You are on page 1of 22

Your Employment Solution Professionals!

Smart Brains Institute of Engineering Design & Research


12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

HAZARDOUS AREA STUDY

Hazardous area classification:

The hazardous area classification is an important aspect of identifying an area on which


selection and installation of electrical equipment are made. For any project it is very
important to classify the hazardous area properly as it has cost implication to it. If the
area is not classified properly then the selection of electrical apparatus will be improper
leading to increased expenses of project or unsafe work environment. An area can be
termed as hazardous or non hazardous depending upon the type of gas/vapour or dust
or fiber is released in a quantity sufficient to cause ignitable mixture or a possible of
flame.

The aim of area classification is to avoid ignition due to the release of gas which
may occur time to time in course of normal operation or failure of equipment.
Article 500 of NFPA 70, National Electrical Code, designates hazardous area as any
location in which a combustible material is or may be present in the atmosphere in
sufficient concentration to produce an ignitable mixture. Article 500 defines three major
categories of hazardous location:

(1) Class I ; in which the combustible material is a gas or vapor


(2) Class II ; in which the combustible material is a dust
(3) Class III ; in which the combustible material is a fiber or flying

Electrical classification considers some system/ process failures, the recommended


practices for classification does not take into for all situations that might involve
catastrophic failure, or catastrophic discharge from, process vessels, pipelines, tanks, or
systems. Such events are so rare that it is impractical to design electrical systems for
such circumstances.

Before classification of hazardous area few terms and definition should be kept in mind

1.0 DEFINITIONS
Definitions which are more frequently used have been listed below for ease of
reference:
Explosive Gas Atmosphere: A mixture with air of flammable materials in the
form of gas, vapour, or mist, in which, after ignition, combustion spreads
throughout the unconsummated mixture.
Flammable material: Material consisting of flammable vapour, liquid and/or mist.
Combustible Liquids - A liquid having a flash point at or above 38C (100F).
Flammable (explosive) Limits: The lower and upper percentages by volume of
concentration of gas in a gas-air mixture that will form an ignitable mixture.
Flammable (explosive) Range: Flammable vapour or gas and air mixture
concentrations between the upper and lower explosive limits.
Lower flammable limit (LFL): It is the lowest percentage by volume of gas or
Vapour in a gas-air mixture below which the mixture is too lean to be ignited.

ELECTRICAL ENGINEERING DESIGN 1/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Upper Flammable Limit (UFL): It is the highest percentage by volume of gas or


Vapour in a gas-air mixture above which the mixture is too rich to ignite.
Flammable Liquid - Liquids with a flash point below 38C(100F ) and have a
vapour pressure not exceeding 276kPA (40 psia)at 38C(100F).
Flame Propagation - The spread of a flame in a combustible environment outward
from the point at which the combustion starts.
Flash Point: It is minimum temperature of Liquid at which vapour in sufficient
concentration is given off to form an ignitable mixture with air, near the surface of
a liquid, which gives a momentary flash on application of a small pole flame under
specified conditions of test as per IS:1448 (Part-1)
Hazardous (Flammable) Atmosphere: An atmosphere containing any flammable
gas or vapour in a concentration capable of ignition.
Lighter than air: Gases with a vapour density less than 1.0. In process industries,
the boundary between compounds which may be considered lighter-than-air is set at
a relative vapour density of 0.75.
Heavier than air gas: Gases with a vapour density greater than 1.0.

Ignition Temperature: The lowest temperature at which ignition occurs in a mixture


of explosive gas and air when the method specified in IS: 7820 is followed.
Ignitable Mixture: A mixture that is between the upper and lower limits of the
flammable range and is capable of propagating flame away from the source of
ignition.
Flame proof Apparatus: Apparatus in an enclosure that is capable of
withstanding 4 times the explosion pressure of an internal gas or vapour
developed during an internal explosion and which prevents transmission of the
explosion to the surrounding external atmosphere thereby preventing ignition of
surrounding flammable atmosphere.
Increased Safety Apparatus:
Intrinsically Safe Apparatus: Apparatus that ensure the maximum level of current
and voltage measured as energy is about 1Watts or less.
Intrinsically Safe Circuit - A circuit in which any spark or thermal effect is incapable
of causing ignition of a mixture of flammable or combustible material in air.
Non classified Location - A location that is not classified as Class I,II or III.
Non incendive System: A system not capable of causing ignition under normal
conditions of operation.
Pressurizing: The process of supplying an enclosure or building with clean air or
inert gas at sufficient positive pressure to prevent the entrance of hazardous dusts
(Class II hazardous areas).
Purging: The process of supplying an enclosure with clean air or inert gas or a
room/building with clean air at a sufficient flow rate and positive pressure to reduce,
to an acceptably safe level, the concentrations of any flammable gas or vapour
initially present, and to maintain the safe level by positive pressure with or without
continuous flow (Class I hazardous areas).

ELECTRICAL ENGINEERING DESIGN 2/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Temperature Identification Number (T-Rating): A number proceeded by the letter


"T" designating the maximum surface temperature of a piece of equipment.
Source and Grade of Release: A point or location from which a flammable gas,
vapour, mists or liquid may be released into the atmosphere so that a hazardous
atmosphere could be formed.
Ventilation, Adequate: Ventilation (natural or artificial) that is sufficient to prevent
the accumulation of quantities of vapour-air mixtures in concentrations above 25
percent of their lower flammable (explosive) limit (LFL).
Ventilation, Inadequate: Rooms, buildings or spaces that do not have a natural or
a mechanical ventilation system providing for adequate ventilation.
Class I, Zone O: A Class I, Zone O location is a location (1) in which ignitible
concentrations of flammable gases or vapors are present continuously; or (2) in
which ignitible concentrations of flammable gases or vapors are present for long
periods of time.
Class I, Zone 1: A Class I, Zone 1 location is a location (1) in which ignitible
concentrations of flammable gases or vapors are likely to exist under normal
operating conditions; or (2) in which ignitable concentrations of flammable gases
or vapors may exist frequently because of repair or maintenance operations or
because of leakage; or (3) in which equipment is operated or processes are
carried on, of such a nature that equipment breakdown or faulty operations could
result in the release of ignitible concentrations of flammable gases or vapors and
also cause simultaneous failure of electrical equipment in a mode to cause the
electrical equipment to become a source of ignition; or (4) that is adjacent to a
Class I, Zone O location from which ignitible concentrations of vapors could be
communicated, unless communication is prevented by adequate positive pressure
ventilation from a source of clean air and effective safeguards against ventilation
failure are provided.
Class I, Zone 2: A Class I, Zone 2 location is a location (1) in which ignitible
concentrations of flammable gases or vapors are not likely to occur in normal
operation and if they do occur will exist only for a short period; or (2) in which
volatile flammable liquids, flammable gases, or flammable vapors are handled,
processed, or used, but in which the liquids, gases, or vapors normally are
confined within closed containers of closed systems from which they can escape,
only as a result of accidental rupture or breakdown of the containers or system, or
as the result of the abnormal operation of the equipment with which the liquids or
gases are handled, processed, or used; or (3) in which ignitible concentrations of
flammable gases or vapors normally are prevented by positive mechanical
ventilation, but which may become hazardous as a result of failure or abnormal
operation of the ventilation equipment; or (4) that is adjacent to a Class I, Zone 1
location, from which ignitible concentrations of flammable gases or vapors could
be communicated, unles s such communication is prevented by adequate
positive-pressure ventilation from a source of clean air, and effective safeguards
against ventilation failure are provided.
Gas groups: For purposes of testing, approval, and area classification, various
air mixtures (not oxygen enriched) are grouped as in below.
Group I: A term used by IEC 79-10 to describe atmospheres containing firedamp
(a mixture of gases, composed mostly of methane, found underground, usually in

ELECTRICAL ENGINEERING DESIGN 3/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

mines). Since this recommended practice does not apply to installations


underground in mines, this term is not used further.
Group II: The group used to describe gases found aboveground and is
subdivided into IIC, IIB, and IIA, , according to the nature of the gas or vapor, for
protection techniques d, ia, ib [ia], and [ib], and, where applicable, n and o.
Group IIA: Atmospheres containing acetone, ammonia, ethyl alcohol, gasoline,
methane, propane, or flammable gas, flammable liquid produced vapor, or
combustible liquid produced vapor mixed with air that may burn or explode having
either a maximum experimental safe gap (MESG) value greater than 0.90 mm (35
mils) or a minimum igniting current ratio (MIC ratio) greater than 0.80. (NFPA 497)
Group 11B: Atmospheres containing acetaldehyde, ethylene, or flammable gas,
flammable liquid produced vapor, or combustible liquid produced vapor mixed with
air that may burn or explode having either a maximum experimental safe gap
(MESG) value greater than 0.50 mm (20 mils) and less than or equal to 0.90 mm
(35 mils) or a minimum igniting current ratio (MIC ratio) greater than 0.45 and less
than or equal to 0.80. (NFPA 497).
Group IIC: Atmospheres containing acetylene, hydrogen, or flammable gas,
flammable liquid produced vapor, or combustible liquid produced vapor mixed with
air that may burn or explode, having either a maximum experimental safe gap
(MESG) value less than or equal to 0.50 mm (20 mils) or a minimum igniting
current ratio (MIC ratio) less than 0.45. (NFPA 497) .
Hazardous (classified) location: A location where fire or explosion hazards may
exist due to flammable gases or vapors, flammable liquids, combustible dust, or
ignitible fibers or flyings. Unless specifically indicated otherwise, locations
containing combustible dust, ignitible fibers or flyings are outside the scope of this
recommended practice.
Unclassified location (non-hazardous location): A location not classified as
Class I, Zone O, Zone 1, or Zone 2.
combustible liquid (Class II, IIIA, and IIIB Liquids): Any liquid that has a
closed-cup flash point at or above 37.8C (100F), as determined by the test
procedures and apparatus outlined in NFPA 30. Combustible Liquids are
subdivided as follows:
Class II liquids-liquids having flash points at or above 37.8C (100F) and below
60C (140F).
Class IIIA liquids-liquids having flash points at or above 60C (140F) and below
93C (200F).
Class IIIB liquids-liquids having flash points at or above 93C (200F).

Condition necessary for ignition


As we are all aware off that, for a fire to occur it must satisfy three requirements,
and they are
a) Flammable materials-source of gas/ vapour
b) Oxygen from air to form an ignitable mixture with flammable material
c) Ignition temperature in our case electrical installations.

ELECTRICAL ENGINEERING DESIGN 4/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Area classification of flammable gas/vapour and liquids

Three grades of release are defined in terms of their likely frequency and duration:
1. Continuous Grade Release: A release that is continuous or nearly so or that
occurs for long periods which occur frequently (1000 hours/ year) normally leads
to Zone 0.
2. Primary Grade Release: A release that is likely to occur periodically or
occasionally in normal operation (100 hours/ year) normally leads to a Zone 1.
3. Secondary Grade Release: A release that is not likely to occur in normal
operation or may occur for a very short period (10 hours/ year) normally leads to
a Zone 2.
4. Adjacent Hazardous Zones In many locations where a hazardous area is
identified and numbered as 0, 1 or 2 the immediate surroundings are given the
next higher number, except for an original Zone 2 area, which automatically is
surrounded by a non-hazardous area. A Zone 0 area is surrounded by a Zone
1 area, which in turn is, surrounded by a Zone 2 area. A Zone 2 area stands
alone. During the preparation of drawings that show the extent and shapes of
the areas surrounding a source, it is usually found that overlapping areas
create complicated geometrical shapes, e.g. two adjacent circular boundaries
almost touching each other. In these situations the shapes should be simplified
by using tangent lines. Local pockets within the geometry should be absorbed
into a more uniform shape, especially non-hazardous pockets in Zone 2
geometry. Experience shows that equipment located in a non-hazardous area
that is near to a Zone 2 area will usually be of the same specification as that
which is to be installed in the Zone 2 area. The same approach is sometimes
used for Zone 2 areas near to a Zone 1 area if the equipment are small items
e.g. junction boxes, lighting fittings, instrument casings, and local control
stations.
5.

North American hazardous area classification is based on class and divisions, a


similarity/comparison between zones and division is given below

Table-1

Gas group classifications

ELECTRICAL ENGINEERING DESIGN 5/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Gases are classified in accordance to the amount of energy required for ignition. They
are denoted by three digit code, the first two digits may be I or II and third digit is A, B or
C.

NORTH AMERICA
IEC 60079-0 /
EXAMPLE OF NFPA 70 NFPA 70 CENELEC
GASES Article 500, Article 505, EN 50014
NFPA 497 NFPA 497 Note e
Note b, d Note c, d
Acetylene A II C II C
Hydrogen B II C II C + H2
Propylene Oxide
Ethyl Oxide B II B II B
Butadiene
Cyclopropane
Ethyl ether C II B II B
Ethylene
Acetone
Benzene
Butane
D II A II A
Propane
Hexane
Natural gas
Table-2

Gases and Vapors are categorized according to their maximum experimental safe
gaps (MESG).

Temperature code
To avoid ignition due to hot surfaces, equipments are classified in accordance to
maximum surface temperature of any part of equipment under normal or fault
condition at ambient temperature of 40C.This is known as temperature code
classification.

ELECTRICAL ENGINEERING DESIGN 6/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Table-3

TYPES OF PROTECTION FOR HAZARDOUS AREAS


Most electrical equipment consists of live or active static parts, and in some cases such
as motors, solenoid valves and relays moving mechanical parts, encased in an
enclosure. The electrically live conductors are kept out of touch to prevent electric shock
hazards. The detrimental effects of the atmosphere e.g. rain, sprayed water, fine dust
and particles are kept out of contact with the conductors, insulation, bearings and the
like. For equipment that is to be used in hazardous areas there is the additional
requirement that gases and vapours should be restricted from entering into the
enclosure. There are various basic methods that attempt to ensure that this requirement
is achieved at a more or less degree, which generally is dependent upon the Zone of the
intended area of installation.
The design of the enclosure with regard to hazardous area applications is defined by
several lower case letter codes, mostly single digits for electrical power equipment but
occasionally two digits for very low energy electronic equipment. The most frequently
encountered codes are d, e, n, p and i. The lesser used codes are o, m, s and q. Table
10.4 gives a brief description of each code.
The codes are usually embraced with double or single quotation marks, or less often
single round brackets ( ). The code is prefixed with the letters Ex or EEx. Occasionally
two letters are combined for special designs of equipment e.g. Ex de for some types of
motors.

ELECTRICAL ENGINEERING DESIGN 7/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Type of Protection d
This type of protection is also referred to as flameproof in some literature. An enclosure
that is designed as typed will be able to withstand an internal explosion of the gas-air
mixture without being damaged beyond repair. Furthermore the mating surfaces of joints
e.g. terminal boxes, bearing seals on shafts, will be so designed that the flame inside the
enclosure will not pass to the outside with sufficient energy to ignite the environmental
gas-air mixture. In effect the design of the surfaces is such as to act as a very slow
pressure relief system for the internal explosion. (Care should be exercised when
dismantling such an enclosure after an internal explosion has occurred, because there
may be some residual pressure internally.) By the form of the design these enclosures
are usually robust, heavy duty and often made of thick cast iron, steel or bronze with
many bolts to fasten the fabricated sections and lids. They are therefore the most
expensive enclosures when compared with the e or p types. It becomes impractical to
manufacture d type enclosures for very large ratings of motors. The amount of metal
and machining required would not be economical and so the p type would be an
alternative. This type of protection is mainly intended for Zone 1 areas. In addition the
electrical components inside the enclosure may be of the sparking type e.g.
commutators for DC motors, local control stations with push buttons, relay boxes. When
an internal explosion occurs or under normal running conditions, the outside surface of
the enclosure must not exceed the gas-air autoignition temperature i.e. Temperature
Class.
The maintenance procedures for working with Ex d equipment need to be exercised
with care so that the machined surfaces are not degraded or damaged. BS5345 was
introduced in 1976 to address this and similar subjects. See Reference 4 for practical
view of the problems involved with
maintenance of hazardous area equipment.

Type of Protection e
Type e is also called increased safety and intended for apparatus that is to be installed
in a Zone 1 area. Two of the allowable features of the type d enclosures, namely
permitting sparking components and no Temperature Class limit to the internal
components, cannot be incorporated into the type e designs. The practical aspect of this
is the removal of a source of ignition i.e. a spark or a hot surface. In many types of
equipment e.g. luminaries, terminal boxes, junction boxes, some designs of motor
control stations, telephones and public address speakers, the elimination of these two
sources of ignition is not a difficult problem.
For motors the removal of sparking components, such as a commutator is not too
difficult, but the prevention of a hot internal surface is a problem for the designer. Clearly
a DC motor cannot be designed as an e type machine. The identification of hot-spots in
the windings or core of a motor at the design stage is extremely difficult. This applies
especially to the rotor cage of an induction motor. Consequently the design of an e
motor needs to be somewhat conservative. For example the temperature rise of the
windings needs to be reduced. The power output of an e type motor for a given frame
size is generally found to be less than for type d or p motors. There are also restrictions
on the allowable starting current and run-up time. Hence the motor characteristics will
need to be more carefully matched to the driven machine. High inertia rotors in the
driven machines should therefore be avoided. This conservativeness is also supported
by the requirement that the protective relay equipment at the motor control centre shall

ELECTRICAL ENGINEERING DESIGN 8/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

have special characteristics. Hence the use of an e type motor means that a system of
components or equipment must be used, not just the motor by itself. This adds an
element of unusualness to the circuits in a motor control centre, and for this reason the
use of e type motors in the oil industry is not common practice.

Type of Protection i
Intrinsically safe type i protection is not applicable to electrical power equipment. It is
mainly intended for electronic measuring and control circuits i.e. instrumentation and
telemetry. The principle behind i protections is that a circuit and its devices do not have
sufficient operating energy or stored energy to cause a spark that will ignite the gas-air
mixture. A spark can occur but it must be inherently too weak to ignite the mixture. There
are two sub-divisions of type i, namely ia and ib. The type ia has a more stringent
specification than ib and is therefore allowed to be used in a Zone 0 area. Type ib
equipment cannot be used in a Zone 0 area. Like the type e protection of motors a
system approach is required for type i equipment. The system includes the source of
power and its Zener Barrier, the interconnecting cables which by their nature have
inductance and capacitance, and the connected apparatus or load. If the connected
apparatus has inherent capacitance or inductance then extra attention must be paid to
the design and certification of the system.

Type of Protection m
Type m enclosures are encapsulations, for example an electronic circuit encapsulated in
solid epoxy resin or fire-resistance solid material. There are very few examples in
electrical power equipment used in the oil industry.

Type of Protection N and n


This type of protection does not have any particular title description. It also has some
mixed connotations with type of protection N which is very similar but not identically the
same.The subject of type of protection N attracted much debate in the 1980s and
1990s, as much of which centered around whether or not sparking equipment could be
included in an enclosure. The N was originally developed in the UK and became
covered by BS4683 Part 3. BS4683 has been superseded by BS6941, which has been
updated in 1997. BS5000 part 16 covers no sparking motors with the type of protection
N. The use of type of protection N in zone 2 areas may not be universally assumed to
be completely satisfactory, as described in Reference 5 which recommends that some
action should be taken to reduce the hazardous situation when a release of gas occurs.
Taking appropriate action manually may not be achievable on a highly reliable basis in
practice. A form of automatic action will be needed such as a fire and gas detection
scheme, with alarms and tripping functions. References 1 and 5 give good descriptions
of the background to the development of the type N concept. Type n was not covered
by the early editions of IEC60079, it became included as Part 15 in 1987.
The basic concept of type n protection was to have an enclosure design that would be
suitable for Zone 2 areas. The application to Zone 1 areas was deliberately excluded.
Consequently it should be possible to design an enclosure which is better than standard
industrial designs of good quality and which has some similarity with type e designs.
The intent was to have non-sparking components inside a suitable enclosure, and to
have a certifiable item of equipment for Zone 2 use. Inherent in the concept of a good
quality industrial design for use in a Zone 2 area is the need for a robust water and dust

ELECTRICAL ENGINEERING DESIGN 9/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

resistant enclosure. Hence the IEC and BSI standards require a certain high level of
ingress protection, see sub-section 10.6. In most cases the minimum ingress protection
is IP54, but fully insulated conductors IP44 may be used e.g. motors. As far as motors
are concerned, the emphasis on hot surfaces, high starting currents and extended run-
up times is not as great as with type e for Zone 1 areas, due to the inherently lower risk
of hazard in a Zone 2 area. Special protective relays are not required and a system
approach is not used. Similar design features in the mechanical part will be found e.g.
clearances of fan blades, length of the air-gap between the rotor surface and the stator
inner surface. Oil company specifications often call for non-sparking materials for the
construction of the fans. Other types of equipment than motors are often chosen with
type n enclosures, e.g. luminaries, junction boxes, terminal boxes, if the designer can
be sure that they will be located in a Zone 2 or non-hazardous area.

Type of Protection o
With this type of protection the active and sparking parts of the equipment are immersed
in mineral oil. The concept is similar to that used in the manufacture of bulk oil immersed
and small volume oil immersed switchgear (both of which are seldom encountered
nowadays). Oil immersion finds application with electronic and telemetering equipment.
Type o protection is only permitted in Zone 2 and non-hazardous areas. Oil immersed
switchgear is not normally specified in the oil industry because there are far better
insulating media available in modern designs e.g. SF6 and vacuum.

Type of Protection p
This is also known as pressurization or continuous dilution. It is mainly applied to large
motors, control panels, display panels, and occasionally special purpose generators.
Type p protection is suitable for Zone 1 and Zone 2 areas.
Type p protection allows well-designed standard industrial equipment to be used in
hazardous areas, provided that the enclosure is suitable for pressurisation by air or an
inert gas. The enclosure should be reasonably airtight so that the pressurisation can be
maintained by a modest throughput of air or gas.
The pressurisation process is carried out in two parts, the first part when the equipment
is ready to be energised and the second part to cater for the running and shutdown of
the equipment. The first part is called purging. Air or inert gas is passed into and vented
from the enclosure, to purge out any gas-air mixture that may be present. The equipment
is prevented from being energized until the purging cycle is complete. The purging cycle
will need to pass a prescribed volume of air or inert gas through the equipment.
Measuring devices will be incorporated into the purging equipment to ensure that the
necessary volume of air or gas has been passed. If the purging equipment fails then the
enclosure cannot be energised. The purging equipment maintains a throughput of air or
gas to balance the leakage to atmosphere from joints, bearing seals, gaskets and the
like, and to maintain a prescribed pressure inside the enclosure. The purging air must be
drawn from a non-hazardous area source e.g. through suitable ducting or from a plant air
compressor. If the enclosure is large, as in the case of high voltage motors, then
the use of plant air may present problems of air consumption. The purging gas for a
small enclosure may be taken from high-pressure storage cylinders, using a suitable
pressure reduction regulator. Wherever the purging medium is derived from, it should be
filtered and dried so that the enclosure is not contaminated or dampened, and the
insulation of the internal components degraded.

ELECTRICAL ENGINEERING DESIGN 10/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Type of Protection q
This type of protection uses sand or similar dry powder to exclude the flammable gas-air
mixture. It is mainly intended for electronic equipment as it has very little application in
the oil industry.

Type of Protection s
Type s protection is also called special protection and enables unusual designs to be
designed, tested and certified. It is a little used method and the applications are mainly
suited to electronic and low power equipment.

Type of Protection de
The type of protection de is a hybrid of the d and e types. It is mainly used for motors.
The concept is that the motor is type d whilst its terminal boxes are type e. This hybrid
concept evolved from the difficulties experienced with the use of direct and indirect
entry of the cables at their terminal boxes. A direct entry requires a barrier gland, which is
filled with a compound to displace all the air pockets inside the gland where the cable
conductors are exposed. An indirect entry does not require a barrier gland. However,
with both methods the cable gland must be of the type of protection d, with the correct
threading to suit the terminal box. The type e terminal box contains the winding
terminations, which are usually in the form of threaded studs mounted on a robust
flameproof partition or interface. The studs are sealed into through-type insulators,
which are often made of epoxy resin compound. The arrangement ensures a strong
hermetical seal between the internal volume of the motor and that of the terminal box.
Since the components inside the terminal box are of the non-sparking type and their
surface temperature is kept low by design, then the box can be certified as type e.
There must be a fully sealed barrier or interface between the type d part and the type e
part. Barrier glands are generally unpopular in the oil industry because of the practical
difficulties associated with making and remaking the glands in difficult environments, for
example during periods of routine maintenance. The introduction of BS5345 in the mid-
1970s focused attention on maintenance and installation of hazardous area equipment
for the first time. It placed responsibility on the user of equipment in addition to that which
already existed for the manufacturers.
Keeping the materials clean and dry whilst the glanding is being prepared is sometimes
difficult e.g. outdoors offshore in bad weather, in dusty desert conditions. Overall the type
e terminal box with a non-barrier type d gland provides an economical as
well as a very practical method of terminating cables. The method has potential with
equipment other than motors e.g. local control stations, switched
socket outlets.

CERTIFICATION OF HAZARDOUS AREA EQUIPMENT


In general the installation designer and the user require confidence that manufactured
equipment for use in a hazardous area carries an internationally recognized certificate. In
addition the certificate should be the result of laboratory testing of a sample of the same
equipment. The laboratory should be specialized in the type of testing required.

ELECTRICAL ENGINEERING DESIGN 11/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

In the UK and Europe a certificate is required from the manufacturer for equipment that
is to be used in Zone 1 and Zone 2 areas. In some situations a certificate will be
obtained for a system of components, for example with intrinsically safe equipment.
In the USA the practice is slightly different. Only equipment that will be installed in a
Division 1 area should require a certificate.
For manufacturers offering a range of products, the process of testing and obtaining a
certificate is expensive and time consuming. Subsequent modification to a design can
also be a long and expensive process for retesting and re-approval.
Over the last 15 years there has been a process called harmonisation of the various
national standards within the UK and Europe with the internationally accepted IEC
standards. This has made the subject of certification rather complicated, but as time
passes the results should be simpler to obtain both for the manufacturer and to the
satisfaction of the user. The harmonization process has been managed by the
Committee of Electrotechnical Standardisation (CENELEC) in Europe. The committee
standardises many subjects of electrical and electronic engineering, not only those
pertaining to hazardous area equipment and its installation. When equipment is certified
in accordance with a CENELEC standard the symbol Ex is odified to become EEx. This
serves to give the designer and the user extra confidence in the certification.
The certification process, like so many other manufacturing functions, is now being
influenced by the generally accepted requirement for quality assurance, through the
ISO9000, 9001 and 9002 standards.
There are several permutations for certification involving European harmonisation and
countries inside or outside the EC (European Community). Equipment can be
manufactured in any country. The manufacturer may choose to design his equipment to
the national standards of his country, or he may wish to cover a wider market by using an
international or even a CENELEC standard. Once the equipment is manufactured,
samples of it will need to be tested. There may be a testing authority in the particular
country, or for some reason the manufacturer may choose to have the testing carried
out in another country e.g. the testing laboratory may have a wider scope of facilities.
Eventually the manufacturer will obtain a certificate. The installation designer and the
user may need to carefully scrutinise the whole sequence of events leading up to the
issuance of a valid certificate. Reference 1 explains the European situation in detail,
together with the various types of certificates that are obtainable from within Europe and
from other continents. The subject is complex and requires careful study to ensure that
the correct documentation is obtained.

MARKING OF EQUIPMENT NAMEPLATES


Hazardous area equipment that has been tested and approved by a recognized
laboratory should have a marking plate attached to its surface, in a place easily seen by
the user. This plate is usually the nameplate that shows the normal information such as
the name of the manufacturer, voltage, rated power, full load current, frequency, model
number, serial number, ambient temperature and date of manufacture. The additional
information to be shown for the hazardous area application, should be at least the
following:
Applicable national or international standard e.g. BS5501 Part 5, IEC60079 Part 2.
Name or abbreviation of the testing laboratory that issued the certificate, e.g.
BASEEFA.

ELECTRICAL ENGINEERING DESIGN 12/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Approved symbol for the certifying authority, and if appropriate the EEC hexagonal
symbol.
Type of protection e.g. EEx d, Ex e, Ex n.
Gas Group e.g. IIA, IIB, IIC.
Temperature Class e.g. T6.
Certificate unique identification number.

Now we move on to the procedures/ steps to be followed for classification of an


area into hazardous and non hazardous.

PROCEDURES
In preparing the electrical area classification, a number of steps are followed:
Step 1- The flammable material present in the unit is defined.
Step 2- Plot plan of the area for which hazardous area classification to be made.
Step 3- The flammable material content per process equipment is defined.
Step 4- The grade of sources of release and ventilation type is determined.
Step 5- The type of zones is determined.
Step 6- Classification of temperature class.
Step 7- The extent of zones is determined.
Step 8- The minimum required types of protection for electrical and instrument
equipment are determined.

To understand the steps better, we move into a depth of the steps-

STEP 1:
Flammable Material present in the project Area
The flammable materials present in the project area are to be listed in a tabular form
called Hazardous Source List..
For the purpose of area classification, the flammable materials have an indication of gas
groups and temperature class.
Flammable materials are classified as by gas groups, according to their maximum
experimental safe gaps and minimum ignition currents. Gas groups are I, IIA, IIB and IIC.
Gas group IIC (Hydrogen) is the most stringent. Gas groups of the flammable materials
(as determined by tests) are derived from IEC 79-12. Flammable materials are classified
by Temperature classes such that the maximum surface temperature of the electrical
apparatus is below the lowest ignition temperature of the explosive gas mixture.
Temperature classes are T1 through T6 in which T6 (85 deg C) is the most stringent.
This is an vital input for classification of hazardous area. This information has to
acquire from process department.

STEP-2:
Plot plan of the area for which hazardous area classification to be made.
The plot plan should indicate all the equipments like vessels, containers, tanks, pumps,
flanges, valves, etc wherever there is a possibility of release of gases.
This is another vital input for classification of the area. A proper and prcised plot
plan depicting each equipment of the area is very important for proper
classification. This is also to be acquired and validated from process department

ELECTRICAL ENGINEERING DESIGN 13/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

STEP-3:
The flammable material content per process equipment is listed in the source list. The
process equipment of the plant often do not contain products of only one gas group but
mixtures of products of different gas groups.
Unless unique gas group/ temperature class is available for a particular mixture,
definition of the area is based on following:
Upon release, gas mixtures are considered to separate immediately into their separate
gases. The percentage (by volume) of the individual components of the mixture is
indicated in source list.
For mixtures from flammable materials of gas groups IIA/ IIB with hydrogen (gas group
IIC), the hydrogen can be discarded if, under any process condition, it constitutes less
than 30% volume of the mixture. The definition of a certain area is based on the
minimum temperature class and most stringent gas group of any gas within a mixture,
possible within that area
If the separate gases of a mixture are both lighter and heavier than air, the extent of each
separate area is indicated on the area classification layout. Conversely, when mixture is
composed of lighter-than-air and heavier-than-air gases and the mixture density is less than
75% of the density of air at standard conditions, the extent of the classified area shall
satisfy the requirements for lighter-than-air vapours.
Where the mixture has a density equal to or greater than 75% of air at standard conditions,
it shall be considered as heavier-than-air vapours for area classification purposes.
This is another input, which is also a part of source list to be furnished by process
department

STEP 4:
The grade of sources of release and ventilation type.
Unless otherwise mentioned, all sources of release are of secondary grade (a source
which is not expected to release in normal operations and, if it releases, is likely to do so
only infrequently and for short periods).
This is part of source list and the information is generally furnished in the source
list.

STEP 5: Classification of Zones


The classification of zone is based on the expected existence, the probability of
existence, or the non existence of an atmosphere, containing a concentration of vapours
or gases within the flammable limits of the specific flammable material involved. They
may be classified as Zone 0, Zone 1 or Zone 2. This information can be obtained from
grade of source of release.

This step and all other steps following it is part of output and is responsibility of
electrical department

STEP 6: Classification of temperature class.


Once we have the hazardous source list we must identify the temperature class of the
equipment. The temperature class depends upon the auto ignition temperature of the
gas handled by the equipment. Temperature classification should be always lower than

ELECTRICAL ENGINEERING DESIGN 14/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

the auto ignition temperature of the gas. Classification of temperature class should be
based on Table-3 shown above.

STEP 7:Extent of zones


The extent of zone classification can be based on standards like IEC60079, API505, IP,
and OISD113. Here in our study we are going to adhere with API505.The extent of
classifications are made on the plot plan, a well as sectional view.

After classification of the zones and identifying extent of zones , the most vital step and
aim for all the exercise is done that is selection of equipment as per the area
classification, so that the project is cost effective and safe.

STEP 8: Types of protection


The Types of protection for electrical and instrument which are allowed to be used
certain types of zones, are based on local regulations and/or contract requirements.

Some special considerations

1. Gas / Vapour in an enclosed hazardous area can be diluted by dispersion or


diffusion into the air until it's concentration is below the lower flammable limit (LFL).
Degree of ventilation (natural or artificial) can determine the Division / Zone. For
further details, refer IEC 60079-10 Annex B, API RP 500 Section 6.3.

2. In vendor supplied skids handling flammable liquids / gases, welded piping is used
and skid is categorized as general purpose. When flanged connection is used as
interface with such a skid, a Class I, Div 2 (alternatively Class I, Zone 2) area is
created. This requires all devices on the skid under influence of this new hazardous
area, to be suitable for this area. This leads to a major problem with potential costly
fixes. It is recommended that welded piping be used whenever possible. Also,
placing large motors / devices with contacts in the 4.6 m (15) radius zone of a
potential leak source like a flange, shall be avoided.

In vendor supplied skids handling flammable liquids / gases, welded piping is used
and skid is categorized as general purpose. When flanged connection is used as
interface with such a skid, a Class I, Div 2 (alternatively Class I, Zone 2) area is
created. This requires all devices on the skid under influence of this new hazardous
area, to be suitable for this area. This leads to a major problem with potential costly
fixes. It is recommended that welded piping be used whenever possible. Also,
placing large motors / devices with contacts in the 4.6 m (15) radius zone of a
potential leak source like a flange, shall be avoided.

3 When a mixture contains gases of different Groups, the area classification shall be
based on following conditions:

ELECTRICAL ENGINEERING DESIGN 15/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Ignition temperature of that gas (or vapour) having lowest ignition temperature shall
be considered. Alternatively, tests for ignition temperature may be required.
If specific gravity of resultant mixture is greater than 1, than gas shall be considered
heavier than air. If specific gravity is less than 1, than gas shall be considered
lighter than air.

4 Charging of non-sealed battery cells leads to creation of Hazardous area since the
cells act as primary source of emission of Hydrogen. Battery rooms that are
adequately ventilated as per guidelines laid by IEEE 484 shall be treated as
unclassified. For interiors of unventilated Battery room, electrical area classification
shall be Class I, Division I ( or alternatively, Zone 1 ), Group B ( or alternatively
Group IIC ).

Special precaution shall be exercised in classifying hazardous locations associated with


Crude Oil. Crude oil contains volatile light ends which may be released during storage
and handling or upon heating. Flash point of crude oil can range from zero to over 150F
(-17C to 66C). The volatile light ends of crude oils, such as propane, butane and pentane,
upon leakage or other release to atmosphere, may volatilize at ambient temperature. Being
heavier than air, the vaporized hydrocarbons may travel for considerable distances and
accumulate in hazardous concentrations

Electrical Area Classification Drawing:


The drawings are as per API

ELECTRICAL ENGINEERING DESIGN 16/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

ELECTRICAL ENGINEERING DESIGN 17/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

ELECTRICAL ENGINEERING DESIGN 18/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

ELECTRICAL ENGINEERING DESIGN 19/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

ELECTRICAL ENGINEERING DESIGN 20/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

ELECTRICAL ENGINEERING DESIGN 21/22


Your Employment Solution Professionals!
Smart Brains Institute of Engineering Design & Research
12-A, Ahinsha Khand II, Indirapuram, Ghaziabad, U.P

Here are few drawings of typical equipments and classification of the zones as per
API. For any other specialized type of equipment refer API or OISD. The extent of
classification may vary from one standard to other slightly but the basic concept
remains same.

Electrical installations in areas where flammable liquids, gases, or vapors are produced,
processed, stored or otherwise handled can be suitably designed if the locations of
potential sources of release and accumulation are clearly defined. Once a location has
been classified, requirements for electrical equipment and associated wiring should be
determined from applicable publications. Applicable publications may include NFPA 70
(NEC) or API RP 14F.

ELECTRICAL ENGINEERING DESIGN 22/22

You might also like