You are on page 1of 4

Schenck make Belt Weigher calibration procedure with Intecont Plus

1) Speed Calibration
Take down the data from Technical Data Sheet
a) Diameter of tacho wheel, b) No of teethes on wheel,
Calculation of Imp/mtr

Imp/mtr = Rev/mtr X Imp/rev (No. of Teeths on wheel)

For, calculation of Rev/mtr = 1000 / (Dia of wheel x 22/7)


Diameter of wheel = 200 mm
= 1000 / (200 x 22/7) = 1000 / 628.57 = 1.59

Imp/mtr = 1.59 X 20 = 31.81

Calculated data enter in Parameter = B04


To enter this parameter go through following procedure-
1) Press Function Distributor Key

2) Press Up or Down Key till display shows Programming

3) Press Enter Key

4) Press Up or Down Key till display shows Enter Parameters

5) Press Enter Key

6) Display will shows Password


Enter password 07734 in numeric keys (Display will not show the entered data)

7) After giving password press Enter Key

8) Display will show Block A


Dialog Behavior (Display flashing with A)

9) Press Up Key till display shows Block B


Rated Data

10) Press Enter Key

1
11) Press Up or Down Key till display shows Charact. Val. Ns
B04 50.0 I/m
12) Press Prepare entry key

13) Enter the calculated data and press Enter Key

14) To come out normal display Press Abort key at any time.

For Speed Calibration follow steps.

Run the empty belt

Speed calibration follow steps given

1) Press Function Distributor Key

2) Press Up or Down Key till display shows Calibration Functions

3) Press Enter Key

4) Display will shows Password


Enter password 07734 in numeric keys (Display will not show the entered data)

5) After giving password press Enter Key

6) Press Up or Down Key till display shows LB: Imp/Belt Circuit

7) Press Enter Key

8) In run program display shows >. LB: 100 sec


11457 I/B

9) After program complete display shows >. v 0.0508 m/s


70932 I/B

10) After showing this display press enter key


The data will be automatically stored in parameter D06.

After completing speed program proceed for tare program.

2
2) Tare Calibration :-
There are two Tare calibration parameters,
i) Under Function Distributor without password (Normally this is used for operation
people). The name indicates >0: Zero Set
ii) Second under Calibration Function with password protected. The name indicates
TW: Tare
The difference between two Tare programs is as follows,
>0: Zero Set TW: Tare
a) Not required Password. a) Required password.
b) The result differences with Basic Tare b) The result is directly stored in
are store in D 05 Tare Correction T D04 Basic Tare and same data
and add to D03 Total Tare are stored in D03 Total Tare

Before Tare calibration ensure the following,


1) Clean mechanical equipment of weigher in weighing area.
2) Run the empty belt with Nominal Feed Rate set point in volumetric mode. (reference
parameter B02)

Tare calibration follow steps given

1) Press Function Distributor Key

2) Press Up or Down Key till display shows Calibration Functions

3) Press Enter Key

4) Display will shows Password


Enter password 07734 in numeric keys (Display will not show the entered data)

5) After giving password press Enter Key

9) Press Up or Down Key till display shows TW: Tare

10) Press Enter Key

11) In run program display shows >. TW: 90.02%


Tara 55.32%

9) After program complete display shows >. Dev 2.45%


Tara 53.20%

11) After showing this display press enter key


The data will be automatically stored in parameter D04.

After completing tare program proceed for span program.


3
3) Span Calibration:-

Hang known weight on the weigh cradle, enter this weight value in the parameter
C08.
To start Span Calibration follow the steps given.

1) Press Function Distributor Key

2) Press Up or Down Key till display shows Calibration Functions

3) Press Enter Key

4) Display will shows Password


Enter password 07734 in numeric keys (Display will not show the entered data)

5) After giving password press Enter Key

6) Press Up or Down Key till display shows CW: Check Weight

7) Press Enter Key

8) In run program display shows >. CW: 90.02%


Set/Act 55.32%

9) After program complete display shows >. CW 2.45%


Kor 53.20%

10) After showing display note down the value and enter in parameter D02