You are on page 1of 44

User Guide and Instruction Manual

PS-SP Series 3:1, 1030 kVA


INPUT:
3X220 VAC
OUTPUT: 220 VAC, 192 VDC
WITH BYPASS ISOLATION TRANSFORMER (OPTION)

Release 1.1, January 2009

Har Hotzvim Industrial Park


14 Hartom St., PO Box 45029, Jerusalem 91450, Israel
Tel: +972-2-588-8222 Fax: +972-2-582-8875
Email: info@gamatronic.co.il Website: www.gamatronic.com
Gamatronic Electronic Industries Ltd.
Har Hotzvim Industrial Park
14 Hartom St., PO Box 45029, Jerusalem 91450 Israel
Tel: +972-2-588-8222 Fax: +972-2-582-8875
Email: info@gamatronic.co.il Website: www.gamatronic.com

The equipment described in this document is not intended for use in connection
with any application requiring fail-safe performance, unless the application
design includes appropriate redundancy. This exclusion includes the operation
of nuclear power facilities, air traffic control or navigation systems, weapons
control systems, life-support systems, or any other system whose failure could
lead to injury, death, environmental damage or mass destruction.

Copyright 2009 by Gamatronic Electronic Industries Ltd. All rights reserved worldwide.
The information contained in this document is proprietary and is subject to all relevant copyright, patent and other laws
protecting intellectual property, as well as any specific agreement protecting Gamatronic Electronic Industries Ltd.
rights in the aforesaid information. Neither this document nor the information contained herein may be published,
reproduced or disclosed to third parties, in whole or in part, without the express, prior, written permission of
Gamatronic Electronic Industries Ltd. In addition, any use of this document or the information contained herein for any
purposes other than those for which it was disclosed is strictly forbidden.
Gamatronic Electronic Industries Ltd. reserves the right, without prior notice or liability, to make changes in equipment
design or specifications.
Information supplied by Gamatronic Electronic Industries Ltd. is believed to be accurate and reliable. However, no
responsibility is assumed by Gamatronic Electronic Industries Ltd. for the use thereof nor for the rights of third parties
which may be affected in any way by the use thereof.
Any representation(s) in this document concerning performance of Gamatronic Electronic Industries Ltd. product(s) are
for informational purposes only and are not warranties of future performance, either express or implied. Gamatronic
Electronic Industries Ltd. standard limited warranty, stated in its sales contract or order confirmation form, is the only
warranty offered by Gamatronic Electronic Industries Ltd. in relation thereto.
This document may contain flaws, omissions or typesetting errors; no warranty is granted nor liability assumed in
relation thereto unless specifically undertaken in Gamatronic Electronic Industries Ltd. sales contract or order
confirmation. Information contained herein is periodically updated and changes will be incorporated into subsequent
editions. If you have encountered an error, please notify Gamatronic Electronic Industries Ltd. All specifications are
subject to change without prior notice.

ii PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.

TABLE OF CONTENTS
1. SAFETY PRECAUTIONS ...................................................................................... 1
1.1 Dos .............................................................................................................. 1
1.2 Donts........................................................................................................... 1
2. GENERAL FEATURES ......................................................................................... 2
2.1 Major Subsystems ...................................................................................... 3
2.1.1 Rectifier/Charger................................................................................. 3
2.1.2 Batteries............................................................................................... 3
2.1.3 Inverter................................................................................................. 3
2.1.4 Static Switch........................................................................................ 3
2.1.5 Control System ................................................................................... 3
2.2 Control Panel .............................................................................................. 4
2.3 Power On Self Tests ................................................................................... 5
2.4 Measurement............................................................................................... 5
2.5 Real-Time..................................................................................................... 6
2.6 Communications......................................................................................... 6
2.7 Event Logs .................................................................................................. 6
2.8 Ease of Use ................................................................................................. 6
2.9 Battery Check.............................................................................................. 6
2.10 Service Mode............................................................................................... 6
2.11 Connections ................................................................................................ 6
2.12 Parallel Operation (Option) ........................................................................ 7
2.12.1 Centralized vs. Decentralized Static Switch..................................... 7
3. CONTROL PANEL & INDICATORS ..................................................................... 9
3.1 Function buttons on the smaller cabinets ............................................. 11
3.2 Information Buttons ................................................................................. 11
3.3 The Control Panel on the Larger Cabinet ............................................... 15
3.3.1 Function Buttons on the Larger Cabinet ........................................ 15
3.3.2 Information Buttons on the Larger Cabinet ................................... 16
3.4 The LOG, SET, and HELP Buttons for All Models ................................. 20
3.4.1 System Fault Diagnostics ................................................................ 23
3.5 LED Indicators .......................................................................................... 25
3.6 Terminal Connections .............................................................................. 26
4. OPERATING THE PS SERIES UPS ................................................................. 27
4.1 Turning the UPS ON ................................................................................. 27
4.2 Turning the UPS OFF ............................................................................... 27
4.3 Activating MAINTENANCE BYPASS (Optional) ..................................... 28
4.4 Deactivating MAINTENANCE BYPASS (Optional) ................................. 28
4.5 Setting the Real-Time Clock .................................................................... 29
4.6 RS232 Interface......................................................................................... 29
4.7 The Alarm Interface .................................................................................. 30
4.8 Remote Monitor Box (Optional)............................................................... 32
4.8.1 Connecting the Monitor Box to the UPS MS/MP ............................ 32
5. TROUBLESHOOTING......................................................................................... 33
6. SITE PREPARATION .......................................................................................... 36
6.1 Site Preparation and Considerations...................................................... 36
6.2 Accessibility.............................................................................................. 36
6.3 Circuit Breakers ........................................................................................ 36

PS 3:1, 1030 kVA, 220 Vac out iii


Gamatronic Electronic Industries Ltd.

7. INSTALLATION ...................................................................................................37
7.1 Installation Procedure...............................................................................37
8. TECHNICAL SPECIFICATIONS ..........................................................................39
PS 3:1...........................................................................................................39

LIST OF FIGURES
Figure 1: UPS Operational Schematic ...................................................................................2
Figure 2: Control panel on smaller units (PC074).................................................................4
Figure 3: Control panel on medium-sized units (PC075) .....................................................4
Figure 4: Control panel on the larger units (PC085).............................................................5
Figure 5: Special parallel communication cable...................................................................7
Figure 6: Cabling for centralized ST.SW. configuration ......................................................8
Figure 7: Cabling for decentralized ST.SW. configuration ..................................................8
Figure 8: PC074 console .........................................................................................................9
Figure 9: PC075 console .........................................................................................................9
Figure 10: PC085 console .....................................................................................................10
Figure 11: Control panel on the larger cabinet ...................................................................15
Figure 12: LOG Messages Structure....................................................................................20
Figure 13: Active Current Sharing........................................................................................24
Figure 14: Voltage Correction...............................................................................................24
Figure 15: LED indicators on the PC074 and PC075 cabinets ..........................................25
Figure 16: LED indicators on the PC085 cabinet ................................................................25
Figure 17: Terminal connections on the stand-alone model.............................................26
Figure 18: Local-direct connection for monitoring and control........................................29
Figure 19: RS232 Connector Pin Assignment.....................................................................30
Figure 20: Troubleshooting flowchart .................................................................................34
Figure 21: PC Board Check Points & Voltage Ranges.......................................................35

LIST OF FIGURES
Table 1: Log Variables ...........................................................................................................21
Table 2: LED indicators and their meaning .........................................................................25
Table 3: Minimum recommended wire grades (cross-sectional area) .............................37

STANDARDS AND CONVENTIONS


This manual contains diagrams which include images of the LCD display screen of the
UPS. Unless otherwise indicated, the readings shown in the screen images are
representational only, and are not intended to match the readings on a specific
system in a particular environment.

iv PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.

1. SAFETY PRECAUTIONS

1.1 Dos
Read this manual carefully before operating the UPS.
Review the safety precautions described below to avoid damaging users or
equipment.
Install the UPS in a clean and well-ventilated location.
Leave at least 20 cm of clearance space between the ventilation holes of the
UPS and other objects or walls.
The UPS must be well grounded to the buildings grounding system with a
conductor that has a current carrying capacity that matches the rating of the
UPS.
If the unit contains an external battery cabinet, periodically check the grounding
connection between the external cabinet and the main UPS cabinet. (The
batterys cabinet body must be connected with the grounding screw located on
the rear panel of the electronic cabinet.)
Use the UPS only for its intended purpose.
Allow only qualified technicians to service the UPS. There are no user-
serviceable components. Do not try to repair it yourself!

WARNING
Appropriate precautions should be taken during inspection and servicing as
there is a risk of lethal electric shock. (The battery cabinet contains a series of
12-Volt batteries that provide high voltage and energy in the UPS body even
when the UPS is not connected to the electricity mains.)

1.2 Donts
Do not open the cover under any circumstances.
Do not insert any objects through the ventilation holes.
Do not put objects on the UPS.
Do not move the UPS while it is operating.
Do not turn the UPS upside down during transportation.
Do not connect or disconnect the cable to the battery cabinet before the battery
circuit breaker is turned off.
Do not turn on the battery circuit breaker when the battery cabinet is
disconnected from the UPS.

WARNING
Do not touch the battery terminals of external batteries with bare hands.

PS 3:1, 1030 kVA, 220 Vac out Safety Precautions 1


Gamatronic Electronic Industries Ltd.

2. GENERAL FEATURES
The PS Series 3:1 Phase, Uninterruptible Power Supply (UPS) employs Pulse Width
Modulation (PWM) and is controlled by a 16-bit micro-controller, to provide reliable,
sophisticated protection for every type of line fluctuation, including interruption of the
mains (electrical) supply.

Figure 1: UPS Operational Schematic

In case of a power failure, the UPS provides backup power for a specific period of time.

The unit is oriented to operate like module in parallel with similar Gamatronic UPS
systems. The load is shared between the units. The parallel system is the most reliable
energy source for any critical load. If the system uses N+1 UPS units (the redundant
parallel system), the output voltage is not interrupted even if one of the units is faulty. If
the parallel system is equipped with additional Gamatronic Static Switch unit, the output
voltage is not interrupted even if more than one UPS is faulty.

The Gamatronic parallel UPS system contains the following features:

Each UPS is equipped with its own battery set


Up to 10 units can be connected in parallel

The system is user-friendly. Its operation is simple and requires no previous technical
knowledge. The UPS operates on-line and once activated, the unit provides voltage of
220 V at a stabilized 60 Hz frequency to any practical load.

When backup service is provided (on main line power breakdown), the UPS is powered
by batteries and maintains a constant output voltage supply. The system informs the
operator by means of LED indicators and audible signals of the occurrence of a power
failure.

2 General Features PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.
An LCD display on the UPS front panel provides real-time, current operational status
providing the user with complete information regarding the operational status of the
UPS.

Using an RS232 communications port, similar status information may be viewed on a


computer monitor. Additionally, the system may be connected to a remote location via
a modem and a telephone line.

The unit consists of two major subsystems:

Electronic Cabinet, including all electronic devices: charger, inverter, static


switch, microprocessor board, panel, etc.
Battery Cabinets, including batteries and circuit breaker.

2.1 Major Subsystems


The device consists of the following modules:

2.1.1 Rectifier/Charger
The Rectifier/charger supplies stabilized DC voltage to the device at 216 2V

2.1.2 Batteries
The batteries are connected to the charger output and supply voltage during power
failures. The batteries are housed in the battery cabinets. The UPS include n internal
2-pole Battery circuit breaker as shown in figure 1.

2.1.3 Inverter
The inverter receives a DC voltage from the charger or batteries and supplies a
regulated, frequency-stabilized, AC voltage (power). The inverter incorporates an IGBT
transistorized bridge; driver, (PC968 board), an L-C filter circuit, isolated output
transformer circuit, current transformer, PC906 board, and a PC801 control board.

2.1.4 Static Switch


In case the inverter can't supply the load with the correct voltage (i.e. because of
overload, inrush current on connecting the load, inverter malfunction, etc.), the
ST.SW/Bypass automatically transfers the load from the inverter to the mains without
voltage interruption or disturbance. When the UPS is in BYPASS mode, the load draws
power directly from the mains, bypassing the inverter. The ST.SW automatically
switches the load back to the inverter when inverter's output voltage returns to normal.

The inverter is synchronized with the mains in both frequency and phase to ensure
correct operation of the static switch. The static switch includes PC690/PC920 boards
and RA101 - RA103 contactors.

2.1.5 Control System


The control system performs the following functions:

a. Tests input, bypass, inverter, battery voltage, output current, input/output


signal frequency, and temperature.
b. Controls the inverter and the bypass contactorRA101and manages
the static switch and charger voltage during battery tests.
PS 3:1, 1030 kVA, 220 Vac out General Features 3
Gamatronic Electronic Industries Ltd.
c. Controls the ALARM interface.
d. Reads the panel keyboard and sends messages to the front panel LCD
display.
e. Communicates with devices via the RS232 interface.
The control system includes the PC801 control board, PC075 panel board, PC873
power supply, current, and temperature sensors. Measured voltages and currents are
connected to the control board via the PC800 interface board.

2.2 Control Panel


The UPS is equipped with an LCD-display and touch pad control panel that enables the
user to effectively manage the UPS. Once the UPS is installed, the control panel
serves as the users primary interface with the system. Messages, warnings and error
conditions are relayed to the user through the control panels LCD display and through
audible alarms.

Figure 2: Control panel on smaller units (PC074)

Figure 3: Control panel on medium-sized units (PC075)

4 General Features PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.

Figure 4: Control panel on the larger units (PC085)

2.3 Power On Self Tests


The UPS automatically performs a series of diagnostic tests when initially powered on.

2.4 Measurement
The user can receive real-time information regarding the units operation and condition
simply by pressing the appropriate status buttonthe real-time results are displayed on
the front LCD panel. A sample display follows.

PS 3:1, 1030 kVA, 220 Vac out General Features 5


Gamatronic Electronic Industries Ltd.

2.5 Real-Time
The system includes a real-time clock and calendar that sequentially manage the log
file and provides the user with historical data. This information is accessible via the
LCD display or, optionally, through the RS-232 communications port.

2.6 Communications
The UPS relays all the measured data and events of the log file through an RS232
communications port to a host computer or, using a modem connected to a telephone
line, to a remote location, or via GMAC or GMACi, proprietary SNMP agents, for
network access.

2.7 Event Logs


The system compiles a listing of up to 256 extraordinary events of the mains, unit and
load during operation. This data is written to the log file and can be accessed easily at
any time through the display panel or computer (optional). This information is very
useful for maintenance and analyzing performance statistics.

2.8 Ease of Use


The UPS includes an on-line help feature that explains the systems features and
describes each of the LCD control buttons and indicators.

2.9 Battery Check


The unit automatically and continuously checks the battery cabinet connection with the
UPS.

2.10 Service Mode


The UPS has a technicians SERVICE MODE that is password protected. Access to
the service mode is only permitted after the technician successfully enters an assigned
password.

2.11 Connections
All connectionsconnection panel, input, output, and ST. SW are accessed via the
rear panel of the UPS.

6 General Features PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.

2.12 Parallel Operation (Option)


Each UPS can optionally operate in parallel with similar units as part of a modular UPS
system. Up to 10 units can be connected in parallel.

Special technical solutions are used to synchronize all the units of the system, to
prevent circulation of energy between the UPS units and to isolate the faulty unit from
the common power bus. In addition, an active current sharing circuit changes the
output voltage of each UPS to provide proportional load sharing between the units.

One of the system's units takes on the function of Master. This unit is synchronized to
the mains power. The other units are Slaves and follow the Master. The function of
Master is not dedicated to one of the units. Any normally functioning UPS can be the
Master.

2.12.1 Centralized vs. Decentralized Static Switch


The UPS employs a Static Switch for functional over-ride. In parallel mode there are 2
possible options of Static Switch operation, centralized and decentralized.

In decentralized mode each UPS includes its own Static Switch which works
independently. However, if one UPS were to fail, the Static Switch would instantly be
triggered and supply the load directly from the mains. This would connect the inverter
of the other UPS directly to the mains which could potentially damage the other UPS.
Therefore, as illustrated below, (Figure 7A) to avoid such a hazard in decentralized
mode, the Static Switches are synchronized using a 3-wire cable.

For additional security, a second option is available as a centralized Static Switch. As


illustrated below, (Figure 7C) there is only one Static Switch (in a separate housing) for
the entire system. This method goes a long way in increasing system reliability,
because the output voltage is constant even if both UPSs are disconnected.

Figure 5: Special parallel communication cable

PS 3:1, 1030 kVA, 220 Vac out General Features 7


Gamatronic Electronic Industries Ltd.

Figure 6: Cabling for centralized ST.SW. configuration

Figure 7: Cabling for decentralized ST.SW. configuration

8 General Features PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.

3. CONTROL PANEL & INDICATORS


The control panel serves as an interface between the UPS and the user. Real-time
information is displayed visually and audibly. Textual information is presented through
the LCD display. Messages notifying of alarm conditions are reinforced with an audible
alarm to alert the user of extraordinary circumstances.

The LCD control panel includes function buttons for controlling the unit and
informational buttons for reporting the status of the UPS.

The console model will be either PC074 (Figure 8), PC075 (Figure 9), or PC085 (. The
two consoles have the same functionality; the placement of their buttons and LEDs is
slightly different.

In some of the diagrams throughout this user manual only one of the console models is
shown, for simplicitys sake.

The control panels of the smaller and medium cabinets (PC074 and PC075) are very
similar to each other. The control panel of the larger cabinet (PC085) is rather different
in arrangement. Because of this, the PC074 and PC075 panels are explained together
in section XXXX, and the PC075 panel is described separately in section XXX.

Figure 8: PC074 console

Figure 9: PC075 console


PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 9
Gamatronic Electronic Industries Ltd.

Figure 10: PC085 console

10 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

3.1 Function buttons on the smaller cabinets


BUTTON DESCRIPTION

UPS OFF
Pressing the UPS OFF button turns off the UPS. Confirmation of this action is
required. Wait 2 seconds, and confirm it by pressing UPS OFF again.

UPS ON
Pressing the UPS ON button turns on the UPS and sequentially displays the results
of the start-up diagnostic tests

ALARM OFF
Pressing the ALARM OFF button silences the alarm that sounds when there is a
system fault. If another fault occurs, the alarm returns to active mode.
Note: The ALARM LED remains lit until the problem is resolved to notify users
about the continued existence of a system fault.
BATTERY TEST
Pressing the BATTERY TEST button manually initiates a battery test. The unit also
continuously checks the battery cabinet connection with the UPS. Battery checks
are automatically performed at the following times:
Upon start-up
Every 200 hours of accumulated operating time
After battery cabinet reconnection (following a disconnection)
INV
Pressing the INV button connects the inverter to the output, manually taking the
UPS out of BYPASS mode.
Note: There is no display associated with this action.

B/P
Pressing the B/P button connects the mains to the output, putting the unit into
BYPASS mode. The unit requires confirmation of this action. Wait approximately 2
seconds, and confirm the selection by pressing the B/P button a second time.

3.2 Information Buttons


The UPS continually monitors its operational status. The user can display real-time
information about this status by pressing the appropriate information button. If an alarm
is triggered, the information buttons (except for LOG and ?) display information for
approximately 10 seconds, after which the LCD display reverts to the default STATUS
display.

The UPS maintains an event history in its log. The log can be accessed by pressing the
LOG button or, alternatively, by a computer through the optional RS232 connection or
at a remote location via modem communications.

Where appropriate, the LCD display provides information per R, S, and T phase and for
both voltage and current.

Sample LCD displays are presented below.

PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 11
Gamatronic Electronic Industries Ltd.
IN (Input)
Press the IN button to display the
units input voltage.

NOTE: Input current current display is


available as an option.

B/P (Bypass)
Press the B/P button to display the
units bypass voltage and current.

INV (Inverter)
Press the INV button to display the
unit's inverter voltage and current.

12 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.
OUT (Output)
Press the OUT button to display the
units output voltage and current.

FREQ (Frequency)
Press the FREQ button to display the
units output and bypass frequency.

The operating inverter frequency is determined by the bypass frequency when operating
normally. Otherwise, the inverter frequency is determined by the quartz oscillator and
should be set at 50/60 Hz.

BATT (Battery)
Press the BATT button
to display the battery voltage.

Note: Battery current display is also


available as an option

PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 13
Gamatronic Electronic Industries Ltd.
TIME
Press the TIME button to display the
units current day/month (DD/MM), and
current time (HH:MM:SS).

STAT (Status)
Press the STAT button to display the
units status and accumulated working
time (HHHHH:MM:SS).

For status and fault analysis, see

System Fault Diagnostics on page 23.

Note: This is the UPSs default display.


TEMP (Temperature)
Press the TEMP button to display the
status of the unit's heatsink
temperature.

14 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

3.3 The Control Panel on the Larger Cabinet


The control panel has 6 function buttons for controlling the unit and 12 information
buttons for reporting the status of the UPS.

Figure 11: Control panel on the larger cabinet

3.3.1 Function Buttons on the Larger Cabinet


BUTTON DESCRIPTION
UPS ON/OFF
When the UPS is OFF, pressing the UPS ON/OFF button turns on the UPS and
sequentially displays the results of the start-up diagnostic tests
When the UPS is ON, pressing the UPS ON/OFF button turns off the UPS.
Confirmation of this action is required. Wait 2 seconds, and confirm it by pressing
UPS OFF again.
BATTERY TEST
BATT Pressing the BATTERY TEST button manually initiates a battery test. The unit also
TEST continuously checks the battery cabinet connection with the UPS. Battery checks
are automatically performed at the following times:
Upon start-up
Every 200 hours of accumulated operating time
After battery cabinet reconnection (following a disconnection)

PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 15
Gamatronic Electronic Industries Ltd.
B/P INV
B/P When the UPS is in Inverter mode, pressing the B/P INV button connects the
INV mains to the output, putting the unit into Bypass mode. The unit requires
confirmation of this action. Wait approximately 2 seconds, and confirm the selection
by pressing the B/P INVbutton a second time.
When the UPS is in Bypass mode, pressing the B/P INV button connects the
inverter to the output, manually taking the UPS out of Bypass mode.
Note: There is no display associated with this action.
ALARM OFF
Pressing the ALARM OFF button silences the alarm that sounds when there is a
system fault. If another fault occurs, the alarm returns to active mode.
Note: The ALARM LED remains lit until the problem is resolved to notify users
about the continued existence of a system fault.

3.3.2 Information Buttons on the Larger Cabinet


The UPS continually monitors its operational status. The user can display real-time
information about this status by pressing the appropriate information button. If an alarm
is triggered, the information buttons (except for LOG and ?) display information for
approximately 10 seconds, after which the LCD display reverts to the default STATUS
display.

The UPS maintains an event history in its log. The log can be accessed by pressing the
LOG button or, alternatively, by a computer using the optional RS232 connection, or
from a remote location via a modem.

Where appropriate, the LCD display provides information for the R, S, and T phases
and for voltage and current.

Sample LCD displays are presented below.

IN (Input)
Press the IN button to display
the units Input Voltage.

NOTE: Input current current


display is available as an
option.

16 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.
B/P (Bypass)
Press the B/P button to display
the units bypass voltage and
current.

INV (Inverter)
Press the INV button to display
the unit's Inverter Voltage and
Current.

OUT (Output)
Press the OUT button to display
the units Output Voltage and
Current.

PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 17
Gamatronic Electronic Industries Ltd.
FREQ (Frequency)
Press the FREQ button to
display the units Bypass and
Inverter Frequency.

The operating inverter frequency is determined by the bypass frequency when operating
normally. Otherwise, the inverter frequency is determined by the quartz oscillator and should
be set at 50/60 Hz.

BATT (Battery)
Press the BATT button
to display the battery voltage.

Note: Battery current display is


also available as an option

TIME
Press the TIME button to
display the units current
day/month (DD/MM), and
current time (HH:MM:SS).

To set the proper time or date


use the SET button, described
on page 21.

18 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.
STAT (Status)
Press the STAT button to
display the units status and
accumulated working time
(HHHHH:MM:SS).

For status and fault analysis,


see System Fault Diagnostics
on page 23.

Note: This is the default display.


TEMP (Temperature)
Press the TEMP button to
display the status of the unit's
thermosensors.

PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 19
Gamatronic Electronic Industries Ltd.

3.4 The LOG, SET, and HELP Buttons for All Models
LOG
Pressing the LOG button displays the units event log, which contains information about
the last extraordinary events of the mains, unit and load that occurred while the unit was
operating.

The log contains the 256 most recent events, each of which can be perused using the up
arrow

Each log occupies 2 windows. The first window to appear is the first part of the most
recent fault. Press the down arrow to view the second window of the event.

To view the 1st window of a previous event, press the up arrow ; pressing the up
arrow once again will show the 1st window of the event previous to that. The down arrow
will show the second window. See the cycle in Figure 12 below.

Figure 12: LOG Messages Structure

To view the contents of the log:


Press the LOG button to enter LOG
mode.
Press the arrow buttons to scroll
through the information recorded in
the log.

20 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

Each log entry occupies two pages (two "screenfuls"); use the up and down arrow keys
to navigate the pages of the log file.

The first screen provides a description of the event with date and time. The
second screen shows the log number, variable values and fault results. The log
variables include typical UPS parameters for the event, listed in Table 1.

Table 1: Log Variables

Event LOG Variable


Overload Sum of currents in all phases
Inverter fault Vinv (average inverter voltage) in all phases
Bypass fault Vbyp (average bypass voltage) in all phases where
there is a bypass voltage fault
or
Hz (Frequency) where there is a bypass frequency
fault
Input fault Average Vin on all phases
High temperature Temperature C
Rectifier fault, battery low DC voltage
Other fault Average Vout for all phases

Faults are represented as a hexadecimal word comprising 16 bits:

Bit 0: 1 = Overload
Bit 1: Inverter
Bit 2: Bypass
Bit 3: Rectifier
Bit 4: Input
Bit 5: Phase sequence
Bit 6: Temperature
Bit 7: Battery test failure
Bit 8: Output
Bit 9: Load on bypass
Bit 10: Circulation (for parallel)
Bit 11: Slave receive failure (parallel only)

For example, fault 0009H = 0000000000001001 binary which translates as overload and
battery test failure.

SET (Time Mode)


Pressing this button sets the units real-time clock (see section 4.5 on page 29).

"?" (Help Button)

Pressing this button provides on-line configuration data for display purposes.
Note: Configuration can be modified in service mode only
Use the UP and DOWN arrows to scroll through the information.

PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 21
Gamatronic Electronic Industries Ltd.
The following messages are presented:

Model type: True on-line UPS, model name etc.)


Serial number
Nominal power
Number of phases in and out
Nominal input and output voltage between phase and neutral
Voltage range of input and bypass
Nominal output current per phase
Nominal output frequency
Frequency tracking range when the inverter is synchronized to the
bypass
Number of batteries connected in series
Nominal capacity of each battery (for use in calculating backup duration
where the battery current meter option is installed)
DC shutdown voltage in battery discharge mode
Bypass: YES for option with bypass, NO for option without bypass
Rectifier: YES for UPS, NO for DC/AC inverter
Distance shutdown: YES if EPO and shutdown via interface alarm and
RS232 are supported, NO if shutdown is inhibited
Par. Operation: YES for parallel UPS, NO for stand-alone UPS
Load LED bar: Triple for panel with 3 LED bars, Single for one integral
bar
Input current meter: YES for specified option, NO as standard
Battery current meter: YES for specified option, NO as standard
Date of manufacture: Format DD/MM/YY
Date of last battery installation: Format DD/MM/YY
Software version number
To quit the help, press the ? button once again.

22 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

3.4.1 System Fault Diagnostics


Select the STAT button and press the down arrow . The display will show 2 bytes
representing the FAULT (see LOG on page 20) followed by two bytes (each of 8 bits)
are now on display, each representing the STATE and the INSTRUCTION.

To use the hexadecimal indicators, make a note of the bit representations.

The STATE byte indications are as follows:

Bit 0: UPS power 1 = ON, 0 = OFF


Bit 1: Load supply 1 = On bypass, 0 = On inverter
Bit 3: Audible alarm 1 = Disabled, 0 = Enabled
Bit 4: Load transfer 1 = In progress, 0 = Pending
Bit 5: Battery check 1 = In progress, 0 = Pending

The INSTRUCTION byte indications are as follows:

Bit 0: UPS power 1 = ON, 0 = OFF


Bit 1: Load supply 1 = On bypass, 0 = On inverter
Bit 5: Battery check 1 = In progress, 0 = Pending

To view fault condition details, press the down arrow , and 9 bytes are displayed on
the panel:
Byte 1 shows input diagnostics. Indications are as follows:

Bit 0: 1 = Fault is in phase R


Bit 1: 1 = Fault is in phase S
Bit 3: 1 = Fault is in phase T
Bit 7: 1 = Fault exists

Byte 2 shows the result of bypass symptoms analysis.

Byte 3 shows result of inverter symptoms analysis.

Byte 4 shows output voltage diagnostics. Indications are as per byte 1.

Byte 5 shows DC voltage diagnostics. Indications are as follows:

Bit 0: 1 = Battery is currently discharging


Bit 1: 1 = Battery is discharged
Bit 2: 1 = Battery is disconnected
Bit 3: 1 = Battery check failed
Bit 4: 1 = Excessive current difference in battery sets. (Option)
Bit 6: 1 = Rectifier failure
Bit 7: 1 = Fault exists

Byte 6 shows measured temperature diagnostics. Indications are as follows:

Bit 0: 1 = Shutdown limit exceeded


Bit 1: 1 = Alarm limit exceeded
Bit 2: 1 = Fault detected by bi-metal temperature sensor
Bit 7: 1 = Fault exists

Byte 7 shows bypass frequency diagnostics:

Bit 0: 1 = Bypass frequency incorrect

Byte 8 shows over-current diagnostics. Indications are as follows:

PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 23
Gamatronic Electronic Industries Ltd.
Bit 0: 1 = Over-current detected in phase R
Bit 1: 1 = Over-current detected in phase S
Bit 2: 1 = Over-current detected in phase T
Bit 7: 1 = Fault exists

Byte 9 shows load transferring diagnostics. Indications are as follows:

Bit 0: 1 = Transferring started


Bit 1: 1 = Inverter is OFF
Bit 2: 1 = Inverter restarting
Bit 3: 1 = Inverter under diagnosis
Bit 4: 1 = Switching to inverter SRSW SCR is ON
Bit 5: 1 = Switching to inverter SRSW SCR is OFF
Bit 6: 1 = System in wait state

To view the active current sharing status, press the down arrow .

Iact IaR IaS IaT

Iavr IavR IavS IavT

Figure 13: Active Current Sharing

I and Ia in the results of active average current measurements on phases R, S and T


using a half-scale offset. Zero current is presented as 128. With positive current this
value increases, with negative current, this value decreases.

To view the register used for inverter voltage correction, press the down arrow .

CORR RR RS RT

Figure 14: Voltage Correction

24 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

3.5 LED Indicators


LED Indicators provide information regarding the status or operation at a glance of the
UPS. They are color coded so that the user can easily and quickly identify areas for
concernRed indicates a fault or abnormal status (usually associated with an audible
alarm),

Figure 15: LED indicators on the PC074 and PC075 cabinets

Figure 16: LED indicators on the PC085 cabinet

Table 2: LED indicators and their meaning

DEFAULT
INDICATOR INDICATION WHEN ON
STATUS
BYPASS Bypass input voltage is normal. Green
B/P Load connected to bypass. Red
OVERLOAD The UPS is overloaded. Red
BATTERY TEST Battery not normal. Red
SYNC Inverter is synchronized with bypass. Green
Rectifier/charger is operating
CHARGER Green
normally.
INVERTER Inverter is operating normally. Green
INV. Load is on the inverter. Green
LOAD LEVEL Load level. Green
LOAD LEVEL Overload condition (load > 100 %). Red

PS 3:1, 1030 kVA, 220 Vac out Control Panel & Indicators 25
Gamatronic Electronic Industries Ltd.

3.6 Terminal Connections

Figure 17: Terminal connections on the stand-alone model

26 Control Panel & Indicators PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

4. OPERATING THE PS SERIES UPS


4.1 Turning the UPS ON
To turn the UPS on:

Turn ON the CHARGER and ST. SW circuit breakers.

WAIT 1 minute and then turn ON the BATTERY circuit


breaker.

The UPS performs a self-test (that takes approximately


one minute). Verify that the UPS OFF message is "UPS off"
displayed on the LCD after the test is completed.

Press the UPS ON button.The message UPS ON


PLEASE WAIT appears as the unit turns on.

When the UPS is completely turned on:


"UPS OK"
The UPS OK message is displayed
TIME indicates how long the Inverter is
working.
"TIME XXXXXXXX"
Only green display lights are lit.
Turn on the OUTPUT circuit breaker

4.2 Turning the UPS OFF


To turn the UPS off:
Turn off all the loads connected to the UPS.
Press the UPS OFF button on the display panel.
Turn off all the circuit breakers.

PS 3:1, 1030 kVA, 220 Vac out Operating the PS Series UPS 27
Gamatronic Electronic Industries Ltd.

4.3 Activating MAINTENANCE BYPASS (Optional)


MAINTENANCE BYPASS allows the parallel UPS system to be shut down for servicing
without the users being affected.

To activate the MAINTENANCE BYPASS mode:


1. Verify that the SYNC and BYPASS lights of the Static Switch unit are lit. (If they
are not lit, the load cant go into BYPASS mode.)
2. Press the INV/BYP button to put the load in BYPASS mode.
3. Verify that the LOAD ON BYP light is lit.
4. Turn ON the MAINTENANCE BYPASS circuit breaker.
5. Turn OFF the OUTPUT circuit breaker of the UPS units.
6. Press twice on the UPS OFF button on the display panel.
7. Turn OFF the ST.SW, CHARGER and BATTERY circuit breakers.
If there are no lights lit on the display panel it is possible to service the UPS.

Note:
1. The MAINTENANCE BYPASS mode cannot be serviced when it is
activated.
2. Do not turn the ST.SW off or on if there is galvanic insulation on the
ST.SW.
3. Any special, non-standard instructions are on the UPS by the circuit
breakers.

4.4 Deactivating MAINTENANCE BYPASS


(Optional)
To deactivate MAINTENANCE BYPASS and retransfer the load to the UPS units:
Operate all the UPS units in the parallel system. After all the unit comes into normal
operation mode, lift up OUTPUT circuit breakers.
Pull down the MAINTENANCE BYPASS switch.
Press IVV/BYP switch of the Static Switch unit and verify that LED LOAD ON INV is lit.

WARNING
NEVER lift the MAINTENANCE BYPASS circuit breaker without first putting
the UPS in BYPASS mode (the red BYPASS light must be lit).

28 Operating the PS Series UPS PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

4.5 Setting the Real-Time Clock


The real time clock is composed of the date and time fields and may be set by the
user. The date field contains three subfields (DD/MM/YY) and the time field contains
two subfields (HH:MM).

To set the real time clock:


Press the TIME button to enter the time mode.
The normal TIME display is shown on the LCD panel.
Press the SET button to initiate setting mode.
The year is presented as 2 digits.
Press the SET button to increase the value.
Press the up arrow to continue with the settings, setting month [1-12], day
[1-31], hour [0-23] and minutes [0-59].
The UPS is connected to a computer or a modem using a shielded cable, with an
RS232-type 9-pin female connector. Maximum allowed cable length is 15 meters.
There are two types of UPS connections:

Directly to a host computer via dedicated software.


Remote monitor through a SNMP/WEB management programs for
communication with a computer network (optional).

Figure 18: Local-direct connection for monitoring and control

4.6 RS232 Interface


The UPS supports standard UPS protocol. Full information about the status of the UPS,
the value of its parameters, and the memory events log is displayed on a user-friendly
graphic interface. The graphic interface also allows the user to use the host computer
to execute a set of instructions for the UPS that includes shutdown, restart, battery
check, etc.

PS 3:1, 1030 kVA, 220 Vac out Operating the PS Series UPS 29
Gamatronic Electronic Industries Ltd.
Communication parameters: RS232
COM Tx Rx
2400 Baud rate
No parity
1 stop bit
5 1
No flow control
9 6

SIGNAL UPS
RD 2
TD 3
GND 5

Figure 19: RS232 Connector Pin Assignment

4.7 The Alarm Interface


The following diagram describes the alarm interface.

30 Operating the PS Series UPS PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

OUTPUT CIRCUIT SCHEMATIC DIAGRAM


UPS SIDE EXT. SIDE
NORMALLY OPEN
5 LOW BATTERY SIGNAL

NORMALLY OPEN
3 LINE FAIL SIGNAL

NORMALLY CLOSED
6 LINE FAIL SIGNAL

MAXIMUM
24VDC/1A
COMMON
4
ISOLATED FROM GROUND

LINE FAIL OUTPUT SIGNAL


LINE (TYP. +/- 3mA)

GROUND
-9V

NORMALLY OPEN
MAX. 24VDC/1A GENERAL FAULT

1
UPS SHUTDOWN
VIA AN EXTERNAL PULSE
(INPUT RESISTANCE TYP, 5Kohm)

PS 3:1, 1030 kVA, 220 Vac out Operating the PS Series UPS 31
Gamatronic Electronic Industries Ltd.

4.8 Remote Monitor Box (Optional)


The remote monitor box can be located a maximum distance of 50m from the UPS. It
is directly connected to the UPS with a 4-wire cable connected to the REMOTE
MONITOR interface of the UPS.

The control panel on the front of the monitor box displays audio and visual information
about the condition of the UPS, the mains, and the load. It also contains the following
function buttons:

UPS ON
UPS OFF
INV
ALARM OFF
BATTERY TEST
B/P

4.8.1 Connecting the Monitor Box to the UPS MS/MP


Attach the back of the monitor box to the wall.
The UPS PC908 card in the monitor box is connected to the PC021 card on the rear
panel of the UPS with a 4-wire cable connected to the appropriate 1-4 Pin male or
female DB9 connector terminal in the UPS row of terminals.
The cable is attached to the side of the monitor box with two screws.

DB9

Row of Terminals

The measurements of the Monitor box are: Length - 265mm, height -135 mm, and
distance between the screws on the back of the box - 200mm.

32 Operating the PS Series UPS PS 3:1, 1030 kVA, 220 Vac out
Gamatronic Electronic Industries Ltd.

5. TROUBLESHOOTING
If the unit stops operating normally, a red alarm light (ALARM) flashes, a warning beep
sounds, and one of the following emergency messages appears on the LCD:

MESSAGE STATE COMMENTS


BATTERY LOW Battery is low
1. Input voltage is too
low.
Corrects itself automatically when the
INPUT FAULT 2. Input voltage is too
input voltage stabilizes or returns.
high.
3. No input voltage
1. Bypass voltage is
too low.
Corrects itself automatically when the
B/P FAULT 2. Bypass voltage is
bypass voltage stabilizes or returns.
too high.
3. No bypass voltage
The unit goes to bypass and stays that
way as long as there is an overload. The
OVERLOAD Overload
load transfers from bypass to inverter
when the load is corrected.
Make up to 7 attempts to reconnect to the
INVERTER FAULT Malfunctioning inverter
inverter.
Over 90 paralyzes the inverters action
OVER and transfers the load to bypass. It returns
Over temperature
TEMPERATURE automatically to normal operation only
after the temperature goes below 55.
BATT. NOT Check the status of the battery switch and
Battery is not connected
CONNECT the connections to the batteries.
A slow beep indicates that the battery is
starting to discharge.
BATTERY UNDER Power failure. Inverter
LOAD operating on batteries. A fast beep and a TEST BATT light
indicates that the battery has almost
finished discharging.
The frequency bypass Works on an independent frequency of the
BYPASS FREQ.
exceeds the allowable inverter and will synchronize back when
FAULT
limits. the frequency will return to normal.
FAULT CONDITION Self-test has a negative
Call service technician
SERVICE REQUIRED result

RECTIFIER FAULT DC voltage is faulty Call service technician

Note: The following procedures are relevant in cases where the unit is not operating
normally and there are no LCD display panel messages.
These procedures are to be performed BY A TRAINED TECHNICIAN ONLY.

In the event that the unit has stopped operating in a normal manner, and the display
panel is not functioning, the technician should perform the following:

PS 3:1, 1030 kVA, 220 Vac out Troubleshooting 33


Gamatronic Electronic Industries Ltd.

Figure 20: Troubleshooting flowchart

34 Troubleshooting PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.

CHASSIS CHECK
BOARD VOLTAGE
POINT
PC 801 TP10 5V 5%
PC 800 P13/1 12V 5%
PC 800 P13/2 12V 20%

Figure 21: PC Board Check Points & Voltage Ranges

PS 3:1, 1030 kVA, 220 Vac out Troubleshooting 35


Gamatronic Electronic Industries Ltd.

6. SITE PREPARATION

6.1 Site Preparation and Considerations


The UPS is designed to operate under varied environmental conditions.

To insure long-term, trouble-free operation:


Select a well-ventilated and dust-free site that is conveniently located to both the
electrical closet and the desired load.
Make sure that there is a minimum of 20 cm. clearance.
Make sure that the air vents are not obstructed.
o
Make sure that the room temperature does not exceed 40 C. UPS operation and
battery charging generates heat. Battery life can be extended by insuring a cool
operating site.
Place electrical equipment (load, computer monitor, etc.) at least 1 meter from the
UPS.

6.2 Accessibility
All access to the UPS is accomplished through the rear panel of the UPS.

All connectionsconnection panel, input, output, and STSW are accessed via the
rear panel of the UPS.

6.3 Circuit Breakers


The UPS has circuit breakers that are accessible through the rear of the unit.

Charger
Static Switch
Output
Battery Switch (optional it may be located on the battery cabinet)
The UPS also has a Maintenance Bypass switch. This switch must only be operated
by qualified technical personnel according to the special procedures described in 4.3
and 4.4.

36 Site Preparation PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.

7. INSTALLATION

7.1 Installation Procedure


To prepare the UPS for the initial power-up:

1. Open the front access door using a flathead screwdriver to turn the lock.
2. Remove the lower access panel.
3. Turn OFF ALL of the circuit breaker switches:

RECTIFIER
BYPASS
OUTPUT
BATTERY (optional)
MAINTENANCE BYPASS (optional)
4. Connect the batteries to the UPS.
5. Connect the unit to the mains (electrical) cabinet with the grades of wire shown
in the following table. If local or national codes are stricter, follow those codes.

Table 3: Minimum recommended wire grades (cross-sectional area)

FOR PS-SP 3-1, 3X220 VAC INPUT, 220 VAC OUTPUT, 192 VDC
RECTIFIER BYPASS
UPS OUTPUT BATTERY
AC INPUT AC INPUT
10 kVA 6 mm2 10 mm2 10 mm2 16 mm2

15 kVA 10 mm2 16 mm2 16 mm2 25 mm2

20 kVA 16 mm2 25 mm2 25 mm2 35 mm2

30 kVA 25 mm2 35 mm2 35 mm2 50 mm2

6. Turn ON the CHARGER and ST.SW circuit breakers of the


first UPS in the parallel system.

7. The UPS performs a self-test (that takes approximately one


minute). Verify that the UPS OFF message is displayed on "UPS OFF"
the LCD display after the test is completed.

8. Press UPS ON. The UPS is ready for use and begins charging the batteries.

9. After the UPS comes into normal operation:


a. Lift up the OUTPUT circuit breaker
b. Measure the AC voltage between the UPS and BYPASS phase
terminals of the Static Switch unit.
PS 3:1, 1030 kVA, 220 Vac out Installation 37
Gamatronic Electronic Industries Ltd.
c. Verify that the voltage between the terminals is no more than 20V.

10. Measure AC voltage between UPS phase- neutral terminals (V1)

11. Pull down OUTPUT circuit breaker of the UPS and:


a. Operate the next UPS in the parallel system. Repeat all checks
(Steps 6-11) and verify that output voltage V2 does not differ from V1
by more than 4V.
b. Repeat the check (Step 12) for all the UPS units in the system.
c. Observe the LCD messages in STAT indication mode. Verify that one
of the UPS is the Master and others are Slaves.
12. Lift up the OUTPUT circuit breakers.
13. Measure the current between the UPS units in no load condition (circulation
current).
14. Verify that the current between each two UPS units is less than 0.1*Inom (for
example, 7 A for 20 kVA). If this value is exceeded, regulate the current with
potentiometer R102 of PC871 PWM board.
15. Press the INV/BYP key of the Static Switch unit and verify that transfer from UPS
to mains power and vice-versa is performed normally.
16. Lift up the OUTPUT circuit breaker of the Static Switch unit.
17. Verify that load is shared between the UPS units. (The difference between output
currents should be no more than 0.1*Inom. Adjust R102 of PC871 if necessary.

38 Installation PS 3:1, 1030 kVA, 220 Vac out


Gamatronic Electronic Industries Ltd.

8. TECHNICAL SPECIFICATIONS

PS 3:1
AC INPUT (Rectifier/charger) 10 kVA 15 kVA 20 kVA 30 kVA

Voltage (V) 3 X 220 Vac (3Ph +G)


Voltage range +10 % -15 %
Frequency 57-63 Hz
Power walk-in 12 sec.
Protection Circuit breaker, RFI filter
Power Factor 0.80
BYPASS AC INPUT 220 Vac / 60 Hz 2-Phase
OUTPUT
Voltage (V) 220 Vac / 60 Hz, Phase-Common
Power
(kVA) 10 15 20 30
(kW) 8 12 16 24
Efficiency ac-ac
at 100% load (%) 89
at 50% Load (%) 88
Heat dissipation (W) at full load
989 1483 1978 2966
(1W = 3.4 BTU)
Inverter efficiency at 100% load (%) 92
Regulation 2%
Frequency tracking range 1, 2 3 Hz., selectable
Slew rate 1 Hz/Sec.
Overload:
at 125% 10 Minutes
at 150% 30 Seconds
at 1000% 1 Cycle
Load P.F. 0.8
Waveform Sinusoidal
Crest factor 3:1
Total harmonic distortion (THD) Less than 2 % (at linear load)
Protection Overload & short circuit
Dynamic response to 100% load
change 2%
Transition time: to and from line Less than 0.5 msec.
Rejection ratio More than 100 dB
Nominal DC voltage 192 Vdc

PS 3:1, 1030 kVA, 220 Vac out Technical specifications 39


Gamatronic Electronic Industries Ltd.

COMMUNICATION OPTIONS
RS232 interface SNMP
Alarm interface Shutdown software
Remote indication panel Optional
LCD DATA
Input Voltage
Output & inverter Voltage, Current, Frequency
Bypass Voltage & frequency
Batteries Voltage & Current
Temperature Heat sink
Log (events memory) 256 lost events
ENVIRONMENT & OTHER
Ambient temperature:
Operating -10 to 40 C
Storage -20 to 60 C
Relative humidity 95 % max., non-condensing
Altitude 1500 m w/o derating
UPS Standard
General & Safety EN50091-1
EMC EN50091-2
Design ENV50091-3
MTBF (hours)
With ST. Switch 250,000
Without ST. Switch 100,000
Audible noise (dB) at 1.5m 54
PHYSICAL
Size (cm)
Height 75 95 95 130
Width 24 40 40 55
Depth 80 83.5 83.5 80
Weight (kg)
W/O batteries 200 220 240 275

40 Technical specifications PS 3:1, 1030 kVA, 220 Vac out

You might also like