PREGUNTA N1

CALCULO DE LOS INTERRUPTORES TERMOMAGNETICOS


P FP Vn In In Id Icat. RT RM Ia/In
ITEM DESCRIPCION GENERAL KW V A A 3xXA
1 1,524 1 380 2,316 0,00 2,316 2,779 4 0,579 5,905 8,5
2 13,901 0,84 380 25,143 -32,86 21,1-13,6j 30,172 25 1,006 7,724 6,4
3 19,124 0,89 380 32,647 -27,13 29,1-14,9j 39,177 32 1,020 7,591 6,2
4 27,590 0,84 380 49,903 -32,86 41,9-27,1j 59,884 50 0,998 7,186 6
5 37,912 0,79 380 72,913 -37,81 57,6-44,7j 87,496 80 0,911 6,125 5,6
6 46,050 0,89 380 78,613 -27,13 70-35,8j 94,335 80 0,983 7,665 6,5
CCM01 7 55,645 0,88 380 96,073 -28,36 84,5-45,6j 115,287 100 0,961 7,263 6,3
8 67,216 0,89 380 114,746 -27,13 102,1-52,3j 137,695 125 0,918 7,160 6,5
9 92,147 0,89 380 157,307 -27,13 140-71,7j 188,769 160 0,983 7,551 6,4
10 110,577 0,82 380 204,883 -34,92 168-117,3j 245,860 250 0,820 5,999 6,1
11 181,579 0,86 380 320,791 -30,68 275,9-163,7j 384,950 400 0,802 6,063 6,3
12 181,579 0,84 380 328,429 -32,86 275,9-178,2j 394,115 400 0,821 5,813 5,9
1268,416-
SUB TOTAL 834,844 0,856 380 1481,199 -31,091 1777,439 1600 0,926 4,629 -
764,9j
13 223,008 0,91 380 372,336 -24,495 338,8-154,4j 446,804 630 0,591 4,6808 6,6
14 264,092 0,9 380 445,829 -25,842 401,2-194,3j 534,995 630 0,708 7,1333 8,4
ARRANQUE 15 313,417 0,87 380 547,343 -29,541 476,2-269,9j 656,811 800 0,684 5,9113 7,2
INDIVIDUAL 16 361,635 0,86 380 638,893 -30,683 549,4-326j 766,671 800 0,799 6,1334 6,4
17 397,799 0,86 380 702,782 -30,683 604,4-358,6j 843,339 1000 0,703 5,4817 6,5
18 386,221 0,86 380 682,329 -30,683 586,8-348,2j 818,794 1000 0,682 5,2403 6,4
EDIFICIO 185 0,85 380 330,680 -31,788 281,1-174,2j 396,817 400 0,827 4,1335 -
COMPUTO 75 0,85 380 134,060 -31,788 114-70,6j 160,872 200 0,670 3,3515 -
SERV. AUX. 258 0,85 380 461,165 -31,788 392-242,9j 553,398 630 0,732 3,6600 -
5012,316-
TOTAL GENERAL DE LA BARRA 2781,017 0,865 380 5792,800 -30,087 6951,36 6300 0,91949 4,5975 -
2904j
TRANSFORMADOR DE CORRIENTE
CARACTERISTICAS DE
DEFINICION DE CONDUCTOR KWH KVARH TOTAL TOTAL
CONDUCTOR CATALOGO
PUNTO L(tot) Scu Is Ip Rc Wc S W Q S W Q S W Q S W Q S W Q S Q BURDEN FP RT Snom 1,2(ANSI)
20
A 50 6 5 145,56 0,1458 3,646 5 3,25 3,80 7 3,85 5,85 10,75 9,65 10,75+9,65j 14,45 0,732 150/5 1,2(ANSI)
KVAR
RELE
DIFERENCIAL
B1 50 6 5 145,6 0,1458 3,646 3 1,5 2,598 5,146 2,5981 5,15+2,6j 5,77 0,468 150/5 10KVAR 1,2(ANSI)
B2 50 6 5 6661,7 0,1458 3,646 3 1,5 2,598 5,146 2,5981 5,15+2,6j 5,77 0,468 8000/5 10KVAR 1,2(ANSI)
CONDUCTOR A KWH KVARH COFIMETRO KW TOTAL
C 90 4 5 380,3 0,3938 9,844 8 6,72 4,34 5 3,25 3,8 7 3,85 5,846 7,5 5,625 4,96 4 2,4 3,2 31,689 22,146 31,69+22,15j 38,66 0,61 400/5 45KVAR 1,2(ANSI)
D 60 4 5 1703,4 0,2625 6,563 8 6,72 4,34 5 3,25 3,8 7 3,85 5,846 7,5 5,625 4,96 4 2,4 3,2 28,408 22,146 28,41+22,15j 36,02 0,66 2000/5 45KVAR 1,2(ANSI)
E 70 4 5 530,3 0,3063 7,656 8 6,72 4,34 5 3,25 3,8 7 3,85 5,846 7,5 5,625 4,96 4 2,4 3,2 29,501 22,146 29,5+22,15j 36,89 0,64 600/5 45KVAR 1,2(ANSI)

TRANSFORMADOR DE POTENCIA
PUNTO Vp Vs Snom Scat RTP

A 20KV 120V 12KVA 15KVA 20/0,12KV

B1 -
B2 -

C 380 120 31,5KVA 40KVA 3,8/1,2V


D 380 120 31,5KVA 40KVA 3,8/1,2V
E 380 120 31,5KVA 40KVA 3,8/1,2V