GSE*2
(unit : mm)
ARNU12GSE*2
ARNU15GSE*2
282
Number Name Descripition
1 Air discharge grill
2 Air suction grill
- 81 -
1
Note
265
ARNU24GS5*2
(unit : mm)
(unit : mm)
- 82 -
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
804 applicable national codes.
281
1. Funtions ......................................................................................84
2. Operation Details........................................................................85
3. Dimensions .................................................................................88
1. Function
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator piping
temperature reaches 25C.
High head height Drain pump A standard drain-head height of up to 700mm is possible.
2. Operation Details
(1) The function of main control
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C, fan operates
at low speed, when it becomes lower than 40C fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
24
ARNU12GVEA2
(unit : mm)
Signal receiver & Operation indicator Model W H D
900 1 200 ARNU09GVEA2 900 490 200
490
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
- 88 -
applicable national codes.
Air suction grill
<Ceiling Installation> 2 <Floor Installation>
587
273
(unit : mm)
650
- 89 -
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
(Ceiling Suspended type)
2
1. Function ......................................................................................91
2. Operation Details........................................................................92
3. Dimensions .................................................................................95
1. Function
Indoor Unit
Operation ON/OFF by Remote controller
Room temperature control Maintains the room temperature in accordance with the Setting Temperature.
Starting Current Control Indoor fan is delayed for 5 seconds at the starting.
Auto Restart Although the air-conditioner is turned off by a power failure, it is restarted auto-
matically previous operation mode after power supply.
Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during defrosting.
Hot start after defrost ends.
Hot-start Control (Heating) The indoor fan does not rotate until the evaporator piping
temperature reaches 25C.
High head height Drain pump A standard drain-head height of up to 700mm is possible.
2. Operation Details
(1) The function of main control
Soft-Dry Operation
The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
T Off
T On
Setting Temperature
(Thermal ON)
Minimum
1min 3min 1min
Thermal ON OFF ON
Outdoor fan ON OFF ON
Setting Setting C Setting
Indoor fan Off Low Low fan Low fan Low Off Off Low fan
spped spped spped
4way valve ON
Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C, fan operates
at low speed, when it becomes lower than 40C fan stops.
- B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
- C To be operated "Low" except initial Hotstart operation
Hot-Start Control
The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30C.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
1 min 1 min
Thermal ON
Outdoor fan ON
Indoor fan Setting fan Setting fan
Off Low speed Off Low speed
4way Valve ON
Initial Hotstart On state
Power Off On
Operation Off On
Cooling operation Heating operation
Defrost operation
(unit : mm)
635
ARNU07GCEA2
ARNU09GCEA2 1067 635 203
3. Dimensions
ARNU12GCEA2
ARNU15GCEA2
70
49
ARNU09GCEU2 978 639 190
148.3 148.3
<With Case> 2 ARNU12GCEU2
ARNU15GCEU2
(unit : mm)
Number Name Descripition
- 95 -
1 Air discharge grill
978 190
2 Air suction grill
794 13 161 14
20.4
Note
1. Unit should be installed in compliance with the installation manual
in the product box.
2. Unit shall be grounded in accordance with the local regulations or
639
applicable national codes.
62.8
<Without Case>
203
ARNU18GCFA2 ARNU18GCFU2
1
Dimensions
ARNU24GCFA2 ARNU24GCFU2
203
1345
635
Model W H D
ARNU18GCFA2
ARNU24GCFA2 1345 635 203
70
49.4
ARNU18GCFU2
148.3 1048.4 1256 639 190
- 96 -
1256 Note
1098 109.8 190
1072 30
21.4
161 14 1. Unit should be installed in compliance with the installation manual
in the product box.
81.4
2. Unit shall be grounded in accordance with the local regulations or
applicable national codes.
639
145
70
<Without Case>
Self-diagnosis function
Self-Diagnosis Function
Error Indicator
This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
If more than two troubles occur simultaneously, lower number of error code is first displayed.
After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
011 051 : No.105 error of master unit
Error
Error Type Error Point Main Reasons
No.
01 Indoor unit air sensor error 1. Indoor unit PCB wrong connection
02 Indoor unit pipe inlet sensor error Indoor unit sensor is 2. Indoor unit PCB failure
open/short
06 Indoor unit pipe outlet sensor error 3. Sensor problem (main reason)
Is sensor properly No
Connect properly to PCB
connected to PCB?
Yes
Yes
** In case the value is more than 100k (open) or less than 100 (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(5% margin) Normal
Air temp sensor: 10C = 20.7k : 25C= 10k : 50C= 3.4k
Pipe temp sensor: 10C = 10k : 25C= 5k : 50C= 1.8k
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
* If there is no remote controller to replace : Use another units remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause
Check any surrounded noise ( check the distance with main power cable)
make safe distance from the devices generate electromagnetic wave
*** After replacing indoor unit PCB, do Auto Addressing & input units address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
Error
Error Type Error Point Main Reasons
No.
No
Drain pump blocked by Check the drain head height
foreign particles? and slope***
float
(High position Open)
Condensate water
float
MAX 450
Error
Error Type Error Point Main Reasons
No.
Yes
Yes
Check if the
transmission cable is
properly connected No
Re connect transmission cable
to indoor / outdoor
terminal block?*
Outdoor PCB fault
Replace after checking
Yes
Indoor PCB fault
Replace after checking
* (Note1) Transmission from IDU is normal if voltage * If the DC voltage between transmission terminal A, B
fluctuation(-9V ~ +9V) exists when checking DC voltage of indoor unit is fluctuate within (-9V~+9V) then
of communication terminal between IDU and ODU transmission from outdoor unit is normal
Error
Error Type Error Point Main Reasons
No.
Indoor unit outlet pipe Indoor unit outlet pipe Refer to CH02
06 temperature sensor temperature sensor open
error or short
Error
Error Type Error Point Main Reasons
No.
Yes Yes
END
ON ON
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON ON
1 2 3 4 5 6 7 1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Error
Error Type Error Point Main Reasons
No.
- Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control
Error
Error Type Error Point Main Reasons
No.
Indoor unit BLDC fan motor Indoor BLDC fan motor 1. Motor connector connection fault
10 failure feedback signal is absent 2. Indoor PCB fault
(for 50 sec.) 3. Motor fault
Is connector No
connection proper? Connect properly
Yes
Is fan motor No
Replace indoor unit fan motor
normal?*
Yes
* It is normal when check hall sensor of indoor fan motor as shown below
** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the
address of central control
(Notice: The connection of motor connector to PCB should be done under no power
supplying to PCB)
Error
Error Type Error Point Main Reasons
No.
Indoor unit transmission error Indoor unit doesnt get sig- 1. Indoor 485 transmission PCB fault
11 nal from ODU for 3 minutes 2. After PCB replacing, auto addressing
continuously was not done
Yes Yes
END