GALLANT-GPR-1_prn

Gallant Ispat 25MW / Folder /


SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

Gallant Ispat 25MW / Folder / GALLANT-GPR-1

MLFB: 7UM6221**B923CE0
Parameter-set version: V04.70.02
Device path: D:\D4PROJ\Gallant_\P7DI\GV\SD\00000001
Author:
Creation date: 09.10.17 17:43:02
Last modified: 09.10.17 17:45:18
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS
1 Device Configuration ................................................................................................................................................ 3
2 General Device Settings ....................................................................................................................................... 4
2.1 Group Device; Group General .............................................................................................................................. 4
3 Power System Data 1 ........................................................................................................................................... 5
3.1 Group Power System Data 1; Group Power System ........................................................................................... 5
3.2 Group Power System Data 1; Group Generator/Motor ........................................................................................ 5
3.3 Group Power System Data 1; Group CT's ........................................................................................................... 5
3.4 Group Power System Data 1; Group VT's ............................................................................................................ 6
3.5 Group Power System Data 1; Group Breaker .......................................................................................................... 6
3.6 Group Power System Data 1; Group Transducer ................................................................................................ 6
4 Settings groups .................................................................................................................................................... 7
4.1 Group Power System Data 2; Group General ...................................................................................................... 7
4.2 Group O/C I> (with undervoltage seal-in); Group O/C I> ..................................................................................... 7
4.3 Group O/C I>> (with direction); Group O/C I>> .................................................................................................... 7
4.4 Group Inverse O/C Time Protection; Group IDMT ............................................................................................... 7
4.5 Group Thermal Overload Protection; Group Therm Overload ............................................................................. 8
4.6 Group Thermal Overload Protection; Group Temp. Input .................................................................................... 8
4.7 Group Unbalance Load (Negative Sequence); Group Unbalance Load .............................................................. 8
4.8 Group Differential Protection; Group General ...................................................................................................... 9
4.9 Group Differential Protection; Group I-Diff ........................................................................................................... 9
4.10 Group Differential Protection; Group Characteristic ................................................................................................. 9
4.11 Group Underexcitation Protection; Group Underexcitation ................................................................................ 10
4.12 Group Underexcitation Protection; Group Characteristics ................................................................................. 10
4.13 Group Reverse Power Protection; Group Reverse Power ..................................................................................... 10
4.14 Group Forward Power Supervision; Group Forward Power ............................................................................... 11
4.15 Group Impedance Protection; Group General .................................................................................................... 11
4.16 Group Impedance Protection; Group Zones ...................................................................................................... 11
4.17 Group Impedance Protection; Group Power swing ................................................................................................ 11
4.18 Group Out-of-Step Protection; Group Out-of-Step ................................................................................................. 12
4.19 Group Undervoltage Protection; Group Undervoltage ....................................................................................... 12
4.20 Group Overvoltage Protection; Group Overvoltage ........................................................................................... 13
4.21 Group Frequency Protection; Group Frequency Prot. ........................................................................................ 13
4.22 Group Overexcitation Protection (U/f); Group Overexcitation ............................................................................ 13
4.23 Group Overexcitation Protection (U/f); Group Characteristics ........................................................................... 14
4.24 Group Rate-of-frequency-change protection; Group df/dt Protect. .................................................................... 14
4.25 Group Rate-of-frequency-change protection; Group Stage 1 ............................................................................ 14
4.26 Group Rate-of-frequency-change protection; Group Stage 2 ............................................................................ 14
4.27 Group Stator Earth Fault Protection; Group Stator E Fault .................................................................................... 15

Page 1 of 16
GALLANT-GPR-1_prn

Gallant Ispat 25MW / Folder /


SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

4.28 Group Sensitive Earth Current Protection; Group Sens. E Fault ....................................................................... 15
4.29 Group Breaker Failure Protection; Group Breaker Failure ..................................................................................... 15
4.30 Group Inadvertent Energisation; Group Inadvert. En. ............................................................................................ 16
4.31 Group Measurement Supervision; Group MeasSupervision .................................................................................. 16
4.32 Group Supervision; Group General .................................................................................................................... 16

Page 2 of 16
GALLANT-GPR-1_prn
Device Configuration
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0104 Fault values Instantaneous values
0112 Overcurrent Protection I> Side 2
0113 Overcurrent Protection I>> Non-Directional on side 2
0114 Inverse O/C Time Protection with IEC-characteristic on side 2
0116 Thermal Overload Protection Enabled
0117 Unbalance Load (Negative Sequence) Enabled
0118 Startup O/C protection Disabled
0120 Differential Protection Generator/Motor
0121 Restricted earth fault protection Disabled
0130 Underexcitation Protection Enabled
0131 Reverse Power Protection Enabled
0132 Forward Power Supervision Enabled
0133 Impedance Protection Enabled
0135 Out-of-Step Protection Enabled
0136 Loss of synchronism protection Disabled
0140 Undervoltage Protection Enabled
0141 Overvoltage Protection Enabled
0142 Over / Underfrequency Protection Enabled
0143 Overexcitation Protection (U/f) Enabled
0144 Inverse Undervoltage Protection Up< Disabled
0145 Rate-of-frequency-change protection with 2 df/dt stages
0146 Jump of Voltage Vector Disabled
0150 Stator Earth Fault Protection non-directional only U0
0151 Sensitive Earth Current Protection with Iee2
0152 Stator Earth Fault Prot. 3rd Harmonic Disabled
0154 Sensitive Earth Current Protection B Disabled
0155 Interturn Protection Disabled
0160 Rotor Earth Fault Protection (R, fn) Disabled
0165 Motor Starting Time Supervision Disabled
0166 Restart Inhibit for Motors Disabled
0167 Motor Starting Supervision B Disabled
0170 Breaker Failure Protection Side 1
0171 Inadvertent Energisation Enabled
0172 DC Voltage/Current Protection Disabled
0180 Fuse Failure Monitor Enabled
0181 Measured Values Supervision Enabled
0182 Trip Circuit Supervision Disabled
0185 Threshold Supervision Disabled
0186 External Trip Function 1 Disabled
0187 External Trip Function 2 Disabled
0188 External Trip Function 3 Disabled
0189 External Trip Function 4 Disabled
0190 External Temperature Input Disabled
0191 Ext. Temperature Input Connection Type 6 RTD simplex operation

Page 3 of 16
GALLANT-GPR-1_prn
General Device Settings
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

2 General Device Settings

2.1 Group Device; Group General


Group Device; Group General
No. Settings Value Group

0610 Fault Display on LED / LCD Display Targets on every Pickup All
0615 Minimum hold time of latched LEDs 5 min All
0640 Start image Default Display image 1 All

Page 4 of 16
GALLANT-GPR-1_prn
Power System Data 1
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

3 Power System Data 1

3.1 Group Power System Data 1; Group Power System


Group Power System Data 1; Group Power System
No. Settings Value Group

0242 Starpoint of Side 1 is Isolated All


0244 Starpoint of side 2 is Isolated All
0270 Rated Frequency 50 Hz All
0271 Phase Sequence L1 L2 L3 All
0272 Scheme Configuration Direct connected to busbar All
0274A Storage of th. Replicas w/o Power Supply NO All
0276 Unit of temperature measurement Degree Celsius All

3.2 Group Power System Data 1; Group Generator/Motor


Group Power System Data 1; Group Generator/Motor
No. Settings Value Group

0251 Rated Primary Voltage Generator/Motor 11.00 kV All


0252 Rated Apparent Power of the Generator 31.25 MVA All

3.3 Group Power System Data 1; Group CT's


Group Power System Data 1; Group CT's
No. Settings Value Group

0201 CT-Strpnt. Side1 in Direct. of Object NO All


0202 CT Rated Primary Current Side 1 2000 A All
0203 CT Rated Secondary Current Side 1 1A All
0204 Correction Angle CT W0 0.00 All
0205 CT Ratio Prim./Sec. Iee1 50.0 All
0210 CT-Strpnt. Side2 in Direct. of Object NO All
0211 CT Rated Primary Current Side 2 2000 A All
0212 CT Rated Secondary Current Side 2 1A All
0213 CT Ratio Prim./Sec. Iee2 50.0 All
0214 Grounded Terminal CT Iee2 Terminal Q7 All

Page 5 of 16
GALLANT-GPR-1_prn
Group Power System Data 1; Group VT's
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

3.4 Group Power System Data 1; Group VT's


Group Power System Data 1; Group VT's
No. Settings Value Group

0221 Rated Primary Voltage 11.00 kV All


0222 Rated Secondary Voltage (Ph-Ph) 110 V All
0223 UE Connection not connected All
0224 VT Ratio Prim./Sec. Ue 36.4 All
0225A Matching Ratio Ph.-VT to Broken-Delta-VT 1.73 All

3.5 Group Power System Data 1; Group Breaker


Group Power System Data 1; Group Breaker
No. Settings Value Group

0280 Minimum TRIP Command Duration 0.15 sec All


0281 Closed Breaker Min. Current Threshold 0.04 A All

3.6 Group Power System Data 1; Group Transducer


Group Power System Data 1; Group Transducer
No. Settings Value Group

0295 Transducer 1 10 V All


0296 Transducer 2 10 V All
0297 Transducer 3 with filter All

Page 6 of 16
GALLANT-GPR-1_prn
Settings groups
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

4 Settings groups

4.1 Group Power System Data 2; Group General


Group Power System Data 2; Group General
No. Settings Value Group

1108 Measurement of Active Power for Generator A

4.2 Group O/C I> (with undervoltage seal-in); Group O/C I>
Group O/C I> (with undervoltage seal-in); Group O/C I>
No. Settings Value Group

1201 Overcurrent Time Protection I> ON A


1202 I> Pickup 1.12 A A
1203 T I> Time Delay 3.00 sec A
1204 State of Undervoltage Seal-in ON A
1205 Undervoltage Seal-in Pickup 88.0 V A
1206 Duration of Undervoltage Seal-in 5.00 sec A
1207A I> Drop Out Ratio 0.95 A

4.3 Group O/C I>> (with direction); Group O/C I>>


Group O/C I>> (with direction); Group O/C I>>
No. Settings Value Group

1301 Overcurrent Time Protection I>> ON A


1302 I>> Pickup 2.46 A A
1303 T I>> Time Delay 0.20 sec A

4.4 Group Inverse O/C Time Protection; Group IDMT


Group Inverse O/C Time Protection; Group IDMT
No. Settings Value Group

1401 Inverse O/C Time Protection Ip ON A


1402 Ip Pickup 0.88 A A
1403 T Ip Time Dial 0.20 sec A
1405 IEC Curve Normal Inverse A

Page 7 of 16
GALLANT-GPR-1_prn

Gallant Ispat 25MW / Folder /


SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

Group Inverse O/C Time Protection; Group IDMT(2)


No. Settings Value Group

1407 Voltage Influence Voltage controlled A


1408 U< Threshold for Release Ip 88.0 V A

4.5 Group Thermal Overload Protection; Group Therm Overload


Group Thermal Overload Protection; Group Therm Overload
No. Settings Value Group

1601 Thermal Overload Protection ON A


1602 K-Factor 0.87 A
1603 Thermal Time Constant 600 sec A
1604 Thermal Alarm Stage 100 % A
1610A Current Overload Alarm Setpoint 0.80 A A
1612A Kt-Factor when Motor Stops 1.0 A
1615A Maximum Current for Thermal Replica 2.46 A A
1616A Emergency Time 100 sec A

4.6 Group Thermal Overload Protection; Group Temp. Input


Group Thermal Overload Protection; Group Temp. Input
No. Settings Value Group

1605 Temperature Rise at Rated Sec. Curr. 100 C A


1607 Temperature Input Disabled A
1608 Temperature for Scaling 100 C A

4.7 Group Unbalance Load (Negative Sequence); Group Unbalance Load


Group Unbalance Load (Negative Sequence); Group Unbalance Load
No. Settings Value Group

1701 Unbalance Load Protection ON A


1702 Continously Permissible Current I2 12.3 % A
1703 Warning Stage Time Delay 5.00 sec A
1704 Negativ Sequence Factor K 13.5 sec A
1705 Time for Cooling Down 598 sec A
1706 I2>> Pickup 25 % A
1707 T I2>> Time Delay 1.50 sec A

Page 8 of 16
GALLANT-GPR-1_prn

Gallant Ispat 25MW / Folder /


SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

4.8 Group Differential Protection; Group General


Group Differential Protection; Group General
No. Settings Value Group

2001 Differential Protection ON A


2005 Increase of Trip Char. During Start OFF A

4.9 Group Differential Protection; Group I-Diff


Group Differential Protection; Group I-Diff
No. Settings Value Group

2021 Pickup Value of Differential Curr. 0.05 I/InO A


2026A T I-DIFF> Time Delay 0.00 sec A
2031 Pickup Value of High Set Trip 4.0 I/InO A
2036A T I-DIFF>> Time Delay 0.00 sec A

4.10 Group Differential Protection; Group Characteristic


Group Differential Protection; Group Characteristic
No. Settings Value Group

2041A Slope 1 of Tripping Characteristic 0.15 A


2042A Base Point for Slope 1 of Charac. 0.00 I/InO A
2043A Slope 2 of Tripping Characteristic 0.50 A
2044A Base Point for Slope 2 of Charac. 2.50 I/InO A
2051A I-RESTRAINT for Start Detection 0.10 I/InO A
2052A Factor for Increasing of Char. at Start 1.0 A
2053 Maximum Permissible Starting Time 5.0 sec A
2061A Pickup for Add-on Stabilization 4.00 I/InO A
2062A Duration of Add-on Stabilization 15 Cycle A
2063A Time for Cross-blocking Add-on Stabiliz. 15 Cycle A

Page 9 of 16
GALLANT-GPR-1_prn
Group Underexcitation Protection; Group Underexcitation
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

4.11 Group Underexcitation Protection; Group Underexcitation


Group Underexcitation Protection; Group Underexcitation
No. Settings Value Group

3001 Underexcitation Protection ON A


3011 T-Short Time Delay (Char. & Uexc<) 0.50 sec A
3012 State of Excitation Volt. Supervision ON A
3013 Excitation Voltage Superv. Pickup 2.00 V A
3014A Undervoltage blocking Pickup 25.0 V A

4.12 Group Underexcitation Protection; Group Characteristics


Group Underexcitation Protection; Group Characteristics
No. Settings Value Group

3002 Susceptance Intersect Characteristic 1 0.43 A


3003 Inclination Angle of Characteristic 1 80 A
3004 Characteristic 1 Time Delay 5.00 sec A
3005 Susceptance Intersect Characteristic 2 0.39 A
3006 Inclination Angle of Characteristic 2 90 A
3007 Characteristic 2 Time Delay 5.00 sec A
3008 Susceptance Intersect Characteristic 3 1.10 A
3009 Inclination Angle of Characteristic 3 90 A
3010 Characteristic 3 Time Delay 0.50 sec A

4.13 Group Reverse Power Protection; Group Reverse Power


Group Reverse Power Protection; Group Reverse Power
No. Settings Value Group

3101 Reverse Power Protection ON A


3102 P> Reverse Pickup -0.50 % A
3103 Time Delay Long (without Stop Valve) 5.00 sec A
3104 Time Delay Short (with Stop Valve) 1.00 sec A
3105A Pickup Holding Time 0.00 sec A

Page 10 of 16
GALLANT-GPR-1_prn
Group Forward Power Supervision; Group Forward Power
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

4.14 Group Forward Power Supervision; Group Forward Power


Group Forward Power Supervision; Group Forward Power
No. Settings Value Group

3201 Forward Power Supervision ON A


3202 P-forw.< Supervision Pickup 2.5 % A
3204 T-P-forw.< Time Delay 5.00 sec A
3203 P-forw.> Supervision Pickup 96.6 % A
3205 T-P-forw.> Time Delay oo sec A
3206A Method of Operation Method accurate A

4.15 Group Impedance Protection; Group General


Group Impedance Protection; Group General
No. Settings Value Group

3301 Impedance Protection ON A


3302 Fault Detection I> Pickup 0.98 A A
3303 State of Undervoltage Seal-in ON A
3304 Undervoltage Seal-in Pickup 88.0 V A
3305 Duration of Undervoltage Seal-in 4.00 sec A
3312 T END: Final Time Delay 3.00 sec A

4.16 Group Impedance Protection; Group Zones


Group Impedance Protection; Group Zones
No. Settings Value Group

3306 Impedance Zone Z1 108.20 Ohm A


3307 Impedance Zone Z1 Time Delay 1.00 sec A
3308 Impedance Zone Z1B 65.00 Ohm A
3309 Impedance Zone Z1B Time Delay oo sec A
3310 Impedanz Zone Z2 65.00 Ohm A
3311 Impedance Zone Z2 Time Delay oo sec A

4.17 Group Impedance Protection; Group Power swing


Group Impedance Protection; Group Power swing
No. Settings Value Group

3313 Power Swing Blocking OFF A

Page 11 of 16
GALLANT-GPR-1_prn

Gallant Ispat 25MW / Folder /


SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

Group Impedance Protection; Group Power swing(2)


No. Settings Value Group

3314 Distance betw. Power Swing - Trip-Pol. 8.00 Ohm A


3315 Rate of Change of dZ/dt 300.0 Ohm/s A
3316A Power Swing Blocking locks out Zone Z1 A
3317A Power Swing Action Time 3.00 sec A

4.18 Group Out-of-Step Protection; Group Out-of-Step


Group Out-of-Step Protection; Group Out-of-Step
No. Settings Value Group

3501 Out-of-Step Protection ON A


3502 Pickup Current for Measuring Release I1> 120.0 % A
3503 Pickup Current for Measuring Release I2< 20.0 % A
3504 Resistance Za of the Polygon (width) 8.89 Ohm A
3505 Reactance Zb of the Polygon (reverse) 22.54 Ohm A
3506 Reactance Zc of Polygon (forward char.1) 8.23 Ohm A
3507 Reactance Dif. Char.1 - Char.2 (forward) 4.82 Ohm A
3508 Angle of Inclination of the Polygon 90.0 A
3509 Number of Power Swing: Characteristic 1 1 A
3510 Number of Power Swing: Characteristic 2 3 A
3511 Holding Time of Fault Detection 20.00 sec A
3512 Min. Signal Time for Annun. Char. 1/2 0.05 sec A

4.19 Group Undervoltage Protection; Group Undervoltage


Group Undervoltage Protection; Group Undervoltage
No. Settings Value Group

4001 Undervoltage Protection ON A


4002 U< Pickup 99.0 V A
4003 T U< Time Delay 5.00 sec A
4004 U<< Pickup 88.0 V A
4005 T U<< Time Delay 2.50 sec A
4006A U<, U<< Drop Out Ratio 1.05 A

Page 12 of 16
GALLANT-GPR-1_prn
Group Overvoltage Protection; Group Overvoltage
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

4.20 Group Overvoltage Protection; Group Overvoltage


Group Overvoltage Protection; Group Overvoltage
No. Settings Value Group

4101 Overvoltage Protection ON A


4102 U> Pickup 121.0 V A
4103 T U> Time Delay 5.00 sec A
4104 U>> Pickup 126.5 V A
4105 T U>> Time Delay 2.50 sec A
4106A U>, U>> Drop Out Ratio 0.95 A
4107A Measurement Values Voltage protection with U-Phase-Phase A

4.21 Group Frequency Protection; Group Frequency Prot.


Group Frequency Protection; Group Frequency Prot.
No. Settings Value Group

4201 Over / Under Frequency Protection ON A


4202 f1 Pickup 47.40 Hz A
4204 T f1 Time Delay 2.50 sec A
4205 f2 Pickup 48.50 Hz A
4207 T f2 Time Delay 5.00 sec A
4208 f3 Pickup 52.60 Hz A
4210 T f3 Time Delay 2.50 sec A
4211 f4 Pickup 51.50 Hz A
4213 T f4 Time Delay 5.00 sec A
4214 Handling of Threshold Stage f4 Freq. prot. stage automatic A
4215 Minimum Required Voltage for Operation 66.0 V A

4.22 Group Overexcitation Protection (U/f); Group Overexcitation


Group Overexcitation Protection (U/f); Group Overexcitation
No. Settings Value Group

4301 Overexcitation Protection (U/f) ON A


4302 U/f > Pickup 1.10 A
4303 T U/f > Time Delay 5.00 sec A
4304 U/f >> Pickup 1.40 A
4305 T U/f >> Time Delay 1.00 sec A

Page 13 of 16
GALLANT-GPR-1_prn
Group Overexcitation Protection (U/f); Group Characteristics
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

4.23 Group Overexcitation Protection (U/f); Group Characteristics


Group Overexcitation Protection (U/f); Group Characteristics
No. Settings Value Group

4306 U/f = 1.05 Time Delay 20000 sec A


4307 U/f = 1.10 Time Delay 200 sec A
4308 U/f = 1.15 Time Delay 100 sec A
4309 U/f = 1.20 Time Delay 60 sec A
4310 U/f = 1.25 Time Delay 30 sec A
4311 U/f = 1.30 Time Delay 15 sec A
4312 U/f = 1.35 Time Delay 4 sec A
4313 U/f = 1.40 Time Delay 1 sec A
4314 Time for Cooling Down 3600 sec A

4.24 Group Rate-of-frequency-change protection; Group df/dt Protect.


Group Rate-of-frequency-change protection; Group df/dt Protect.
No. Settings Value Group

4501 Rate-of-frequency-change protection ON A


4518 Minimum Operating Voltage Umin 77.0 V A
4519A Reset Hysteresis for df1/dt & df2/dt 0.10 Hz/s A
4520A Measuring Window for df1/dt & df2/dt 5 Cycle A

4.25 Group Rate-of-frequency-change protection; Group Stage 1


Group Rate-of-frequency-change protection; Group Stage 1
No. Settings Value Group

4502 Mode of Threshold (df1/dt >/<) -df/dt< negative rate of freq. change A
4503 Pickup Value of df1/dt Stage 1.5 Hz/s A
4504 Time Delay of df1/dt Stage 2.00 sec A
4505 AND logic with pickup of stage f1 OFF A

4.26 Group Rate-of-frequency-change protection; Group Stage 2


Group Rate-of-frequency-change protection; Group Stage 2
No. Settings Value Group

4506 Mode of Threshold (df2/dt >/<) +df/dt> positive rate of freq. change A
4507 Pickup Value of df2/dt Stage 1.5 Hz/s A

Page 14 of 16
GALLANT-GPR-1_prn

Gallant Ispat 25MW / Folder /


SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

Group Rate-of-frequency-change protection; Group Stage 2(2)


No. Settings Value Group

4508 Time Delay of df2/dt Stage 2.00 sec A


4509 AND logic with pickup of stage f2 OFF A

4.27 Group Stator Earth Fault Protection; Group Stator E Fault


Group Stator Earth Fault Protection; Group Stator E Fault
No. Settings Value Group

5001 Stator Earth Fault Protection ON A


5002 U0> Pickup 5.5 V A
5005 T S/E/F Time Delay 0.20 sec A

4.28 Group Sensitive Earth Current Protection; Group Sens. E Fault


Group Sensitive Earth Current Protection; Group Sens. E Fault
No. Settings Value Group

5101 Sensitive Earth Current Protection ON A


5102 IEE> Pickup 50 mA A
5103 T IEE> Time delay 1.00 sec A
5104 IEE>> Pickup 200 mA A
5105 T IEE>> Time Delay 0.20 sec A
5106 IEE< Pickup (Interrupted Circuit) 0.0 mA A

4.29 Group Breaker Failure Protection; Group Breaker Failure


Group Breaker Failure Protection; Group Breaker Failure
No. Settings Value Group

7001 Breaker Failure Protection ON A


7002 Start with Internal TRIP Command Start Breaker Failure with CFC A
7003 Supervision Current Pickup 0.08 A A
7004 TRIP-Timer 0.25 sec A

Page 15 of 16
GALLANT-GPR-1_prn
Group Inadvertent Energisation; Group Inadvert. En.
Gallant Ispat 25MW / Folder /
SIMATIC GALLANT-GPR-1/7UM622 09.10.17 17:46:07

4.30 Group Inadvertent Energisation; Group Inadvert. En.


Group Inadvertent Energisation; Group Inadvert. En.
No. Settings Value Group

7101 Inadvertent Energisation ON A


7102 I Stage Pickup 0.9 A A
7103 Release Threshold U1< 66.0 V A
7104 Pickup Time Delay T U1< 5.00 sec A
7105 Drop Out Time Delay T U1< 1.00 sec A

4.31 Group Measurement Supervision; Group MeasSupervision


Group Measurement Supervision; Group MeasSupervision
No. Settings Value Group

8101 Measurement Supervision OFF A


8102 Voltage Threshold for Balance Monitoring 50 V A
8103 Balance Factor for Voltage Monitor 0.75 A
8104 Current Balance Monitor Side 1 0.50 A A
8105 Balance Factor for Current Monitor S1 0.50 A
8106 Current Balance Monitor Side 2 0.50 A A
8107 Balance Factor for Current Monitor S2 0.50 A
8108 Summation Thres. for Volt. Monitoring 10 V A
8109 Factor for Volt. Sum. Monitoring 0.75 A
8110 Summated Cur. Mon. Threshold on Side 1 0.10 A A
8111 Summated Current Mon. Factor on Side 1 0.10 A
8112 Summated Cur. Mon. Threshold on Side 2 0.10 A A
8113 Summated Current Mon. Factor on Side 2 0.10 A

4.32 Group Supervision; Group General


Group Supervision; Group General
No. Settings Value Group

8001 Fuse Failure Monitor ON A

Page 16 of 16