Professional Documents
Culture Documents
Eugeniusz Rosoowski
Protection and Control
of Distributed Energy Resources
Chapter 2
eugeniusz.rosolowski@pwr.edu.pl
2. Instrument Transformers 2. Relay protection of distribution networks
INSTRUMENT TRANSFORMERS
1. Voltage (Potential) Transformers (VTs, PTs) are much like small
power transformers, differing only in details of design.
2. Current Transformers (CTs) have their primary windings
connected in series with the power circuit.
2. Instrument Transformers 2. Relay protection of distribution networks
INSTRUMENT TRANSFORMERS
In both cases the transformer can be represented by the equivalent
circuit of below figure.
np V pN np I sN
= - for VT = - for CT
ns VsN ns I pN
2. Instrument Transformers 2. Relay protection of distribution networks
INSTRUMENT TRANSFORMERS
Main source of error: magnetizing current.
t2
VOLTAGE TRANSFORMERS
a) b)
VOLTAGE TRANSFORMERS
CURRENT TRANSFORMERS
CURRENT TRANSFORMERS
CT transient errors
Mechanizm of CT saturation
Magnetizing characteristic
2. Instrument Transformers 2. Relay protection of distribution networks
CT transient errors
CURRENT TRANSFORMERS
CURRENT TRANSFORMERS
CURRENT TRANSFORMERS
Rogowski coil
dI 1
E=H
dt
Vout =
RC E dt
Line Protection
Objects Technique
Phase fault protection Overcurrent Protection
Earth fault protection Directional Protection
Auto-Reclosing Negative-sequence Protection
Distribution Network Protection Unit Protection of Feeders
ungrounded system Distance Protection
resonant grounded system
high-resistance grounded system
effectively grounded
2. Line Protection 2. Relay protection of distribution networks
a
t=k b
+c t=k
R
k = 0.01K10.00 I I
b
1 1
I ref I ref
2. Line Protection 2. Relay protection of distribution networks
time
Tripping time characteristics -
example
a
t=k b
+c
I
1
I ref
k = 0.01K10.00
current
2. Line Protection 2. Relay protection of distribution networks
Ungrounded System
In ungrounded systems there are no intentionally applied
grounding. However, they are grounded by the natural capacitance
of the system to ground. They are frequently applied in industrial
supplying networks (e.g. in mine networks).
values,
causing high
V V
transient over-
voltages.
Cb Cb
S fa
3. Network earthing issues 2. Relay protection of distribution networks
Intermittent fault
3. Network earthing issues 2. Relay protection of distribution networks
Differential current:
id = is1 is 2
4. Line differential protection 2. Relay protection of distribution networks
I OP = | I s1 I s 2 | - operating current
I RT = | I s1 + I s 2 | - restraint current
I OP
= const - percentage diff. protection
I RT
4. Line differential protection 2. Relay protection of distribution networks
R
k=
L
IA IB IA IB
5. Distance protection 2. Relay protection of distribution networks
VA VA
Z FL = = = dZ '
1L
Z 0' L Z1' L I A k0 I0
I A + I0
Z1' L
5. Distance protection 2. Relay protection of distribution networks
Protection characteristics
a) Circle characteristic
b) MHO characteristic
c) Quadrilateral
characteristic
d) Lenticular
characteristic
5. Distance protection 2. Relay protection of distribution networks
Sources of errors
Distance elements should measure the positive-sequence
impedance of the line section between the relay and fault. A
number of the problems cause distance relay measuring errors, e.g.:
a) Fault resistance and infeed effect;
b) Switch-onto-fault;
c) Mutual coupling in parallel lines;
d) Load and system unbalance;
e) Power swing due to electromechanical oscillations
(in transmission lines);
f) Current transformer saturation;
g) CVT transients (in EHV lines);
h) Intercircuit faults;
i)
6. Autoreclosing 2. Relay protection of distribution networks
Automatic reclosing
Automatic reclosing (autoreclosing) is a control scheme for quickly
reclosing breaker after clearing a temporary fault in order to restore
the system to normal state as quickly as possible.
It is considered here that the fault is temporary and, once reclosed,
the system will be restored to its normal condition. Adequate
outage time must be allowed for the fault path to deionize if the
scheme is to succeed.
6. Autoreclosing 2. Relay protection of distribution networks
Automatic reclosing
Autoreclosing
Reclosing to a permanent fault is called an unsuccessful reclosing.
Important lines, especially tie lines that connect important
generating stations, often require autoreclosing in order to maintain
system stability for a given desired operating condition.
Autoreclosing at distribution networks is useful in order to limit the
outage time of the consumers.
If reclosing is used in the network with distributed generation it may
have to be dalayed to give the small generating units time to switch
off prior to reclosing.
Autoreclosing scheme should detect a fault type to introduce
reclosing only faulty phases.
6. Autoreclosing 2. Relay protection of distribution networks
Transient fault
6. Autoreclosing 2. Relay protection of distribution networks
Autoreclosing cycles
successful reclosing
Single-shot Reclosing
cycle
unsuccessful reclosing
7. Transformer Protection 2. Relay protection of distribution networks
Transformer Protection
Transformer Protection
Introduction
Transformer failures are expensive and also may be dengerous for
personnel. The cost of energy not delivered because of transformer
unavailability and additional costs may be very high.
Transformer protection scheme should disconnect the transformer
before extensive damage occurs in the transformer and the system.
Main transformer abnormal conditions are as follows:
internal faults (interturn, phase-to-phase, phase-to-ground),
overload,
overexcitation causing saturation the transformer core,
sudden gas pressure,
tap changer failures (if a tap changing mechanism is installed)
and others.
7. Transformer Protection 2. Relay protection of distribution networks
I OP = | I s1 I s 2 | | IW 1 IW 2 | - operating current
I RT = | I s1 + I s 2 | | IW 1 + IW 2 | - restraint current
- operating current
(t ) = vm (t )dt + (0)
Harmonic restraint:
Blocking if:
with: k2 0.2
7. Transformer Protection 2. Relay protection of distribution networks
Differential protection
Buchholz protection
conservator
tank
Introduction
Introduction
Generator circuits
8. Generator Protection 2. Relay protection of distribution networks
Introduction
Differential Protection
scheme for split-phase
windings type of
generator:
two sets of differential
relays in each phase.
8. Generator Protection 2. Relay protection of distribution networks
N B
87Q
1
(
I 1 = I A + aI B + a2I C
3
)
1
(
I 2 = I A + a 2 I B + aI C
3
)
a = e j 2 / 3
I OP = I 1 + I 2 + L + I n I RT = k ( I 1 + I 2 + L + I n )
k scaling factor
Special problem with fault at F1 incorrectly opening of the section
9. Bus Protection 2. Relay protection of distribution networks
a) Current transformers
mounted on both sides of
breaker - no unprotected
region.
b) Current transformers
mounted on circuit side
only of breaker - fault
shown not cleared by
circuit protection.
9. Bus Protection 2. Relay protection of distribution networks
Protected zones
Protected zones
Protected zones
10. Breaker Failure Protection 2. Relay protection of distribution networks
A breaker will be considered to have failed if, after the trip signal has
been generated, the breaker has:
not started opening within a preset time frame (determined by
switches internal to the breaker),
the breaker has not fully opened within a preset time frame
(determined by switches internal to the breaker), or
if the current has not been broken by the breaker within a preset
time (determined by current measurement devices).
10. Breaker Failure Protection 2. Relay protection of distribution networks
TB open, fault at F
11. Motor Bus Transfer 2. Relay protection of distribution networks