Professional Documents
Culture Documents
Operations 305B
Operate Process Control
Systems
OPERATE PROCESS
CONTROL SYSTEMS
Contents vii
Introduction 1
The Module 5
What is Competency?
Being COMPETENT at a job is: -
Re-Sitting Questionnaires
Repeats of activities
The Assessor will also tell you which elements of the competency you are
not yet competent in.
These tables are REALLY useful to help you study and identify
what you need to be able to do and know. Make sure you
understand these and ask your tutor if you do not.
Unit Name
and Code
Element or Part
of the
Competency
UNIT TITLE: PMA MAIN 201A
Undertake Minor Maintenance
Challenger TAFE 2004
Version 2 May 2005
Next Review May 2006
Issued by Training Coordinator ACEPT
371827881.doc
ELEMENT 1 OF 4: Able to Correctly Select and Use Spanners and Wrenches
ended spanners, questions
spanners and Incomplete
wrenches and state the socket spanners, then
purpose of each. hook spanners, pin
Indicates a knowledge
spanners, shifting Practical
and skills based outcome with an
assessment of learning
spanners, flogging activity
consisting of (real
a practical exercise.
spanners, pipe or
wrenches, strap simulated)
wrench, tension
wrench
Indicates a worked example or practical written exercise.
What you
must be How you
The scope of
able to do can be
things you
assessed
must be able to
do
Indicates important information and Critical Points.
STOP!
CHECKPOINT
5.2 Examine the condition for signs of severity and check log
for currency of the occurrence
5.7 Provide face to face details of the alarm and action taken to the
next supervisor at shift changeover.
7.5 Follow through items initiated until final resolution has occurred
In turn, operator interface units are used to control and monitor the process.
The various sub-sections include:
Each of these sub-sections constitutes a major part within the control system. A brief
description of each sub-section is given below detailing its primary function.
Communication
Highway
Field Interface Unit Distributed Control Distributed Control Field Interface Unit
Entity Entitiy
Communication Highway
The communication highway can be considered as the major artery for all information
flow between the various components of the DCS. The communication highway
provides a reliable high-speed communication path for data travelling between
controller entities, operator interfaces, and other devices.
This upper level in the communication system is a highly secure system that provides
exceptional data integrity. Data throughput is maintained under heavy loading, which
may occur during plant-upset conditions. Various methods of data compression are
used to achieve this end.
I/O System
Process I/O signals interface to the Distributed Control Entity via termination modules
or units. The terminations are connected directly the their corresponding slave
module which digitise the data and then pass the information, via the slave bus to the
Processor module. There are a variety of slave modules to suit various process
signals types.
Data acquisition begins at the RTU or PLC level and includes meter readings and
equipment statuses that are communicated to the SCADA as required. Data is then
compiled and formatted in such a way that a control room operator using the SCADA
can make appropriate supervisory decisions that may be required to over-ride normal
RTU (PLC) controls.
SCADA systems typically implement a distributed database which contains data
elements called points. A point represents a single input or output value monitored or
controlled by the system. Points can be either "hard" or "soft". A hard point is
representative of an actual input or output connected to the system, while a soft point
represents the result of logic and math operations applied to other hard and soft
points. The point values are normally stored as value-timestamp combinations; the
value and the timestamp when the value was recorded or calculated. A series of
value-timestamp combinations is the history of that point.
[edit]
Human Machine Interface
The HMI/SCADA industry was essentially born out of a need for a user friendly front-
end to a control system containing programmable logic controllers (PLC). While a
PLC does provide automated, pre-programmed control over a process, they are
usually distributed across a plant, making it difficult to gather data from them
manually. Additionally, the PLC information are usually in a crude user-unfriendly
format. The HMI/SCADA gathers information from the PLCs via some form of
communication method, and combines and formats the information. Since the early
1990s the role of SCADA systems in large civil engineering solutions has changed,
requiring them to perform more operations automatically. A sophisticated HMI may
also be linked to a database to provide instant trending, diagnostic data, scheduled
maintenance procedures, logistic information, detailed schematics for a particular
sensor or machine, and expert-system troubleshooting guides. Since about 1998,
virtually all major PLC manufacturers have offered integrated HMI/SCADA systems,
many of them using open and non-proprietary communications protocols. Numerous
specialized third-party HMI/SCADA packages offering built-in compatibility with most
major PLCs have also entered the market, allowing mechanical engineers, electrical
engineers and technicians to configure HMIs themselves, without the need for a
custom-made program written by a software developer.
Hardware solutions
SCADA solutions often have Distributed Control System (DCS) components. Use of
"smart" RTUs or PLCs, which are capable of autonomously executing simple logic
processes without involving the master computer, is increasing. A functional block
programming language, IEC 61131-3, is frequently used to create programs which
run on these RTUs and PLCs. Unlike a procedural language such as the C
programming language or FORTRAN, IEC 61131-3 has minimal training
requirements by virtue of resembling historic physical control arrays. This allows
SCADA system engineers to perform both the design and implementation of a
program to be executed on a RTU or PLC.
System components
The three components of a SCADA system are:
1. Multiple Remote Terminal Units (also known as RTUs or Outstations).
2. Master Station and HMI Computer(s).
3. Communication infrastructure
Master Station
The term "Master Station" refers to the servers and software resposible for
communicating with the field equipment (RTUs, PLCs, etc), and then to the HMI
software running on workstations in the control room, or elsewhere. In smaller
SCADA systems, the master station may be composed of a single PC. In larger
SCADA systems, the master station may include multiple servers, distributed
software applications, and disaster recovery sites.
The SCADA system usually presents the information to the operating personnel in
the form of a mimic. This means that the operator can see a representation of the
plant being controlled. For example, a picture of a pump connected to a pipe can
show the operator that the pump is running and how much fluid it is pumping through
the pipe at the moment. The operator can then switch the pump off. The HMI
software will show the flow rate of the fluid in the pipe decrease in real time.
The HMI package for the SCADA system typically includes a drawing program that
the operators or system maintenance personnel use to change the way these points
are represented in the interface. These representations can be as simple as an on-
screen traffic light, which represents the state of an actual traffic light in the field, or
as complex as a multi-projector display representing the position of all of the
elevators in a skyscraper or all of the trains on a railway. Initially, more "open"
platforms such as Linux were not as widely used due to the highly dynamic
development environment and because a SCADA customer that was able to afford
the field hardware and devices to be controlled could usually also purchase UNIX or
OpenVMS licenses. Today, all major operating system are used for both master
station servers and HMI workstations.
Operational philosophy
Instead of relying on operator intervention, or master station automation, RTUs may
now be required to operate on their own to control tunnel fires or perform other
safety-related tasks. The master station software is required to do more analysis of
data before presenting it to operators including historical analysis and analysis
associated with particular industry requirements. Safety requirements are now being
applied to the system as a whole and even master station software must meet
stringent safety standards for some markets.
For some installations, the costs that would result from the control system failing is
extremely high. Possibly even lives could be lost. Hardware for SCADA systems is
generally ruggedized to withstand temperature, vibration, and voltage extremes, but
in these installations reliability is enhanced by having redundant hardware and
communications channels. A failing part can be quickly identified and its functionality
automatically taken over by backup hardware. A failed part can often be replaced
without interrupting the process. The reliability of such systems can be calculated
statistically and is stated as the mean time to failure, which is a variant of mean time
between failures. The calculated mean time to failure of such high reliability systems
can be in the centuries.
Almost all Control Systems require the Control Technician to input some information
or command in order to do its job. These commands may be anything from setting in
instructions, starting or stopping machinery, or activating an emergency sequence.
The Control Technician will also need to access information from the control system
data storage facilities, and this requires to technician to supply the system with
information or commands in order to display the desired information.
KEYBOARD
TRACKBALL or MOUSE
With a touch screen, all that is required is to touch the screen with your finger on the
touch pad and it will activate the tag. Touch screens generally do not have the depth
of control that is available with a mouse or trackball. Usually they are just for
changing from one display to another or calling up the faceplate of a controller.
Keyboards can be used for all the above, with the addition of being able to type in
information such as Shift Logs, Test results etc. Of course, the keyboard is
essential for engineers to configure and adjust any controllers. Keyboards are
also excellent for rapid call-up of specific pages. These displays usually have
a dedicated button on the keypads. Such a display could be an Alarm
Summary, Emergency sequence controller or the like.
The console keyboard is the communication interface between the operator and the
distributed control system. The keyboard provides interaction with the graphic
displays to enable the operator to adjust process parameters for efficient control of
the process. It also allows control of process alarms, access to process trend and
archive data, and in some cases engineering and maintenance functions.
The keyboard is an electronic device that connects directly into the console hardware
and provides a tactile and audible feedback to operator key actions. A membrane that
is a rugged long lasting surface suitable for the industrial control room environment
generally covers it. Designed for operator ease, the keys are divided into specific
areas to allow for ergonomic operation.
Printer activation
Password access
User defined keys: These keys can be assigned to specific
displays. This allows one key access to
frequently called displays. Overview displays
are normally assigned to these keys.
The operator control console is the human-machine interface for the distributed
control system (DCS). The control console provides a window into the DCS to allow
the production operator to monitor and effectively control the process. The operator
can start and stop drives and pumps, adjust process set points to maintain
production targets, monitor and trend important process variables, and easily
interpret and manage process alarms.
Effectively the operator control console replaces the traditional control room mimic
panel. This has allowed the CHALLENGERisation of control in most modern
manufacturing facilities. This also realised a dramatic cost reduction in the
installation and running of these plants.
As shown on Appendix 3-A, the Operator Control Console is an integral part of the
DCS. Without the operator control console there is no effective way to view and
control the process.
In normal operation the operator console performs the following:
Receives operator commands from the keyboard, touch screen or similar, and
transmits the command via the communication system to the DCS
Updates process information on displays as new values are received from the
DCS
Maintains a list of the last set of alarms, this could be as many as 1000
Provides a printing facility for alarms, reports, screen displays, system events
Anyone who is familiar with the Microsoft product Windows (and who isnt!) should
have no difficulty navigating around a control consul using this system.
As stated, most PC literate people are very familiar with the format.
Many windows can be displayed on the screen at the same time; enabling
operators to more easily customise the display according to personal
preference or the situation. Group displays of Faceplates, trends, process
graphics and alarms may all be displayed at the same time.
STOP!
CHECKPOINT
3/. What is the component that links all the other components together?
___________________________________________________________________
Graphic Displays
The purpose of console graphic displays is to provide the operator with a truly
representative image of the current conditions of the process. This provides real time
data of important process values and the operating status of plant equipment. It is the
visual link between the operator and the process.
Operator console displays are organised in a hierarchical structure of plant overview
displays, secondary displays, group displays and loop details. This allows the
operator to quickly and easily find displays, and to observe process parameters with
a wide view, or in varying levels of detail.
Graphic displays are usually based on plant layout. This could be in the form of
Piping and Instrument Diagrams (P&ID's) or Plant Schematics. This form of structure
enables the operator to graphically picture the process and provide a clearer
understanding of control requirements.
Static Display Elements
There are a number of elements that make up a dynamic graphic display. These
elements fall into two categories. Either static/operational elements or dynamic
elements
The static/operational elements include:
Touch pads
Text information
Graphic description
These elements convey low priority graphical information to the operator and enable
movement between displays.
Display Hierarchy
A clear structured hierarchy of displays greatly assists operators in finding the display
of interest. From an ergonomic point of view, displays should be organised in three
levels.
A secondary level that shows more detailed information of a part of the primary
level. Secondary displays may be accessed from display select points in the
primary display or directly from dedicated `display select panels'. These
displays will also have a series of `standard associated displays', including
group, trend, report, status, help, and alarm displays. Generally each primary
display will have a number of secondary displays associated with it.
A tertiary level that shows still further details on a part of the secondary level
display. Tertiary displays may be accessed by display select points on the
secondary display.
There is an index display associated with each primary display.
Index displays are used to go directly to secondary or tertiary displays.
Display Select Summary
This facility is used to assist operators in finding their way through the
display hierarchy and are summarised below:
User defined keys Linked directly to the overview displays.
Indexes
Each primary or overview display has an associated index
display that covers the secondary and tertiary displays in
that area.
Area identification Each primary display has an identification icon
that appears on every display under the
primary display.
Split screen points These points assist the operator in following
process lines that span over more than one
display.
Display select points Branching or Zoom points. Either touch or
keypad selected, they are used to provide
more detail on a specific area of the display
schematic. Usually links to a tertiary display.
Standard associated displays Linked to operating displays, these standard
displays may include group, trend, report,
status, help, and alarm displays.
Display select panel keys These keys can be used to directly call up
secondary displays.
A PRIMARY LEVEL DISPLAY
Effective communication is something that is developed over time, with the Control
Operator being fully conversant with both the control of the plant, and experience as
a field operator as well. Ideally, both the Control Operator and Field Operator should
have experience of both ends of the communication scenario.
Safety Issues
Emergency Issues
Production Changes
Equipment Malfunctions
Requests to investigate possible problems
Non-routine equipment operation
Maintenance issues
Laboratory results
STOP!
CHECKPOINT
SET POINTS are the target for the computer to aim for. It will try to control the
PROCESS VARIABLE to achieve the SET POINT. Set Points are typically commands
given to the computer by the operator using an input device such as mentioned
above.
OUTPUT is the amount of effort the controller is using to achieve the SETPOINT. It is
expressed as a percentage (%) opening of the valve that the computer is controlling.
If the OUTPUT is 50%, then of course, the computer has made the valve open half
way. The operator can also change the OUTPUT by running the controller on
MANUAL MODE. When the controller is set to AUTOMATIC MODE, the controller
decides the OUTPUT, not the operator.
Imagine a car, it has many PARAMETERS; temperature, speed,
level, flow etc. Look at the parameter temperature; there are
the Oil, Water and Air-conditioning temperatures. These are
some of the cars Process Variables. Suppose the car has a
Cruise Control. It controls the speed of the car. The control operator
(driver) commands the control to maintain a speed of 100kmph. This is a
SET POINT. The controller will adjust the OUTPUT to maintain a speed of
100kmph AUTOMATICALLY. The driver can also change the output
themselves, by disabling the cruise control and pushing the accelerator
pedal. This changes the OUTPUT .MANUALLY.
Controller Modes
Automatic
Manual
Cascade/Automatic
Automatic Control
In automatic mode, a controller will adjust the output, and control the final control
element (valve, switch etc.) to align the process variable with a set point or target.
The Control Operator selects this set point.
Automatic mode is generally the normal mode employed during steady plant
operation.
Manual Control
In manual mode, the output is adjusted by the Control Operator to control the final
control element (valve, switch etc.) The Control Operator must adjust the output to
control the process variable. The process variable will tend to wander unless the
operator is constantly changing the output with changing plant conditions.
Manual control as applied to switch controllers such as pump stop/start situations
usually means that the Control Operator has to switch the equipment on or off.
Cascade/automatic Control
Cascade control is a form of automatic control. The main difference is that one
controller determines the set point for the other controller.
The Control Operator will determine a set-point for the Primary or Master Controller,
this will in turn determine the set-point for the Secondary or Slave Controller.
This form of control is used to achieve closer and faster control when slow processes
are involved, such as on process heaters like crude oil heaters. A cascade control
system can achieve a 10 to 100 times improvement in control over a single loop
system used on the same process.
Cascade control is used for more accurate and faster primary loop control over
single-loop control by using a related secondary loop to pre-empt a deviation before it
develops in the primary loop.
Both these controllers must be run on Automatic for the cascade facility to work.
Usually the Parameters being controlled are different to each controller.
Dynamic elements convey high priority information to the operator that is essential to
control the process. These elements include:
Analogue elements
Digital elements
Faceplate elements
Trend elements
Process Control Loops
Control loops are the building blocks of a DCS. They pass information and
commands between Controllers, Measuring devices, Valves etc.
A
Process
Disturbance
or Load
Process
Variable
Final
Control Process
Element
Set Point
Error Signal
Measuring
Controller
Element
Closed Loop
Here is a typical Closed Loop as it would appear on a Process & Instrument
FT
FIC
FY
I/P
PUMP
Diagram (P&ID)
Analogue Elements
There are various ways of displaying analogue information. The decision to use one
type of representation over another is dependent on the importance of the value. A
very important value will normally be shown in a bar and numeric form, with less
important values in numeric form only.
Colours of the values should conform to a predefined convention, similar to the
above colour chart. More important values will be displayed in a bright shade, with
less important values in a darker shade.
The values should change colour whenever the parameter goes into an alarm state.
For example, if a pressure creates a high priority alarm then the value should go from
green to red. The type of alarm should also be indicated next to the value. For
example, an `H' or 'L' to represent a high or low alarm condition.
The three common analogue elements include, numerical, bar and deviation bar.
These are described below.
Numerical
The value is displayed as a dynamic value, eg. 74 Mpa. The engineering unit will be
in a lower intensity than the value. The engineering unit may sometimes be omitted
and replaced by a live data designator. This approach relies on the majority of live
data having the same engineering unit type.
Bar
The value is displayed as a vertical bar that changes in size with the magnitude with
the parameter. A graduated grid along side the bar indicates the zero and span
points. A set point would be indicated by a triangle next to the bar.
Deviation Bar
The deviation from the normal or set point is shown as a bar that moves above or
below the required value.
Digital Elements
STOP!
CHECKPOINT
Control keys
Control keys allow the operator to interact with an assigned control faceplate on a
graphic display. Once a faceplate has been selected either by keyboard input, touch
screen or track-ball, these keys allow the operator to perform any of the following
functions, dependent on faceplate type:
Stop and start devices
With a Windows based system, clicking on the Output or Set-point buttons will raise
a keypad window into which the numerical value can be selected, instead of having
to use the alpha-numeric keypad of the keyboard.
Many windows displays also allow you to drag set-point arrows on the faceplate to
change the value.
A clear understanding of the control keys is essential to ensure the operator provides
effective control of the process. The layout of the control keys will vary from one
vendor to another. It will be necessary for the operator to familiarise themselves with
the applicable keyboard to ensure they gain effective control of the process.
Faceplate Elements
Faceplate elements provide a means for the operator to interface directly with a
particular process control loop. The faceplate element is a graphical representation of
the parameters associated with a control loop. This control loop can either be an
analogue or digital loop.
To assist in the understanding of the control keys, we will review their operation with
respect to three common control faceplates. Namely the PID controller, hand switch,
and Gap controller faceplates.
Analogue Loops
A typical example of an analogue control loop would be that of a flow control system.
The faceplate would display all or some of the following parameters:
Loop number description of loop and tag name
Low/high alarms indication of the low and high alarm limit values
Deviation alarm deviation limit indicators
L
oop F
IC
-1
010 X
n
umbe
r F
lo
w C
ont
rolV
alv
e
Con
tro
lmo
de M
an
ual A
ut
o
K
lt
rs/h
r E
ng
in
ee
ri
n gu
ni
t
5
000
Z
er
o/s
panv
al
u e
s
2
500 S
etpoint
P
roces
s 2
250
v
al
u e
v
ari
a b
le L
ow /
h i
gh
a
la
rm s
0
.0
O
UT4
2%
O
ut
putv
al
u e
Loop number
HS-2001B X
CONDENSATE STANDBY PUMP
Control mode
Manual Auto
Gap Control
Gap Control is the simplest form of automatic control. It is also called two-position
control. Either side of the set point are two switch points, on and off. When the
process variable deviates to these switch points, the controller changes the final
control element from one position to another. These positions are either on or off,
open or closed. For a motor, the positions would be on or off. A valve would be
open or closed.
Lets look at a Level controller for a vessel. The desired level is 45%. The High switch
point is set at 50%; the Low switch point is set at 40%. These are 5% either side of
the desired level. This is called the Dead-band or Gap, the range in which no action
is taken by the loop.
If we start with the final control element (in this case a valve) OPEN, the level will
drop until it reaches 40%, then the valve will CLOSE, until the level reaches 50%,
when it will open again.
Alarm Status
LEVEL [%] Engineering Unit
100 Scale
High Alarm
Low Alarm
0.0
GAP CONTROLLER
FACEPLATE
Activating a Faceplate
With a Windows based system, you can continue to use the cursor to click on the
command buttons of the faceplate to change the control mode instead of having to
use the keyboard control keys.
Pop-up Elements
Graphic displays with a large number of control points utilise the space saving
feature of Pop-up elements. The pop-up element displays an operator control
faceplate in a predefined location on the graphic. Usually a maximum of one, or two,
pop-ups is permitted on any one graphic display.
The pop-up allows the operator to take control of important controller actions while
still monitoring other related process parameters. This prevents the operator toggling
between group displays (faceplate displays) and the operating graphic display.
STOP!
CHECKPOINT
STOP OFF
4/. The feature that allows you to look at and operate a Faceplate while still
looking at a graphic display is called a __________________
Maintenance schedules
Spreadsheet reports
Trend Displays
Operator console trend displays provide the screen equivalent of strip chart pen
recorders. Trend display elements can be configured into any display to show the
operator from one to typically eight trends. This element is available is full screen or
smaller height sizes to permit graphic displays to be built around the trend element.
The following is a summary of the trend display element:
When displayed on the console screen, each trend display element appears as
a strip chart with coloured coded trend lines.
For analogue variables, the height of the trend element represents the full span
of the variable in engineering units.
For digital variables (on/off, a section of the screen of the display element can
be used to show steps for the on/off states.
The time span shown on the screen is a function of the selected width of the
trend element and the trend resolution.
The trend element also shows the current value, tag identification and alarm
information for the trended variable.
Trend Elements
Live data can be shown in a trended format using pre-configured trend display
elements. These elements provide a history of data over a pre-defined period, which
is usually dependent on the resolution of the trended data.
Time
Cursor
100%
80%
79 DegC TI2001 Lean Glycol
60%
70% LIC2002 Glycol
40% PI2001 Base 1 minute
60 kpa
20% 1.5 Kltr/hr FIC2001 Rich Glycol 5 minutes
1.5 Kltr/hr FIC2001 Lean Glycol
0% 15 minutes
75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 min
1 hour
8 hours
FIC 2001
100%
0
80%
79 DegC TI2001 Lean Glycol
60%
70% LIC2002 Glycol
40% PI2001 Base 1 minute
60 kpa
20% 1.5 Kltr/hr FIC2001 Rich Glycol 5 minutes
1.5 Kltr/hr FIC2001 Lean Glycol
0% 15 minutes
75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 min
1 hour
8 hours
Clicking on a Process variable will raise a Pop-up showing various information about
the Tag, such as its range (compared to 100% of the trend), alarm settings etc.
Trend Display Manipulation
Once a trend display is shown on the console screen, the trend can be manipulated
to assist operator analysis of the process. The following activities are supported.
Modify range
The range of the variable initially shown on the trend element is established upon
configuration. The range actually shown by the trend element can be changed by the
operator to magnify changes in-the process variable on the screen and facilitate
analysis of process conditions.
Pan
The data shown on the trend display can be shifted back in time (within the limits of
the stored data on the hard disk) to provide a historical perspective of the process
variable. The same time span is shown by the trend element, but it is shifted back in
time.
Zoom
The time- span shown on the screen can be expanded or compressed to facilitate
analysis of the trend. Zooming in reduces the period of time shown on the screen.
Zooming out increases the period of time shown on the screen. Zooming in and
reducing the range of the variable shown, has the effect of magnifying the trend data.
Window Magnifying
The time scale for a windowed section of the trend display can be increased to
facilitate determination of the exact time of a process disturbance.
STOP!
CHECKPOINT
2/. Operator Interface Units would typically use historical data to create?
4/. What is the purpose of, and how do you use the Time Cursor?
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
5/. Pop up displays from the Trend Display will often show us?????
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
To this end, it is necessary to view the alarm system, not as a separate function, but
as an integral part of the operating interface that actively complements the other
operating functions.
Typically, the alarm management in a DCS will reside within the Operator Interface
Units, with some associated logic located in the Distributed Control Entities.
The Distributed Controlling Entities are responsible for detecting the alarm condition
and reporting it to the Operator Interface Units. The OIU is responsible for handling
the grouping, prioritisation, inhibiting, annunciation and logging of the alarm
condition.
Process problems are announced with alarms. Field input loops are wired and
configured into the Distributed Control Entities that are distributed throughout the
process plant.
Within the Distributed Control Entities, processor modules are configured with
various types of input loops. The processor modules are able to raise a variety of
alarms based on the type of process loop. Once received at the OIU console, the
process loops are defined with one of the following tag types:
Analogue Tags
Analogue tags report a real number together with several associated alarm states,
i.e. high-high, high, low, low-low, out-of-range. When alarms are not required for a
loop, the alarm thresholds are set to a value outside the operating limits.
Digital Tags
Digital tags have two possible states, 0 or 1. Either of these states may be
designated as an alarm state.
Hand Switch tags have two states that the operator may set or reset. This point may
also include several feedback indications. This point can be configured to have a
single alarm state.
Station Tags
Station tags represent control loop faceplates with their associated parameters.
Station points may generate the following alarm types:
High & low Process variable has exceeded a defined threshold.
PV-SPIndicates the process variable.
Deviation Has deviated from the set point by more than a defined amount.
These events will vary depending upon the vendor equipment being used. However,
most of these events will occur in one form or another.
The alarm operation and the way alarms are grouped and/or prioritised will vary from
one vendor to another. Each of these items will be discussed further in general terms.
Alarm Operation
When a process alarm occurs a sequence of events will occur. The operator must
respond to these events. These are summarised below:
1) An alarm indicator will flash in the system information section at the top of
the screen.
3) The alarm will flash and appear in a colour configured for the point.
4) The point will continue to flash until acknowledged by the operator using
the 'Alarm Acknowledge' key.
5) At this time the alarm will go steady but remain on the alarm summary and
in other configured displays in its alarm colour.
6) When the point returns to normal (a non-alarm state) the point will return to
its normal colour and remain in the alarm summary until acknowledged.
(Vendors differ on how they handle return-to-normal (RTN) alarms.
7) Another method clears the point from the alarm summary when it RTN
without the need for operator acknowledgment) at this time it will clear from
the alarm summary display. This is not a satisfactory configuration in some
circumstances, as it could be intermittent, momentary, and be difficult for
the operator to investigate.
Alarm Groups
Alarms can be grouped to coincide with specific plant areas. If a tag in a group goes
into alarm, that alarm group will flash in its associated alarm summary display.
Additionally, audible tones can be assigned to sound when a tag goes into alarm.
The alarm summary screen can be called up to see which point is in alarm, so the
operator can take the necessary action.
The display select panel indicators can also be configure to flash whenever any point
on the associated graphic is in alarm. This provides an easy to see method for
identifying alarms in specific process areas.
Alarm groups can also be used for selective alarm reporting to particular Operator
Interface Unit consoles.
A primary display showing an alarm situation; the alarm button is lit up, and the
process variable mimic in alarm state is showing red.
Alarm Priorities
Medium-priority (Mauve).
Low-priority (Yellow).
Fault-priority (Brown).
If alarms of different priority occur, the highest priority alarms take precedence over
low priority alarm tags. This feature can be used to sort alarms in the alarm summary
displays. Alarm priorities can also be assigned to a unique colour. This allows the
operator to quickly identify high priority alarms and take the necessary action.
ALARMS HISTORY
Acknowledge ALL
Medium priority
These alarms represent deviations from normal operating conditions,
however they do not represent an immediate threat to production or
equipment.
Low Priority
These alarms represent operator information events and do not represent a threat to
production or equipment.
Fault priority
These alarms represent faults to DCS hardware or other associated hardware.
We will now look at two procedures for handling alarms, using the display select
panel.
Procedure 1
Procedure 2
There are significant advantages to this scheme. Firstly the 'display select panel' acts
as an interactive alarm annunciator. The operator can immediately recognise which
areas of the plant are in alarm.
Secondly, this scheme shows the alarm graphically, as opposed to the alarm
summary where the alarm is identified by the operator having to physically read the
loop name and description.
a) Press the 'ALARM' key on the keyboard to access the master alarm display.
b) Select/touch the 'ALARM' indicator at the top of the graphic to view the correct
alarm for this graphic area.
The alarm summary screen displays a list of all current alarms. As alarms occur they
are logged into the alarm summary buffer. Whenever an operator calls up the alarm
summary screen, the buffer displays the current list of alarms. Alarms may be either
process related or system hardware faults.
Vendors of Distributed Control Systems vary how they handle and display alarms.
Generally however, there will be a master alarm summary that contains a list of all
alarms, and minor alarm summaries that will contain a sub-set of these alarms.
The format in which alarms will be displayed also varies. Some systems display
alarms in chronological order with no grouping or prioritisation. Other systems will
have an option to group alarms by groups or priority, or both.
The alarm summary display will contain some or all of the following elements:
Tag name Process loop name and number.
Alarm type/group Alarm type, i.e. 'H' (high), 'L' (low), 'A' (digital) or Alarm
group number, e.g. '38'.
With this information the operator is properly informed of the nature and type of
alarm. This information is also logged onto the alarm printer and historic storage
device for later retrieval if required.
Alarm Inhibiting
Alarm inhibiting is a means of disabling alarm actions from occurring. Alarm inhibiting
may also be termed as '
alarm override'. If a process tag is inhibited and then goes into alarm, this tag will not
be annunciated by the control system.
There are two basic methods of alarm inhibiting:
Manual inhibiting.
Automatic inhibiting.
Each tag defined in the operator interface unit may be individually inhibited.
During these circumstances, the operator may decide to temporarily inhibit the tag
until normal operation is resumed. This will stop annoying alarms from interfering with
true process alarms.
Using special control tags, initiate logic that in turn inhibits or enables alarms.
Allow the operator to globally inhibit alarms when the associated process
equipment is not in service, and automatically re-enables alarms when the
equipment is returned to service.
Automatically inhibit low priority alarms when process shutdown occurs, and
automatically re-enable alarms when the process is restarted.
This form of alarm inhibiting removes unnecessary alarms from the alarm summary
displays. This ensures only relevant alarms are annunciated.
It is vitally important that the operator is aware of inhibits on a loop which they may
be operating. There are several ways of indicating this when viewing the tag on either
a graphical or faceplate display. This may include:
Colour change The process variable or state will change to a unique colour
indicating the alarm has been inhibited.
Alarm indicator The alarm indicator field adjacent to each tag may display a
unique character indicating the alarm has been inhibited.
!
Inhibiting alarms, for whatever reason, involves risk. It is
absolutely
vital that any enterprise has a SAFE WORK SYSTEM that
will address the risks involved in Alarm
Inhibiting.
This system may only apply to higher levels of alarm,
or may apply in progressively tighter control for ascending
levels of alarm.
The colour convention used to distinguish various alarm priorities varies. There are
no international conventions that can be used. Conventions are left to the discretion
of the control systems vendor or user.
However, as a guide, the colours chosen to depict various alarm conditions should be
reserved for alarms only, and not used for any other purpose.
As an example, the following colours could be used:
STOP!
CHECKPOINT
Importance
Location
Time of Occurrence
Importance and Time of Occurrence
4/. What information is usually displayed for a particular alarm in an Alarm
Summary?
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
5/. Why can Inhibiting or Disabling Alarms be hazardous, and how should the risk
be controlled?
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
XY Graphs
The operator console provides the capability to graph process variables as a function
of another process variable. When displayed on the screen, this graph appears as a
single page XY graph with coloured trend lines. The current value, the identification,
and alarm information for the trended variables is also displayed.
Other Trending Formats
Trending data can also be displayed in a variety of other formats. The trending format
will depend on operation requirements. Other formats may include:
Three-dimensional graphs
Pareto charts
Histograms
Pie charts
Spreadsheet Reports
The spreadsheet reporting function that is integral with the operator interface units is
used to create and print spreadsheet reports. Spreadsheet reports tabulate and
summarise plant operation. This may include:
System event reports Drive/pump run hour reports
Historical data
Process Events
When an discrete (on/off device (pump/drive, valve/damper changes state, this event
is logged into the system event report.
Operator Actions
When an operator changes the mode of a controller, adjusts set points or outputs,
starts a drive, acknowledges an alarm, or any other operator action, this event is
logged into the system event report.
Event triggered
Event Triggered
These reports are activated by a specific process or system event. A typical event
report would be a test report or a plant shutdown status report.
Automatically
These reports are the most common type of report. The report is processed on a
periodic basis, usually at a specific time each day or month. A typical automatic
report would be a daily production report or a monthly inventory report.
Trend Logs: This log collects and prints trend data at specified
intervals.
Trip Logs: This log provides a history of-values before and
after a specific process or system event.
Snapshot Log: This log collects and prints current process
values. Snapshot logs may be event or time
triggered.
Logging Functions
Logging retrieval
The log retrieval function allows logs that have been stored on the hard disk to be
printed. This includes custom logs and system event logs. This function provides a
Demand Log capability for custom logs and event logs. The Demanded Log can
either be a previously stored log, or a current log.
To access the log retrieval function, use the log By Name' key. The system will then
prompt for the name and type of log to be processed.
Log Status
Log status provides an overview of the status of all log reports. It allows the operator
to change the log's status. This includes activating and deactivating logs and
cancelling logs waiting to print
To access the log status function, press the `Log Summary' key.
Data Archiving and Retrieval
Data archival and retrieval functions are standard feature of all modern DCS operator
consoles. Hard disk storage on operator consoles is not unlimited so this facility
provides a way to store and retrieve process and system data to and from the hard
disk device.
Data archiving is a standard requirement to maintain an audit trail of plant operations.
Data archiving also provides an accurate digital history of process operations for
subsequent analysis and process improvement studies.
Data Archiving
Data archiving enables the user to move historical data from the hard disk onto
removable long-term storage devices. Historical data stored on the hard disk is
automatically, or manually transferred to the removable archive device. The type of
historical data that can be archived includes:
Trend data
Process events
System events
Spreadsheet reports
The most common archive devices today, are the optical disk storage medium. These
devices have a large storage capacity and are easily removed and stored.
Data Retrieval
Data retrieval enables the user to move archived data from long-term storage
devices back into an historical data area on the hard disk of the operator console.
When retrieving archived data, the user specifies a period of time and the name of
the archive medium to obtain the data. The data is then copied from the removable
archive medium into a reserved section on the hard disk. Once the data has been
copied it can be accessed in the following ways:
Trends can be displayed, manipulated and printed from the screen in the
normal format.
Process and system events (alarms, etc.) can be printed in their original format.
STOP!
CHECKPOINT
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
________________________________________
2/. Name five (5) formats in which Real Time Trends can be displayed.
On Demand
Event Triggered
Automatic
The displays available to the Control Operator allow an insight into the status of
various pieces of equipment on the plant.
Some of the more common sources of information are: -
Hand-switch Faceplates
These will indicate the on or off status of equipment. Typically they will apply to
rotating machinery such as motors, centrifuges, rotating filters and cooling fans.
Other items may include the position of valves or the status of heating elements.
Hand switches are of course Digital controllers and as such will indicate either on or
off, or more correctly 0 state or 1 state.
Group Displays
Group Displays may be constructed for a particular item of equipment such as a
major compressor, or they may be constructed for a section of a plant. They give the
Operator access to relevant faceplates for the equipment in question on the one
display.
Alarm Summaries
Alarm summaries may be configured so that any change in status of a piece of
equipment will trigger an alarm.
The alarm may be simple, perhaps just an on or off statement, but on more
complex equipment such as a large compressor, there could be many alarms tied to
the various monitoring facilities. These could include: -
Usually the Primary, or highest level of display in which the equipment is shown, will
have an alarm indication showing that there is an alarm state for the compressor. The
Operator would than access the detailed display from the primary to assess the
STOP!
CHECKPOINT
actual status of the equipment.
1/. Name three (3) types of display that will give an indication of equipment
status.
On/Off Status
Speed
Alarm Status
On/Off and Alarm Status
2.0 Access control information
INTERPRET ALARMS
2.3 At the completion of this topic, the learner
must be able to interpret alarms and prioritize
steps to ensure control of system is
maintained
In 1.6 we looked at Alarms and Summaries. The summary is complied by the Alarm
Management System. This system displays the alarms according to their importance.
Each alarm is assigned a priority according to the needs of the plant. When several
alarms are active, the Alarm Manager will display them in order of priority, and in a
sub order of event log (the time the alarm occurred).
!
REAL.
Faults in alarm systems do occur, but to assume a fault can
lead to serious plant problems, or even
TREAT ALL ALARMS
disastrous results. AS REAL
UNTIL PROVED OTHERWISE
Reacting to an alarm
When an alarm is raised, it is important to react to it in a logical and organised way.
Determine the Priority of the alarm
Go to the graphic display that shows the alarm in CONTEXT.
Examine all the information related to that point.
Determine the cause of the alarm state
Take corrective action
Monitor the corrective action until the alarm state Returns to Normal (RTN)
ALARM
%
100
If we click on the Contactor Base Controller Tag LIC 1001, we
80
can bring up the Faceplate.
60
You can see that the process variable analogue bar is yellow
(set-point alarm state) because it is outside the error limits set
for the process variable compared to the set point.
0
We can also see that the Output is 100%, meaning that the
OUT 100%
controller has called for maximum output to bring the level
down.
You have now analysed the alarm state and found that the
Base Level is too high because not enough Flow is leaving
the contactor.
There is not much you can do from the control room. You will have to communicate
the problem to a Field Technician. His experience should lead him to possible
sources of the problem, though you could suggest the following.
Check that the Flow Control Valve IS 100% OPEN
Check for any restriction between the contactor and the stripper.
(cluevalves??? What about the filter?)
Resolution
The Field Operator reports that the Differential Pressure between the inlet and outlet
of the Filter is way too high, indicating that the filter element needs replacing. He
changes over the filters and the problem is solved. IS IT?
Monitoring
You think you have solved the problem? Dont forget to monitor the solution to
ensure it works!
On the Trend we can see where the Flow started to drop off, causing the Level to
rise.
After corrective action, we see the flow rapidly rise, causing the level to drop. There is
a period of instability while the Controllers steady out.
Its just one more tool you can use to analyse a problem!
So Remember!
I. DETERMINE THE PRIORITY
II. FIND THE CAUSE
III. TAKE CORRECTIVE ACTION
IV. MONITOR THE RESULTS
STOP!
CHECKPOINT
1/. If you cannot find the cause of an alarm on the DCS you should.
Ignore it
Put in a Maintenance Request
Monitor the situation while a Field Operator checks
Disable the alarm
Those students who have completed the units Contribute to Quality and Apply
Quality will be familiar with some of the factors that can contribute to variations in a
process, but lets revisit some of them here.
Human interactions
Poor training
Not following SOPs
Not following blend recipes or production guidelines
Incorrect blend recipes or production guidelines
Mechanical interactions
Unsuitable equipment
Malfunctioning equipment
Materials interactions
Off Spec feed-stocks
Incorrect feedstocks
Unsuitable feedstocks
Low Feedstock
Consider a process plant that separates Oil, Gas and Water, and then treats each in
turn.
If we keep a steady federate, and the feed composition remains constant to the
above figures, the control system on Automatic, will eventually steady the process
out.
The Trend will look something like this: -
Control systems are not particularly good at coping with rapid change, and level
controllers are probably one of the worst!
If the composition of the feed stock changed slowly, it would be OK, however rapid
changes or swings are likely to de stabilise the control of the plant, leading to off
spec product, energy wastage etc.
Look at the Trend for the separator when the feed consistency is erratic.
The main aim of our solution should be to keep a steady flow of water to the
treatment plant.
The flow of water from the separator is dictated by the requirements of the Level
Controller LIC301. Automatic mode controls the level. So what do we do?
Look at the Trend, and see if there is a rough average water flow.
There is.
Lets say 30% of the FI 301s range is the average water flow.
So what is the range of FI 301? We can find this several ways. Clicking on the
Process Variable on the trend will bring up the Pop Up which shows detail for the
loop, including its range.
The only way we can do this is to put the Level Control LIC301 on MANUAL.
We will have to adjust the valve opening or OUTPUT to achieve a flow of 3 kltr/hr.
Lets bring up the faceplate of LIC301 to see what it would look like on MANUAL.
Dont forget though, the water flow is not being automatically controlled and will
waver a bit.
The control operator will have to keep a close eye on the process and make
occasional fine adjustments to the Output of LIC 301 in order to maintain two things: -
STOP!
CHECKPOINT
2/. Control Loops operating in Manual mode can help minimise variations in
process variables, but a controller on manual must
be___________________________________ by the Control Operator.
The sequence of events for a malfunctioning Level Controller is shown. The Control
Operator has added notes indicating the problem and reason for the change in
operating mode.
In 2.1 we looked at the access of data and information. All this information can be
used to identify problems with the process and the actual DCS itself.
Trend displays are probably the most useful tool. They allow us to look at process
variables, set points and outputs in relation to each other. We can view this data as it
happens (real time) or historically by scrolling back the trend.
As you can see the time scale is set to 5-minute intervals. The trend is a smooth
curve.
Changing the time scale
We can change the time scale to suit our needs.
Now lets change the time scale to 30 second intervals.
Now we have a picture of the Process Variable over a much shorter timescale.
Its not as smooth as we thought!
The larger the time scale the less detail we have about the trend.
Is this swing in the process variable a problem? It depends on the process.
This could possibly indicate that the controller PIC301 is a bit sticky and is not
responding smoothly.
We would not have picked this up on a bigger time scale. Zooming in lets us examine
a trend in finer detail.
This is just ONE example of accessing and using Historical Data to detect and
analyse problems.
2/. Next, as the change is reaching the Control Valve FCV-01, the set point for the
new feed rate should be PARTIALLY set. Remember, you are increasing the feed
by 3000kl/d, so dont do it all at once. Increase by 1000 kl/d only for now.
3/. The new feed will now be approaching the heater. Our Operations Guidelines
suggest a heater outlet of 256C. That is a rise of 14C, so lets go halfway for
now. Increase the set point of TCV-01 to 249C.
4/. We will now wait until the new feedstock, GOO B hits the column before
making an adjustment to the Tower Top. The required 120C is only a minor 2C
increase so it would be feasible to do that in one move. Increase the set point of
TCV-02 to 120C.
5/. Now we could make the next 1000kl/d increase in the feed, and raise the
Heater Outlet to the recommended temp. 256C.
6/. Now it would be appropriate to examine the behaviour of the process variables
of the column to check that they are within the expected range. Product should be
increasing and levels in the column and overhead drum should be under control.
7/. Now we can finally make the last feed increase to 8000kl/d.
8/. After ensuring that the process is under control and after an appropriate time
lapse, sampling of the products should take place to ensure quality.
Control Enhancements
A DCS may have Resident Programmes that assist the operator to maintain
control of the plant, and help to ensure production changes are
carried out in easy, less disruptive steps.
Ramping Programs
These are programs that interface with one or more related
controller loops.
They allow a Control Technician to enter a TARGET SETPOINT, and then the
program will gradually increase the actual set point over a defined time range
(ramping up) or gradually decrease the set-point (ramping down).
The Ramping Program may allow: -
Selection of a Target Set-point to be achieved over a selected time interval.
Eg. Set point is 5000 kl/d, Target is set at 8000 kl/d Time interval is selected as 1
hour. So the program will increase the set point by 3000 kl/d over the space of 1
hour.
Selection of a Target Set-point to be achieved in fixed increments.
Eg. Set point is 5000 kl/d, Target is set at 8000 kl/d Increment is 500 kl/d per 15
mins. Every 15 mins the set point will be changed by 500 kl/d. It will take 90 mins.
To achieve the target.
STOP!
CHECKPOINT
economic and environmentally efficient heater operation.
In 3.3 we looked at how a simple change of process conditions and set points could
be implemented.
It is the responsibility of the Control Operator to Optimise the process, possibly in
consultation with Production Planners and Process Engineers.
What IS Optimisation?
Raw materials, Utilities and Services such as water, electricity, fuel and steam are all
added costs to a process. It is vital to minimise the input of these costs. By optimising
the operation of the process these costs can be reduced. Optimising the process to
maximise waste heat recovery is one target.
SPECIFICATION
Feed 8000 kl/d of GOO B
Product 6000 kl/d of STUFF X 56 - 60 Burs/sec
2000 kl/d of STUFF Y no spec.
So..we have set in our set points, the plant is running steadily, and we have just
received the sample result of STUFF X.
We know that if we increase the heater outlet temperature, more of STUFF X will be
made, and less of STUFF Y.
We also know that we should increase the Tower Top temperature if we do this,
otherwise the extra STUFF X will be condensed and fall back down the tower into
STUFF Y.
We also know that the more STUFF X we heat out of the GOO, the higher will be
our Lab Result.
But check out the result, its at the LOWER END of the specification, so we could
afford to increase this by a few points.
Everything indicates that we could make MORE STUFF X from the same amount of
feed GOO B.
But one final check. We should contact the Production Planner and ensure it is a
smart thing to do.
The Planner will consider issues such as: -
STOP!
CHECKPOINT
ADJUST PRODUCTION
3.5 At the completion of this topic, the learner
must be able to adjust production in response
to test results and control panel information.
Most process plant requires testing of raw materials, process and products. Often
analyzers built into the process continuously monitor this. However, not all processes are
monitored as automatically, and these monitors themselves need to be regularly
checked for accuracy.
Operating Guidelines for product are usually the result of a combination of theoretical
and experiential inputs.
Crude Oil for instance varies so much depending on its source that it is almost
impossible to predict its PRECISE behavior during the refining process.
A Production Plan and Operating Guidelines for a cargo of crude oil will be built up from:
A production process produces a light hydrocarbon oil. The main specifications are
Density and Flash Point. Flash Point is the temperature at which the lightest, or most
volatile components will vaporize and ignite.
The Production plan and Production Guidelines are implemented and the unit is running
steady. The analyzers indicate that the product is on spec. The following actions are
suggested.
A product sample is taken for Laboratory Analysis.
The laboratory result is reported and the analyzer check filled in: -
If you look at the results table you will see that there is some variance between the
laboratory test results and the analyzer reading at the time.
While the analyzer showed that the oil was on spec. for Flash Point, the laboratory result
shows it outside the allowable range of 102C 0.5 C.
The smart move for this would be to arrange another check sample, labs DO make
mistakes.
The density result is spot on, but obviously the analyzer is slightly out, but well within the
acceptable range.
ACTION
An instrument technician should recalibrate the Flash Point Analyzer as it is reading
outside the acceptable error.
If there is a delay in having it recalibrated, then the process should be run to an analyzer
target of 101 C to compensate for the error.
STOP!
CHECKPOINT
3/. Why is it important to note plant operating conditions when taking test samples?
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
3.0 Control process variations and monitor normal operations.
In 2.5 we looked at Operating Notes that can be entered into report pages of a DCS.
We also looked at the importance of them.
We have also looked at why Production Plans and Operating Guidelines do not
always end up being an accurate model of how the process will operate.
If a Control Technician cannot meet the Production Plan, or the process ends up
deviating from the Operating Guidelines, it is important to ensure that the
deviations/irregularities are noted and where possible explained. If they are, people
such as Engineers, Planners, Maintenance, Materials Purchasers, Marketing Reps.
and Accountants can learn valuable lessons and be able to: -
programmed off-take of B product could not be achieved at the given spec. due to
the need to reduce Tower Top temp. to achieve the spec.
Explain the reason, bearing in mind that a person that needs to know may
have limited operational knowledge (eg. a Materials Purchaser)
STOP!
CHECKPOINT
1/. Who would need to know if a production target could not be achieved due to a
mechanical failure?
___________________________________________________________________________
___________________________________________________________________________
2/. Who would need to know if a production plan needed to be modified because
raw materials were not to specification?
___________________________________________________________________________
___________________________________________________________________________
3/. Who would need to know if a production plan had to be modified because a
piece of equipment did not have the capacity to do the job?
___________________________________________________________________________
___________________________________________________________________________
4.0 Facilitate planned and unplanned process start-ups and shutdowns.
The shut down and start up of process plant is usually the busiest time for a Control
Technician. It can also possess the potential for the most risk because: -
The plant is not in stable operation.
Activities are not of a routine nature.
There are a greater number of personnel involved.
There are many activities that need to be coordinated, often happening
simultaneously.
These will vary greatly depending on the process; they may also vary within the
same plant depending on the reason for the shutdown. There may be separate
procedures for: -
Production Shut-downs/Start-ups are for when there is no requirement for the plant to
be operating. Usually the shutdown involves a minimum of work, and is shut down in
such a manner, and left in such a state to facilitate easy and rapid start-up when
production is required again.
After a Major Overhaul, the start-up procedure may involve the pressure testing of
equipment, the purging of air from vessels and pipe-work, and the filling of systems.
It will also, of course involve many more checks to ensure that the system is
complete mechanically.
During the pre-check period the Control Technician will be busy with
Instrument/electrical technicians checking such things as control valve operation and
ESD operation.
All these shutdown types are Planned Shutdowns. Procedures should be in place for
personnel to follow. On occasion it may be necessary to modify a procedure prior to
the shutdown. This is particularly so of Partial Overhaul Shut-downs.
Emergency Shutdowns
Emergency shutdowns are not planned, in that no one can predict when they will
occur. During an emergency shutdown there is the highest potential for risk of any
shutdown or start-up situation.
The nature of the emergency can vary in type and severity from process to process,
and also the size of the plant.
1) Safeguard personnel
2) Safeguard the Environment
3) Safeguard Property
4) Safeguard Profits
Having identified typical emergencies on a plant, procedures to deal with these can
be written.
Not all emergency shutdowns can be catered for in procedures, and the experience
and knowledge of the Control Technician needs to be applied to ensure safety of
personnel, environment and plant.
Accessibility
Because procedures need to be accessed immediately a situation is detected, they
must be available to the Control Technician in an easy to access format.
Consequently, a safe plant should have these procedures in hard copy, located
adjacent to the Controllers workstation.
Some DCS systems have them on screen. The Operator can often access them
from a menu using dedicated keypad or windows buttons.
!
Online emergency procedures should ALWAYS
be available in hard copy in case the nature of
the emergency prevents access to the Online
format eg. DCS Failure.
The Control Technician must use all the skills, experience and knowledge they have
to deal with the situation.
You could do worse than follow the first five actions from the Hazard Plan
We have looked at the on screen menu facility that will display appropriate
emergency measures for the process.
DCS systems may have enhanced programmes that can actually control the
shutdown to a greater or lesser degree.
Because of the likely high volume of radio traffic, messages must be clear and
concise.
It is critical that the Control Operator communicate with other areas that may be
affected by the shutdown or start-up.
Depending on the radio system at your workplace, it may be useful for those on the
area to go to a dedicated Shutdown Channel so as not to be distracted by other
traffic, nor monopolise the frequency to the detriment of other users.
Places of work all have varying Emergency Plans and Procedures. The actual
responsibilities of the Control Technician may vary from site to site, but typically they
may be charged with: -
Generally, once the Incident Management Team has set up, the Control Technician
will then act under their direction.
!
collected before, during and after an incident MUST be retained
and in an unaltered state. This information may be used to
investigate the incident, and could possibly be used as
evidence depending on the seriousness of the event
STOP!
CHECKPOINT
1/. Why do plant Shutdowns and Start-ups have the potential for higher
risk than normal operations?
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
2/. Name five (5) possible Emergency Shutdown procedures.
______________________________________________________________
_____________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
6/. Name five (5) groups that should be given as much notice as possible of a
Shutdown or Start-up?
______________________________________________________________
______________________________________________________________
______________________________________________________________
______________________________________________________________
____________________________
During the operation of a process using a DCS, it can sometimes become confusing,
with a whole range of data and information available to the operator.
The first indication of an alarm state is usually an audible indication, the Alarm
Sound. It doesnt tell the operator much at all. Except that an Unacknowledged
Alarm State exists. On hearing the alarm sound the Control Operator is faced with
several questions: -
What is the alarm?
What system is it in?
Is it a critical (high priority) alarm?
Is it a False Alarm?
The first reaction of the operator is to SILENCE that annoying alarm sound!
DONT!!!!!!!!!!!
Some DCS are configured so that when you silence an alarm you also acknowledge
it.
Others only silence the alarm, but it remains in the Unacknowledged state, and
continues to flash in displays or summaries.
Once you have silenced and/or acknowledged an alarm there is a danger you will
forget it!
!
BEFORE YOU ACKNOWLEDGE AN ALARM YOU SHOULD
ALWAYS DETERMINE ITS LOCATION AND IMPORTANCE
Faceplates
Primary and Secondary Displays
Alarm Summaries
Event Log Reports
Alarm Reports
Find a control loop on the plant, and then locate its control tag on a
Primary or Secondary Display. Now draw a block diagram showing all
the other displays, face-plates, logs, reports and summaries in with
which this process variable is associated, noting any alarm indication
STOP!
CHECKPOINT
facilities.
1/. Why should you NEVER acknowledge an alarm before determining its
location and importance?
______________________________________________________________
______________________________________________________________
______________________________________________________________
There are other indications that can demonstrate the importance or severity of an
alarm condition.
Stepped Alarms
Some alarms are configured to alarm at different process values as the severity of
the condition increases.
For example: -
If the pressure continues to rise and become more critical a further alarm may be
triggered
The every fact that the process variable has a PAHH facility gives some indication
that an alarm condition for this part of the process is a serious situation.
This alarm hierarchy can go one step further.
Compressors are for compressing gases; they do NOT like liquids, as they are
incompressible.
Unless the compressor is a specialised Wet Gas Compressor, severe damage can
be done if liquids enter a compressor.
To this end, a Suction Knockout Pot (K/O Pot) is usually installed before the inlet to
the compressor. This pot may be drained automatically by Level Control, or manually
by the field technician.
As an added security, this vessel can be fitted with high-level alarms.
In this case the K/O Pot has three alarms in ascending order of severity.
The final alarm LASH takes the situation out of the hands of the Control Technician.
Should the level go past the LAH trigger, the LASH will automatically shut down the
compressor in order to protect the machine from liquid carryover damage.
Other severe conditions may be indicated by alarms that monitor machinery and
equipment rather than the process.
Examples include
Vibration alarms
Heat alarms
Smoke alarms
Emission alarms
Like process variable alarms, they may be stepped and/or be tied into shutdown
systems.
Frequency of Alarms
Frequency of a particular alarm could be cause for concern. While the severity of the
condition indicated by one single event may not be of any great consequence,
repeated occurrence of this event could indicate machinery/instrument malfunction,
the possibility of cumulative damage over a period of time, or a design problem.
STOP!
CHECKPOINT
3/. How can a System Event Log help analyse an alarm state?
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
Much of this has already been covered, so we will just look again at the various
screens that may assist the Control Technician to identify alarm states or abnormal
conditions.
Perhaps it would be wise to view these options in the light of a possible failure of one
or more alarm indications!
Nothing is foolproof of course, and DCS systems are no different. The possibility of a
failure in the DCS to alert about an alarm state is quite real, though there are a great
number of other tactics a Control Operator can employ to avoid non-detection of
abnormal conditions.
The beauty of such a system is that within a particular loop, or for a particular
process variable/equipment state, there may be many indications of abnormal
condition.
Lets look at some of them.
Indicator Description Location
Analogue Value The value of the process Primary/Secondary
variable Displays, Faceplates
Trends, Overviews
Set-point Alarm (or PV-SP Deviation too far either Faceplate
Deviation) side of the set point by a Alarm Summary
defined amount eg. 10% Event Log
High & Low Alarm Process Variable has Faceplate
exceeded a defined Alarm Summary
threshold Event Log
Hard Wired Alarm An alarm independent of Usually a separate alarm
the DCS. Connected to the light or display, on or near
control room by a wire, as the consol but not
opposed to the Data dependant on the DCS.
Highway Has its own response
button.
Examples
A flow of 1000 m3/hr into a vessel, and a flow of 500 m3/hr out, level is steady.
The only alarms on the vessel are soft and work off the level indicator, which is
obviously not working!
PARAMETER SP PV Units
LEVELS
Inlet Gas Scrubber 15 %
Contactor 60 58 % UTILITIES
Reboiler 75 76 % L.P. Steam 318 Kpa
Surge Tank 60 60 % Instrument Air 747 Kpa
Flash Tank (glycol) 100 % Plant Air 654 Kpa
Flash Tank (oil) 5 % Cooling Water 21 C
Glycol Storage 50 %
TEMPERATURES ENVIRONMENT
Wet Gas Inlet 72 C Ambient Temp. 23 C
Dry Gas Outlet 68 C
Glycol Inlet 76 C Wind Strength 28 km/h
Reboiler 190 195 C
Stripper 100 C Wind Direction
PRESSURES
N
Inlet Gas Scrubber 102 Kpa
Contactor Top 114 Kpa
Contactor Base 112 Kpa
Flash Tank 43 Kpa
FLOWS
Wet Gas 250 m3/hr
Dry Gas 239 m3/hr
Lean Glycol 1.6 1.5 kl/hr
Rich Glycol 1.6 kl/hr
STOP!
CHECKPOINT
______________________________________________________________
2/. Why?
______________________________________________________________
RESPOND TO ALARMS
5.4 At the completion of this topic, the learner
must be able to respond to the alarm or
incident by following procedures
Certain alarms or incidents will have given procedures to correct or respond with.
Others may not, and this is where the Control Technician requires a thorough
understanding of the plant, process and the DCS.
Alarms may require the implementation of an: -
Emergency Procedure
Environmental Procedure
Safety Procedure
Product Movement Procedure
Standard Operational Procedure.
Not all of these will require actual changes to the operation of the process by the
Control Technician, however, as the initial alarm or condition is first relayed to the
Control Room, it is usually the Control Technician who initiates the response
procedure by communication with relevant people.
Deteriorating Situations
More often then not, serious situations start off as small incidents, irregularities or a
single alarm. This alarm may not be a particularly high priority alarm, but is only the
first indication that something is starting to go wrong. It may NOT develop, then again
it MAY!
Calling it Quits
At some time during the response to an alarm or irregularity it will become clear that
the situation is becoming increasingly unstable.
Procedures are implemented, changes made and moves are made to compensate.
The Control Operator may eventually have to make a decision (perhaps in
consultation) to make the plant safe, by shutting down or whatever is the
appropriate action.
This decision should NOT be influenced by any other factors other than SAFETY.
Remember the order?
Safeguard Life
Safeguard Environment
Safeguard Property
Safeguard Profit
The financial consequences of a production half should NEVER intrude upon any
decision where Safety is at risk.
Workplace Ethics, Procedures and Culture should always support decisions based
on Safety.
STOP!
CHECKPOINT
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
3/. Write down the order of importance of an Emergency Response
1)
2)
3)
4)
Urgency
Methods available
Who it is communicated to
STOP!
CHECKPOINT
2/. Give Five (5) ways that information may be reported.
In 2.5 we looked at recording irregularities and variations, and the same conditions
apply here. The DCS will record the fact that an alarm has been going off regularly,
associated data may show the reason, and then again it may not. It is the
responsibility of the Control Technician to fill in the gaps in information that the DCS
does not collect and store.
It is also mandatory to inform the on-coming shift about any serious situation, even if
it has been dealt with.
Obviously if an alarm or irregularity is still ongoing, it must be drawn to the attention
of the next shift.
Information you should convey to them should include
They can follow up your corrective actions to ensure you have dealt with the
situation.
Should the situation recur they can base their action on that taken by you.
They may reassess the cause if the problem recurs.
When assessing the effectiveness of a solution check: -
Plan
Act
Check
STOP!
CHECKPOINT
1/. What information about an alarm or abnormal situation should you convey to
your relief?
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
2/. When assessing the effectiveness of a corrective action, what should you
check for?
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
Hazard identification has become particularly important in the Chemical, Oil and
Hydrocarbons industries since the Longford Incident. In this incident, which occurred
on September 25, 1998 at Essos Longford (Victoria) gas processing plant, two
workers were killed, and eight others injured. As a result of this incident, and the
subsequent findings, Victoria has revised its OH&S legislation with additional
regulations pertaining to Major Hazard Facilities. Other states are likely to follow with
similar changes.
In Victoria, the OH&S (Major Hazard Facilities) Regulations came into effect on 1 July
2000. The Regulations focus on the safety of people at major hazard facilities
(workers, contractors and visitors), the safety of those who may be affected by an
incident at a major hazard site (neighbours, local community) and the safety of
property.
MHF REGULATIONS
The Victorian Occupational Health and Safety (Major Hazard Facilities) Regulations
set out specific obligations for companies operating major hazard facilities. Under the
new laws the operating companies must:
establish and implement a safety management system
identify all major incidents that could occur, and the hazards that could cause
those major incidents
assess the risk of these hazards and potential major incidents
adopt control measures to eliminate or reduce, so far as is practicable, risk to
health and safety
prepare emergency plans in conjunction with local emergency services and
municipal councils
consult with health and safety representatives in all relevant matters
provide safety information to the local community and consult with municipal
councils in relation to matters that could affect the local community
prepare a safety case and apply for a licence
revise the safety case at time frames and following specific requirements.
A Safety Case is a written document in which the operator of a major hazard site
describes what measures are in place to prevent a major incident and also to deal
with the situation should such an incident occur. The Safety Case must demonstrate
that the measures are appropriate and adequate and that risks have been reduced
as far as practicable. A Safety Case can only be written following a full examination
of:
the facilitys activities
the potential for major incidents
risk control measures.
The New South Wales Occupational Health and Safety Act 2000, though not
applicable outside NSW, states that:
Employees must take reasonable care of the health and safety of themselves and
others. Employees must co-operate with employers in their efforts to comply with
occupational health and safety requirements.
Other states have similar legislation, often referred to as duty of care. That is,
employees in all parts of Australia have obligations regarding Occupational Health
and Safety regulations.
Controls to Controls to
Event causing reduce likelihood Incident reduce severity
a hazard of an incident of incident
Control measures include the presence of an operator who has the skills to recognise
the potential for an incident to occur because of the incorrect quantity of pentane in
the weigh tank. The operator would then follow procedures to prevent the incident.
The important aspect is that the operator identifies the situation in the first place.
IDENTIFYING HAZARDS
A hazard is any situation with the potential to cause harm, injury, or damage to plant
and equipment. All workplaces have potential hazards that can lead to a minor or
major incident. Identifying and dealing with a hazard is often common sense, such as
seeing a leaking gland in a pipe and notifying the appropriate personnel. Other
examples include hearing unusual noises in an item of plant, noticing a leaking
containment vessel, observing incorrect or unusual instrument readings (eg pressure,
temperature, flow rate).
In some cases, a certain level of skill is needed to identify a workplace hazard. That
is, the operator needs to know if a noise is indeed unusual, that the instrument
readings are incorrect, or that a containment vessel should not be leaking. Employers
operating a major hazard facility are obliged under the Victorian legislation to provide
training for employees.
Plants that are not categorised as major hazard facilities also have obligations under
the relevant OH&S acts, which include providing a safe workplace. In other words,
there are obligations on employers to provide appropriate training in hazard control,
and obligations on employees to recognise and assess a potential hazard.
Hazards can also arise from the normal operation of items of equipment. For
example, you might notice that the barriers or warning signs around a certain item of
equipment are missing. The hazard is therefore not the item of equipment, but the
missing signs or barriers.
The risks arising from a hazard will depend on many factors, including:
the type of workplace (eg, oil refinery, chemical plant, hydrocarbons plant)
the nature of the hazard (eg, small or large leakage, fire, loss of containment)
the situation at the time (eg, circumstances where a loss of containment of a
flammable substance would be greater if welding was being conducted
nearby).
The risks that could arise also vary considerably and could include:
environmental risks (pollution, chemical fallout over adjacent properties, fire)
risks to other workers (injury or death)
risks leading to plant damage and failure (eg, bearing failure causing a shaft to
seize, which in turn could cause other equipment items to fail, due to a loss of
output from the equipment suffering bearing failure)
risks leading to loss of product (eg, gases or liquid products escaping, which
in turn could mean the plant loses profitability, leading to potential closure).
You would normally assess the likely risks from a hazard you have identified before
taking action. If the potential risks are high, you need to take action immediately. If
there were minimal risks (eg, a very small leak from a gland), you would still report
the leak, but perhaps after you return to base. However, if in doubt about the
potential risks, report the hazard immediately.
In some cases you will be able to deal with the hazard yourself. For example, if you
notice a leaking gland that simply requires tightening, you would tighten the gland,
providing its within your scope of skill level. Or you might hear a noise that indicates
a bearing problem that you can solve by topping up the bearing oil containers. The
important thing to remember is that you should only make repairs you are qualified to
undertake.
FOLLOWING PROCEDURES
Most workplaces have procedures in place to deal with hazardous situations. The
aim of these procedures is to ensure the correct action is taken, and by the
appropriate personnel. If you identify a hazardous situation, you would take
appropriate action in accordance with the correct procedures. Otherwise you might
make the situation worse, or cause yourself injury. If there were no procedures, you
would take action in accordance with your skill level.
The essential aspect is to take appropriate action. If there are no procedures and the
problem is outside your skill level, report the problem immediately, even if it appears
minor. The Longford incident could have been prevented if the observation of ice
around a pipe had been acted on appropriately.
STOP!
CHECKPOINT
1/. List the hazards associated with your immediate work area.
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
2/. Assess the likely risks arising from each of the above hazards.
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
3/. State the type of action you should take to control each of the above hazards.
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
IDENTIFY PROBLEMS
7.1 At the completion of this topic, the learner
must be able to identify possible problems in
equipment, control systems or process
A plant that has been fully commissioned and operating in a steady-state condition
will have little if any need for intervention by the control room operator. Intervention
by the operator would be limited to start up or shut down of the process, adjusting
production set points, and maintaining production reports.
However, not all plants operate for a long duration without some type of abnormal
situation occurring. This may include mechanical failures within the process,
maintenance requirements, or on going enhancements to the production process.
It is therefore necessary for the operator to be cognitive of process conditions,
abnormal situations, maintenance personal work scopes, and other factors that will
effect the operation of the process.
Examples of abnormal conditions can include: -
Maintenance or tuning of control equipment requiring the operation of that
control loop to be placed in Manual Mode, or even physical bypass operation
by a technician on the plant itself.
Production specifications and plans that require operation of the plant outside
of normal operating parameters (but within safety guidelines)
Examples include: -
Categorising Problems
Problems likely to be detected by the control technician can be broadly divided into
three categories.
Feed/product Quality Problems
Control Problems
Machinery & Equipment Problems
Design Problems
Poor Operating (personnel)
Control Problems
Process Control equipment is malfunctioning, preventing the Control Technician
running the plant according to the parameters dictated by the plan.
Design Problems
The process design is not capable of achieving the production targets/specs.
Undersized equipment.
Equipment not capable of achieving precise quality specs.
Actioning Problems
All problems must be dealt with. The main issues facing the Control Technician
are: -
Prioritising actions
Documenting/recording the problem/action
AND
If the problem is outside the scope of the Control Technician; who to report
it to.
Safeguard Life
Safeguard Environment
Safeguard Property
Safeguard Profit
STOP!
CHECKPOINT
1/. Give three examples of scenarios that may require abnormal operation of the
process.
Level Sensor
Loop Problems
There are a fair few things that can go wrong with a process control loop and they
are generally not within the scope of responsibility of the Control Technician to
remedy. It is however, important for the technician to recognise the problem and
report it to the necessary people for rectification.
Gain Problems
The speed at which a controller responds to a change in the LOAD is called the
GAIN.
If the Gain is too low the controller will respond too slowly and may not be able to
keep pace with a changing process variable.
If the Gain is too high the controller will react far too quickly and will cause cycling, or
erratic control as it makes too greater changes for only a small change in process
variables.
Normal Operation
Process Variable
Set Point
PV PV
SP SP
TIME TIME
Typically, High Gain will cause the erratic, unstable control illustrated above.
Low Gain will cause the slow response as above right, in this case it is not even fast
enough to control the process and the process variable is wandering further away
from the set point each cycle!
Calibration Problems
For a DCS to control properly it must have CORRECT DATA input in order to control
correctly. A frequent fault in a DCS is that the actual proportional signal (usually in
milliamps) from the sensor (eg. Level Indicator, Temp. Indicator) is out of calibration
with the actual process variable.
A check is made of the contents of feed tank A and it is found that far more A has
been used than the program indicates.
Obviously, FIC 201 is NOT controlling the flow of feed A correctly to the desired
program amount.
FI 201 is out of calibration. It is not sending the correct signal to the DCS and so the
DCS is controlling using incorrect data.
It would be impossible for individual operators to rush around and control the
numerous processes and activities required to maintain a continuous operation.
It is therefore imperative that this 'nerve' system is highly reliable, and that
contingencies are in place in the event of any hardware failures.
One of the primary objectives of a Distributed Control System is to ensure that there
are no single-points-of-failure within the hardware system.
The term redundancy in this case means additional components that automatically
kick-in in the event of a 'primary' component failure. 'Backup system' is another term
used to describe redundant components.
Hardware Alarms
All DCS hardware components have associated alarm and status information that is
relayed via the communication system to the operator interface. This information
appears in a series of diagnostic displays. These displays are used by personnel to
monitor the system for hardware problems.
Diagnostic information not only informs the technician of failed equipment, but also
reports on the operating condition of the equipment. This may include out-of-range
field input parameters, low power supply voltages, faulty redundant modules,
communication data errors, etc.
Hardware status alarms will have a high priority due to the possible loss of
production.
Cabinet temperatures.
Communication system.
CONTROL CENTRE
21 DCE NORMAL
10 DCE NORMAL
22 DCE FAULT
11 DCE NORMAL
23 DCE NORMAL
12 DCE NORMAL
24 DCE OFFLINE
13 DCE OFFLINE
25 DCE NORMAL
The hardware status of the entire Distributed Control System is shown on the System
Status Overview display. This display gives an overview of all the nodes (or DCE
sub-systems) and provides the following status information.
Communication system.
This overview status display also provides access to sub-levels of diagnostic displays
for each node.
It is essential that the production operator interpret critical failure modes correctly to
ensure safe operation of the plant equipment.
This type of failure mode needs to be addressed urgently so production downtime is
minimised. The production operator should immediately contact qualified engineers
or technicians to investigate the failure.
If the Operator Consols are still operational, the Control Technician should call up the
status displays in order to locate the hardware fault. This information will be required
when discussing the failure with the engineer or technician.
The operator should also peruse the alarm summary for any unusual priority alarms,
for example, high-pressure alarms that may represent a danger to personnel or
equipment.
The operator should also peruse the operating displays to determine whether the
process has shutdown properly. The DCS failure may have caused part of the
process to stop operation, while another area is still in operation and may need to be
manually stopped.
Most critical failure modes are tested for their effects during the commissioning phase
of the plant.
This will ensure that on the loss of a major node or processing module DCE, outputs
default to predetermined states. This will in-turn ensure a safe shutdown of the
process, with pumps, valves, drives, dampers, etc. going to fail-safe states or
positions.
Internal configuration safety interlocks will further ensure that other areas of the DCS
unaffected by the failure will be notified via the communication system and shutdown
if required.
It is essential that the production operator interpret critical failure modes correctly to
ensure safe operation of the plant equipment.
A DCE power supply unit or feeder has failed, and the system is now operating on
a single supply or power feeder.
This kind of failure is obviously less critical than the above 'critical failure' mode as
the process is still in operation. However, DCS integrity has been decreased and the
problem should be investigated and rectified when practicable.
Should any question arise regarding the integrity of a primary module, the redundant
module will assume a bump-less control, automatically and immediately. When a
primary module fails over to its backup or redundant module, the changeover is
seamless and bump-less to the process.
However a hardware alarm is raised to indicate the failure of the primary unit.
DCS Failure Recovery
The rectification of critical hardware faults may require certain sections of the DCS to
be isolated while repairs are undertaken, or that the process plant is unable to be
restarted until the fault is fully rectified. Engineers or technicians will normally carry
out this task in consultation with the control room operator to ensure hardware status
alarms have cleared.
Recovery from a critical hardware faults may require the downloading of system
software if major processing modules have been damaged. Recovery from a power
down situation will not require the reloading of software, but will require the operator
to go through a proper start-up procedure of the process plant.
It is imperative the operator confirms that all hardware status alarms have cleared
prior to restarting the process.
The rectification of non-critical hardware faults can usually be done while the DCS is
on-line and the process in operation.
Engineers or technicians will normally carry out this task in consultation with the
control room operator to ensure hardware status alarms have cleared.
Most DCS vendors incorporate on-line changes for all redundant components. This
simply means the failed component is removed or unplugged, and replaced with a
known good spare. These modules may be inserted and removed under power.
On Power-Up
One of the most stressful occasions for the control room operator is during the start-
up of a process plant, or the associated control system. The operator can become
very confused with the amount of information unless they follow a concise procedure.
Generally modern process plants will have in-house procedures to follow when
starting up the process.
1/. How could you tell that a Flow Control Valve was stuck?
______________________________________________________________
______________________________________________________________
______________________________________________________________
______________________________________________________________
______________________________________________________________
______________________________________________________________
______________________________________________________________
2/. Is this indicative of too high or too low GAIN on a control loop?
Normal Operation
Process Variable
Set Point
PV
SP
TIME
3/. Check out this MASS BALANCE
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
6/. What is a Non-critical Failure?
___________________________________________________________________
___________________________________________________________________
8/. What display would you go to check the DCS system Hardware?
7.0 Resolve problems
We will look at the problems that are within the scope of the Control Technician to fix,
or fix in cooperation with a Field Technician. Any other problems, as have been
described, will need to be reported to the appropriate personnel.
In 7.3 we deduced that the Control Valve was stuck. It was not responding to
changes in output. The Field technician will have to stand by the valve while the
Control Operator performs the following sequence of checks and movements.
Have the Field Technician check that the Air Supply to the valve is
sufficient. Pneumatically operated valves usually have two pressure
gauges. One shows the Air supply, the other shows the Output pressure
(the pressure applied to the diaphragm to move the valve).
If the Supply Pressure is low than the reason will have to be investigated.
Have the Field Technician observe the Output Pressure while you adjust
the Output on the DCS Faceplate from 0% to 10% then 20%. The Output
Gauge should show increasing pressure. If not then there is a fault within
the actuator and it must be reported to the Instrument Technician. If the
Output Pressure mirrors moves made by the Control Operator, go to the
next step.
The next step is called Stroking the valve.
The technique is to subject the valve to radical changes in output to try to free up
the jammed shaft.
Put the Control Valve on Bypass Control. That is, using the hand valve to control the
process variable, the downstream isolation valve being closed. This will prevent any
sudden change in process variable if the valve frees up.
With the Field Technician standing by, change the output from 0% to 100%, and then
back to 0%.
Repeat this several times until the Field Technician observes the valve moving
smoothly.
If the valve does not free up report it to Maintenance, its beyond your scope to fix.
Verify that the valve opening corresponds to the %Output on the Faceplate. Do this
by having the position observed at 0%, 25%, 50%, 75% and 100% Outputs.
To return to service
In 7.3 we decided that the level sensor for the water tank was stuck, giving us a
constant reading.
We will look at the Float Chamber type sensor. This device is a cylinder attached by
pipe-work (tapping lines) to the vessel. The level in the vessel and chamber rise and
fall together (or should). A float inside the chamber rises and falls with the level. The
float is connected to a transmitter device that usually sits atop the chamber.
There is scale,
debris or high
viscosity material in
the chamber
preventing the float
from moving with the
level.
Take this action: - Place the Controller on Manual and control the flow. Judge what is
required to maintain the level (the same as whats going in!).
Isolate the level equipment from the vessel and drain the contents. This may be
enough to displace any debris in the chamber.
Now slowly open the LOWER isolation valve. This will allow liquid from the vessel to
flow into and out of the chamber. If it doesnt, you have found the blockage in the
pipe-work.
To displace stubborn debris in the pipe-work, blow back into the vessel with water,
air or steam.
NOTE SAFETY CONSIDERATIONS RELATIVE TO THE VESSEL AND
!
ITS CONTENTS. Eg. Water cannot be put into a vessel containing
liquids hotter than 90C. or boilover could result. Do not exceed the design pressure
of the vessel OR the chamber.
And
NEVER POKE SOMETHING UP AN ORIFICE TO CLEAN IT OUT.
(Two Process Technicians were killed in 1964 doing that to a drain on a propane
drum)
Now shut the lower isolation valve and open the top isolation valve. Blow Back
again to clear the top lines.
Isolate the chamber from the vessel and open the chamber drain and top vent.
Flush the chamber with steam or hot water.
If this procedure does not work then disassembly of the chamber may be required.
Report to maintenance.
STOP!
CHECKPOINT
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
2/. What are the safety considerations when blowing clear tapping lines for a
float chamber?
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
7.0 Resolve problems
FOLLOW THROUGH
7.5 At the completion of this topic, the learner
must be able to follow through items initiated
until final resolution has occurred
Whether the Control Technician, the Field Technician or anyone else attends to a
control problem, it will be up to the Control Technician to monitor the result of
the corrective action to ensure that the fix was appropriate.
It is often up to the control technician to place Priority on the resolution of problems.
They may have to guide, advise or even hassle the appropriate personnel to rectify
problems according to the priority assigned by the Control technician.
Remember!
Safeguard Life
Safeguard Environment
Safeguard Property
Safeguard Profit
OPERATOR CREATED GROUP DISPLAYS
These are Group Displays customised by the Control Technician according to their
needs. Creating a group display to monitor Problem Areas of the process is a great
way to keep an eye on these areas on ONE screen.
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
7.0 Resolve problems
REPORT PROBLEMS
7.6 At the completion of this topic, the learner
must be able to report problems outside area
of responsibility to designated person.
As mentioned, while it may be within the ability of the Control Technician to identify
problems, and even suggest the cause and solution, not all issues are within the area
of responsibility of the Control Technician.
Is it?
SAFE? Doing the job will NOT create a hazard to yourself or others
EFFICIENT? Are you the best person for the job, will it detract from your
prime tasks? Could your time be spent more productively?
It is important to know WHO to report problems to. Various workplaces will have
different titles for these people. Dont forget that you may need to inform more than
one person. They may not be the people to fix it, but really need to know the problem
if it impacts upon their patch.
As a guide.
Work Requests
Plant Modification Requests
Software Modification Requests
Non-Conformance Reports
Etc etc.
STOP!
CHECKPOINT
3/. The Feed Flow Control Valve to your plant does not respond to the DCS, and
stroking has not cured the problem, but it is getting the correct Output
Pressure etc. Who would you report this to, and how?
4/. Is there any one else who might like to know about this?
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
conditions. or simulated)
analysing failure modes
variation/loss of feed
1.5 Access historical data
and information. unstable control of pressure,
Oral questions
then Complete
temperature level & flows
control equipment failure
Practical
activity (real
Incomplete
1.6 Acknowledge messages change in atmospheric Oral questions
and alarms conditions (rain, temperature, then Complete
wind, lightning)
emergency situations
Practical
activity (real
Incomplete
or simulated)
UNIT TITLE : OPS 305B
OPERATE PROCESS CONTROL SYSTEMS
ELEMENT 2 OF 7 : Access Control Information
Complete
may include:
4.4 Implement all required Oral questions
emergency responses loss of power/utilities then
and ensure the
outcomes of these
analysing failure modes
variation/loss of feed
Practical
activity (real or
Incomplete
responses are simulated)
unstable control of pressure,
communicated to all
temperature level & flows
affected areas
control equipment failure
4.5 Log all required
information for further process plant trips
Oral questions
then Complete
action to provide a
historical record of all
change in atmospheric
conditions (rain, Practical
activity (real or
Incomplete
events. temperature, wind, lightning) simulated)
emergency situations
UNIT TITLE : OPS 305B
OPERATE PROCESS CONTROL SYSTEMS
Complete
change in atmospheric
5.6 Record the information Oral questions
conditions (rain, temperature,
on the appropriate log then
and/or ensure the
operations database is
wind, lightning)
emergency situations Practical
activity (real
Incomplete
updated with details of or simulated)
the alarm.
5.7 Provide face to face
details of the alarm and
Oral questions
then Complete
action taken to the next
supervisor at shift
Practical
activity (real
Incomplete
changeover. or simulated)
5.8 Follow-up the incident to
see that appropriate
Oral questions
then Complete
action has been taken.
Practical
activity (real
Incomplete
or simulated)
UNIT TITLE : OPS 305B
OPERATE PROCESS CONTROL SYSTEMS
printers or simulated)
fire and gas detection/protection
6.3 Implement measures
to control risks in
systems
emergency shutdown systems
Oral questions
then Complete
line with procedures
and duty of care.
communications systems Practical
activity (real
Incomplete
or simulated)
Typical problems for your plant may
include:
loss of power/utilities
analysing failure modes
variation/loss of feed
unstable control of pressure,
temperature level & flows
control equipment failure
process plant trips
change in atmospheric
conditions (rain, temperature,
wind, lightning)
emergency situations
UNIT TITLE : OPS 305B
OPERATE PROCESS CONTROL SYSTEMS
7.5 Follow through items analysing failure modes Oral questions
initiated until final variation/loss of feed then Complete
resolution has occurred unstable control of pressure,
temperature level & flows
Practical
activity (real
Incomplete
control equipment failure or simulated)
7.6 Report problems outside
area of responsibility to
process plant trips Oral questions
then Complete
Incomplete
change in atmospheric
designated person. conditions (rain, temperature, Practical
wind, lightning) activity (real
emergency situations or simulated)
NOTES
NOTES
NOTES
NOTES