Solo SOVEREIGN

The Nobel Solo Sovereign unit is a totally self contained fire suppression system detection and release control panel.

lffilfi* svst*r$

Fire Protection Module


ON/OK
AHM
SENSOR ULT
FIREX FAULT
Press to Test

The Sovereign can be used with a variety of thermal switching type detectors and will activate of up to 3 Stat-X units

of any size. Extreme low power design gives extended battery life and individual units may be linked to form a

system.
Features

./ A small, self contained battery powered unit with >3 year battery life. The actual time is temperature
dependent the lower the temperature the longer the life.

./ The Sovereign supports the actuation of 1-3 Stat-X units of any size. These being interconnected in series

with each other.

./ External thermal switch/s or Linear heat sensors can be used, as well as self contained battery operated

optical smoke detectors that have a set ofvolt free contacts that close on detection of an alarm condition.

./ Each Sovereign unit can be linked into an "all-fire" system where one-of-many detectors operates all the
Stat-X units in the system.

./ Powered with a widely available CR123a (replaceable) 3V lithium camera cell.

,/ Environmentally protected lP65 polycarbonate box with transparent lid and integral 10mm gland.

./ Comprehensive cell monitoring, and self test for faults and circuit continuity.

./ Battery life will be dependent on ambient temperature exposure, the following is a guide to expected
confidence of battery life on pressing of the battery/panel test button.

The below are rough guidance only and should not replace the need for regular 3 monthly confidence tests.

-2ooc 3-10 years.

-1ooc 3-10 years.

ooc 3-5 years.

looc 3-5 years.

zooc 3-5 years.

3ooc 3-5 years.

40oc+ 2-3 years.

NOTE: Onsite conditions can vary so will affect battery life in different locations
therefore for complete confidence replace battery Annually.
FRONT PANEL I NDICATORS/SWITCH ES

LED indicators and beeper are pulsed to maximize

battery life.

oN/oKAY LED

ALARM LED RED internal audible alarm sounds

SENSOR FAU LT LED flashing RED

FIREX FAULT LED flashing RED

TEST BUTTON for initiating representative


Hi-current pulse battery test checks all functions, LED's

and circuits. Faults remain illuminated whilst pressed.

lf all LED's function and the internal sounder emits a

Single beep then battery confidence levels can be taken as a minimum

3 months remaining life.

REAR CONNECTIONS

Dump See wiring diagram


Sensor 22K End of Line resistor
Volt Free contacts NC,COM, NO

Alarm 1 &2 "Link Through" connections.


See below

FIREX 1 &2linked to Stat-X E units (non polar)


FUNCTIONS

,/ Monitoring of internal and external thermal switches for alarm condition.

'/ Automatic activation of up to 3 Stat-X units in response to alarm.


,/ Manual activation by placing an MCP at the end of Sensor circuit.
,/ Actuation delay settable 5 or 10 seconds via dip switch.

DIP switch for user settable options


Position L ON Auto Delay, +5sec

Position 2 ON Auto Delay +l,0sec


Position 3 ON Slave mode (see below)

Position 4 ON Internal22K EOL on AIARM contacts

User defaults are all set to "OFF". The functions are enabled when moved to "ON" only.

,/ Periodic automatic self test:

Sensor loop continuity test: Monitors for fault conditions.

Firex continuity test: Monitors for extinguisher loop continuity.

,/ Front status LED's report a fault in realtime.


,/ Push button initiated test:
./ Battery test: High current pulse test of battery assures operational capability.
,/ An internal Audible alarm is activated on alarm.
,/ Real-time LED indications blink to save power, indications become constant during pushbutton test.
Cable connections

The connections are via 9 way PCB terminal block with spring push type terminal options accepting wires from
o.2mm2 to 1.0mm2 cross sectional area.

Access to test switch, battery and terminals.

Removal of the transparent outer lid gains access to the decal mounted test switch, which should be operated at

regular intervals to check battery health. Beneath the decal label remove 2 screws which retain the PCB- The board

can then be extracted from the base gaining access to the battery holder and connector block.

Temperature capability
-20 to 50C (standard battery)

-50 to 70C option (high spec battery)

Dimensions
65mm x 50mm x 35mm excluding gland

Gland will handle 10mm max diameter cable bundle

Mounting
The unit can be surface mounted by means of the two screw holes, which are diagonally opposed on 38mm x 53mm

rectangle.
Without Manual release

Linear Heat Sensor

1 to 3 Stat-X Units
DIP Switches
Set to OFF
Un less tim e d elay is

req u ired

With Optional Manual release

Linear Heat Sensor


with Manual release
switch inline

3"r{
Flra Proftecton Modub
2}KEOL :tr_:r t ot'YOXnY
O nmRna
= o SENSOR FAULr
O F]REX FAULT

1 to 3 Stat-X Units
DIP Switches
Set to OFF
Unless time delay is
req u ired
Solo Sovereign
Multi Unit connection
Via Linear Heat sensor

MA-STER

Linear Heat
Through
Risk No.1

Fira Prffiion irofib


DIP Switch
SENSQH FAULT 4 set to ON
Return :,T**,FAULT
Linear Heat
too folaster
from last
slave unit

No.2
Linear Heat
Through
Risk {:tv slrtti'ur

Hre Pruftcdm
s
Solo Sowrsrqn

kh&rh
* olrt;oxRy
DIP Switch
{} *u*nnit
I SENSOR FAULT
4 set to ON
|l FIREX FAULT

Linear Heat No.3


Through
Risk

Frs fuectbn lffirb


* oNioKAY
I ALARM DIP Switch
I SENS0H FAr"iLT
4 set to ON
|) FrHrx FAULT

No.4
Stat-X u nits not shown for cla ritY
Notel: Eachunitisstill dependantonitsownbatterysupplyforactuationoftheStat-Xunitsattachedtoit. lfone
Sovereign unit/battery is not functioning then only the Stat-X units of the fully functional Sovereign will be activated.

lf one of the Sovereign units should fail to function in a looped system then this will not prevent the other
Sovereigns from functioning and actuating. Faults will remain independently on each Sovereign and will not affect

any other in that looP.

Note Z: When Sovereign units are linked in the "Slave" configuration this disables the TEST button from activating
the ALARM contacts in a system that uses the ALARM contacts'

It also enables an immediate response mode (the "DUMP" connection) without waiting for the wake-up every 2

seconds and also circumvents the delaytime set on USRl and 2.

The Sovereign units can also be linked for Multi Stat-X actuation using only one mode of detection from the Master

Sovereign unit by utilizing the "Dump" connections'

MASTER
Dump Connections

22KEOL

DIP Switch
1 set to OFF
2 set to OFF
3 set to OFF
4 set to OFF

DIP Switch
1 set to OFF
2 sel to OFF
3 set to ON
4 set to ON
tical smoke detectors.
(Stat-X units not shown for clarity)

The Sovereign unit can be used with specific self powered detectors that have the ability to produce a volt free
contact to enable a switching circuit. This will allow a detector to be monitored for continuity with a 22K end of line

resistor. The detectors have an integrated audible and visual alarm signal that will activate as a fire condition is

sensed.

22K
EOL
Relay VFC
Normally
Open

Connection and wiring diagrams are provided with the detector.

Two stage alarm and activation

Relay VFC
Normally
Open

r+
-q'* /.li ,f//

,r, 4i

This configuration will allow for two detectors in a circuit to detect a fire condition before the Sovereign panel
releases the Stat-X units effectively giving a two stage alarm.

Batteries should be changed in the detectors on an annual basis.